COLUMN DESIGN SUMMARY

Project Name : 3 STOREY COMMERCIAL BUILDING


Client Name : CE 2L
Engineer Name : SHEENA ANG
Design File : D:\new 3 storey\staad 3 storey-Column-1.R1.rcdx
Analysis File : D:\new 3 storey\staad 3 storey.STD
Analysis Last Modified : 11/03/2020 2:37:46 PM

Design Code: ACI 318M - 2014


Load Combinations :
1. 1.4 (LOAD 3: DL)
2. 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
3. 1.2 (LOAD 3: DL) +0.5 (LOAD 4: LL)
4. 1.2 (LOAD 3: DL)
5. 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
6. 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
7. 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
8. 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
9. 0.9 (LOAD 3: DL)
10. 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
11. 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
12. 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
13. 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)

Levels : 1. FOUNDATION
2. 4m
3. 7m
4. 10m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column/Wall : C1
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 11 15 94.34 12.28 139.55 1.51 0.92 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 8 12 180.01 -22.21 85.14 1.51 0.55 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 8 12 45.81 -11.49 38.53 1.51 0.28 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C2
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 11 15 200.81 5.56 127.02 1.51 0.77 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 5 9 184.79 84.49 19.99 1.51 0.54 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 5 9 34.92 40.14 4.08 1.51 0.28 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C3
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 12 16 234.41 125.47 -7.52 1.51 0.75 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 7 11 184.5 -83.48 23.76 1.51 0.55 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 7 11 34.92 -39.37 5.02 1.51 0.27 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C4
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 234.42 -125.26 -2.9 1.51 0.74 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 5 9 178.88 83.93 20.73 1.51 0.54 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 5 9 34.86 39.65 4.47 1.51 0.28 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C5

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 234.91 -125.42 -5 1.51 0.74 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 10 14 123.61 79.31 14.75 1.51 0.52 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 10 14 25.64 37.74 3.37 1.51 0.26 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C6
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 12 16 233.18 125.21 -0.65 1.51 0.74 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 7 11 178.14 -83.75 19.79 1.51 0.54 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 7 11 34.68 -39.59 4.29 1.51 0.27 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C7
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 276.99 -122.02 -9.75 1.51 0.71 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 5 9 206.46 70.3 22.89 1.51 0.47 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 5 9 41.26 33.25 5.83 1.51 0.23 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C8
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 236.76 -117.01 -12.08 1.51 0.7 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 5 9 159.83 73.76 19.23 1.51 0.49 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 8 12 43.41 14.12 31.29 1.51 0.24 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C9
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
1 TO 2 400 X 400 C25 : Fy420 11 15 244.21 8.35 159.21 1.51 0.94 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 6 10 175.15 -32.53 -112.13 1.51 0.74 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 6 10 35.71 -7.93 -55.89 1.51 0.39 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C10
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 11 15 258.89 -1.52 143.96 1.51 0.84 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 6 10 199.55 15.35 -90.39 1.51 0.56 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 6 10 25.06 2.12 -38.21 1.51 0.27 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C11
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 11 15 270.71 6.44 138.21 1.51 0.8 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 6 10 218.98 -22.95 -82.4 1.51 0.53 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 11 15 18.67 -3.14 -35.98 1.51 0.25 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C12
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 11 15 303.42 -0.2 132.1 1.51 0.75 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 11 15 153.77 8.27 -77.42 1.51 0.49 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 11 15 18.4 1.53 -34.49 1.51 0.24 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C13
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 11 15 277.29 2.37 127.24 1.51 0.73 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 11 15 140.51 -1.21 -74.99 1.51 0.47 12-#16 #10 @ 75 + #10 @ 200

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
3 TO 4 400 X 400 C25 : Fy420 11 15 17.71 -0.53 -33.38 1.51 0.23 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C14
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 11 15 302.28 4.76 122.39 1.51 0.7 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 11 15 153.36 -10.11 -72.56 1.51 0.46 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 11 15 18.51 -2.77 -32.27 1.51 0.23 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C15
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 12 16 331.15 117.25 8.23 1.51 0.66 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 11 15 166.55 -1.44 -69.71 1.51 0.43 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 11 15 19.53 -0.36 -31.27 1.51 0.22 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C16
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 11 15 255.71 -4.24 116.81 1.51 0.68 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 6 10 194.63 36.49 -80.38 1.51 0.58 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 6 10 35.48 8.05 -42.08 1.51 0.3 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C17
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 331.73 -119.15 -8.54 1.51 0.67 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 13 17 167.14 -1.4 70.37 1.51 0.44 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 13 17 19.2 -0.34 31.23 1.51 0.22 12-#16 #10 @ 75 + #10 @ 200

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column/Wall : C18
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 13 17 241.93 8.29 -159.1 1.51 0.94 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 8 12 174.95 -32.63 112.43 1.51 0.74 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 8 12 35.4 -7.92 55.96 1.51 0.39 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C19
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 13 17 259.05 -1.62 -144.03 1.51 0.84 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 8 12 200.84 15.52 91.68 1.51 0.57 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 8 12 24.64 2.14 38.22 1.51 0.27 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C20
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 13 17 271.01 6.37 -138.28 1.51 0.8 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 8 12 220.34 -23.04 83.73 1.51 0.54 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 8 12 24.28 -4.16 35.92 1.51 0.25 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C21
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 13 17 303.84 -0.3 -132.18 1.51 0.75 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 13 17 154.05 8.39 78.02 1.51 0.49 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 13 17 18 1.55 34.39 1.51 0.24 12-#16 #10 @ 75 + #10 @ 200

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column/Wall : C22
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 13 17 277.61 2.28 -127.32 1.51 0.73 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 13 17 140.73 -1.16 75.61 1.51 0.48 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 13 17 17.34 -0.5 33.28 1.51 0.23 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C23
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 12 16 292.97 122.93 1.23 1.51 0.7 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 13 17 153.75 -10.13 73.2 1.51 0.47 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 13 17 18.15 -2.75 32.19 1.51 0.23 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C24
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 290.76 -118.45 -10.55 1.51 0.69 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 8 12 195.1 36.66 80.9 1.51 0.58 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 8 12 35.38 8.05 42.27 1.51 0.3 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C25
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 13 17 102.74 12.38 -138.87 1.51 0.91 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 6 10 179.62 -22.3 -85.26 1.51 0.55 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 6 10 45.49 -11.52 -38.4 1.51 0.28 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C26

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 242.45 -133.49 9.92 1.51 0.79 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 5 9 189.26 88.98 -26.29 1.51 0.59 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 5 9 35.64 42.14 -5.84 1.51 0.29 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C27
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 12 16 233.9 132.69 0.55 1.51 0.78 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 7 11 185.56 -87.92 -23.03 1.51 0.57 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 7 11 34.55 -41.34 -4.46 1.51 0.29 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C28
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 237.49 -132.46 5.19 1.51 0.78 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 5 9 181.39 88.36 -23.31 1.51 0.57 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 5 9 35 41.61 -4.98 1.51 0.29 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C29
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 12 16 238.13 132.73 5.31 1.51 0.79 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 12 16 125.31 -83.91 -15.97 1.51 0.55 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 12 16 25.79 -39.8 -3.57 1.51 0.28 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C30
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
1 TO 2 400 X 400 C25 : Fy420 12 16 237.97 132.43 7.43 1.51 0.79 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 7 11 181.45 -88.19 -24.03 1.51 0.58 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 7 11 35.07 -41.56 -5.34 1.51 0.29 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C31
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 12 16 288.46 129.42 10.06 1.51 0.75 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 7 11 212.32 -75.49 -24.66 1.51 0.5 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 7 11 42.92 -34.97 -6.13 1.51 0.24 12-#16 #10 @ 75 + #10 @ 200

Column/Wall : C32
Level Size (mm) Material LC Analysis P (kN) Mx My Pt (%) Interaction Main Reinforcement Links
LC No (kNm) (kNm) Ratio
1 TO 2 400 X 400 C25 : Fy420 10 14 232.21 -123.66 -5.6 1.51 0.74 12-#16 #10 @ 75 + #10 @ 200
2 TO 3 400 X 400 C25 : Fy420 5 9 158.65 76.92 -12.13 1.51 0.49 12-#16 #10 @ 75 + #10 @ 200
3 TO 4 400 X 400 C25 : Fy420 6 10 43.27 14.17 -31.31 1.51 0.24 12-#16 #10 @ 75 + #10 @ 200

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
COLUMN DESIGN CALCULATIONS
Project Name : 3 STOREY COMMERCIAL BUILDING
Client Name : CE 2L
Engineer Name : SHEENA ANG
Design File : D:\new 3 storey\staad 3 storey-Column-1.R1.rcdx
Analysis File : D:\new 3 storey\staad 3 storey.STD
Analysis Last Modified : 11/03/2020 2:37:46 PM

Definitions Of Terms:
All forces in units kN and m
All reinforcement details like area, spacing in mm
Neutral axis angle for resultant design moment is with respect to local major axis.
1 βdns = Ratio to account for reduction of stiffness of columns due to sustained axial loads
2 δns = Moment magnification factor for frames not braced against sidesway
3 Δo = First-order relative deflection between the top and bottom of the story due to Vu in mm
4 ∑Pu = Total factored vertical load in kN. (Clause 10.10.5.2)
5 δu = Design displacement in mm
6 λ = Modification factor reflecting the reduced mechanical properties of concrete
Coefficient defining the relative contribution of concrete strength to nominal wall shear
7 ac =
strength
Cross-sectional area of a structural member measured to the outside edges of transverse
8 Ach =
reinforcement in sqmm
Gross area of concrete section bounded by web thickness and length of section in the
9 Acv =
direction of shear force considered in sqmm
Effective cross-sectional area within a joint in a plane parallel to plane of reinforcement
10 Aj =
generating shear in the joint in sqmm
11 As = Area of non-prestressed longitudinal tension reinforcement in sqmm
12 Avmin = Minimum area of shear reinforcement within spacing 's' in sqmm
13 B = Width of column/ wall in mm
Cross-sectional dimension of member core measured to the outside edges of the transverse
14 bc =
reinforcement composing area Ash in mm
15 c = Distance from extreme compression fiber to neutral axis in mm
16 Cc = Clear cover to longitudinal reinforcement in mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
17 Cm = Factor relating actual moment diagram to an equivalent uniform moment diagram
18 D = Depth / diameter of column in mm
Distance from extreme compression fiber to centroid of longitudinal tension reinforcement
19 d =
in mm
Distance from extreme compression fiber to centroid of longitudinal compression
20 d' =
reinforcement,mm
21 Ec = Modulus of elasticity of concrete in N/sqmm
22 EI = Flexural stiffness of compression member in N-sqmm
23 f'c = Specified compressive strength of concrete cylinder in N/sqmm
24 fy = Specified yield strength of reinforcement in N/sqmm
25 fyt = Specified yield strength fy of transverse reinforcement in N/sqmm
26 hw = Height of entire wall from base to top of wall segment considered in mm
27 Icr = Moment of Inertia of concrete crack section
28 k = Effective length factor for compression member
Length of compression member in a frame, measured center-to-center of the joints in the
29 lc =
frame in mm
Moment of inertia of gross concrete section about centroidal axis neglecting reinforcement
30 lg =
in mm4
31 lw = Length of entire wall in mm
32 lux = Un-supported length for compression member along D in mm
33 luy = Un-supported length for compression member along B in mm
34 MCap = Moment capacity of section for a given NA angle at design Pu in kNm
35 Mcr = Cracking Moment
36 MRes = Resultant design moment at a given load angle to local major axis in kNm
Factored moment amplified for the effects of member curvature used for design of
37 Mc =
compression member in kNm
38 Mm = Factored moment modified to account for effect of axial compression in kNm
39 Mux = Factored moment acting on a section along D in kNm (From Analysis)
40 Muy = Factored moment acting on a section along B in kNm (From Analysis)
41 M1 = Smaller factored end moment on a compression member in kNm
Factored end moment on a compression member at the end at which M1 acts, due to loads
42 M1ns =
that cause no appreciable sidesway in kNm
Factored end moment on compression member at the end at which M1 acts, due to loads
43 M1s =
that cause appreciable sidesway in kNm
44 M1sldr = Smaller factored end moment on a compression member due to slenderness effect in kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
45 M2 = Larger factored end moment on compression member in kNm
46 M2min = Minimum value of moment M2 as per minimum eccentricity of column
Factored end moment on compression member at the end at which M2 acts, due to loads
47 M2ns =
that cause no appreciable sidesway in kNm
Factored end moment on compression member at the end at which M2 acts, due to loads
48 M2s =
that cause appreciable sidesway in kNm
49 M2sldr = Largest factored end moment on a compression member due to slenderness effect in kNm
50 Mnb = Flexure Capacity for Beam
51 Mnc = Flexure Capacity for Column
52 Mnty = Nominal Flexure strength of column at top along depth in kNm
53 Mnby = Nominal Flexure strength of column at bottom along depth in kNm
54 Mntx = Nominal Flexure strength of column at top along width in kNm
55 Mnbx = Nominal Flexure strength of column at bottom along width in kNm
56 Nu = Factored axial force normal to cross section occurring simultaneously with Vu in kN
57 Pc = Critical buckling load in kN
Ratio of area of distributed transverse reinforcement to gross concrete area perpendicular to
58 pt =
that reinforcement
59 Pω = Ratio of As to B x d
60 Q = Stability index for storey
61 r = Radius of gyration of cross section of a compression member in mm
62 Vc = Nominal shear strength provided by concrete in kN
63 Vj = Shear Force acting at the joint in kN
64 Vn = Nominal shear strength in kN
65 Vn' = Nominal shear strength at joint in kN
66 Vus = Factored horizontal shear in a storey in kN
67 Vux = Factored shear at section along D in kN (From Analysis)
68 Vux1 = Shear induced due to column flexural capacity along width, kN
69 Vux2 = Shear due to enhanced earthquake factor along width, kN
70 Vuy = Factored shear at section along B in kN (From Analysis)
71 Vuy1 = Shear induced due to column flexural capacity along depth, kN
72 Vuy2 = Shear due to enhanced earthquake factor along depth, kN
73 y = Neutral axis depth.
74 β = It is a Neutral Axis angle corresponding to load angle to find out MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Code References:
ACI 318M - 2014
Sr.No Element Clause / table
1 Minimum area of longitudinal reinforcement for column : 18.7.4
2 Maximum area of longitudinal reinforcement for column : 18.7.4
3 Minimum longitudinal and transverse reinforcement for wall : 18.10.2.1
4 Minimum diameter of transverse ties : 25.7.2
5 Minimum spacing of transverse ties : 25.7.2
6 Maximum spacing of longitudinal and transverse reinforcement for wall : 18.10.2.1
7 Applicability of boundary element : 18.10.6
8 Area and spacing of special confining reinforcement : 18.7.5
9 Slenderness Moments : 6.2.5
10 Shear Strength provided by concrete for column : 22.5.5
11 Design of shear for non-ductile wall : 11.5.4
12 Design of shear for ductile wall : 18.10.4.1
13 Minimum Flexural Strength of Columns : 18.7.3
14 Shear Check at Column Joint : 18.8.4.1
15 Shear Strength of Column : 18.3.3, 18.4 & 18.6.5
16 fs,perm : 10.6.4
17 fc,perm : 10.2.7.1
18 Wcr : Eq 4.2(a)

Sway Calculation (Stability Index)


For Global-X Direction
Level Load Combination Story Height (m) Gravity Load P Relative Story Shear (kN) Stability Index (Q) Sway Condition
Analysis (kN) Displacements (mm)
A B C D B x C / (A x D)
0m to 4m 9 4 11678.152 15.205 1446.022 0.031 Non Sway
4m to 7m 9 3 6351.276 11.628 1016.035 0.024 Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
7m to 10m 9 3 1024.402 5.949 274.776 0.007 Non Sway

For Global-Y Direction


Level Load Combination Story Height (m) Gravity Load P Relative Story Shear (kN) Stability Index (Q) Sway Condition
Analysis (kN) Displacements (mm)
A B C D B x C / (A x D)
0m to 4m 12 4 11678.166 16.23 1445.85 0.033 Non Sway
4m to 7m 10 3 6351.276 13.036 1016.035 0.027 Non Sway
7m to 10m 10 3 1024.402 7.061 274.776 0.009 Non Sway

General Data
Column No. : C1
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3600 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 357
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Location = Bottom Joint
Put = 80.76 kN
Muxt = -13.92 kNm
Muyt = -56.22 kNm
Vuxt = 48.96 kN
Vuyt = -6.55 kN
Pub = 94.34 kN
Muxb = 12.28 kNm
Muyb = 139.55 kNm
Vuxb = 48.96 kN
Vuyb = -6.55 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 350 x 400 No Beam 37.333 - 3.341
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 350 x 400 No Beam 46.667 - 2.662

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = 12.28 kNm
M2 = -13.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.12
M1 = -56.22 kNm
M2 = 139.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.83
27.12 < 38.83, Column not slender along B

Calculation of Design Moment

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -13.92 - -13.92
Major Axis Mux (bottom) 12.28 - 12.28
Minor Axis Muy (top) -56.22 - -56.22
Minor Axis Muy (bottom) 139.55 - 139.55

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 94.34 kN
Mux = 12.28 kNm
Muy = 139.55 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 346 kN
Mux = 0.38 kNm
Muy = -147.21 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 346 kN
φ Pn = 346 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 84.97 deg
MRes = 140.09 kNm
( φ ) MCap = 152.64 kNm
Capacity Ratio = MRes/ MCap
= 0.918 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 0.69 105.56 871.63 1005.3 120.31 33.8 345 392.7 49.6 120.31 0 49.6 0
350 x 400 270 -0.56 117.57 980.16 1005.3 120.31 70.18 564.21 565.5 70.41 0 120.31 0 70.41

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top - 120.31 120.31 -
Bottom - 49.6 70.41 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 120.31 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 120.31 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 346 kN
Mnty = 204.61 kNm
Pu Bottom = 327.9 kN
Mnby = 202.91 kNm
Vuy1 = 113.2 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 120.31 KN-m
Mnby = 0 KN-m
Vuy2 = 33.42 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 132.32 kN
Muy = 106.51 kNm
Vuy3 = 35.6395 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.2 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 85.7 kNm
φVcy = 76.78 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 60.7 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.39 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3600 mm
Pu Top = 346 kN
Mntx = 204.61 kNm
Pu Bottom = 327.9 kN
Mnbx = 202.91 kNm
Vux1 = 113.2 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Beam Capacity at Joint:
Lux = 3600 mm
Mntx = 120.31 KN-m
Mnbx = 0 KN-m
Vux2 = 33.42 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 94.34 kN
Mux = 139.55 kNm
Vux3 = 48.9567 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.2 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 124.72 kNm
φVcx = 73.3 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 66.49 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 36.65 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C1
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 389
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 180.01 kN
Muxt = -22.21 kNm
Muyt = 85.14 kNm
Vuxt = -45.02 kN
Vuyt = -16.12 kN
Pub = 193.59 kN
Muxb = 26.14 kNm
Muyb = -49.89 kNm
Vuxb = -45.02 kN
Vuyb = -16.12 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 71.111 5000 x 350 x 400 No Beam 37.333 - 3.341
Top 71.111 5000 x 350 x 400 No Beam 37.333 - 3.818
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 No Beam 46.667 - 2.662
Top 71.111 4000 x 350 x 400 No Beam 46.667 - 3.042
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -22.21 kNm
M2 = 26.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = -49.89 kNm
M2 = 85.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -22.21 - -22.21
Major Axis Mux (bottom) 26.14 - 26.14
Minor Axis Muy (top) 85.14 - 85.14
Minor Axis Muy (bottom) -49.89 - -49.89

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 180.01 kN
Mux = -22.21 kNm
Muy = 85.14 kNm

Φ Pn, Max Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 193.59 kN
Mux = 26.14 kNm
Muy = -49.89 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 193.59 kN
φ Pn = 193.59 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 75.38 deg
MRes = 87.99 kNm
( φ ) MCap = 158.92 kNm
Capacity Ratio = MRes/ MCap
= 0.554 < 1

Beam Capacity At Joint:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.17 83.3 676.17 804.24 97.98 9.74 345 392.7 49.6 97.98 0 49.6 0
350 x 400 270 -0.08 89.84 732.89 804.24 97.98 43.09 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 97.98 97.98 -
Bottom - 49.6 56.86 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 97.98 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 0.69 105.56 871.63 1005.3 120.31 33.8 345 392.7 49.6 120.31 0 49.6 0
350 x 400 270 -0.56 117.57 980.16 1005.3 120.31 70.18 564.21 565.5 70.41 0 120.31 0 70.41

Effective Moment for Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 120.31 120.31 -
Bottom - 49.6 70.41 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 120.31 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 120.31 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 193.59 kN
Mnty = 189.66 kNm
Pu Bottom = 180.01 kN
Mnby = 188.32 kNm
Vuy1 = 145.38 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 97.98 KN-m
Mnby = 120.31 KN-m
Vuy2 = 83.96 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 160.09 kN
Muy = 73.68 kNm
Vuy3 = -38.6694 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 145.38 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 48.51 kNm
φVcy = 90.89 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 90.81 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 45.44 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 379.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 379.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 193.59 kN
Mntx = 189.66 kNm
Pu Bottom = 180.01 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 188.32 kNm
Vux1 = 145.38 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 97.98 KN-m
Mnbx = 120.31 KN-m
Vux2 = 83.96 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 142.74 kN
Mux = 80.48 kNm
Vux3 = -41.8121 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 145.38 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 58.04 kNm
φVcx = 86.75 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 97.72 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 43.37 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 408.17 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 408.17 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C1
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 390
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 45.81 kN
Muxt = -11.49 kNm
Muyt = 38.53 kNm
Vuxt = -15.02 kN
Vuyt = -10.01 kN
Pub = 59.39 kN
Muxb = 18.52 kNm
Muyb = -6.52 kNm
Vuxb = -15.02 kN
Vuyb = -10.01 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 No Beam 37.333 - 3.818
Top 71.111 5000 x 350 x 400 No Beam 37.333 - 1.909
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 No Beam 46.667 - 3.042
Top 71.111 4000 x 350 x 400 No Beam 46.667 - 1.521
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -11.49 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M2 = 18.52 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = -6.52 kNm
M2 = 38.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.03
22.52 < 36.03, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -11.49 - -11.49
Major Axis Mux (bottom) 18.52 - 18.52
Minor Axis Muy (top) 38.53 - 38.53
Minor Axis Muy (bottom) -6.52 - -6.52

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 45.81 kN
Mux = -11.49 kNm
Muy = 38.53 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 59.39 kN
Mux = 18.52 kNm
Muy = -6.52 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 59.39 kN
φ Pn = 59.39 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 73.4 deg
MRes = 40.2 kNm
( φ ) MCap = 145.35 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.277 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 0.91 32.97 345 392.7 49.57 8.34 345 392.7 49.6 49.57 0 49.6 0
350 x 400 270 -1.13 37.64 384.54 392.7 49.57 20.86 345 392.7 49.6 0 49.57 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 49.57 49.57 -
Bottom - 49.6 49.6 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 49.6 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 49.6 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.17 83.3 676.17 804.24 97.98 9.74 345 392.7 49.6 97.98 0 49.6 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
350 x 400 270 -0.08 89.84 732.89 804.24 97.98 43.09 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 97.98 97.98 -
Bottom - 49.6 56.86 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 97.98 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 59.39 kN
Mnty = 175.85 kNm
Pu Bottom = 45.81 kN
Mnby = 174.41 kNm
Vuy1 = 134.71 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 49.6 KN-m
Mnby = 97.98 KN-m
Vuy2 = 56.76 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 39.43 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 31.11 kNm
Vuy3 = -13.5244 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.71 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.91 kNm
φVcy = 111.19 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 39.21 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 55.59 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Top = 59.39 kN
Mntx = 175.85 kNm
Pu Bottom = 45.81 kN
Mnbx = 174.41 kNm
Vux1 = 134.71 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 49.6 KN-m
Mnbx = 97.98 KN-m
Vux2 = 56.76 KN
Critical Analysis Load Combination : 12
Critical Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 45.81 kN
Mux = 38.53 kNm
Vux3 = -15.0195 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 134.71 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 31.32 kNm
φVcx = 101.86 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 54.75 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 50.93 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C2
Level : 0m To 4m
Design Code = ACI 318M - 2014

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 365
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 187.24 kN
Muxt = -0.29 kNm
Muyt = -40.05 kNm
Vuxt = 41.78 kN
Vuyt = -1.46 kN
Pub = 200.81 kN
Muxb = 5.56 kNm
Muyb = 127.02 kNm
Vuxb = 41.78 kN
Vuyb = -1.46 kN

Effective Length Calculation


Calculation Along Major Axis Of Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.481
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 No Beam 26.797 - 4.652
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 27.12
M1 = -0.29 kNm
M2 = 5.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.64
27.12 < 34.64, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -40.05 kNm
M2 = 127.02 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.78
27.5 < 37.78, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.29 - -0.29
Major Axis Mux (bottom) 5.56 - 5.56
Minor Axis Muy (top) -40.05 - -40.05
Minor Axis Muy (bottom) 127.02 - 127.02

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 200.81 kN
Mux = 5.56 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 127.02 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 435.04 kN
Mux = -2.28 kNm
Muy = -7.92 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 435.04 kN
φ Pn = 435.04 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87.49 deg
MRes = 127.14 kNm
( φ ) MCap = 165.15 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.77 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.96 99.62 818.74 1005.3 120.31 47.44 402.5 452.4 56.86 120.31 0 56.86 0
350 x 400 180 0.69 105.28 869.1 1005.3 120.31 26.56 345 392.7 49.6 120.31 0 49.6 0
300 x 350 270 -0.81 93.67 864.9 942.48 101.16 32.87 315 339.3 39 0 101.16 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 101.16 -
Bottom 49.6 56.86 39 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 435.04 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnty = 206.51 kNm
Pu Bottom = 416.94 kN
Mnby = 206.12 kNm
Vuy1 = 114.62 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 101.16 KN-m
Mnby = 0 KN-m
Vuy2 = 28.1 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 235.6 kN
Muy = 126.25 kNm
Vuy3 = 50.5895 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.62 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 89.2 kNm
φVcy = 76.48 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 63.57 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.24 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 435.04 kN
Mntx = 206.51 kNm
Pu Bottom = 416.94 kN
Mnbx = 206.12 kNm
Vux1 = 113.05 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 177.17 KN-m
Mnbx = 0 KN-m
Vux2 = 48.54 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 200.81 kN
Mux = 127.02 kNm
Vux3 = 41.7774 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.05 kN
λ = 1
φ = 0.6
deff = 342 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
ρw (50% of As provided) = 0.018
Mm = 95.44 kNm
φVcx = 75.63 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 62.36 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 37.82 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Table For Links
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C2
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 401
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 184.79 kN
Muxt = 84.49 kNm
Muyt = 19.99 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuxt = -14.25 kN
Vuyt = 49.22 kN
Pub = 198.36 kN
Muxb = -63.12 kNm
Muyb = -22.76 kNm
Vuxb = -14.25 kN
Vuyb = 49.22 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.481
Top 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.693
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 4.652
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -63.12 kNm
M2 = 84.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 19.99 kNm
M2 = -22.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 84.49 - 84.49
Major Axis Mux (bottom) -63.12 - -63.12

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (top) 19.99 - 19.99
Minor Axis Muy (bottom) -22.76 - -22.76

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 184.79 kN
Mux = 84.49 kNm
Muy = 19.99 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 240.8 kN
Mux = -8.42 kNm
Muy = -30.46 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 240.8 kN
φ Pn = 240.8 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 13.31 deg
MRes = 86.83 kNm
( φ ) MCap = 160.34 kNm
Capacity Ratio = MRes/ MCap
= 0.542 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.67 77.24 624.18 804.24 97.98 25.63 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.17 84.64 687.76 804.24 97.98 6.39 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 -0.72 74.83 676.3 804.24 87.71 14.13 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.96 99.62 818.74 1005.3 120.31 47.44 402.5 452.4 56.86 120.31 0 56.86 0
350 x 400 180 0.69 105.28 869.1 1005.3 120.31 26.56 345 392.7 49.6 120.31 0 49.6 0
300 x 350 270 -0.81 93.67 864.9 942.48 101.16 32.87 315 339.3 39 0 101.16 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 101.16 -
Bottom 49.6 56.86 39 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 240.8 kN
Mnty = 194.32 kNm
Pu Bottom = 227.22 kN
Mnby = 192.98 kNm
Vuy1 = 148.96 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 101.16 KN-m
Vuy2 = 72.64 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 125.11 kN
Muy = 82.72 kNm
Vuy3 = 47.9649 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 148.96 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 63.05 kNm
φVcy = 85.55 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 105.68 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.77 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 441.44 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 441.44 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 240.8 kN
Mntx = 194.32 kNm
Pu Bottom = 227.22 kN
Mnbx = 192.98 kNm
Vux1 = 146.15 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 177.17 KN-m
Vux2 = 122.55 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 163.96 kN
Mux = 67.22 kNm
Vux3 = -31.7534 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 146.15 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 41.44 kNm
φVcx = 95.35 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 84.66 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 47.67 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 353.65 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 353.65 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C2
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 430
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Location = Top Joint
Put = 34.92 kN
Muxt = 40.14 kNm
Muyt = 4.08 kNm
Vuxt = -6 kN
Vuyt = 18.25 kN
Pub = 48.5 kN
Muxb = -14.59 kNm
Muyb = -13.91 kNm
Vuxb = -6 kN
Vuyb = 18.25 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.693
Top 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 0.847
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 2.658

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = -14.59 kNm
M2 = 40.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.36
19.14 < 38.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 4.08 kNm
M2 = -13.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.52
22.95 < 37.52, Column not slender along B

Calculation of Design Moment

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 40.14 - 40.14
Major Axis Mux (bottom) -14.59 - -14.59
Minor Axis Muy (top) 4.08 - 4.08
Minor Axis Muy (bottom) -13.91 - -13.91

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 34.92 kN
Mux = 40.14 kNm
Muy = 4.08 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 60.61 kN
Mux = -7.09 kNm
Muy = 0.46 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 60.61 kN
φ Pn = 60.61 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 5.8 deg
MRes = 40.35 kNm
( φ ) MCap = 145.15 kNm
Capacity Ratio = MRes/ MCap
= 0.278 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.22 28.97 345 392.7 49.57 12.05 345 392.7 49.6 49.57 0 49.6 0
350 x 400 180 0.91 31.51 345 392.7 49.57 6.27 345 392.7 49.6 49.57 0 49.6 0
300 x 350 270 0.18 22.51 270 314.16 36.18 14.88 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Left Right Left Right
Top 49.57 49.57 36.18 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.67 77.24 624.18 804.24 97.98 25.63 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.17 84.64 687.76 804.24 97.98 6.39 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 -0.72 74.83 676.3 804.24 87.71 14.13 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 60.61 kN
Mnty = 175.98 kNm
Pu Bottom = 47.03 kN
Mnby = 174.54 kNm
Vuy1 = 134.81 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 25.49 kN
Muy = 39.16 kNm
Vuy3 = 17.4829 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.81 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 35.15 kNm
φVcy = 97.94 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 61.45 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 48.97 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 60.61 kN
Mntx = 175.98 kNm
Pu Bottom = 47.03 kN
Mnbx = 174.54 kNm
Vux1 = 132.27 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 10
Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 42 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 26.89 kNm
Vux3 = -3.8616 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.27 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 20.29 kNm
φVcx = 120.54 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 19.54 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.27 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C3
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 366
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 220.83 kN
Muxt = -74.49 kNm
Muyt = 9.26 kNm
Vuxt = -4.19 kN
Vuyt = -50 kN
Pub = 234.41 kN
Muxb = 125.47 kNm
Muyb = -7.52 kNm
Vuxb = -4.19 kN
Vuyb = -50 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.481
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 No Beam 26.797 - 4.652
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = -74.49 kNm
M2 = 125.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -7.52 kNm
M2 = 9.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -74.49 - -74.49
Major Axis Mux (bottom) 125.47 - 125.47
Minor Axis Muy (top) 9.26 - 9.26
Minor Axis Muy (bottom) -7.52 - -7.52

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 234.41 kN
Mux = 125.47 kNm
Muy = -7.52 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 433.25 kN
Mux = 2.29 kNm
Muy = -7.94 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 433.25 kN
φ Pn = 433.25 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 3.43 deg
MRes = 125.7 kNm
( φ ) MCap = 168.2 kNm
Capacity Ratio = MRes/ MCap
= 0.747 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.08 100.71 828.44 1005.3 120.31 23.99 345 392.7 49.6 120.31 0 49.6 0
350 x 400 180 -0.96 99.72 819.65 1005.3 120.31 47.87 402.5 452.4 56.86 120.31 0 56.86 0
300 x 350 270 0.05 92.55 853.42 942.48 101.16 30.93 315 339.3 39 0 101.16 0 39

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 101.16 -
Bottom 56.86 49.6 39 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 433.25 kN
Mnty = 206.47 kNm
Pu Bottom = 415.15 kN
Mnby = 206.09 kNm
Vuy1 = 114.6 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 101.16 KN-m
Mnby = 0 KN-m
Vuy2 = 28.1 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 234.41 kN
Muy = 125.47 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy3 = -50.0032 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.6 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 88.61 kNm
φVcy = 76.55 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 63.42 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.27 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 433.25 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = 206.47 kNm
Pu Bottom = 415.15 kN
Mnbx = 206.09 kNm
Vux1 = 113.03 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 177.17 KN-m
Mnbx = 0 KN-m
Vux2 = 48.54 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 198.9 kN
Mux = 122.19 kNm
Vux3 = 39.9676 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.03 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 90.91 kNm
φVcx = 76.13 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 61.5 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.06 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C3
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 415
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 184.5 kN
Muxt = -83.48 kNm
Muyt = 23.76 kNm
Vuxt = -15.7 kN
Vuyt = -48.19 kN
Pub = 198.08 kN
Muxb = 61.04 kNm
Muyb = -23.32 kNm
Vuxb = -15.7 kN
Vuyb = -48.19 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.481
Top 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.693
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 4.652
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 22.52
M1 = 61.04 kNm
M2 = -83.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -23.32 kNm
M2 = 23.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -83.48 - -83.48
Major Axis Mux (bottom) 61.04 - 61.04
Minor Axis Muy (top) 23.76 - 23.76
Minor Axis Muy (bottom) -23.32 - -23.32

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 184.5 kN
Mux = -83.48 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 23.76 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 240.31 kN
Mux = 8.36 kNm
Muy = -30.62 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 240.31 kN
φ Pn = 240.31 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 15.89 deg
MRes = 86.79 kNm
( φ ) MCap = 158.39 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.548 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.66 82.83 672.12 804.24 97.98 5.77 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.67 77.19 623.7 804.24 97.98 25.66 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 0.19 74.13 669.44 804.24 87.71 12.72 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
350 x 400 0 -1.08 100.71 828.44 1005.3 120.31 23.99 345 392.7 49.6 120.31 0 49.6 0
350 x 400 180 -0.96 99.72 819.65 1005.3 120.31 47.87 402.5 452.4 56.86 120.31 0 56.86 0
300 x 350 270 0.05 92.55 853.42 942.48 101.16 30.93 315 339.3 39 0 101.16 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 101.16 -
Bottom 56.86 49.6 39 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 240.31 kN
Mnty = 194.27 kNm
Pu Bottom = 226.74 kN
Mnby = 192.93 kNm
Vuy1 = 148.92 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 101.16 KN-m
Vuy2 = 72.64 KN
Critical Analysis Load Combination : 16

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 124.94 kN
Muy = 81.65 kNm
Vuy3 = -46.9111 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 148.92 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 62 kNm
φVcy = 85.88 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 105.07 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.94 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 438.89 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 438.89 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 240.31 kN
Mntx = 194.27 kNm
Pu Bottom = 226.74 kN
Mnbx = 192.93 kNm
Vux1 = 146.11 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 177.17 KN-m
Vux2 = 122.55 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 163.78 kN
Mux = 65.21 kNm
Vux3 = -30.7485 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 146.11 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 39.46 kNm
φVcx = 96.83 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 82.14 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 48.41 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 343.1 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 343.1 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C3
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 431
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 34.92 kN
Muxt = -39.37 kNm
Muyt = 5.02 kNm
Vuxt = -5.96 kN
Vuyt = -17.84 kN
Pub = 48.5 kN
Muxb = 14.15 kNm
Muyb = -12.84 kNm
Vuxb = -5.96 kN
Vuyb = -17.84 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.693
Top 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 0.847
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 2.658
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = 14.15 kNm
M2 = -39.37 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.31
19.14 < 38.31, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 5.02 kNm
M2 = -12.84 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.69
22.95 < 38.69, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -39.37 - -39.37
Major Axis Mux (bottom) 14.15 - 14.15
Minor Axis Muy (top) 5.02 - 5.02
Minor Axis Muy (bottom) -12.84 - -12.84

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 34.92 kN
Mux = -39.37 kNm
Muy = 5.02 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 60.8 kN
Mux = 5.55 kNm
Muy = 0.22 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 60.8 kN
φ Pn = 60.8 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 7.27 deg
MRes = 39.69 kNm
( φ ) MCap = 144.87 kNm
Capacity Ratio = MRes/ MCap
= 0.274 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.34 30.71 345 392.7 49.57 5.36 345 392.7 49.6 49.57 0 49.6 0
350 x 400 180 -0.22 29.16 345 392.7 49.57 12.14 345 392.7 49.6 49.57 0 49.6 0
300 x 350 270 -0.42 21.67 270 314.16 36.18 14.59 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 36.18 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.66 82.83 672.12 804.24 97.98 5.77 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.67 77.19 623.7 804.24 97.98 25.66 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 0.19 74.13 669.44 804.24 87.71 12.72 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 60.8 kN
Mnty = 176 kNm
Pu Bottom = 47.22 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnby = 174.56 kNm
Vuy1 = 134.83 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 25.37 kN
Muy = 38.39 kNm
Vuy3 = -17.0809 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.83 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 34.4 kNm
φVcy = 98.65 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 60.29 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 49.33 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 60.8 kN
Mntx = 176 kNm
Pu Bottom = 47.22 kN
Mnbx = 174.56 kNm
Vux1 = 132.29 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 10
Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 42.11 kN
Mux = 26.74 kNm
Vux3 = -4.1126 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.29 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 20.12 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcx = 121 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 18.8 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.5 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C4
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 367
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 220.84 kN
Muxt = 74.05 kNm
Muyt = 7.45 kNm
Vuxt = -2.59 kN
Vuyt = 49.84 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pub = 234.42 kN
Muxb = -125.26 kNm
Muyb = -2.9 kNm
Vuxb = -2.59 kN
Vuyb = 49.84 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.481
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 No Beam 26.797 - 4.652
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = 74.05 kNm
M2 = -125.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -2.9 kNm
M2 = 7.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.66
27.5 < 38.66, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 74.05 - 74.05
Major Axis Mux (bottom) -125.26 - -125.26
Minor Axis Muy (top) 7.45 - 7.45
Minor Axis Muy (bottom) -2.9 - -2.9

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 234.42 kN
Mux = -125.26 kNm
Muy = -2.9 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 412.33 kN
Mux = -10.28 kNm
Muy = -126.1 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 412.33 kN
φ Pn = 412.33 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 1.32 deg
MRes = 125.29 kNm
( φ ) MCap = 169.07 kNm
Capacity Ratio = MRes/ MCap
= 0.741 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.08 98.03 804.7 1005.3 120.31 46.83 402.5 452.4 56.86 120.31 0 56.86 0
350 x 400 180 -1.08 100.65 827.9 1005.3 120.31 23.87 345 392.7 49.6 120.31 0 49.6 0
300 x 350 270 -0.58 87.78 804.98 942.48 101.16 28.68 315 339.3 39 0 101.16 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 101.16 -
Bottom 49.6 56.86 39 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 412.33 kN
Mnty = 206.02 kNm
Pu Bottom = 394.23 kN
Mnby = 205.64 kNm
Vuy1 = 114.35 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 101.16 KN-m
Mnby = 0 KN-m
Vuy2 = 28.1 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 234.42 kN
Muy = 125.26 kNm
Vuy3 = 49.8408 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.35 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 88.4 kNm
φVcy = 76.55 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 63 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.28 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 412.33 kN
Mntx = 206.02 kNm
Pu Bottom = 394.23 kN
Mnbx = 205.64 kNm
Vux1 = 112.78 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 177.17 KN-m
Mnbx = 0 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vux2 = 48.54 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 205.2 kN
Mux = 116.52 kNm
Vux3 = 37.9885 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 112.78 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 84.25 kNm
φVcx = 76.93 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 59.76 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.47 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C4
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 405
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 178.88 kN
Muxt = 83.93 kNm
Muyt = 20.73 kNm
Vuxt = -14.19 kN
Vuyt = 48.44 kN
Pub = 192.46 kN
Muxb = -61.36 kNm
Muyb = -21.83 kNm
Vuxb = -14.19 kN
Vuyb = 48.44 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.481
Top 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.693
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 4.652
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -61.36 kNm
M2 = 83.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Klux /r = 22.95
M1 = 20.73 kNm
M2 = -21.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 83.93 - 83.93
Major Axis Mux (bottom) -61.36 - -61.36
Minor Axis Muy (top) 20.73 - 20.73
Minor Axis Muy (bottom) -21.83 - -21.83

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 178.88 kN
Mux = 83.93 kNm
Muy = 20.73 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 229.54 kN
Mux = -13.26 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = -33.69 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 229.54 kN
φ Pn = 229.54 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 13.87 deg
MRes = 86.45 kNm
( φ ) MCap = 159.33 kNm
Capacity Ratio = MRes/ MCap
= 0.543 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
350 x 400 0 -0.65 75.39 608.42 804.24 97.98 25.05 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.66 82.74 671.31 804.24 97.98 5.68 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 -0.47 70.16 630.89 804.24 87.71 11.37 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.08 98.03 804.7 1005.3 120.31 46.83 402.5 452.4 56.86 120.31 0 56.86 0
350 x 400 180 -1.08 100.65 827.9 1005.3 120.31 23.87 345 392.7 49.6 120.31 0 49.6 0
300 x 350 270 -0.58 87.78 804.98 942.48 101.16 28.68 315 339.3 39 0 101.16 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 101.16 -

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 49.6 56.86 39 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 229.54 kN
Mnty = 193.21 kNm
Pu Bottom = 215.96 kN
Mnby = 191.87 kNm
Vuy1 = 148.1 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 101.16 KN-m
Vuy2 = 72.64 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 124.89 kN
Muy = 81.05 kNm
Vuy3 = 46.4658 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 148.1 kN
λ = 1
φ = 0.6

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 61.41 kNm
φVcy = 85.96 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 103.57 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.98 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 432.63 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 432.63 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 229.54 kN
Mntx = 193.21 kNm
Pu Bottom = 215.96 kN
Mnbx = 191.87 kNm
Vux1 = 145.31 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 177.17 KN-m
Vux2 = 122.55 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 161.98 kN
Mux = 63.16 kNm
Vux3 = -29.9716 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 145.31 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 37.69 kNm
φVcx = 98.11 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 78.66 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 49.06 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C4
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 432
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 34.86 kN
Muxt = 39.65 kNm
Muyt = 4.47 kNm
Vuxt = -5.74 kN
Vuyt = 18.1 kN
Pub = 48.44 kN
Muxb = -14.65 kNm
Muyb = -12.75 kNm
Vuxb = -5.74 kN
Vuyb = 18.1 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.693

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 0.847
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 2.658
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = -14.65 kNm
M2 = 39.65 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.43
19.14 < 38.43, Column not slender along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 4.47 kNm
M2 = -12.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.21
22.95 < 38.21, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 39.65 - 39.65
Major Axis Mux (bottom) -14.65 - -14.65
Minor Axis Muy (top) 4.47 - 4.47
Minor Axis Muy (bottom) -12.75 - -12.75

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 34.86 kN
Mux = 39.65 kNm
Muy = 4.47 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 60.25 kN
Mux = -7.39 kNm
Muy = 0.27 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 60.25 kN
φ Pn = 60.25 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 6.43 deg
MRes = 39.9 kNm
( φ ) MCap = 145.04 kNm
Capacity Ratio = MRes/ MCap
= 0.275 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.34 29.14 345 392.7 49.57 12.14 345 392.7 49.6 49.57 0 49.6 0
350 x 400 180 -0.34 30.81 345 392.7 49.57 5.42 345 392.7 49.6 49.57 0 49.6 0
300 x 350 270 0.07 20.77 270 314.16 36.18 14.04 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 36.18 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.65 75.39 608.42 804.24 97.98 25.05 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.66 82.74 671.31 804.24 97.98 5.68 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 -0.47 70.16 630.89 804.24 87.71 11.37 270 314.16 36.2 0 87.71 0 36.2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 60.25 kN
Mnty = 175.94 kNm
Pu Bottom = 46.68 kN
Mnby = 174.5 kNm
Vuy1 = 134.78 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 25.22 kN
Muy = 38.41 kNm
Vuy3 = 17.0163 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.78 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 34.45 kNm
φVcy = 98.6 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 60.32 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 49.3 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 60.25 kN
Mntx = 175.94 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 46.68 kN
Mnbx = 174.5 kNm
Vux1 = 132.24 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 19.8 kN
Mux = 14.96 kNm
Vux3 = -2.1832 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.24 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 11.84 kNm
φVcx = 121.13 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 18.51 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.57 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C5
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 368
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 221.34 kN
Muxt = 74.37 kNm
Muyt = 8.28 kNm
Vuxt = -3.32 kN
Vuyt = 49.96 kN
Pub = 234.91 kN
Muxb = -125.42 kNm
Muyb = -5 kNm
Vuxb = -3.32 kN
Vuyb = 49.96 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 1.335
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 No Beam 26.797 - 4.652
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M1 = 74.37 kNm
M2 = -125.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -5 kNm
M2 = 8.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 74.37 - 74.37
Major Axis Mux (bottom) -125.42 - -125.42
Minor Axis Muy (top) 8.28 - 8.28
Minor Axis Muy (bottom) -5 - -5

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 234.91 kN
Mux = -125.42 kNm
Muy = -5 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 379.17 kN
Mux = -7.73 kNm
Muy = -121.57 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 379.17 kN
φ Pn = 379.17 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 2.28 deg
MRes = 125.52 kNm
( φ ) MCap = 168.72 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.744 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.09 93.98 769.06 804.24 97.98 48.06 402.5 452.4 56.86 97.98 0 56.86 0
350 x 400 180 -1.08 93.94 768.69 804.24 97.98 48.11 402.5 452.4 56.86 97.98 0 56.86 0
300 x 350 270 -0.41 85.93 786.32 804.24 87.71 26.79 299.68 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 56.86 56.86 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 154.84 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 379.17 kN
Mnty = 205.32 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 361.06 kN
Mnby = 204.93 kNm
Vuy1 = 113.96 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 87.71 KN-m
Mnby = 0 KN-m
Vuy2 = 24.36 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 233.99 kN
Muy = 125.42 kNm
Vuy3 = -49.9641 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.96 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 88.62 kNm
φVcy = 76.49 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 62.45 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.24 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 379.17 kN
Mntx = 205.32 kNm
Pu Bottom = 361.06 kN
Mnbx = 204.93 kNm
Vux1 = 112.4 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 154.84 KN-m
Mnbx = 0 KN-m
Vux2 = 42.42 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 182.82 kN
Mux = 112.02 kNm
Vux3 = 36.4265 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 112.4 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 83.27 kNm
φVcx = 77.02 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 58.95 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.51 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C5
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 412
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Top Joint
Put = 123.61 kN
Muxt = 79.31 kNm
Muyt = 14.75 kNm
Vuxt = -9.9 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyt = 45.71 kN
Pub = 133.79 kN
Muxb = -57.78 kNm
Muyb = -14.93 kNm
Vuxb = -9.9 kN
Vuyb = 45.71 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 1.335
Top 71.111 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 1.525
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 4.652
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -57.78 kNm
M2 = 79.31 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 14.75 kNm
M2 = -14.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 79.31 - 79.31
Major Axis Mux (bottom) -57.78 - -57.78
Minor Axis Muy (top) 14.75 - 14.75

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (bottom) -14.93 - -14.93

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 123.61 kN
Mux = 79.31 kNm
Muy = 14.75 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 211.38 kN
Mux = -3.61 kNm
Muy = -33.39 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 211.38 kN
φ Pn = 211.38 kN
Pt min for φ Pn = 0.5 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 10.54 deg
MRes = 80.67 kNm
( φ ) MCap = 154.57 kNm
Capacity Ratio = MRes/ MCap
= 0.522 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.65 72.67 585.32 603.18 74.78 26.31 345 392.7 49.6 74.78 0 49.6 0
350 x 400 180 -0.65 72.64 585.05 603.18 74.78 26.32 345 392.7 49.6 74.78 0 49.6 0
300 x 350 270 -0.29 69.01 619.76 804.24 87.71 10.17 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 74.78 74.78 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 124.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.09 93.98 769.06 804.24 97.98 48.06 402.5 452.4 56.86 97.98 0 56.86 0
350 x 400 180 -1.08 93.94 768.69 804.24 97.98 48.11 402.5 452.4 56.86 97.98 0 56.86 0
300 x 350 270 -0.41 85.93 786.32 804.24 87.71 26.79 299.68 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 56.86 56.86 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 154.84 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 211.38 kN
Mnty = 191.41 kNm
Pu Bottom = 197.81 kN
Mnby = 190.07 kNm
Vuy1 = 146.73 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 87.71 KN-m
Vuy2 = 67.47 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 123.2 kN
Muy = 79.33 kNm
Vuy3 = -45.7282 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 146.73 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 59.96 kNm
φVcy = 86.26 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 100.78 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Check for Minimum Shear Reinforcement
0.5 x φVcy = 43.13 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 420.96 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 420.96 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 211.38 kN
Mntx = 191.41 kNm
Pu Bottom = 197.81 kN
Mnbx = 190.07 kNm
Vux1 = 143.96 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 124.38 KN-m
Mnbx = 154.84 KN-m
Vux2 = 105.36 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 149.09 kN
Mux = 61.46 kNm
Vux3 = -29.3273 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 143.96 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 38.02 kNm
φVcx = 97.54 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 77.37 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 48.77 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C5
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 433
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Top Joint

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Put = 25.64 kN
Muxt = 37.74 kNm
Muyt = 3.37 kNm
Vuxt = -3.95 kN
Vuyt = 16.18 kN
Pub = 35.82 kN
Muxb = -10.8 kNm
Muyb = -8.48 kNm
Vuxb = -3.95 kN
Vuyb = 16.18 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 1.525
Top 71.111 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 0.763
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 2.658
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = -10.8 kNm
M2 = 37.74 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.44
19.14 < 37.44, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 3.37 kNm
M2 = -8.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.76
22.95 < 38.76, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
A B C
Major Axis Mux (top) 37.74 - 37.74
Major Axis Mux (bottom) -10.8 - -10.8
Minor Axis Muy (top) 3.37 - 3.37
Minor Axis Muy (bottom) -8.48 - -8.48

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 25.64 kN
Mux = 37.74 kNm
Muy = 3.37 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 56.38 kN
Mux = -0.84 kNm
Muy = -0.17 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 56.38 kN
φ Pn = 56.38 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 5.1 deg
MRes = 37.89 kNm
( φ ) MCap = 144 kNm
Capacity Ratio = MRes/ MCap
= 0.263 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.35 28.61 345 392.7 49.57 12.14 345 392.7 49.6 49.57 0 49.6 0
350 x 400 180 -0.34 28.62 345 392.7 49.57 12.13 345 392.7 49.6 49.57 0 49.6 0
300 x 350 270 -0.12 20.23 270 314.16 36.18 13.47 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 49.57 49.57 36.18 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.65 72.67 585.32 603.18 74.78 26.31 345 392.7 49.6 74.78 0 49.6 0
350 x 400 180 -0.65 72.64 585.05 603.18 74.78 26.32 345 392.7 49.6 74.78 0 49.6 0
300 x 350 270 -0.29 69.01 619.76 804.24 87.71 10.17 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 74.78 74.78 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 124.38 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 56.38 kN
Mnty = 175.53 kNm
Pu Bottom = 42.81 kN
Mnby = 174.09 kNm
Vuy1 = 134.47 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 25.64 kN
Muy = 37.74 kNm
Vuy3 = 16.1845 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.47 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 33.71 kNm
φVcy = 99.24 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 58.71 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 49.62 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 56.38 kN
Mntx = 175.53 kNm
Pu Bottom = 42.81 kN
Mnbx = 174.09 kNm
Vux1 = 131.93 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 124.38 KN-m
Vux2 = 84.36 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 17.06 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 14.35 kNm
Vux3 = -2.2249 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 131.93 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 11.67 kNm
φVcx = 120.84 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 18.48 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.42 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C6
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 369
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 219.6 kN
Muxt = -73.97 kNm
Muyt = 6.56 kNm
Vuxt = -1.8 kN
Vuyt = -49.81 kN
Pub = 233.18 kN
Muxb = 125.21 kNm
Muyb = -0.65 kNm
Vuxb = -1.8 kN
Vuyb = -49.81 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.481
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 No Beam 26.797 - 4.652
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = -73.97 kNm
M2 = 125.21 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -0.65 kNm
M2 = 6.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.19
27.5 < 35.19, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -73.97 - -73.97
Major Axis Mux (bottom) 125.21 - 125.21
Minor Axis Muy (top) 6.56 - 6.56
Minor Axis Muy (bottom) -0.65 - -0.65

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 233.18 kN
Mux = 125.21 kNm
Muy = -0.65 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 410.23 kN
Mux = -5.09 kNm
Muy = -117.07 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 410.23 kN
φ Pn = 410.23 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 0.3 deg
MRes = 125.21 kNm
( φ ) MCap = 169.37 kNm
Capacity Ratio = MRes/ MCap
= 0.739 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.15 100.23 824.17 1005.3 120.31 24.83 345 392.7 49.6 120.31 0 49.6 0
350 x 400 180 -1.09 97.85 803.1 804.24 97.98 46.85 402.5 452.4 56.86 97.98 0 56.86 0
300 x 350 270 -0.28 84.01 767.11 804.24 87.71 24.91 278.15 314.16 36.2 0 87.71 0 36.2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 120.31 87.71 -
Bottom 56.86 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 410.23 kN
Mnty = 205.98 kNm
Pu Bottom = 392.13 kN
Mnby = 205.59 kNm
Vuy1 = 114.33 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 87.71 KN-m
Mnby = 0 KN-m
Vuy2 = 24.36 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 233.18 kN
Muy = 125.21 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy3 = -49.8077 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.33 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 88.55 kNm
φVcy = 76.53 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 62.99 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.27 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 410.23 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = 205.98 kNm
Pu Bottom = 392.13 kN
Mnbx = 205.59 kNm
Vux1 = 112.76 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 177.17 KN-m
Mnbx = 0 KN-m
Vux2 = 48.54 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 205.49 kN
Mux = 107.52 kNm
Vux3 = 34.873 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 112.76 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 75.21 kNm
φVcx = 78.28 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 57.46 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 39.14 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C6
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 413
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 178.14 kN
Muxt = -83.75 kNm
Muyt = 19.79 kNm
Vuxt = -13.82 kN
Vuyt = -48.31 kN
Pub = 191.72 kN
Muxb = 61.15 kNm
Muyb = -21.67 kNm
Vuxb = -13.82 kN
Vuyb = -48.31 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.481
Top 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.693
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 4.652
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 22.52
M1 = 61.15 kNm
M2 = -83.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 19.79 kNm
M2 = -21.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -83.75 - -83.75
Major Axis Mux (bottom) 61.15 - 61.15
Minor Axis Muy (top) 19.79 - 19.79
Minor Axis Muy (bottom) -21.67 - -21.67

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 178.14 kN
Mux = -83.75 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 19.79 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 228.58 kN
Mux = 6.28 kNm
Muy = -33.18 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 228.58 kN
φ Pn = 228.58 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 13.3 deg
MRes = 86.06 kNm
( φ ) MCap = 159.66 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.539 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.63 82.34 667.9 804.24 97.98 6.28 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.65 75.31 607.72 804.24 97.98 25.08 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 -0.14 67.79 607.95 804.24 87.71 8.99 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
350 x 400 0 -1.15 100.23 824.17 1005.3 120.31 24.83 345 392.7 49.6 120.31 0 49.6 0
350 x 400 180 -1.09 97.85 803.1 804.24 97.98 46.85 402.5 452.4 56.86 97.98 0 56.86 0
300 x 350 270 -0.28 84.01 767.11 804.24 87.71 24.91 278.15 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 120.31 87.71 -
Bottom 56.86 49.6 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 228.58 kN
Mnty = 193.11 kNm
Pu Bottom = 215 kN
Mnby = 191.77 kNm
Vuy1 = 148.03 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 87.71 KN-m
Vuy2 = 67.47 KN
Critical Analysis Load Combination : 16

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 124.29 kN
Muy = 80.9 kNm
Vuy3 = -46.3635 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 148.03 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 61.35 kNm
φVcy = 85.97 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 103.43 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.99 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 432.05 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 432.05 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 228.58 kN
Mntx = 193.11 kNm
Pu Bottom = 215 kN
Mnbx = 191.77 kNm
Vux1 = 145.24 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 177.17 KN-m
Vux2 = 122.55 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 161.15 kN
Mux = 59.76 kNm
Vux3 = -28.6922 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 145.24 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 34.42 kNm
φVcx = 101.18 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 73.43 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 50.59 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C6
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 434
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 34.68 kN
Muxt = -39.59 kNm
Muyt = 4.29 kNm
Vuxt = -5.77 kN
Vuyt = -18.02 kN
Pub = 48.26 kN
Muxb = 14.47 kNm
Muyb = -13 kNm
Vuxb = -5.77 kN
Vuyb = -18.02 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.693
Top 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 0.847
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 2.658
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = 14.47 kNm
M2 = -39.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.39
19.14 < 38.39, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 4.29 kNm
M2 = -13 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.96
22.95 < 37.96, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -39.59 - -39.59
Major Axis Mux (bottom) 14.47 - 14.47
Minor Axis Muy (top) 4.29 - 4.29
Minor Axis Muy (bottom) -13 - -13

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 34.68 kN
Mux = -39.59 kNm
Muy = 4.29 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 59.99 kN
Mux = 7.12 kNm
Muy = -13.42 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 59.99 kN
φ Pn = 59.99 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 6.18 deg
MRes = 39.82 kNm
( φ ) MCap = 145.07 kNm
Capacity Ratio = MRes/ MCap
= 0.274 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.43 30.72 345 392.7 49.57 5.45 345 392.7 49.6 49.57 0 49.6 0
350 x 400 180 -0.35 29.17 345 392.7 49.57 12.12 345 392.7 49.6 49.57 0 49.6 0
300 x 350 270 -0.29 19.64 270 314.16 36.18 12.9 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 36.18 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.63 82.34 667.9 804.24 97.98 6.28 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.65 75.31 607.72 804.24 97.98 25.08 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 -0.14 67.79 607.95 804.24 87.71 8.99 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 59.97 kN
Mnty = 175.91 kNm
Pu Bottom = 46.4 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnby = 174.47 kNm
Vuy1 = 134.76 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 25.08 kN
Muy = 38.4 kNm
Vuy3 = -16.9801 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.76 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 34.45 kNm
φVcy = 98.58 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 60.3 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 49.29 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 59.97 kN
Mntx = 175.91 kNm
Pu Bottom = 46.4 kN
Mnbx = 174.47 kNm
Vux1 = 132.22 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 19.98 kN
Mux = 13.74 kNm
Vux3 = -2.2696 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.22 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 10.6 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcx = 121.15 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 18.45 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.58 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C7
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 370
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 263.42 kN
Muxt = 67.47 kNm
Muyt = 10.16 kNm
Vuxt = -4.98 kN
Vuyt = 47.39 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pub = 276.99 kN
Muxb = -122.02 kNm
Muyb = -9.75 kNm
Vuxb = -4.98 kN
Vuyb = 47.39 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 1.665
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 No Beam 26.797 - 4.652
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = 67.47 kNm
M2 = -122.02 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -9.75 kNm
M2 = 10.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 67.47 - 67.47
Major Axis Mux (bottom) -122.02 - -122.02
Minor Axis Muy (top) 10.16 - 10.16
Minor Axis Muy (bottom) -9.75 - -9.75

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 276.99 kN
Mux = -122.02 kNm
Muy = -9.75 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 437.76 kN
Mux = -7.34 kNm
Muy = -111.62 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 437.76 kN
φ Pn = 437.76 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 4.57 deg
MRes = 122.41 kNm
( φ ) MCap = 172.26 kNm
Capacity Ratio = MRes/ MCap
= 0.711 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -2.24 108.27 895.89 1005.3 120.31 26.54 345 392.7 49.6 120.31 0 49.6 0
350 x 400 180 -1.15 103.37 852.03 1005.3 120.31 23.43 345 392.7 49.6 120.31 0 49.6 0
300 x 350 270 -0.45 81.49 741.92 804.24 87.71 22.39 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 87.71 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 169.92 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 437.76 kN
Mnty = 206.57 kNm
Pu Bottom = 419.65 kN
Mnby = 206.18 kNm
Vuy1 = 114.65 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 87.71 KN-m
Mnby = 0 KN-m
Vuy2 = 24.36 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 276.99 kN
Muy = 122.02 kNm
Vuy3 = 47.3863 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.65 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 78.46 kNm
φVcy = 77.96 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 61.15 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.98 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 437.76 kN
Mntx = 206.57 kNm
Pu Bottom = 419.65 kN
Mnbx = 206.18 kNm
Vux1 = 113.08 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 169.92 KN-m
Mnbx = 0 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vux2 = 46.55 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 231.25 kN
Mux = 102.15 kNm
Vux3 = 33.1116 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.08 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 65.78 kNm
φVcx = 80.13 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 54.92 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 40.07 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C7
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 414
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 206.46 kN
Muxt = 70.3 kNm
Muyt = 22.89 kNm
Vuxt = -14.91 kN
Vuyt = 38.89 kN
Pub = 220.04 kN
Muxb = -46.33 kNm
Muyb = -21.81 kNm
Vuxb = -14.91 kN
Vuyb = 38.89 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 1.665
Top 71.111 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 1.903
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 4.652
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -46.33 kNm
M2 = 70.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Klux /r = 22.95
M1 = -21.81 kNm
M2 = 22.89 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 70.3 - 70.3
Major Axis Mux (bottom) -46.33 - -46.33
Minor Axis Muy (top) 22.89 - 22.89
Minor Axis Muy (bottom) -21.81 - -21.81

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 206.46 kN
Mux = 70.3 kNm
Muy = 22.89 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 245.95 kN
Mux = 0.69 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = -22.91 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 245.95 kN
φ Pn = 245.95 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 18.04 deg
MRes = 73.93 kNm
( φ ) MCap = 158.08 kNm
Capacity Ratio = MRes/ MCap
= 0.468 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
350 x 400 0 -0.91 86.41 703.03 804.24 97.98 5.82 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.63 84.66 687.89 804.24 97.98 5.19 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 -0.3 66.25 593.23 603.18 67.29 7.5 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 67.29 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 67.29 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -2.24 108.27 895.89 1005.3 120.31 26.54 345 392.7 49.6 120.31 0 49.6 0
350 x 400 180 -1.15 103.37 852.03 1005.3 120.31 23.43 345 392.7 49.6 120.31 0 49.6 0
300 x 350 270 -0.45 81.49 741.92 804.24 87.71 22.39 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 87.71 -

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 169.92 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 245.95 kN
Mnty = 194.82 kNm
Pu Bottom = 230.11 kN
Mnby = 193.26 kNm
Vuy1 = 149.26 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 67.29 KN-m
Mnby = 87.71 KN-m
Vuy2 = 59.61 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 148.31 kN
Muy = 71.17 kNm
Vuy3 = -39.5482 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 149.26 kN
λ = 1
φ = 0.6

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 47.85 kNm
φVcy = 91.92 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 95.57 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 45.96 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 399.22 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 399.22 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 245.95 kN
Mntx = 194.82 kNm
Pu Bottom = 230.11 kN
Mnbx = 193.26 kNm
Vux1 = 146.45 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 169.92 KN-m
Vux2 = 119.81 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 171.59 kN
Mux = 57.75 kNm
Vux3 = -28.0829 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 146.45 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 30.77 kNm
φVcx = 105.73 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 67.87 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 52.86 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C7
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 435
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 41.26 kN
Muxt = 33.25 kNm
Muyt = 5.83 kNm
Vuxt = -5.91 kN
Vuyt = 12.83 kN
Pub = 54.83 kN
Muxb = -5.22 kNm
Muyb = -11.91 kNm
Vuxb = -5.91 kN
Vuyb = 12.83 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 1.903

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 71.111 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 0.951
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.86

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 No Beam 26.797 - 5.317
Top 71.111 4000 x 300 x 350 No Beam 26.797 - 2.658
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.86
r = 115.47 mm
Kluy /r = 19.36
M1 = -5.22 kNm
M2 = 33.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.88
19.36 < 35.88, Column not slender along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 5.83 kNm
M2 = -11.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.88
22.95 < 39.88, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 33.25 - 33.25
Major Axis Mux (bottom) -5.22 - -5.22
Minor Axis Muy (top) 5.83 - 5.83
Minor Axis Muy (bottom) -11.91 - -11.91

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 41.26 kN
Mux = 33.25 kNm
Muy = 5.83 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 64.36 kN
Mux = 0.18 kNm
Muy = -13.43 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 64.36 kN
φ Pn = 64.36 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 9.95 deg
MRes = 33.76 kNm
( φ ) MCap = 145.05 kNm
Capacity Ratio = MRes/ MCap
= 0.233 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.36 32.12 345 392.7 49.57 6.35 345 392.7 49.6 49.57 0 49.6 0
350 x 400 180 -0.43 31.1 345 392.7 49.57 5.29 345 392.7 49.6 49.57 0 49.6 0
300 x 350 270 -0.14 18.85 270 314.16 36.18 12.12 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 36.18 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.91 86.41 703.03 804.24 97.98 5.82 345 392.7 49.6 97.98 0 49.6 0
350 x 400 180 -0.63 84.66 687.89 804.24 97.98 5.19 345 392.7 49.6 97.98 0 49.6 0
300 x 350 270 -0.3 66.25 593.23 603.18 67.29 7.5 270 314.16 36.2 0 67.29 0 36.2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 67.29 -
Bottom 49.6 49.6 36.2 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 67.29 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 64.36 kN
Mnty = 176.38 kNm
Pu Bottom = 48.52 kN
Mnby = 174.69 kNm
Vuy1 = 135.03 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 67.29 KN-m
Vuy2 = 39.81 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 30.79 kN
Muy = 33.19 kNm
Vuy3 = 12.8151 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 135.03 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 28.35 kNm
φVcy = 105.76 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 48.79 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 52.88 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 64.36 kN
Mntx = 176.38 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 48.52 kN
Mnbx = 174.69 kNm
Vux1 = 132.48 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 23.35 kN
Mux = 13.06 kNm
Vux3 = -2.2268 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.48 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 9.39 kNm
φVcx = 121.51 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 18.29 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.75 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C8
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3600 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 362
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 223.18 kN
Muxt = 57.31 kNm
Muyt = 10.56 kNm
Vuxt = -5.66 kN
Vuyt = 43.59 kN
Pub = 236.76 kN
Muxb = -117.01 kNm
Muyb = -12.08 kNm
Vuxb = -5.66 kN
Vuyb = 43.59 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 5000 x 350 x 400 - 37.333 3.341
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 350 x 400 No Beam 46.667 - 2.662
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M1 = 57.31 kNm
M2 = -117.01 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.88
27.12 < 39.88, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.12
M1 = 10.56 kNm
M2 = -12.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 57.31 - 57.31
Major Axis Mux (bottom) -117.01 - -117.01
Minor Axis Muy (top) 10.56 - 10.56
Minor Axis Muy (bottom) -12.08 - -12.08

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 236.76 kN
Mux = -117.01 kNm
Muy = -12.08 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 327.52 kN
Mux = -14.4 kNm
Muy = -109.09 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 327.52 kN
φ Pn = 327.52 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 5.89 deg
MRes = 117.63 kNm
( φ ) MCap = 167.72 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.701 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 180 -2.24 105.29 869.23 1005.3 120.31 34.9 355.83 392.7 49.6 120.31 0 49.6 0
350 x 400 270 -1.46 95.88 785.78 804.24 97.98 47.04 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 - 97.98 -
Bottom 49.6 - 56.86 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 120.31 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 327.52 kN
Mnty = 202.87 kNm
Pu Bottom = 309.41 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnby = 201.08 kNm
Vuy1 = 112.21 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 97.98 KN-m
Mnby = 0 KN-m
Vuy2 = 27.22 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 130.77 kN
Muy = 106.69 kNm
Vuy3 = -35.7796 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 112.21 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 86.13 kNm
φVcy = 76.63 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 59.3 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.31 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3600 mm
Pu Top = 327.52 kN
Mntx = 202.87 kNm
Pu Bottom = 309.41 kN
Mnbx = 201.08 kNm
Vux1 = 112.21 kN
Shear from Beam Capacity at Joint:
Lux = 3600 mm
Mntx = 120.31 KN-m
Mnbx = 0 KN-m
Vux2 = 33.42 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 110.6 kN
Mux = 101.58 kNm
Vux3 = 34.9931 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 112.21 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 84.19 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcx = 76.88 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 58.88 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.44 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C8
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 410
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 159.83 kN
Muxt = 73.76 kNm
Muyt = 19.23 kNm
Vuxt = -12.42 kN
Vuyt = 38.75 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pub = 173.4 kN
Muxb = -42.46 kNm
Muyb = -18.01 kNm
Vuxb = -12.42 kN
Vuyb = 38.75 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 5000 x 350 x 400 - 37.333 3.341
Top 71.111 No Beam 5000 x 350 x 400 - 37.333 3.818
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 No Beam 46.667 - 2.662
Top 71.111 4000 x 350 x 400 No Beam 46.667 - 3.042
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -42.46 kNm
M2 = 73.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = -18.01 kNm
M2 = 19.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 73.76 - 73.76
Major Axis Mux (bottom) -42.46 - -42.46
Minor Axis Muy (top) 19.23 - 19.23
Minor Axis Muy (bottom) -18.01 - -18.01

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 159.83 kN
Mux = 73.76 kNm
Muy = 19.23 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 184.77 kN
Mux = -28.81 kNm
Muy = -41.66 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 184.77 kN
φ Pn = 184.77 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 14.61 deg
MRes = 76.23 kNm
( φ ) MCap = 157.08 kNm
Capacity Ratio = MRes/ MCap
= 0.485 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 180 -0.91 82.84 672.19 804.24 97.98 10.32 345 392.7 49.6 97.98 0 49.6 0
350 x 400 270 -1.24 75.59 610.08 804.24 97.98 27.61 345 392.7 49.6 0 97.98 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 - 97.98 -
Bottom 49.6 - 49.6 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 97.98 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 180 -2.24 105.29 869.23 1005.3 120.31 34.9 355.83 392.7 49.6 120.31 0 49.6 0
350 x 400 270 -1.46 95.88 785.78 804.24 97.98 47.04 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 - 97.98 -
Bottom 49.6 - 56.86 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 120.31 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 184.77 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnty = 188.79 kNm
Pu Bottom = 171.19 kN
Mnby = 187.45 kNm
Vuy1 = 144.71 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 97.98 KN-m
Mnby = 97.98 KN-m
Vuy2 = 75.37 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 159.83 kN
Muy = 73.76 kNm
Vuy3 = 38.7511 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 144.71 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 48.63 kNm
φVcy = 90.71 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 90 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 45.35 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 375.92 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 375.92 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 184.77 kN
Mntx = 188.79 kNm
Pu Bottom = 171.19 kN
Mnbx = 187.45 kNm
Vux1 = 144.71 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 97.98 KN-m
Mnbx = 120.31 KN-m
Vux2 = 83.96 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 134.02 kN
Mux = 62.47 kNm
Vux3 = -33.1162 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 144.71 kN
λ = 1
φ = 0.6
deff = 342 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
ρw (50% of As provided) = 0.018
Mm = 41.4 kNm
φVcx = 95.08 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 82.71 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 47.54 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 345.48 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 345.48 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Table For Links
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C8
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 428
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 43.41 kN
Muxt = 14.12 kNm
Muyt = 31.29 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuxt = -12.98 kN
Vuyt = 10.72 kN
Pub = 56.99 kN
Muxb = -18.04 kNm
Muyb = -7.65 kNm
Vuxb = -12.98 kN
Vuyb = 10.72 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 5000 x 350 x 400 - 37.333 3.818
Top 71.111 No Beam 5000 x 350 x 400 - 37.333 1.909
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 No Beam 46.667 - 3.042
Top 71.111 4000 x 350 x 400 No Beam 46.667 - 1.521
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = 14.12 kNm
M2 = -18.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = -7.65 kNm
M2 = 31.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.93
22.52 < 36.93, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 14.12 - 14.12
Major Axis Mux (bottom) -18.04 - -18.04

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (top) 31.29 - 31.29
Minor Axis Muy (bottom) -7.65 - -7.65

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 43.41 kN
Mux = 14.12 kNm
Muy = 31.29 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 56.99 kN
Mux = -18.04 kNm
Muy = -7.65 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 56.99 kN
φ Pn = 56.99 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 65.71 deg
MRes = 34.32 kNm
( φ ) MCap = 143.04 kNm
Capacity Ratio = MRes/ MCap
= 0.24 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 180 -1.36 32.98 345 392.7 49.57 8.44 345 392.7 49.6 49.57 0 49.6 0
350 x 400 270 0.57 30.52 345 392.7 49.57 14.56 345 392.7 49.6 0 49.57 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 - 49.57 -
Bottom 49.6 - 49.6 -
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 49.6 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 49.6 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 180 -0.91 82.84 672.19 804.24 97.98 10.32 345 392.7 49.6 97.98 0 49.6 0
350 x 400 270 -1.24 75.59 610.08 804.24 97.98 27.61 345 392.7 49.6 0 97.98 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 - 97.98 -
Bottom 49.6 - 49.6 -
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 97.98 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Luy = 2600 mm
Pu Top = 56.99 kN
Mnty = 175.6 kNm
Pu Bottom = 43.41 kN
Mnby = 174.15 kNm
Vuy1 = 134.52 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 49.6 KN-m
Mnby = 97.98 KN-m
Vuy2 = 56.76 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 39.66 kN
Muy = 30.98 kNm
Vuy3 = 13.4853 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.52 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.74 kNm
φVcy = 111.42 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 38.5 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.5 x φVcy = 55.71 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 56.99 kN
Mntx = 175.6 kNm
Pu Bottom = 43.41 kN
Mnbx = 174.15 kNm
Vux1 = 134.52 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 49.6 KN-m
Mnbx = 97.98 KN-m
Vux2 = 56.76 KN
Critical Analysis Load Combination : 12
Critical Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 43.41 kN
Mux = 31.29 kNm
Vux3 = -12.9814 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 134.52 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.46 kNm
φVcx = 111.95 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 37.61 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 55.98 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C9
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3600 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 360
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 230.63 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muxt = -13.35 kNm
Muyt = -96.11 kNm
Vuxt = 63.85 kN
Vuyt = -5.43 kN
Pub = 244.21 kN
Muxb = 8.35 kNm
Muyb = 159.21 kNm
Vuxb = 63.85 kN
Vuyb = -5.43 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 300 x 350 No Beam 21.438 - 5.788
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 1.3
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = 8.35 kNm
M2 = -13.35 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.12
M1 = -96.11 kNm
M2 = 159.21 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
A B C
Major Axis Mux (top) -13.35 - -13.35
Major Axis Mux (bottom) 8.35 - 8.35
Minor Axis Muy (top) -96.11 - -96.11
Minor Axis Muy (bottom) 159.21 - 159.21

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 244.21 kN
Mux = 8.35 kNm
Muy = 159.21 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 379.8 kN
Mux = 9.59 kNm
Muy = 1.69 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 379.8 kN
φ Pn = 379.8 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87 deg
MRes = 159.43 kNm
( φ ) MCap = 169.38 kNm
Capacity Ratio = MRes/ MCap
= 0.941 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.56 121.93 1020.15 1231.5 144.41 79.02 639.4 804.24 98.12 0 144.41 0 98.12
300 x 350 0 1.66 91.71 844.83 942.48 101.16 4 270 314.16 36.2 101.16 0 36.2 0
350 x 400 270 -1.08 106.32 878.44 1005.3 120.31 74.27 598.85 603.18 74.86 0 120.31 0 74.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top - 101.16 120.31 144.41
Bottom - 36.2 74.86 98.12
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 101.16 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 219.27 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 379.8 kN
Mnty = 205.33 kNm
Pu Bottom = 358.68 kN
Mnby = 204.88 kNm
Vuy1 = 112.39 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 219.27 KN-m
Mnby = 0 KN-m
Vuy2 = 60.07 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 274.72 kN
Muy = 116.11 kNm
Vuy3 = -42.0488 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 112.39 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 72.91 kNm
φVcy = 78.64 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 56.25 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.32 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3600 mm
Pu Top = 379.8 kN
Mntx = 205.33 kNm
Pu Bottom = 358.68 kN
Mnbx = 204.88 kNm
Vux1 = 113.95 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Beam Capacity at Joint:
Lux = 3600 mm
Mntx = 101.16 KN-m
Mnbx = 0 KN-m
Vux2 = 28.1 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 244.21 kN
Mux = 159.21 kNm
Vux3 = 63.8465 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.95 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 120.81 kNm
φVcx = 73.6 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 67.24 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 36.8 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C9
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 397
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 175.15 kN
Muxt = -32.53 kNm
Muyt = -112.13 kNm
Vuxt = 67.02 kN
Vuyt = -21.94 kN
Pub = 188.73 kN
Muxb = 33.27 kNm
Muyb = 88.88 kNm
Vuxb = 67.02 kN
Vuyb = -21.94 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 71.111 5000 x 300 x 350 No Beam 21.438 - 5.788
Top 71.111 5000 x 300 x 350 No Beam 21.438 - 6.615
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 1.3
Top 71.111 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 1.485
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = -32.53 kNm
M2 = 33.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 40

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = 88.88 kNm
M2 = -112.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -32.53 - -32.53
Major Axis Mux (bottom) 33.27 - 33.27
Minor Axis Muy (top) -112.13 - -112.13
Minor Axis Muy (bottom) 88.88 - 88.88

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 175.15 kN
Mux = -32.53 kNm
Muy = -112.13 kNm

Φ Pn, Max Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 215.59 kN
Mux = 36.62 kNm
Muy = 6.52 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 215.59 kN
φ Pn = 215.59 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 73.82 deg
MRes = 116.75 kNm
( φ ) MCap = 157.45 kNm
Capacity Ratio = MRes/ MCap
= 0.741 < 1

Beam Capacity At Joint:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.08 91.21 744.8 804.24 97.98 46.78 402.5 452.4 56.86 0 97.98 0 56.86
300 x 350 0 0.81 76.44 692.03 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
350 x 400 270 -0.65 81.81 663.38 804.24 97.98 50.05 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 87.71 97.98 97.98
Bottom - 36.2 56.86 56.86
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 87.71 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 154.84 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.56 121.93 1020.15 1231.5 144.41 79.02 639.4 804.24 98.12 0 144.41 0 98.12
300 x 350 0 1.66 91.71 844.83 942.48 101.16 4 270 314.16 36.2 101.16 0 36.2 0
350 x 400 270 -1.08 106.32 878.44 1005.3 120.31 74.27 598.85 603.18 74.86 0 120.31 0 74.86

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 101.16 120.31 144.41
Bottom - 36.2 74.86 98.12
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 101.16 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 219.27 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 215.59 kN
Mnty = 191.83 kNm
Pu Bottom = 199.75 kN
Mnby = 190.27 kNm
Vuy1 = 144.19 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 154.84 KN-m
Mnby = 219.27 KN-m
Vuy2 = 141.17 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 190.69 kN
Muy = 71.84 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy3 = -35.8426 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 144.19 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 41.85 kNm
φVcy = 94.66 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 82.55 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 47.33 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 344.8 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 344.8 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 215.59 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = 191.83 kNm
Pu Bottom = 199.75 kN
Mnbx = 190.27 kNm
Vux1 = 146.96 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 87.71 KN-m
Mnbx = 101.16 KN-m
Vux2 = 72.64 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 127.6 kN
Mux = 109.9 kNm
Vux3 = 65.5048 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 146.96 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 89.84 kNm
φVcx = 79.43 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 112.55 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 39.72 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 470.12 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 470.12 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C9
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 394
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 35.71 kN
Muxt = -7.93 kNm
Muyt = -55.89 kNm
Vuxt = 26.33 kN
Vuyt = -8.98 kN
Pub = 49.29 kN
Muxb = 19 kNm
Muyb = 23.08 kNm
Vuxb = 26.33 kN
Vuyb = -8.98 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 No Beam 21.438 - 6.615
Top 71.111 5000 x 300 x 350 No Beam 21.438 - 3.307
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 1.485
Top 71.111 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 0.743
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.84

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 22.95
M1 = -7.93 kNm
M2 = 19 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.01
22.95 < 39.01, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.84
r = 115.47 mm
Klux /r = 18.91
M1 = 23.08 kNm
M2 = -55.89 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.96
18.91 < 38.96, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -7.93 - -7.93
Major Axis Mux (bottom) 19 - 19
Minor Axis Muy (top) -55.89 - -55.89
Minor Axis Muy (bottom) 23.08 - 23.08

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35.71 kN
Mux = -7.93 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = -55.89 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 56.91 kN
Mux = 21.33 kNm
Muy = 3.57 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 56.91 kN
φ Pn = 56.91 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 81.92 deg
MRes = 56.45 kNm
( φ ) MCap = 144.79 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.39 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.13 39.65 402.5 452.4 56.81 24.28 345 392.7 49.6 0 56.81 0 49.6
300 x 350 0 0.42 18.67 270 314.16 36.18 7.45 270 314.16 36.2 36.18 0 36.2 0
350 x 400 270 -0.34 35.84 365.7 392.7 49.57 21.07 345 392.7 49.6 0 49.57 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 36.18 49.57 56.81
Bottom - 36.2 49.6 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 36.2 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 106.41 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
350 x 400 90 -0.08 91.21 744.8 804.24 97.98 46.78 402.5 452.4 56.86 0 97.98 0 56.86
300 x 350 0 0.81 76.44 692.03 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
350 x 400 270 -0.65 81.81 663.38 804.24 97.98 50.05 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 87.71 97.98 97.98
Bottom - 36.2 56.86 56.86
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 87.71 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 154.84 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 56.91 kN
Mnty = 175.59 kNm
Pu Bottom = 41.07 kN
Mnby = 173.9 kNm
Vuy1 = 131.88 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 106.41 KN-m
Mnby = 154.84 KN-m
Vuy2 = 98.59 KN
Critical Analysis Load Combination : 9

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 44.09 kN
Muy = 34.02 kNm
Vuy3 = -9.6416 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 131.88 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 27.09 kNm
φVcy = 106.64 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 42.07 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 53.32 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 56.91 kN
Mntx = 175.59 kNm
Pu Bottom = 41.07 kN
Mnbx = 173.9 kNm
Vux1 = 134.42 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 36.2 KN-m
Mnbx = 87.71 KN-m
Vux2 = 47.66 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 26.84 kN
Mux = 55.6 kNm
Vux3 = 25.8116 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 134.42 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 51.38 kNm
φVcx = 87.68 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 77.89 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 43.84 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C10
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 377
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 245.31 kN
Muxt = 6.67 kNm
Muyt = -74.43 kNm
Vuxt = 54.61 kN
Vuyt = 2.05 kN
Pub = 258.89 kN
Muxb = -1.52 kNm
Muyb = 143.96 kNm
Vuxb = 54.61 kN
Vuyb = 2.05 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.579
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = -1.52 kNm
M2 = 6.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.73
27.5 < 36.73, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -74.43 kNm
M2 = 143.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 6.67 - 6.67
Major Axis Mux (bottom) -1.52 - -1.52
Minor Axis Muy (top) -74.43 - -74.43
Minor Axis Muy (bottom) 143.96 - 143.96

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 258.89 kN
Mux = -1.52 kNm
Muy = 143.96 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 498.21 kN
Mux = -2.8 kNm
Muy = 4.41 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 498.21 kN
φ Pn = 498.21 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.4 deg
MRes = 143.97 kNm
( φ ) MCap = 171.96 kNm
Capacity Ratio = MRes/ MCap
= 0.837 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.81 94.9 877.56 942.48 101.16 36.49 316.99 339.3 39 0 101.16 0 39
300 x 350 0 -0.61 73.12 659.57 804.24 87.71 31.3 315 339.3 39 87.71 0 39 0
300 x 350 270 -0.54 71.27 641.61 804.24 87.71 48.63 427.57 452.4 51.37 0 87.71 0 51.37
300 x 350 180 1.66 92.24 850.26 942.48 101.16 0.84 270 314.16 36.2 101.16 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 87.71 87.71 101.16
Bottom 36.2 39 51.37 39
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 140.16 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 498.21 kN
Mnty = 207.86 kNm
Pu Bottom = 480.1 kN
Mnby = 207.47 kNm
Vuy1 = 113.79 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 152.53 KN-m
Mnby = 0 KN-m
Vuy2 = 41.79 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 246.69 kN
Muy = 122.54 kNm
Vuy3 = 46.9142 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.79 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 83.74 kNm
φVcy = 77.1 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 61.15 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.55 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 498.21 kN
Mntx = 207.86 kNm
Pu Bottom = 480.1 kN
Mnbx = 207.47 kNm
Vux1 = 113.79 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 140.16 KN-m
Mnbx = 0 KN-m
Vux2 = 38.4 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 258.89 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 143.96 kNm
Vux3 = 54.6117 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.79 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 103.25 kNm
φVcx = 74.94 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 64.75 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 37.47 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C10
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 404
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 199.55 kN
Muxt = 15.35 kNm
Muyt = -90.39 kNm
Vuxt = 50.33 kN
Vuyt = 10.61 kN
Pub = 213.13 kN
Muxb = -16.48 kNm
Muyb = 60.58 kNm
Vuxb = 50.33 kN
Vuyb = 10.61 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.579
Top 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.948
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 15.35 kNm
M2 = -16.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 60.58 kNm
M2 = -90.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 15.35 - 15.35
Major Axis Mux (bottom) -16.48 - -16.48
Minor Axis Muy (top) -90.39 - -90.39
Minor Axis Muy (bottom) 60.58 - 60.58

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 199.55 kN
Mux = 15.35 kNm
Muy = -90.39 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 266.07 kN
Mux = -10.85 kNm
Muy = 17.43 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 266.07 kN
φ Pn = 266.07 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 80.36 deg
MRes = 91.68 kNm
( φ ) MCap = 163.33 kNm
Capacity Ratio = MRes/ MCap
= 0.561 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.72 74.58 673.86 804.24 87.71 15.71 270 314.16 36.2 0 87.71 0 36.2
300 x 350 0 -0.46 56.65 502.12 603.18 67.29 14.95 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.35 53.36 471.4 603.18 67.29 30.87 315 339.3 39 0 67.29 0 39

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
300 x 350 180 0.81 77.79 705.36 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 67.29 67.29 87.71
Bottom 36.2 36.2 39 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.81 94.9 877.56 942.48 101.16 36.49 316.99 339.3 39 0 101.16 0 39
300 x 350 0 -0.61 73.12 659.57 804.24 87.71 31.3 315 339.3 39 87.71 0 39 0
300 x 350 270 -0.54 71.27 641.61 804.24 87.71 48.63 427.57 452.4 51.37 0 87.71 0 51.37
300 x 350 180 1.66 92.24 850.26 942.48 101.16 0.84 270 314.16 36.2 101.16 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 87.71 87.71 101.16
Bottom 36.2 39 51.37 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 140.16 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 266.07 kN
Mnty = 196.81 kNm
Pu Bottom = 252.49 kN
Mnby = 195.47 kNm
Vuy1 = 148.03 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 126.7 KN-m
Mnby = 152.53 KN-m
Vuy2 = 105.37 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 126.07 kN
Muy = 72.54 kNm
Vuy3 = 38.8512 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 148.03 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 52.72 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcy = 89.3 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 97.89 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 44.65 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 408.88 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 408.88 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 266.07 kN
Mntx = 196.81 kNm
Pu Bottom = 252.49 kN
Mnbx = 195.47 kNm
Vux1 = 148.03 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 123.91 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 140.16 KN-m
Vux2 = 99.65 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 131.74 kN
Mux = 85.86 kNm
Vux3 = 47.287 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 148.03 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 65.14 kNm
φVcx = 84.79 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 105.4 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 42.4 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 440.26 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 440.26 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C10
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 441
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 25.06 kN
Muxt = 2.12 kNm
Muyt = -38.21 kNm
Vuxt = 15.89 kN
Vuyt = 3.89 kN
Pub = 38.64 kN
Muxb = -9.53 kNm
Muyb = 9.45 kNm
Vuxb = 15.89 kN
Vuyb = 3.89 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.948
Top 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 1.474
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 1.293
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 2.12 kNm
M2 = -9.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.67
22.95 < 36.67, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
r = 115.47 mm
Klux /r = 22.95
M1 = 9.45 kNm
M2 = -38.21 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.97
22.95 < 36.97, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 2.12 - 2.12
Major Axis Mux (bottom) -9.53 - -9.53
Minor Axis Muy (top) -38.21 - -38.21
Minor Axis Muy (bottom) 9.45 - 9.45

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 25.06 kN
Mux = 2.12 kNm
Muy = -38.21 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 45.22 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = -12.93 kNm
Muy = 8.46 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 45.22 kN
φ Pn = 45.22 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 86.82 deg
MRes = 38.27 kNm
( φ ) MCap = 144.14 kNm
Capacity Ratio = MRes/ MCap
= 0.265 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
300 x 350 90 0.18 23.51 270 314.16 36.18 16.43 270 314.16 36.2 0 36.18 0 36.2
300 x 350 0 -0.1 17.29 270 314.16 36.18 10.52 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.16 21.32 270 314.16 36.18 15.71 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 0.42 17.7 270 314.16 36.18 6.6 270 314.16 36.2 36.18 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.72 74.58 673.86 804.24 87.71 15.71 270 314.16 36.2 0 87.71 0 36.2
300 x 350 0 -0.46 56.65 502.12 603.18 67.29 14.95 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.35 53.36 471.4 603.18 67.29 30.87 315 339.3 39 0 67.29 0 39
300 x 350 180 0.81 77.79 705.36 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0

Effective Moment for Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 67.29 67.29 87.71
Bottom 36.2 36.2 39 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 45.22 kN
Mnty = 174.34 kNm
Pu Bottom = 29.38 kN
Mnby = 172.66 kNm
Vuy1 = 130.94 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 126.7 KN-m
Vuy2 = 75.13 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 16.92 kN
Muy = 27.67 kNm
Vuy3 = 10.8016 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 130.94 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 25.01 kNm
φVcy = 109.72 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 35.37 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 54.86 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 45.22 kN
Mntx = 174.34 kNm
Pu Bottom = 29.38 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 172.66 kNm
Vux1 = 130.94 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 123.91 KN-m
Vux2 = 74.07 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 18.81 kN
Mux = 37.9 kNm
Vux3 = 14.9705 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 130.94 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 34.94 kNm
φVcx = 97.2 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 56.23 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 48.6 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C11
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 379
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 257.14 kN
Muxt = -9.47 kNm
Muyt = -70.15 kNm
Vuxt = 52.11 kN
Vuyt = -3.98 kN
Pub = 270.71 kN
Muxb = 6.44 kNm
Muyb = 138.21 kNm
Vuxb = 52.11 kN
Vuyb = -3.98 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.579
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = 6.44 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M2 = -9.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -70.15 kNm
M2 = 138.21 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -9.47 - -9.47
Major Axis Mux (bottom) 6.44 - 6.44
Minor Axis Muy (top) -70.15 - -70.15
Minor Axis Muy (bottom) 138.21 - 138.21

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 270.71 kN
Mux = 6.44 kNm
Muy = 138.21 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 588.84 kN
Mux = 6.52 kNm
Muy = 1.99 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 588.84 kN
φ Pn = 588.84 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87.33 deg
MRes = 138.36 kNm
( φ ) MCap = 172.22 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.803 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.53 99.96 929.94 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 0.05 92.95 857.57 942.48 101.16 34.87 315 339.3 39 0 101.16 0 39
300 x 350 180 -0.61 73.95 667.63 804.24 87.71 31.28 315 339.3 39 87.71 0 39 0
300 x 350 270 -0.53 78.89 716.19 804.24 87.71 42.5 371.31 452.4 51.37 0 87.71 0 51.37

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 101.16 87.71 101.16
Bottom 39 36.2 51.37 39
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 140.16 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 450.1 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnty = 206.83 kNm
Pu Bottom = 432 kN
Mnby = 206.45 kNm
Vuy1 = 113.23 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 152.53 KN-m
Mnby = 0 KN-m
Vuy2 = 41.79 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 257.63 kN
Muy = 122.45 kNm
Vuy3 = -46.8505 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.23 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 81.94 kNm
φVcy = 77.29 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 59.89 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.65 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 588.84 kN
Mntx = 206.52 kNm
Pu Bottom = 570.74 kN
Mnbx = 207.55 kNm
Vux1 = 113.44 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 140.16 KN-m
Mnbx = 0 KN-m
Vux2 = 38.4 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 270.71 kN
Mux = 138.21 kNm
Vux3 = 52.1055 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.44 kN
λ = 1
φ = 0.6
deff = 342 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
ρw (50% of As provided) = 0.018
Mm = 95.64 kNm
φVcx = 75.65 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 62.99 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 37.82 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Table For Links
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C11
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 416
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 218.98 kN
Muxt = -22.95 kNm
Muyt = -82.4 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuxt = 45.25 kN
Vuyt = -15.32 kN
Pub = 232.56 kN
Muxb = 23 kNm
Muyb = 53.3 kNm
Vuxb = 45.25 kN
Vuyb = -15.32 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.579
Top 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.948
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = -22.95 kNm
M2 = 23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 53.3 kNm
M2 = -82.4 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -22.95 - -22.95
Major Axis Mux (bottom) 23 - 23

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (top) -82.4 - -82.4
Minor Axis Muy (bottom) 53.3 - 53.3

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 218.98 kN
Mux = -22.95 kNm
Muy = -82.4 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 310.93 kN
Mux = 25.18 kNm
Muy = 7.95 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 310.93 kN
φ Pn = 310.93 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 74.44 deg
MRes = 85.54 kNm
( φ ) MCap = 161.13 kNm
Capacity Ratio = MRes/ MCap
= 0.531 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.35 86.82 795.26 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 0.19 73.22 660.61 804.24 87.71 14.62 270 314.16 36.2 0 87.71 0 36.2
300 x 350 180 -0.46 57.26 507.83 603.18 67.29 14.86 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.34 61.48 547.73 603.18 67.29 25.2 281.46 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 67.29 87.71 67.29 87.71
Bottom 36.2 36.2 36.2 36.2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.53 99.96 929.94 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 0.05 92.95 857.57 942.48 101.16 34.87 315 339.3 39 0 101.16 0 39
300 x 350 180 -0.61 73.95 667.63 804.24 87.71 31.28 315 339.3 39 87.71 0 39 0
300 x 350 270 -0.53 78.89 716.19 804.24 87.71 42.5 371.31 452.4 51.37 0 87.71 0 51.37

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 101.16 87.71 101.16
Bottom 39 36.2 51.37 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 140.16 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 310.93 kN
Mnty = 201.23 kNm
Pu Bottom = 297.36 kN
Mnby = 199.9 kNm
Vuy1 = 151.37 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 123.91 KN-m
Mnby = 152.53 KN-m
Vuy2 = 104.32 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 131.74 kN
Muy = 73.23 kNm
Vuy3 = -39.1397 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 151.37 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 52.52 kNm
φVcy = 89.92 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 102.41 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 44.96 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 427.79 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 427.79 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 310.93 kN
Mntx = 201.23 kNm
Pu Bottom = 297.36 kN
Mnbx = 199.9 kNm
Vux1 = 151.37 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 123.91 KN-m
Mnbx = 140.16 KN-m
Vux2 = 99.65 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 137.66 kN
Mux = 80.59 kNm
Vux3 = 44.024 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 151.37 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 58.94 kNm
φVcx = 87.28 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 106.82 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 43.64 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 446.19 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 446.19 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C11
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 443
Critical Analysis Load Combination : 15

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 18.67 kN
Muxt = -3.14 kNm
Muyt = -35.98 kNm
Vuxt = 13.78 kN
Vuyt = -4.02 kN
Pub = 28.85 kN
Muxb = 8.93 kNm
Muyb = 5.35 kNm
Vuxb = 13.78 kN
Vuyb = -4.02 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.948
Top 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 1.474
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 1.293
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = -3.14 kNm
M2 = 8.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.21
22.95 < 38.21, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 5.35 kNm
M2 = -35.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.78
22.95 < 35.78, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -3.14 - -3.14
Major Axis Mux (bottom) 8.93 - 8.93
Minor Axis Muy (top) -35.98 - -35.98
Minor Axis Muy (bottom) 5.35 - 5.35

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 18.67 kN
Mux = -3.14 kNm
Muy = -35.98 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 45.12 kN
Mux = 13.96 kNm
Muy = 6.34 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 45.12 kN
φ Pn = 45.12 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 85.02 deg
MRes = 36.12 kNm
( φ ) MCap = 143.12 kNm
Capacity Ratio = MRes/ MCap
= 0.252 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.16 17.64 270 314.16 36.18 5.98 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.42 23.37 270 314.16 36.18 15.8 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.1 16.77 270 314.16 36.18 10.69 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.16 20.95 270 314.16 36.18 15.22 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.35 86.82 795.26 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 0.19 73.22 660.61 804.24 87.71 14.62 270 314.16 36.2 0 87.71 0 36.2
300 x 350 180 -0.46 57.26 507.83 603.18 67.29 14.86 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.34 61.48 547.73 603.18 67.29 25.2 281.46 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 67.29 87.71 67.29 87.71
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 45.12 kN
Mnty = 174.33 kNm
Pu Bottom = 29.28 kN
Mnby = 172.65 kNm
Vuy1 = 130.94 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 123.91 KN-m
Vuy2 = 74.07 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 22.54 kN
Muy = 28.59 kNm
Vuy3 = -12.5118 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 130.94 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 25.05 kNm
φVcy = 109.66 kN
Vuy > φVcy Hence, Shear links required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design of Shear Links Along D
Vsy = (Vuy - φVcy) / φ
= 35.45 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 54.83 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 45.12 kN
Mntx = 174.33 kNm
Pu Bottom = 29.28 kN
Mnbx = 172.65 kNm
Vux1 = 130.94 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 123.91 KN-m
Vux2 = 74.07 KN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 18.67 kN
Mux = 35.98 kNm
Vux3 = 13.7795 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 130.94 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 33.05 kNm
φVcx = 99.01 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 53.2 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 49.51 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C12
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 381
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 289.84 kN
Muxt = 3.99 kNm
Muyt = -67 kNm
Vuxt = 49.79 kN
Vuyt = 1.05 kN
Pub = 303.42 kN
Muxb = -0.2 kNm
Muyb = 132.1 kNm
Vuxb = 49.79 kN
Vuyb = 1.05 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.579
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = -0.2 kNm
M2 = 3.99 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.59
27.5 < 34.59, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Klux /r = 27.5
M1 = -67 kNm
M2 = 132.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 3.99 - 3.99
Major Axis Mux (bottom) -0.2 - -0.2
Minor Axis Muy (top) -67 - -67
Minor Axis Muy (bottom) 132.1 - 132.1

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 303.42 kN
Mux = -0.2 kNm
Muy = 132.1 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 594.17 kN
Mux = -5.5 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 0.77 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 594.17 kN
φ Pn = 594.17 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.92 deg
MRes = 132.1 kNm
( φ ) MCap = 176.62 kNm
Capacity Ratio = MRes/ MCap
= 0.748 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
300 x 350 0 -0.53 85.37 780.67 804.24 87.71 20.56 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.58 88.3 810.2 942.48 101.16 32.33 315 339.3 39 0 101.16 0 39
300 x 350 180 -0.53 100.88 939.56 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 270 -0.54 76.41 691.79 804.24 87.71 40.15 350.04 452.4 51.37 0 87.71 0 51.37

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 87.71 87.71 101.16
Bottom 36.2 36.2 51.37 39
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 480.88 kN
Mnty = 207.49 kNm
Pu Bottom = 462.78 kN
Mnby = 207.1 kNm
Vuy1 = 113.59 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 152.53 KN-m
Mnby = 0 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy2 = 41.79 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 289.86 kN
Muy = 120.84 kNm
Vuy3 = 45.6265 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.59 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 75.26 kNm
φVcy = 78.37 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 58.7 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.18 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 480.88 kN
Mntx = 207.49 kNm
Pu Bottom = 462.78 kN
Mnbx = 207.1 kNm
Vux1 = 113.59 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 137.36 KN-m
Mnbx = 0 KN-m
Vux2 = 37.63 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 303.42 kN
Mux = 132.1 kNm
Vux3 = 49.7875 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.59 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 84.39 kNm
φVcx = 76.99 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 60.99 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.5 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
General Data
Column No. : C12
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 418
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 153.77 kN
Muxt = 8.27 kNm
Muyt = -77.42 kNm
Vuxt = 42.37 kN
Vuyt = 5.82 kN
Pub = 163.96 kN
Muxb = -9.18 kNm
Muyb = 49.66 kNm
Vuxb = 42.37 kN
Vuyb = 5.82 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.579
Top 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.948
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 8.27 kNm
M2 = -9.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 49.66 kNm
M2 = -77.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 8.27 - 8.27
Major Axis Mux (bottom) -9.18 - -9.18
Minor Axis Muy (top) -77.42 - -77.42
Minor Axis Muy (bottom) 49.66 - 49.66

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 153.77 kN
Mux = 8.27 kNm
Muy = -77.42 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 313.47 kN
Mux = -21.44 kNm
Muy = 3.1 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 313.47 kN
φ Pn = 313.47 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 83.91 deg
MRes = 77.86 kNm
( φ ) MCap = 158.93 kNm
Capacity Ratio = MRes/ MCap
= 0.49 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 68.76 617.32 804.24 87.71 4.37 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.47 69.55 624.96 804.24 87.71 12.98 270 314.16 36.2 0 87.71 0 36.2
300 x 350 180 -0.35 87.63 803.47 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.35 59.83 532.11 603.18 67.29 23.68 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 67.29 87.71
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.53 85.37 780.67 804.24 87.71 20.56 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.58 88.3 810.2 942.48 101.16 32.33 315 339.3 39 0 101.16 0 39
300 x 350 180 -0.53 100.88 939.56 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 270 -0.54 76.41 691.79 804.24 87.71 40.15 350.04 452.4 51.37 0 87.71 0 51.37

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 87.71 87.71 101.16
Bottom 36.2 36.2 51.37 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 313.47 kN
Mnty = 201.48 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 299.89 kN
Mnby = 200.15 kNm
Vuy1 = 151.56 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 123.91 KN-m
Mnby = 152.53 KN-m
Vuy2 = 104.32 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 147.55 kN
Muy = 67.12 kNm
Vuy3 = 35.0078 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 151.56 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 43.92 kNm
φVcy = 94.71 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 94.75 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 47.35 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 395.79 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 395.79 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 313.47 kN
Mntx = 201.48 kNm
Pu Bottom = 299.89 kN
Mnbx = 200.15 kNm
Vux1 = 151.56 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 123.91 KN-m
Mnbx = 137.36 KN-m
Vux2 = 98.59 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 153.77 kN
Mux = 77.42 kNm
Vux3 = 42.373 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 151.56 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 53.24 kNm
φVcx = 89.62 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 103.23 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 44.81 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 431.19 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 431.19 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C12
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 446
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 18.4 kN
Muxt = 1.53 kNm
Muyt = -34.49 kNm
Vuxt = 13.26 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyt = 2.4 kN
Pub = 28.58 kN
Muxb = -5.68 kNm
Muyb = 5.27 kNm
Vuxb = 13.26 kN
Vuyb = 2.4 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.948
Top 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 1.474
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 1.293
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 1.53 kNm
M2 = -5.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.22
22.95 < 37.22, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 5.27 kNm
M2 = -34.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.83
22.95 < 35.83, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 1.53 - 1.53
Major Axis Mux (bottom) -5.68 - -5.68
Minor Axis Muy (top) -34.49 - -34.49

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (bottom) 5.27 - 5.27

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 18.4 kN
Mux = 1.53 kNm
Muy = -34.49 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 44.55 kN
Mux = -8.77 kNm
Muy = 6.18 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 44.55 kN
φ Pn = 44.55 kN
Pt min for φ Pn = 0.5 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87.47 deg
MRes = 34.53 kNm
( φ ) MCap = 143.45 kNm
Capacity Ratio = MRes/ MCap
= 0.241 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.16 16.77 270 314.16 36.18 10.7 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 0.07 22.79 270 314.16 36.18 14.94 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.16 17.12 270 314.16 36.18 6.48 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.16 20.3 270 314.16 36.18 14.54 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 68.76 617.32 804.24 87.71 4.37 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.47 69.55 624.96 804.24 87.71 12.98 270 314.16 36.2 0 87.71 0 36.2
300 x 350 180 -0.35 87.63 803.47 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.35 59.83 532.11 603.18 67.29 23.68 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 67.29 87.71
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Design Of Shear

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 44.55 kN
Mnty = 174.27 kNm
Pu Bottom = 28.71 kN
Mnby = 172.59 kNm
Vuy1 = 130.89 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 123.91 KN-m
Vuy2 = 74.07 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 22.17 kN
Muy = 27.91 kNm
Vuy3 = 11.0696 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 130.89 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.43 kNm
φVcy = 110.77 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 33.54 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 55.38 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 44.55 kN
Mntx = 174.27 kNm
Pu Bottom = 28.71 kN
Mnbx = 172.59 kNm
Vux1 = 130.89 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 123.91 KN-m
Vux2 = 74.07 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 18.4 kN
Mux = 34.49 kNm
Vux3 = 13.2567 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 130.89 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 31.6 kNm
φVcx = 100.52 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 50.61 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 50.26 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C13
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 384
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Location = Bottom Joint
Put = 263.71 kN
Muxt = -1.21 kNm
Muyt = -64.54 kNm
Vuxt = 47.96 kN
Vuyt = -0.9 kN
Pub = 277.29 kN
Muxb = 2.37 kNm
Muyb = 127.24 kNm
Vuxb = 47.96 kN
Vuyb = -0.9 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 2.326
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = -1.21 kNm
M2 = 2.37 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -64.54 kNm
M2 = 127.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -1.21 - -1.21
Major Axis Mux (bottom) 2.37 - 2.37
Minor Axis Muy (top) -64.54 - -64.54
Minor Axis Muy (bottom) 127.24 - 127.24

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 277.29 kN
Mux = 2.37 kNm
Muy = 127.24 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 537.47 kN
Mux = 0.06 kNm
Muy = 0.75 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 537.47 kN
φ Pn = 537.47 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 88.93 deg
MRes = 127.26 kNm
( φ ) MCap = 173.57 kNm
Capacity Ratio = MRes/ MCap
= 0.733 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.53 82.16 748.63 804.24 87.71 21.9 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.41 86.3 790.04 804.24 87.71 30.37 315 339.3 39 0 87.71 0 39
300 x 350 180 -0.53 82.12 748.2 804.24 87.71 21.92 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.53 74.52 673.27 804.24 87.71 38.26 332.94 339.3 39 0 87.71 0 39

Effective Moment for Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 87.71 87.71
Bottom 36.2 36.2 39 39
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 537.47 kN
Mnty = 208.7 kNm
Pu Bottom = 519.37 kN
Mnby = 208.31 kNm
Vuy1 = 114.25 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 126.7 KN-m
Mnby = 0 KN-m
Vuy2 = 34.71 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 279.32 kN
Muy = 119.86 kNm
Vuy3 = -44.8855 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 114.25 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 75.93 kNm
φVcy = 78.33 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 59.87 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.16 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 537.47 kN
Mntx = 208.7 kNm
Pu Bottom = 519.37 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 208.31 kNm
Vux1 = 114.25 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 123.91 KN-m
Mnbx = 0 KN-m
Vux2 = 33.95 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 277.29 kN
Mux = 127.24 kNm
Vux3 = 47.9585 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 114.25 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 83.64 kNm
φVcx = 77.16 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 61.81 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.58 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C13
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 420
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 140.51 kN
Muxt = -1.21 kNm
Muyt = -74.99 kNm
Vuxt = 41.13 kN
Vuyt = -0.63 kN
Pub = 150.69 kN
Muxb = 0.67 kNm
Muyb = 48.36 kNm
Vuxb = 41.13 kN
Vuyb = -0.63 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 2.326
Top 71.111 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 2.658
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 0.67 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M2 = -1.21 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 48.36 kNm
M2 = -74.99 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -1.21 - -1.21
Major Axis Mux (bottom) 0.67 - 0.67
Minor Axis Muy (top) -74.99 - -74.99
Minor Axis Muy (bottom) 48.36 - 48.36

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 140.51 kN
Mux = -1.21 kNm
Muy = -74.99 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 285.12 kN
Mux = 0.1 kNm
Muy = 3.01 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 285.12 kN
φ Pn = 285.12 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.08 deg
MRes = 75 kNm
( φ ) MCap = 158.52 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.473 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 66.23 592.96 603.18 67.29 5.72 270 314.16 36.2 67.29 0 36.2 0
300 x 350 90 -0.29 68.3 612.93 804.24 87.71 11.77 270 314.16 36.2 0 87.71 0 36.2
300 x 350 180 -0.34 66.19 592.6 603.18 67.29 5.74 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.34 58.6 520.51 603.18 67.29 22.45 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 67.29 67.29 67.29 87.71
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 103.49 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
300 x 350 0 -0.53 82.16 748.63 804.24 87.71 21.9 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.41 86.3 790.04 804.24 87.71 30.37 315 339.3 39 0 87.71 0 39
300 x 350 180 -0.53 82.12 748.2 804.24 87.71 21.92 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.53 74.52 673.27 804.24 87.71 38.26 332.94 339.3 39 0 87.71 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 87.71 87.71
Bottom 36.2 36.2 39 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 285.12 kN
Mnty = 198.69 kNm
Pu Bottom = 271.54 kN
Mnby = 197.35 kNm
Vuy1 = 149.45 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 123.91 KN-m
Mnby = 126.7 KN-m
Vuy2 = 94.57 KN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 141.81 kN
Muy = 61.1 kNm
Vuy3 = -31.3556 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 149.45 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 38.8 kNm
φVcy = 98.08 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 85.61 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 49.04 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 357.58 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 357.58 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 285.12 kN
Mntx = 198.69 kNm
Pu Bottom = 271.54 kN
Mnbx = 197.35 kNm
Vux1 = 149.45 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 103.49 KN-m
Mnbx = 123.91 KN-m
Vux2 = 85.81 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 140.51 kN
Mux = 74.99 kNm
Vux3 = 41.1275 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 149.45 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 52.9 kNm
φVcx = 89.44 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 100.01 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 44.72 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 417.75 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 417.75 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C13
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 447
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 17.71 kN
Muxt = -0.53 kNm
Muyt = -33.38 kNm
Vuxt = 12.89 kN
Vuyt = -0.17 kN
Pub = 27.89 kN
Muxb = 0 kNm
Muyb = 5.28 kNm
Vuxb = 12.89 kN
Vuyb = -0.17 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 2.658
Top 71.111 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 1.329
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 1.293
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 0 kNm
M2 = -0.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.91
22.95 < 33.91, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 5.28 kNm
M2 = -33.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.9
22.95 < 35.9, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.53 - -0.53
Major Axis Mux (bottom) 0 - 0
Minor Axis Muy (top) -33.38 - -33.38
Minor Axis Muy (bottom) 5.28 - 5.28

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 17.71 kN
Mux = -0.53 kNm
Muy = -33.38 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 43.55 kN
Mux = 0 kNm
Muy = 6.18 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 43.55 kN
φ Pn = 43.55 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.09 deg
MRes = 33.38 kNm
( φ ) MCap = 144.02 kNm
Capacity Ratio = MRes/ MCap
= 0.232 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.16 17.51 270 314.16 36.18 10.07 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.12 22.15 270 314.16 36.18 14.35 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.16 17.55 270 314.16 36.18 10.04 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.15 19.75 270 314.16 36.18 13.98 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 66.23 592.96 603.18 67.29 5.72 270 314.16 36.2 67.29 0 36.2 0
300 x 350 90 -0.29 68.3 612.93 804.24 87.71 11.77 270 314.16 36.2 0 87.71 0 36.2
300 x 350 180 -0.34 66.19 592.6 603.18 67.29 5.74 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.34 58.6 520.51 603.18 67.29 22.45 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 67.29 67.29 67.29 87.71
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 103.49 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 43.55 kN
Mnty = 174.17 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 27.71 kN
Mnby = 172.48 kNm
Vuy1 = 130.81 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 123.91 KN-m
Vuy2 = 74.07 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 17.81 kN
Muy = 27.04 kNm
Vuy3 = 8.4574 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 130.81 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.24 kNm
φVcy = 111.09 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 32.87 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 55.54 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 43.55 kN
Mntx = 174.17 kNm
Pu Bottom = 27.71 kN
Mnbx = 172.48 kNm
Vux1 = 130.81 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 103.49 KN-m
Vux2 = 66.37 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 17.71 kN
Mux = 33.38 kNm
Vux3 = 12.8902 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 130.81 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 30.59 kNm
φVcx = 101.65 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 48.6 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 50.83 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C14
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 386
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 288.7 kN
Muxt = -6.06 kNm
Muyt = -62.09 kNm
Vuxt = 46.13 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyt = -2.71 kN
Pub = 302.28 kN
Muxb = 4.76 kNm
Muyb = 122.39 kNm
Vuxb = 46.13 kN
Vuyb = -2.71 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.579
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = 4.76 kNm
M2 = -6.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -62.09 kNm
M2 = 122.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -6.06 - -6.06
Major Axis Mux (bottom) 4.76 - 4.76
Minor Axis Muy (top) -62.09 - -62.09

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (bottom) 122.39 - 122.39

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 302.28 kN
Mux = 4.76 kNm
Muy = 122.39 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 592.97 kN
Mux = 5.41 kNm
Muy = 0.75 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 592.97 kN
φ Pn = 592.97 kN
Pt min for φ Pn = 0.5 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87.77 deg
MRes = 122.48 kNm
( φ ) MCap = 175.59 kNm
Capacity Ratio = MRes/ MCap
= 0.698 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.57 100.1 931.41 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.28 84.34 770.41 804.24 87.71 28.38 315 339.3 39 0 87.71 0 39
300 x 350 180 -0.53 85.25 779.53 804.24 87.71 20.59 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.54 72.63 654.8 804.24 87.71 36.37 315.88 339.3 39 0 87.71 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 101.16 87.71 87.71
Bottom 36.2 36.2 39 39
Moment Along D:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 479.7 kN
Mnty = 207.46 kNm
Pu Bottom = 461.59 kN
Mnby = 207.08 kNm
Vuy1 = 113.57 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 126.7 KN-m
Mnby = 0 KN-m
Vuy2 = 34.71 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 289.35 kN
Muy = 120.76 kNm
Vuy3 = -45.5729 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.57 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 75.26 kNm
φVcy = 78.36 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 58.68 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.18 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 479.7 kN
Mntx = 207.46 kNm
Pu Bottom = 461.59 kN
Mnbx = 207.08 kNm
Vux1 = 113.57 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = 137.36 KN-m
Mnbx = 0 KN-m
Vux2 = 37.63 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 302.28 kN
Mux = 122.39 kNm
Vux3 = 46.1315 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.57 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 74.86 kNm
φVcx = 78.43 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 58.57 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 39.22 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C14
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 391
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 153.36 kN
Muxt = -10.11 kNm
Muyt = -72.56 kNm
Vuxt = 39.88 kN
Vuyt = -6.67 kN
Pub = 163.54 kN
Muxb = 9.88 kNm
Muyb = 47.05 kNm
Vuxb = 39.88 kN
Vuyb = -6.67 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.579
Top 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.948
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 9.88 kNm
M2 = -10.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 47.05 kNm
M2 = -72.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -10.11 - -10.11
Major Axis Mux (bottom) 9.88 - 9.88
Minor Axis Muy (top) -72.56 - -72.56
Minor Axis Muy (bottom) 47.05 - 47.05

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 153.36 kN
Mux = -10.11 kNm
Muy = -72.56 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu = 313.06 kN
Mux = 20.87 kNm
Muy = 2.96 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 313.06 kN
φ Pn = 313.06 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 82.07 deg
MRes = 73.26 kNm
( φ ) MCap = 158.5 kNm
Capacity Ratio = MRes/ MCap
= 0.462 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.36 86.87 795.77 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.14 67.13 601.64 603.18 67.29 10.54 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 68.68 616.55 804.24 87.71 4.42 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.34 57.38 508.95 603.18 67.29 21.22 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 67.29 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 103.49 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.57 100.1 931.41 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.28 84.34 770.41 804.24 87.71 28.38 315 339.3 39 0 87.71 0 39
300 x 350 180 -0.53 85.25 779.53 804.24 87.71 20.59 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.54 72.63 654.8 804.24 87.71 36.37 315.88 339.3 39 0 87.71 0 39

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 101.16 87.71 87.71
Bottom 36.2 36.2 39 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 313.06 kN
Mnty = 201.44 kNm
Pu Bottom = 299.49 kN
Mnby = 200.11 kNm
Vuy1 = 151.53 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 103.49 KN-m
Mnby = 126.7 KN-m
Vuy2 = 86.87 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 147.39 kN
Muy = 66.76 kNm
Vuy3 = -34.7839 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 151.53 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 43.59 kNm
φVcy = 94.92 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 94.34 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 47.46 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 394.08 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 394.08 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 313.06 kN
Mntx = 201.44 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 299.49 kN
Mnbx = 200.11 kNm
Vux1 = 151.53 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 123.91 KN-m
Mnbx = 137.36 KN-m
Vux2 = 98.59 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 153.36 kN
Mux = 72.56 kNm
Vux3 = 39.8792 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 151.53 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 48.44 kNm
φVcx = 91.99 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 99.23 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 46 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 414.49 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 414.49 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C14
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 450
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 18.51 kN
Muxt = -2.77 kNm
Muyt = -32.27 kNm
Vuxt = 12.52 kN
Vuyt = -2.76 kN
Pub = 28.69 kN
Muxb = 5.49 kNm
Muyb = 5.29 kNm
Vuxb = 12.52 kN
Vuyb = -2.76 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.948
Top 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 1.474
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 1.293
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M1 = -2.77 kNm
M2 = 5.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 5.29 kNm
M2 = -32.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.97
22.95 < 35.97, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -2.77 - -2.77
Major Axis Mux (bottom) 5.49 - 5.49
Minor Axis Muy (top) -32.27 - -32.27
Minor Axis Muy (bottom) 5.29 - 5.29

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 18.51 kN
Mux = -2.77 kNm
Muy = -32.27 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 44.86 kN
Mux = 8.61 kNm
Muy = 6.17 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 44.86 kN
φ Pn = 44.86 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 85.09 deg
MRes = 32.39 kNm
( φ ) MCap = 143.11 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.226 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.16 17.56 270 314.16 36.18 6.19 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.29 21.56 270 314.16 36.18 13.74 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.16 16.87 270 314.16 36.18 10.63 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.16 19.19 270 314.16 36.18 13.41 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
300 x 350 0 -0.36 86.87 795.77 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.14 67.13 601.64 603.18 67.29 10.54 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 68.68 616.55 804.24 87.71 4.42 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.34 57.38 508.95 603.18 67.29 21.22 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 67.29 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 103.49 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 44.86 kN
Mnty = 174.3 kNm
Pu Bottom = 29.02 kN
Mnby = 172.62 kNm
Vuy1 = 130.91 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 103.49 KN-m
Vuy2 = 66.37 KN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 22.47 kN
Muy = 28.22 kNm
Vuy3 = -11.1131 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 130.91 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.69 kNm
φVcy = 110.29 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 34.37 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 55.15 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 44.86 kN
Mntx = 174.3 kNm
Pu Bottom = 29.02 kN
Mnbx = 172.62 kNm
Vux1 = 130.91 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 123.91 KN-m
Vux2 = 74.07 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 18.51 kN
Mux = 32.27 kNm
Vux3 = 12.5241 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 130.91 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 29.36 kNm
φVcx = 103.2 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 46.2 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 51.6 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C15
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 388
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 317.58 kN
Muxt = -54.36 kNm
Muyt = -7.13 kNm
Vuxt = 3.84 kN
Vuyt = -42.91 kN
Pub = 331.15 kN
Muxb = 117.25 kNm
Muyb = 8.23 kNm
Vuxb = 3.84 kN
Vuyb = -42.91 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 2.911
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = -54.36 kNm
M2 = 117.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.56
27.5 < 39.56, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = -7.13 kNm
M2 = 8.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -54.36 - -54.36
Major Axis Mux (bottom) 117.25 - 117.25
Minor Axis Muy (top) -7.13 - -7.13
Minor Axis Muy (bottom) 8.23 - 8.23

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 331.15 kN
Mux = 117.25 kNm
Muy = 8.23 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 647.88 kN
Mux = 0.25 kNm
Muy = 0.73 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 647.88 kN
φ Pn = 647.88 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 4.01 deg
MRes = 117.54 kNm
( φ ) MCap = 178.02 kNm
Capacity Ratio = MRes/ MCap
= 0.66 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -2.2 105.22 985.18 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 90 -0.45 81.75 744.56 804.24 87.71 25.73 287.62 314.16 36.2 0 87.71 0 36.2
300 x 350 180 -0.57 102.66 958.19 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 270 -0.55 70.08 630.05 804.24 87.71 33.84 315 339.3 39 0 87.71 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 148.34 148.34 87.71 87.71
Bottom 36.2 36.2 39 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 184.55 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 512.79 kN
Mnty = 208.17 kNm
Pu Bottom = 491.67 kN
Mnby = 207.72 kNm
Vuy1 = 113.94 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 126.7 KN-m
Mnby = 0 KN-m
Vuy2 = 34.71 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 328.15 kN
Muy = 117.04 kNm
Vuy3 = 42.7482 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.94 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 65.43 kNm
φVcy = 80.32 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 56.04 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 40.16 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 512.79 kN
Mntx = 208.17 kNm
Pu Bottom = 491.67 kN
Mnbx = 207.72 kNm
Vux1 = 113.94 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 184.55 KN-m
Mnbx = 0 KN-m
Vux2 = 50.56 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 327.82 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 116.49 kNm
Vux3 = 43.9724 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.94 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 64.94 kNm
φVcx = 80.43 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 55.85 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 40.22 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C15
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 424
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 166.55 kN
Muxt = -1.44 kNm
Muyt = -69.71 kNm
Vuxt = 38.53 kN
Vuyt = -0.78 kN
Pub = 176.73 kN
Muxb = 0.89 kNm
Muyb = 45.85 kNm
Vuxb = 38.53 kN
Vuyb = -0.78 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 2.911
Top 71.111 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 3.327
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.263
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 0.89 kNm
M2 = -1.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 45.85 kNm
M2 = -69.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -1.44 - -1.44
Major Axis Mux (bottom) 0.89 - 0.89
Minor Axis Muy (top) -69.71 - -69.71
Minor Axis Muy (bottom) 45.85 - 45.85

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 166.55 kN
Mux = -1.44 kNm
Muy = -69.71 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 340.81 kN
Mux = 0.84 kNm
Muy = 2.81 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 340.81 kN
φ Pn = 340.81 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 88.82 deg
MRes = 69.72 kNm
( φ ) MCap = 161.56 kNm
Capacity Ratio = MRes/ MCap
= 0.432 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -1.27 90.11 828.6 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.3 65.68 587.75 603.18 67.29 8.98 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.36 88.99 817.22 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
300 x 350 270 -0.35 55.78 494.01 603.18 67.29 19.67 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 101.16 67.29 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 103.49 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -2.2 105.22 985.18 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 90 -0.45 81.75 744.56 804.24 87.71 25.73 287.62 314.16 36.2 0 87.71 0 36.2
300 x 350 180 -0.57 102.66 958.19 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 270 -0.55 70.08 630.05 804.24 87.71 33.84 315 339.3 39 0 87.71 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 148.34 148.34 87.71 87.71
Bottom 36.2 36.2 39 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 184.55 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 340.81 kN
Mnty = 204.18 kNm
Pu Bottom = 327.24 kN
Mnby = 202.84 kNm
Vuy1 = 153.59 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 103.49 KN-m
Mnby = 126.7 KN-m
Vuy2 = 86.87 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 168.27 kN
Muy = 55.13 kNm
Vuy3 = -26.6231 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 153.59 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 28.67 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcy = 110.76 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 71.39 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 55.38 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 340.81 kN
Mntx = 204.18 kNm
Pu Bottom = 327.24 kN
Mnbx = 202.84 kNm
Vux1 = 153.59 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 137.36 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 184.55 KN-m
Vux2 = 121.48 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 166.55 kN
Mux = 69.71 kNm
Vux3 = 38.528 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 153.59 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 43.52 kNm
φVcx = 95.37 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 97.04 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 47.69 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 405.35 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 405.35 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C15
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 452
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 19.53 kN
Muxt = -0.36 kNm
Muyt = -31.27 kNm
Vuxt = 12.26 kN
Vuyt = -0.13 kN
Pub = 29.71 kN
Muxb = 0.04 kNm
Muyb = 5.48 kNm
Vuxb = 12.26 kN
Vuyb = -0.13 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 3.327
Top 71.111 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 1.663
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 2.586
Top 71.111 3811 x 300 x 350 4000 x 300 x 350 28.126 26.797 1.293
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 0.04 kNm
M2 = -0.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.26
22.95 < 35.26, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
r = 115.47 mm
Klux /r = 22.95
M1 = 5.48 kNm
M2 = -31.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.1
22.95 < 36.1, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.36 - -0.36
Major Axis Mux (bottom) 0.04 - 0.04
Minor Axis Muy (top) -31.27 - -31.27
Minor Axis Muy (bottom) 5.48 - 5.48

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 19.53 kN
Mux = -0.36 kNm
Muy = -31.27 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 46.35 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 0.18 kNm
Muy = 6.08 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 46.35 kN
φ Pn = 46.35 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.33 deg
MRes = 31.27 kNm
( φ ) MCap = 144.35 kNm
Capacity Ratio = MRes/ MCap
= 0.217 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
300 x 350 0 -0.56 17.22 270 314.16 36.18 7.25 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.14 20.66 270 314.16 36.18 12.97 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.16 16.99 270 314.16 36.18 6.61 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.16 18.42 270 314.16 36.18 12.61 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -1.27 90.11 828.6 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.3 65.68 587.75 603.18 67.29 8.98 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.36 88.99 817.22 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 270 -0.35 55.78 494.01 603.18 67.29 19.67 270 314.16 36.2 0 67.29 0 36.2

Effective Moment for Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 101.16 67.29 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 103.49 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 46.35 kN
Mnty = 174.46 kNm
Pu Bottom = 30.51 kN
Mnby = 172.78 kNm
Vuy1 = 131.03 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 103.49 KN-m
Vuy2 = 66.37 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 19.27 kN
Muy = 23.37 kNm
Vuy3 = 5.8759 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 131.03 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 20.34 kNm
φVcy = 119.87 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 18.6 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 59.94 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 46.35 kN
Mntx = 174.46 kNm
Pu Bottom = 30.51 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 172.78 kNm
Vux1 = 131.03 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 137.36 KN-m
Vux2 = 79.15 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 19.53 kN
Mux = 31.27 kNm
Vux3 = 12.255 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 131.03 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 28.2 kNm
φVcx = 104.77 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 43.77 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 52.39 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C16
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3600 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 363
Critical Analysis Load Combination : 15
Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 242.13 kN
Muxt = 12.2 kNm
Muyt = -69.26 kNm
Vuxt = 46.53 kN
Vuyt = 4.11 kN
Pub = 255.71 kN
Muxb = -4.24 kNm
Muyb = 116.81 kNm
Vuxb = 46.53 kN
Vuyb = 4.11 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 5000 x 300 x 350 - 21.438 5.788
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 1.3
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = -4.24 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M2 = 12.2 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.17
27.5 < 38.17, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.12
M1 = -69.26 kNm
M2 = 116.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 12.2 - 12.2
Major Axis Mux (bottom) -4.24 - -4.24
Minor Axis Muy (top) -69.26 - -69.26
Minor Axis Muy (bottom) 116.81 - 116.81

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 255.71 kN
Mux = -4.24 kNm
Muy = 116.81 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 445.28 kN
Mux = -13.49 kNm
Muy = -0.24 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 445.28 kN
φ Pn = 445.28 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87.92 deg
MRes = 116.89 kNm
( φ ) MCap = 170.92 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.684 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.46 97.28 798.05 804.24 97.98 54.88 436.38 452.4 56.86 0 97.98 0 56.86
300 x 350 180 -2.2 101.12 942.01 942.48 101.16 2.61 270 314.16 36.2 101.16 0 36.2 0
350 x 400 270 -1.1 93.12 761.54 804.24 97.98 47.72 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 - 97.98 97.98
Bottom 36.2 - 56.86 56.86
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 101.16 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 154.84 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 445.28 kN
Mnty = 206.73 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 427.18 kN
Mnby = 206.34 kNm
Vuy1 = 113.17 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 154.84 KN-m
Mnby = 0 KN-m
Vuy2 = 42.42 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 287.46 kN
Muy = 116.43 kNm
Vuy3 = 42.2882 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.17 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 71.23 kNm
φVcy = 79.04 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 56.89 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.52 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3600 mm
Pu Top = 445.28 kN
Mntx = 206.73 kNm
Pu Bottom = 427.18 kN
Mnbx = 206.34 kNm
Vux1 = 114.74 kN
Shear from Beam Capacity at Joint:
Lux = 3600 mm
Mntx = 101.16 KN-m
Mnbx = 0 KN-m
Vux2 = 28.1 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 255.71 kN
Mux = 116.81 kNm
Vux3 = 46.531 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 114.74 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 76.6 kNm
φVcx = 78.27 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 60.78 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 39.14 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C16
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 411
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 194.63 kN
Muxt = 36.49 kNm
Muyt = -80.38 kNm
Vuxt = 48.05 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyt = 25.08 kN
Pub = 208.2 kN
Muxb = -38.72 kNm
Muyb = 63.71 kNm
Vuxb = 48.05 kN
Vuyb = 25.08 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 5000 x 300 x 350 - 21.438 5.788
Top 71.111 No Beam 5000 x 300 x 350 - 21.438 6.615
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 1.3
Top 71.111 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 1.485
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 36.49 kNm
M2 = -38.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = 63.71 kNm
M2 = -80.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 36.49 - 36.49
Major Axis Mux (bottom) -38.72 - -38.72
Minor Axis Muy (top) -80.38 - -80.38

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (bottom) 63.71 - 63.71

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 194.63 kN
Mux = 36.49 kNm
Muy = -80.38 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 244.69 kN
Mux = -52.22 kNm
Muy = -1.17 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 244.69 kN
φ Pn = 244.69 kN
Pt min for φ Pn = 0.5 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 65.58 deg
MRes = 88.28 kNm
( φ ) MCap = 152.33 kNm
Capacity Ratio = MRes/ MCap
= 0.58 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.24 75.35 608.06 804.24 97.98 31.23 345 392.7 49.6 0 97.98 0 49.6
300 x 350 180 -1.27 85.82 785.2 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
350 x 400 270 -0.67 75.5 609.37 804.24 97.98 30.36 345 392.7 49.6 0 97.98 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 - 97.98 97.98
Bottom 36.2 - 49.6 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 87.71 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 147.58 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.46 97.28 798.05 804.24 97.98 54.88 436.38 452.4 56.86 0 97.98 0 56.86
300 x 350 180 -2.2 101.12 942.01 942.48 101.16 2.61 270 314.16 36.2 101.16 0 36.2 0
350 x 400 270 -1.1 93.12 761.54 804.24 97.98 47.72 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 - 97.98 97.98
Bottom 36.2 - 56.86 56.86
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 101.16 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 154.84 kNm

Design Of Shear
Design for shear along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 244.69 kN
Mnty = 194.7 kNm
Pu Bottom = 231.11 kN
Mnby = 193.36 kNm
Vuy1 = 146.44 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 147.58 KN-m
Mnby = 154.84 KN-m
Vuy2 = 114.12 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 210.52 kN
Muy = 77.44 kNm
Vuy3 = 39.6397 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 146.44 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 44.34 kNm
φVcy = 93.46 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 88.3 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Check for Minimum Shear Reinforcement
0.5 x φVcy = 46.73 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 368.82 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 368.82 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 244.69 kN
Mntx = 194.7 kNm
Pu Bottom = 231.11 kN
Mnbx = 193.36 kNm
Vux1 = 149.25 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 87.71 KN-m
Mnbx = 101.16 KN-m
Vux2 = 72.64 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 133.63 kN
Mux = 80.94 kNm
Vux3 = 48.3968 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 149.25 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 59.92 kNm
φVcx = 86.63 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 104.38 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 43.31 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 436 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 436 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C16
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 429
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Put = 35.48 kN
Muxt = 8.05 kNm
Muyt = -42.08 kNm
Vuxt = 19.26 kN
Vuyt = 10.26 kN
Pub = 49.05 kN
Muxb = -22.73 kNm
Muyb = 15.68 kNm
Vuxb = 19.26 kN
Vuyb = 10.26 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 5000 x 300 x 350 - 21.438 6.615
Top 71.111 No Beam 5000 x 300 x 350 - 21.438 3.307
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 1.485
Top 71.111 3811 x 350 x 400 4000 x 350 x 400 48.981 46.667 0.743
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Minor axis = 0.84

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 8.05 kNm
M2 = -22.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.25
22.95 < 38.25, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.84
r = 115.47 mm
Klux /r = 18.91
M1 = 15.68 kNm
M2 = -42.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.47
18.91 < 38.47, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
A B C
Major Axis Mux (top) 8.05 - 8.05
Major Axis Mux (bottom) -22.73 - -22.73
Minor Axis Muy (top) -42.08 - -42.08
Minor Axis Muy (bottom) 15.68 - 15.68

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35.48 kN
Mux = 8.05 kNm
Muy = -42.08 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 57.02 kN
Mux = -22.36 kNm
Muy = 1.36 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 57.02 kN
φ Pn = 57.02 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 79.16 deg
MRes = 42.84 kNm
( φ ) MCap = 144.16 kNm
Capacity Ratio = MRes/ MCap
= 0.297 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 0.57 32.82 345 392.7 49.57 16.99 345 392.7 49.6 0 49.57 0 49.6
300 x 350 180 -0.56 19.28 270 314.16 36.18 7.17 270 314.16 36.2 36.18 0 36.2 0
350 x 400 270 -0.33 29.6 345 392.7 49.57 14.56 345 392.7 49.6 0 49.57 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 36.18 - 49.57 49.57
Bottom 36.2 - 49.6 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 36.2 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 99.17 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.24 75.35 608.06 804.24 97.98 31.23 345 392.7 49.6 0 97.98 0 49.6
300 x 350 180 -1.27 85.82 785.2 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
350 x 400 270 -0.67 75.5 609.37 804.24 97.98 30.36 345 392.7 49.6 0 97.98 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 - 97.98 97.98
Bottom 36.2 - 49.6 49.6
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 87.71 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 147.58 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 57.02 kN
Mnty = 175.6 kNm
Pu Bottom = 41.18 kN
Mnby = 173.91 kNm
Vuy1 = 131.89 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 99.17 KN-m
Mnby = 147.58 KN-m
Vuy2 = 93.11 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 44.05 kN
Muy = 37.23 kNm
Vuy3 = 10.929 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 131.89 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 30.31 kNm
φVcy = 102.29 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 49.33 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 51.15 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 57.02 kN
Mntx = 175.6 kNm
Pu Bottom = 41.18 kN
Mnbx = 173.91 kNm
Vux1 = 134.43 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 36.2 KN-m
Mnbx = 87.71 KN-m
Vux2 = 47.66 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 26.66 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 42.18 kNm
Vux3 = 19.4029 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 134.43 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 37.98 kNm
φVcx = 95.45 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 64.96 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 47.73 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C17
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 387
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 318.15 kN
Muxt = 54.92 kNm
Muyt = 7.71 kNm
Vuxt = -4.07 kN
Vuyt = 43.53 kN
Pub = 331.73 kN
Muxb = -119.15 kNm
Muyb = -8.54 kNm
Vuxb = -4.06 kN
Vuyb = 43.53 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 2.911
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = 54.92 kNm
M2 = -119.15 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.53
27.5 < 39.53, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 7.71 kNm
M2 = -8.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 54.92 - 54.92
Major Axis Mux (bottom) -119.15 - -119.15
Minor Axis Muy (top) 7.71 - 7.71
Minor Axis Muy (bottom) -8.54 - -8.54

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 331.73 kN
Mux = -119.15 kNm
Muy = -8.54 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 655.32 kN
Mux = 0.25 kNm
Muy = -1.32 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 655.32 kN
φ Pn = 655.32 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 4.1 deg
MRes = 119.46 kNm
( φ ) MCap = 178.04 kNm
Capacity Ratio = MRes/ MCap
= 0.671 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -1.66 106.12 994.74 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 90 -0.55 69.73 626.73 804.24 87.71 33.96 315 339.3 39 0 87.71 0 39
300 x 350 180 -0.56 103.54 967.41 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
300 x 350 270 -0.44 83.38 760.79 804.24 87.71 22.36 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 148.34 148.34 87.71 87.71
Bottom 36.2 36.2 36.2 39
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 184.55 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 518.9 kN
Mnty = 208.3 kNm
Pu Bottom = 497.78 kN
Mnby = 207.85 kNm
Vuy1 = 114.01 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 126.7 KN-m
Mnby = 0 KN-m
Vuy2 = 34.71 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 331.73 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 119.15 kNm
Vuy3 = 43.5297 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.01 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 66.99 kNm
φVcy = 79.99 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 56.71 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.99 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Top = 518.9 kN
Mntx = 208.3 kNm
Pu Bottom = 497.78 kN
Mnbx = 207.85 kNm
Vux1 = 114.01 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 184.55 KN-m
Mnbx = 0 KN-m
Vux2 = 50.56 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 328.91 kN
Mux = 116.57 kNm
Vux3 = -44.0216 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 114.01 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 64.85 kNm
φVcx = 80.46 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 55.92 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 40.23 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C17
Level : 4m To 7m
Design Code = ACI 318M - 2014

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 423
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 167.14 kN
Muxt = -1.4 kNm
Muyt = 70.37 kNm
Vuxt = -38.92 kN
Vuyt = -0.76 kN
Pub = 177.33 kN
Muxb = 0.87 kNm
Muyb = -46.34 kNm
Vuxb = -38.92 kN
Vuyb = -0.76 kN

Effective Length Calculation


Calculation Along Major Axis Of Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 2.911
Top 71.111 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 3.327
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 22.95
M1 = 0.87 kNm
M2 = -1.4 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -46.34 kNm
M2 = 70.37 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -1.4 - -1.4
Major Axis Mux (bottom) 0.87 - 0.87
Minor Axis Muy (top) 70.37 - 70.37
Minor Axis Muy (bottom) -46.34 - -46.34

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 167.14 kN
Mux = -1.4 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 70.37 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 344.61 kN
Mux = 0.84 kNm
Muy = -5.13 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 344.61 kN
φ Pn = 344.61 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 88.86 deg
MRes = 70.39 kNm
( φ ) MCap = 161.63 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.435 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.72 90.74 834.98 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.35 55.53 491.65 603.18 67.29 19.79 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 89.61 823.53 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 270 -0.32 67.73 607.44 804.24 87.71 6.03 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 101.16 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
300 x 350 0 -1.66 106.12 994.74 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 90 -0.55 69.73 626.73 804.24 87.71 33.96 315 339.3 39 0 87.71 0 39
300 x 350 180 -0.56 103.54 967.41 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 270 -0.44 83.38 760.79 804.24 87.71 22.36 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 148.34 148.34 87.71 87.71
Bottom 36.2 36.2 36.2 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 184.55 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 344.61 kN
Mnty = 204.56 kNm
Pu Bottom = 331.03 kN
Mnby = 203.22 kNm
Vuy1 = 153.88 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 123.91 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnby = 126.7 KN-m
Vuy2 = 94.57 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 170.47 kN
Muy = 56.09 kNm
Vuy3 = -27.0733 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 153.88 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 29.28 kNm
φVcy = 109.9 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 73.3 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 54.95 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 344.61 kN
Mntx = 204.56 kNm
Pu Bottom = 331.03 kN
Mnbx = 203.22 kNm
Vux1 = 153.88 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 137.36 KN-m
Mnbx = 184.55 KN-m
Vux2 = 121.48 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 167.14 kN
Mux = 70.37 kNm
Vux3 = -38.9161 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 153.88 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 44.09 kNm
φVcx = 95.04 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 98.06 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 47.52 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 409.62 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 409.62 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
General Data
Column No. : C17
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 451
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 19.2 kN
Muxt = -0.34 kNm
Muyt = 31.23 kNm
Vuxt = -12.36 kN
Vuyt = -0.13 kN
Pub = 29.38 kN
Muxb = 0.04 kNm
Muyb = -5.83 kNm
Vuxb = -12.36 kN
Vuyb = -0.13 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 3.327
Top 71.111 5000 x 300 x 350 5000 x 300 x 350 21.438 21.438 1.663
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 1.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 0.04 kNm
M2 = -0.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.34
22.95 < 35.34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -5.83 kNm
M2 = 31.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.24
22.95 < 36.24, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.34 - -0.34
Major Axis Mux (bottom) 0.04 - 0.04
Minor Axis Muy (top) 31.23 - 31.23
Minor Axis Muy (bottom) -5.83 - -5.83

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 19.2 kN
Mux = -0.34 kNm
Muy = 31.23 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 46.53 kN
Mux = 0.18 kNm
Muy = -7.16 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 46.53 kN
φ Pn = 46.53 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.38 deg
MRes = 31.23 kNm
( φ ) MCap = 144.33 kNm
Capacity Ratio = MRes/ MCap
= 0.216 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.81 17.4 270 314.16 36.18 7.45 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.16 18.5 270 314.16 36.18 12.51 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.19 17.16 270 314.16 36.18 6.79 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.12 20.53 270 314.16 36.18 12.36 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.72 90.74 834.98 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.35 55.53 491.65 603.18 67.29 19.79 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 89.61 823.53 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 270 -0.32 67.73 607.44 804.24 87.71 6.03 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 101.16 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 46.53 kN
Mnty = 174.48 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 30.69 kN
Mnby = 172.8 kNm
Vuy1 = 131.05 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 123.91 KN-m
Vuy2 = 74.07 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 19.35 kN
Muy = 23.76 kNm
Vuy3 = 5.9643 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 131.05 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 20.72 kNm
φVcy = 118.91 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 20.24 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 59.45 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 46.53 kN
Mntx = 174.48 kNm
Pu Bottom = 30.69 kN
Mnbx = 172.8 kNm
Vux1 = 131.05 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 137.36 KN-m
Vux2 = 79.15 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 19.2 kN
Mux = 31.23 kNm
Vux3 = -12.356 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 131.05 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 28.21 kNm
φVcx = 104.76 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 43.82 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 52.38 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C18
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3600 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 361
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 228.35 kN
Muxt = -13.37 kNm
Muyt = 95.77 kNm
Vuxt = -63.73 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyt = -5.42 kN
Pub = 241.93 kN
Muxb = 8.29 kNm
Muyb = -159.1 kNm
Vuxb = -63.73 kN
Vuyb = -5.42 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 300 x 350 No Beam 21.438 - 5.788
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 1.324
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = 8.29 kNm
M2 = -13.37 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.12
M1 = 95.77 kNm
M2 = -159.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -13.37 - -13.37
Major Axis Mux (bottom) 8.29 - 8.29
Minor Axis Muy (top) 95.77 - 95.77

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (bottom) -159.1 - -159.1

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 241.93 kN
Mux = 8.29 kNm
Muy = -159.1 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 384.79 kN
Mux = 9.63 kNm
Muy = -2.14 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 384.79 kN
φ Pn = 384.79 kN
Pt min for φ Pn = 0.5 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87.02 deg
MRes = 159.32 kNm
( φ ) MCap = 169.15 kNm
Capacity Ratio = MRes/ MCap
= 0.942 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.08 105.84 874.17 1005.3 120.31 74.28 598.97 603.18 74.86 0 120.31 0 74.86
300 x 350 0 1.1 92.62 854.18 942.48 101.16 4.59 270 314.16 36.2 101.16 0 36.2 0
350 x 400 270 -1.31 121.47 1015.93 1231.5 144.41 75.07 605.63 804.24 98.12 0 144.41 0 98.12

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 101.16 144.41 120.31
Bottom - 36.2 98.12 74.86
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 101.16 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 219.27 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 384.79 kN
Mnty = 205.44 kNm
Pu Bottom = 363.67 kN
Mnby = 204.99 kNm
Vuy1 = 112.44 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 219.27 KN-m
Mnby = 0 KN-m
Vuy2 = 60.07 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 278.04 kN
Muy = 118.13 kNm
Vuy3 = -42.7577 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 112.44 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 74.41 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcy = 78.38 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 56.77 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.19 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3600 mm
Pu Top = 384.79 kN
Mntx = 205.44 kNm
Pu Bottom = 363.67 kN
Mnbx = 204.99 kNm
Vux1 = 114.01 kN
Shear from Beam Capacity at Joint:
Lux = 3600 mm
Mntx = 101.16 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 0 KN-m
Vux2 = 28.1 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 241.93 kN
Mux = 159.1 kNm
Vux3 = -63.7341 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 114.01 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 121.06 kNm
φVcx = 73.59 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 67.36 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 36.8 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C18
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 402
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 174.95 kN
Muxt = -32.63 kNm
Muyt = 112.43 kNm
Vuxt = -67.14 kN
Vuyt = -22.01 kN
Pub = 188.53 kN
Muxb = 33.39 kNm
Muyb = -88.92 kNm
Vuxb = -67.14 kN
Vuyb = -22.01 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 No Beam 21.438 - 5.788
Top 71.111 5000 x 300 x 350 No Beam 21.438 - 6.615
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 1.324
Top 71.111 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 1.513
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = -32.63 kNm
M2 = 33.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
r = 115.47 mm
Klux /r = 22.52
M1 = -88.92 kNm
M2 = 112.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -32.63 - -32.63
Major Axis Mux (bottom) 33.39 - 33.39
Minor Axis Muy (top) 112.43 - 112.43
Minor Axis Muy (bottom) -88.92 - -88.92

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 174.95 kN
Mux = -32.63 kNm
Muy = 112.43 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 218.36 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 36.74 kNm
Muy = -7.96 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 218.36 kN
φ Pn = 218.36 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 73.82 deg
MRes = 117.07 kNm
( φ ) MCap = 157.43 kNm
Capacity Ratio = MRes/ MCap
= 0.744 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
350 x 400 90 -0.65 81.52 660.89 804.24 97.98 50.11 402.5 452.4 56.86 0 97.98 0 56.86
300 x 350 0 0.24 77.06 698.19 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
350 x 400 270 -1.1 91.49 747.28 804.24 97.98 43.51 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 87.71 97.98 97.98
Bottom - 36.2 56.86 56.86
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 87.71 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 154.84 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.08 105.84 874.17 1005.3 120.31 74.28 598.97 603.18 74.86 0 120.31 0 74.86
300 x 350 0 1.1 92.62 854.18 942.48 101.16 4.59 270 314.16 36.2 101.16 0 36.2 0
350 x 400 270 -1.31 121.47 1015.93 1231.5 144.41 75.07 605.63 804.24 98.12 0 144.41 0 98.12

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top - 101.16 144.41 120.31
Bottom - 36.2 98.12 74.86
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 101.16 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 219.27 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 218.36 kN
Mnty = 192.1 kNm
Pu Bottom = 202.52 kN
Mnby = 190.54 kNm
Vuy1 = 144.39 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 154.84 KN-m
Mnby = 219.27 KN-m
Vuy2 = 141.17 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 193.18 kN
Muy = 72.69 kNm
Vuy3 = -36.1781 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 144.39 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 42.31 kNm
φVcy = 94.39 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 83.34 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 47.19 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 348.13 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 348.13 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 218.36 kN
Mntx = 192.1 kNm
Pu Bottom = 202.52 kN
Mnbx = 190.54 kNm
Vux1 = 147.17 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 87.71 KN-m
Mnbx = 101.16 KN-m
Vux2 = 72.64 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 126.64 kN
Mux = 109.79 kNm
Vux3 = -65.3416 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 147.17 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 89.88 kNm
φVcx = 79.45 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 112.87 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 39.72 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 471.49 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 471.49 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C18
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 426
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 35.4 kN
Muxt = -7.92 kNm
Muyt = 55.96 kNm
Vuxt = -26.42 kN
Vuyt = -9 kN
Pub = 48.98 kN
Muxb = 19.08 kNm
Muyb = -23.28 kNm
Vuxb = -26.42 kN
Vuyb = -9 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 71.111 5000 x 300 x 350 No Beam 21.438 - 6.615
Top 71.111 5000 x 300 x 350 No Beam 21.438 - 3.307
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 1.513
Top 71.111 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 0.757
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.84

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = -7.92 kNm
M2 = 19.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.98

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
22.95 < 38.98, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.84
r = 115.47 mm
Klux /r = 18.91
M1 = -23.28 kNm
M2 = 55.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.99
18.91 < 38.99, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -7.92 - -7.92
Major Axis Mux (bottom) 19.08 - 19.08
Minor Axis Muy (top) 55.96 - 55.96
Minor Axis Muy (bottom) -23.28 - -23.28

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35.4 kN
Mux = -7.92 kNm
Muy = 55.96 kNm

Φ Pn, Max Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 57.5 kN
Mux = 21.39 kNm
Muy = -4.49 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 57.5 kN
φ Pn = 57.5 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 81.95 deg
MRes = 56.52 kNm
( φ ) MCap = 144.76 kNm
Capacity Ratio = MRes/ MCap
= 0.39 < 1

Beam Capacity At Joint:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.34 35.78 365.08 392.7 49.57 21.02 345 392.7 49.6 0 49.57 0 49.6
300 x 350 0 0.66 18.87 270 314.16 36.18 7.64 270 314.16 36.2 36.18 0 36.2 0
350 x 400 270 0.57 39.57 402.5 452.4 56.81 23.13 345 392.7 49.6 0 56.81 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 36.18 56.81 49.57
Bottom - 36.2 49.6 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 36.2 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 106.41 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.65 81.52 660.89 804.24 97.98 50.11 402.5 452.4 56.86 0 97.98 0 56.86
300 x 350 0 0.24 77.06 698.19 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
350 x 400 270 -1.1 91.49 747.28 804.24 97.98 43.51 402.5 452.4 56.86 0 97.98 0 56.86

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 87.71 97.98 97.98
Bottom - 36.2 56.86 56.86
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 87.71 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 154.84 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 57.5 kN
Mnty = 175.65 kNm
Pu Bottom = 41.66 kN
Mnby = 173.97 kNm
Vuy1 = 131.93 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 106.41 KN-m
Mnby = 154.84 KN-m
Vuy2 = 98.59 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 44.53 kN
Muy = 34.35 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy3 = -9.6749 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 131.93 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 27.35 kNm
φVcy = 106.26 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 42.78 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 53.13 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 57.5 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = 175.65 kNm
Pu Bottom = 41.66 kN
Mnbx = 173.97 kNm
Vux1 = 134.47 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 36.2 KN-m
Mnbx = 87.71 KN-m
Vux2 = 47.66 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 26.4 kN
Mux = 55.5 kNm
Vux3 = -25.7668 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 134.47 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 51.35 kNm
φVcx = 87.7 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 77.94 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 43.85 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C19
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 378
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 245.48 kN
Muxt = 6.75 kNm
Muyt = 74.45 kNm
Vuxt = -54.63 kN
Vuyt = 2.09 kN
Pub = 259.05 kN
Muxb = -1.62 kNm
Muyb = -144.03 kNm
Vuxb = -54.63 kN
Vuyb = 2.09 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.579
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 27.5
M1 = -1.62 kNm
M2 = 6.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.88
27.5 < 36.88, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 74.45 kNm
M2 = -144.03 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 6.75 - 6.75
Major Axis Mux (bottom) -1.62 - -1.62
Minor Axis Muy (top) 74.45 - 74.45
Minor Axis Muy (bottom) -144.03 - -144.03

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 259.05 kN
Mux = -1.62 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = -144.03 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 506.44 kN
Mux = -2.84 kNm
Muy = -5.2 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 506.44 kN
φ Pn = 506.44 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.35 deg
MRes = 144.04 kNm
( φ ) MCap = 171.96 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.838 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.54 70.9 638 804.24 87.71 48.73 428.46 452.4 51.37 0 87.71 0 51.37
300 x 350 0 -0.33 73.94 667.55 804.24 87.71 32.1 315 339.3 39 87.71 0 39 0
300 x 350 270 -0.04 96.44 893.41 942.48 101.16 32.82 315 339.3 39 0 101.16 0 39
300 x 350 180 1.1 93.12 859.24 942.48 101.16 1.4 270 314.16 36.2 101.16 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 87.71 101.16 87.71
Bottom 36.2 39 39 51.37
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 140.16 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Top = 506.44 kN
Mnty = 208.04 kNm
Pu Bottom = 488.34 kN
Mnby = 207.65 kNm
Vuy1 = 113.89 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 152.53 KN-m
Mnby = 0 KN-m
Vuy2 = 41.79 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 250.45 kN
Muy = 124.7 kNm
Vuy3 = 47.7315 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.89 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 85.32 kNm
φVcy = 76.9 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 61.65 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.45 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 506.44 kN
Mntx = 208.04 kNm
Pu Bottom = 488.34 kN
Mnbx = 207.65 kNm
Vux1 = 113.89 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 140.16 KN-m
Mnbx = 0 KN-m
Vux2 = 38.4 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 259.05 kN
Mux = 144.03 kNm
Vux3 = -54.6336 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.89 kN
λ = 1
φ = 0.6

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 103.29 kNm
φVcx = 74.94 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 64.9 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 37.47 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Table For Links
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C19
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 403
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 200.84 kN
Muxt = 15.52 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muyt = 91.68 kNm
Vuxt = -51.12 kN
Vuyt = 10.72 kN
Pub = 214.41 kN
Muxb = -16.63 kNm
Muyb = -61.65 kNm
Vuxb = -51.12 kN
Vuyb = 10.72 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.579
Top 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.948
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Check For Stability Index
Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 15.52 kNm
M2 = -16.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -61.65 kNm
M2 = 91.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 15.52 - 15.52

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Major Axis Mux (bottom) -16.63 - -16.63
Minor Axis Muy (top) 91.68 - 91.68
Minor Axis Muy (bottom) -61.65 - -61.65

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 200.84 kN
Mux = 15.52 kNm
Muy = 91.68 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 270.22 kN
Mux = -11.02 kNm
Muy = -20.21 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 270.22 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ Pn = 270.22 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 80.39 deg
MRes = 92.98 kNm
( φ ) MCap = 163.48 kNm
Capacity Ratio = MRes/ MCap
= 0.569 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.35 53.09 468.82 603.18 67.29 30.99 315 339.3 39 0 67.29 0 39
300 x 350 0 -0.2 57.16 506.9 603.18 67.29 15.45 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 0.11 76.67 694.27 804.24 87.71 12.55 270 314.16 36.2 0 87.71 0 36.2
300 x 350 180 0.24 78.4 711.39 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 67.29 87.71 67.29

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 36.2 36.2 36.2 39
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.54 70.9 638 804.24 87.71 48.73 428.46 452.4 51.37 0 87.71 0 51.37
300 x 350 0 -0.33 73.94 667.55 804.24 87.71 32.1 315 339.3 39 87.71 0 39 0
300 x 350 270 -0.04 96.44 893.41 942.48 101.16 32.82 315 339.3 39 0 101.16 0 39
300 x 350 180 1.1 93.12 859.24 942.48 101.16 1.4 270 314.16 36.2 101.16 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 87.71 101.16 87.71
Bottom 36.2 39 39 51.37
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 140.16 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 270.22 kN
Mnty = 197.22 kNm
Pu Bottom = 256.65 kN
Mnby = 195.88 kNm
Vuy1 = 148.34 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 126.7 KN-m
Mnby = 152.53 KN-m
Vuy2 = 105.37 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 128.02 kN
Muy = 73.64 kNm
Vuy3 = 39.4025 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 148.34 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 53.51 kNm
φVcy = 89 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 98.9 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 44.5 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 413.13 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 413.13 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 270.22 kN
Mntx = 197.22 kNm
Pu Bottom = 256.65 kN
Mnbx = 195.88 kNm
Vux1 = 148.34 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 123.91 KN-m
Mnbx = 140.16 KN-m
Vux2 = 99.65 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 131.88 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 86.4 kNm
Vux3 = -47.5703 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 148.34 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 65.66 kNm
φVcx = 84.68 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 106.1 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 42.34 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 443.19 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 443.19 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C19
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 442
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 24.64 kN
Muxt = 2.14 kNm
Muyt = 38.22 kNm
Vuxt = -16.12 kN
Vuyt = 3.91 kN
Pub = 38.22 kN
Muxb = -9.59 kNm
Muyb = -10.12 kNm
Vuxb = -16.12 kN
Vuyb = 3.91 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.948
Top 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 1.474
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 1.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 2.14 kNm
M2 = -9.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.68
22.95 < 36.68, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -10.12 kNm
M2 = 38.22 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.18
22.95 < 37.18, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 2.14 - 2.14
Major Axis Mux (bottom) -9.59 - -9.59
Minor Axis Muy (top) 38.22 - 38.22
Minor Axis Muy (bottom) -10.12 - -10.12

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 24.64 kN
Mux = 2.14 kNm
Muy = 38.22 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 45.39 kN
Mux = -13 kNm
Muy = -9.54 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 45.39 kN
φ Pn = 45.39 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 86.79 deg
MRes = 38.28 kNm
( φ ) MCap = 144.08 kNm
Capacity Ratio = MRes/ MCap
= 0.266 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.16 21.42 270 314.16 36.18 15.61 270 314.16 36.2 0 36.18 0 36.2
300 x 350 0 -0.16 17.51 270 314.16 36.18 10.74 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.4 23.31 270 314.16 36.18 15.72 270 314.16 36.2 0 36.18 0 36.2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
300 x 350 180 0.66 17.88 270 314.16 36.18 6.78 270 314.16 36.2 36.18 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 90 -0.35 53.09 468.82 603.18 67.29 30.99 315 339.3 39 0 67.29 0 39
300 x 350 0 -0.2 57.16 506.9 603.18 67.29 15.45 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 0.11 76.67 694.27 804.24 87.71 12.55 270 314.16 36.2 0 87.71 0 36.2
300 x 350 180 0.24 78.4 711.39 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 67.29 87.71 67.29
Bottom 36.2 36.2 36.2 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 123.91 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 45.39 kN
Mnty = 174.36 kNm
Pu Bottom = 29.55 kN
Mnby = 172.68 kNm
Vuy1 = 130.96 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 126.7 KN-m
Vuy2 = 75.13 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 17.02 kN
Muy = 28.09 kNm
Vuy3 = 10.9255 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 130.96 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 25.41 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcy = 109.03 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 36.54 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 54.52 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 45.39 kN
Mntx = 174.36 kNm
Pu Bottom = 29.55 kN
Mnbx = 172.68 kNm
Vux1 = 130.96 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 123.91 KN-m
Vux2 = 74.07 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 18.37 kN
Mux = 37.77 kNm
Vux3 = -15.0127 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 130.96 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 34.88 kNm
φVcx = 97.26 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 56.16 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 48.63 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C20
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 380
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 257.43 kN
Muxt = -9.47 kNm
Muyt = 70.2 kNm
Vuxt = -52.13 kN
Vuyt = -3.96 kN
Pub = 271.01 kN
Muxb = 6.37 kNm
Muyb = -138.28 kNm
Vuxb = -52.13 kN
Vuyb = -3.96 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.579
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = 6.37 kNm
M2 = -9.47 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
r = 115.47 mm
Klux /r = 27.5
M1 = 70.2 kNm
M2 = -138.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -9.47 - -9.47
Major Axis Mux (bottom) 6.37 - 6.37
Minor Axis Muy (top) 70.2 - 70.2
Minor Axis Muy (bottom) -138.28 - -138.28

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 271.01 kN
Mux = 6.37 kNm
Muy = -138.28 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 597.09 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 6.57 kNm
Muy = -2.77 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 597.09 kN
φ Pn = 597.09 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87.36 deg
MRes = 138.43 kNm
( φ ) MCap = 172.26 kNm
Capacity Ratio = MRes/ MCap
= 0.804 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
300 x 350 0 -0.52 100.82 938.88 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.53 78.52 712.52 804.24 87.71 42.6 372.24 452.4 51.37 0 87.71 0 51.37
300 x 350 180 -0.33 74.76 675.63 804.24 87.71 32.08 315 339.3 39 87.71 0 39 0
300 x 350 270 -0.89 94.54 873.84 942.48 101.16 31.23 315 339.3 39 0 101.16 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 101.16 101.16 87.71
Bottom 39 36.2 39 51.37
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 140.16 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 456.53 kN
Mnty = 206.97 kNm
Pu Bottom = 438.42 kN
Mnby = 206.58 kNm
Vuy1 = 113.3 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 152.53 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnby = 0 KN-m
Vuy2 = 41.79 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 260.85 kN
Muy = 124.61 kNm
Vuy3 = -47.6665 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.3 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 83.6 kNm
φVcy = 77.07 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 60.38 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.54 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 456.53 kN
Mntx = 206.97 kNm
Pu Bottom = 438.42 kN
Mnbx = 206.58 kNm
Vux1 = 113.3 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 140.16 KN-m
Mnbx = 0 KN-m
Vux2 = 38.4 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 271.01 kN
Mux = 138.28 kNm
Vux3 = -52.1338 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.3 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 95.67 kNm
φVcx = 75.63 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 62.78 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 37.82 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
General Data
Column No. : C20
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 417
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 220.34 kN
Muxt = -23.04 kNm
Muyt = 83.73 kNm
Vuxt = -46.06 kN
Vuyt = -15.39 kN
Pub = 233.92 kN
Muxb = 23.11 kNm
Muyb = -54.41 kNm
Vuxb = -46.06 kN
Vuyb = -15.39 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.579
Top 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.948
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = -23.04 kNm
M2 = 23.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -54.41 kNm
M2 = 83.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -23.04 - -23.04
Major Axis Mux (bottom) 23.11 - 23.11
Minor Axis Muy (top) 83.73 - 83.73
Minor Axis Muy (bottom) -54.41 - -54.41

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 220.34 kN
Mux = -23.04 kNm
Muy = 83.73 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 315.11 kN
Mux = 25.37 kNm
Muy = -10.73 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 315.11 kN
φ Pn = 315.11 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 74.62 deg
MRes = 86.84 kNm
( φ ) MCap = 161.38 kNm
Capacity Ratio = MRes/ MCap
= 0.538 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 87.42 801.38 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.34 61.2 545.08 603.18 67.29 25.32 282.85 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.2 57.76 512.61 603.18 67.29 15.36 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.77 75.34 681.25 804.24 87.71 11.49 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 67.29 87.71 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.52 100.82 938.88 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.53 78.52 712.52 804.24 87.71 42.6 372.24 452.4 51.37 0 87.71 0 51.37
300 x 350 180 -0.33 74.76 675.63 804.24 87.71 32.08 315 339.3 39 87.71 0 39 0
300 x 350 270 -0.89 94.54 873.84 942.48 101.16 31.23 315 339.3 39 0 101.16 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 101.16 101.16 87.71
Bottom 39 36.2 39 51.37
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 140.16 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 315.11 kN
Mnty = 201.65 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 301.53 kN
Mnby = 200.31 kNm
Vuy1 = 151.68 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 123.91 KN-m
Mnby = 152.53 KN-m
Vuy2 = 104.32 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 133.39 kN
Muy = 74.33 kNm
Vuy3 = -39.6855 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 151.68 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 53.35 kNm
φVcy = 89.59 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 103.48 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 44.8 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 432.26 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 432.26 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 315.11 kN
Mntx = 201.65 kNm
Pu Bottom = 301.53 kN
Mnbx = 200.31 kNm
Vux1 = 151.68 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 123.91 KN-m
Mnbx = 140.16 KN-m
Vux2 = 99.65 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 137.87 kN
Mux = 81.16 kNm
Vux3 = -44.3322 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 151.68 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 59.48 kNm
φVcx = 87.13 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 107.59 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 43.56 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 449.41 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 449.41 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C20
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 444
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 24.28 kN
Muxt = -4.16 kNm
Muyt = 35.92 kNm
Vuxt = -14.29 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyt = -5.61 kN
Pub = 37.86 kN
Muxb = 12.67 kNm
Muyb = -6.93 kNm
Vuxb = -14.29 kN
Vuyb = -5.61 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.948
Top 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 1.474
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 1.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = -4.16 kNm
M2 = 12.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.94
22.95 < 37.94, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -6.93 kNm
M2 = 35.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.31
22.95 < 36.31, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -4.16 - -4.16
Major Axis Mux (bottom) 12.67 - 12.67
Minor Axis Muy (top) 35.92 - 35.92

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (bottom) -6.93 - -6.93

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 24.28 kN
Mux = -4.16 kNm
Muy = 35.92 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 45.3 kN
Mux = 14.02 kNm
Muy = -7.42 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 45.3 kN
φ Pn = 45.3 kN
Pt min for φ Pn = 0.5 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 83.39 deg
MRes = 36.16 kNm
( φ ) MCap = 143.66 kNm
Capacity Ratio = MRes/ MCap
= 0.252 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.15 17.82 270 314.16 36.18 6.15 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.16 21.05 270 314.16 36.18 15.11 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.16 16.98 270 314.16 36.18 10.91 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 0.16 23.17 270 314.16 36.18 15.1 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 87.42 801.38 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.34 61.2 545.08 603.18 67.29 25.32 282.85 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.2 57.76 512.61 603.18 67.29 15.36 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.77 75.34 681.25 804.24 87.71 11.49 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 67.29 87.71 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Design Of Shear

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 45.3 kN
Mnty = 174.35 kNm
Pu Bottom = 29.46 kN
Mnby = 172.67 kNm
Vuy1 = 130.95 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 123.91 KN-m
Vuy2 = 74.07 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 22.62 kN
Muy = 29 kNm
Vuy3 = -12.6434 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 130.95 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 25.45 kNm
φVcy = 108.98 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 36.63 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 54.49 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 45.3 kN
Mntx = 174.35 kNm
Pu Bottom = 29.46 kN
Mnbx = 172.67 kNm
Vux1 = 130.95 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 123.91 KN-m
Vux2 = 74.07 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 18.25 kN
Mux = 35.85 kNm
Vux3 = -13.8286 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 130.95 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 32.99 kNm
φVcx = 99.08 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 53.12 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 49.54 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C21
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 382
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Location = Bottom Joint
Put = 290.27 kN
Muxt = 4.07 kNm
Muyt = 67.06 kNm
Vuxt = -49.82 kN
Vuyt = 1.09 kN
Pub = 303.84 kN
Muxb = -0.3 kNm
Muyb = -132.18 kNm
Vuxb = -49.82 kN
Vuyb = 1.09 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.579
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = -0.3 kNm
M2 = 4.07 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.89
27.5 < 34.89, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 67.06 kNm
M2 = -132.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 4.07 - 4.07
Major Axis Mux (bottom) -0.3 - -0.3
Minor Axis Muy (top) 67.06 - 67.06
Minor Axis Muy (bottom) -132.18 - -132.18

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 303.84 kN
Mux = -0.3 kNm
Muy = -132.18 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 601.11 kN
Mux = -5.53 kNm
Muy = -1.42 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 601.11 kN
φ Pn = 601.11 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.87 deg
MRes = 132.18 kNm
( φ ) MCap = 176.64 kNm
Capacity Ratio = MRes/ MCap
= 0.748 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.53 86.19 788.93 804.24 87.71 21.36 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.54 76.07 688.38 804.24 87.71 40.26 351.02 452.4 51.37 0 87.71 0 51.37
300 x 350 180 -0.52 101.74 948.54 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 270 -0.28 89.7 824.4 942.48 101.16 28.77 315 339.3 39 0 101.16 0 39

Effective Moment for Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 148.34 87.71 101.16 87.71
Bottom 36.2 36.2 39 51.37
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 184.55 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 486.65 kN
Mnty = 207.61 kNm
Pu Bottom = 468.55 kN
Mnby = 207.23 kNm
Vuy1 = 113.65 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 152.53 KN-m
Mnby = 0 KN-m
Vuy2 = 41.79 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 293.36 kN
Muy = 122.99 kNm
Vuy3 = 46.4381 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 113.65 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 76.86 kNm
φVcy = 78.11 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 59.24 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.05 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 486.65 kN
Mntx = 207.61 kNm
Pu Bottom = 468.55 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 207.23 kNm
Vux1 = 113.65 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 184.55 KN-m
Mnbx = 0 KN-m
Vux2 = 50.56 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 303.84 kN
Mux = 132.18 kNm
Vux3 = -49.8227 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.65 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 84.4 kNm
φVcx = 77 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 61.09 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.5 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C21
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 419
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 154.05 kN
Muxt = 8.39 kNm
Muyt = 78.02 kNm
Vuxt = -42.71 kN
Vuyt = 5.89 kN
Pub = 164.23 kN
Muxb = -9.28 kNm
Muyb = -50.06 kNm
Vuxb = -42.71 kN
Vuyb = 5.89 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.579
Top 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.948
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 8.39 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M2 = -9.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -50.06 kNm
M2 = 78.02 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 8.39 - 8.39
Major Axis Mux (bottom) -9.28 - -9.28
Minor Axis Muy (top) 78.02 - 78.02
Minor Axis Muy (bottom) -50.06 - -50.06

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 154.05 kN
Mux = 8.39 kNm
Muy = 78.02 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 317.01 kN
Mux = -21.61 kNm
Muy = -5.44 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 317.01 kN
φ Pn = 317.01 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 83.87 deg
MRes = 78.47 kNm
( φ ) MCap = 158.95 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.494 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 69.27 622.28 804.24 87.71 4.86 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.35 59.58 529.68 603.18 67.29 23.8 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 88.24 809.63 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 270 -0.13 71.45 643.34 804.24 87.71 9.91 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 87.71 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
300 x 350 0 -0.53 86.19 788.93 804.24 87.71 21.36 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.54 76.07 688.38 804.24 87.71 40.26 351.02 452.4 51.37 0 87.71 0 51.37
300 x 350 180 -0.52 101.74 948.54 1472.61 148.34 0 270 314.16 36.2 148.34 0 36.2 0
300 x 350 270 -0.28 89.7 824.4 942.48 101.16 28.77 315 339.3 39 0 101.16 0 39

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 148.34 87.71 101.16 87.71
Bottom 36.2 36.2 39 51.37
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 184.55 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 152.53 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 317.01 kN
Mnty = 201.83 kNm
Pu Bottom = 303.44 kN
Mnby = 200.5 kNm
Vuy1 = 151.82 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 123.91 KN-m
Mnby = 152.53 KN-m
Vuy2 = 104.32 KN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 149.36 kN
Muy = 68.21 kNm
Vuy3 = 35.5474 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 151.82 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 44.72 kNm
φVcy = 94.24 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 95.98 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 47.12 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 400.9 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 400.9 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 317.01 kN
Mntx = 201.83 kNm
Pu Bottom = 303.44 kN
Mnbx = 200.5 kNm
Vux1 = 151.82 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 137.36 KN-m
Mnbx = 184.55 KN-m
Vux2 = 121.48 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 154.05 kN
Mux = 78.02 kNm
Vux3 = -42.7054 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 151.82 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 53.8 kNm
φVcx = 89.42 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 104.01 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 44.71 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 434.47 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 434.47 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C21
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 445
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 18 kN
Muxt = 1.55 kNm
Muyt = 34.39 kNm
Vuxt = -13.32 kN
Vuyt = 2.42 kN
Pub = 28.18 kN
Muxb = -5.72 kNm
Muyb = -5.56 kNm
Vuxb = -13.32 kN
Vuyb = 2.42 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 2.948
Top 71.111 4000 x 300 x 350 5000 x 300 x 350 26.797 21.438 1.474
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 1.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 1.55 kNm
M2 = -5.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.25
22.95 < 37.25, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -5.56 kNm
M2 = 34.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.94
22.95 < 35.94, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 1.55 - 1.55
Major Axis Mux (bottom) -5.72 - -5.72
Minor Axis Muy (top) 34.39 - 34.39
Minor Axis Muy (bottom) -5.56 - -5.56

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 18 kN
Mux = 1.55 kNm
Muy = 34.39 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 44.73 kN
Mux = -8.83 kNm
Muy = -7.26 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 44.73 kN
φ Pn = 44.73 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 87.42 deg
MRes = 34.42 kNm
( φ ) MCap = 143.39 kNm
Capacity Ratio = MRes/ MCap
= 0.24 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.16 16.99 270 314.16 36.18 10.92 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.16 20.39 270 314.16 36.18 14.43 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.15 17.3 270 314.16 36.18 6.66 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.31 22.6 270 314.16 36.18 14.27 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 69.27 622.28 804.24 87.71 4.86 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.35 59.58 529.68 603.18 67.29 23.8 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 88.24 809.63 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 270 -0.13 71.45 643.34 804.24 87.71 9.91 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 101.16 87.71 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 44.73 kN
Mnty = 174.29 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 28.89 kN
Mnby = 172.61 kNm
Vuy1 = 130.9 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 123.91 KN-m
Vuy2 = 74.07 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 22.3 kN
Muy = 28.33 kNm
Vuy3 = 11.2015 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 130.9 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.83 kNm
φVcy = 110.04 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 34.77 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 55.02 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 44.73 kN
Mntx = 174.29 kNm
Pu Bottom = 28.89 kN
Mnbx = 172.61 kNm
Vux1 = 130.9 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 137.36 KN-m
Vux2 = 79.15 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 18 kN
Mux = 34.39 kNm
Vux3 = -13.3192 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 130.9 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 31.56 kNm
φVcx = 100.58 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 50.55 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 50.29 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C22
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 383
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 264.03 kN
Muxt = -1.17 kNm
Muyt = 64.62 kNm
Vuxt = -48 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyt = -0.86 kN
Pub = 277.61 kN
Muxb = 2.28 kNm
Muyb = -127.32 kNm
Vuxb = -48 kN
Vuyb = -0.86 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 2.326
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = -1.17 kNm
M2 = 2.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 64.62 kNm
M2 = -127.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -1.17 - -1.17
Major Axis Mux (bottom) 2.28 - 2.28
Minor Axis Muy (top) 64.62 - 64.62

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (bottom) -127.32 - -127.32

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 277.61 kN
Mux = 2.28 kNm
Muy = -127.32 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 543.86 kN
Mux = 0.06 kNm
Muy = -1.38 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 543.86 kN
φ Pn = 543.86 kN
Pt min for φ Pn = 0.5 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 88.97 deg
MRes = 127.34 kNm
( φ ) MCap = 173.63 kNm
Capacity Ratio = MRes/ MCap
= 0.733 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.53 82.95 756.54 804.24 87.71 22.7 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.53 74.17 669.88 804.24 87.71 38.38 333.96 339.3 39 0 87.71 0 39
300 x 350 180 -0.53 82.91 756.09 804.24 87.71 22.73 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.41 87.75 804.65 942.48 101.16 26.87 300.64 314.16 36.2 0 101.16 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 101.16 87.71
Bottom 36.2 36.2 36.2 39
Moment Along D:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 140.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 543.86 kN
Mnty = 208.84 kNm
Pu Bottom = 525.76 kN
Mnby = 208.45 kNm
Vuy1 = 114.32 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 140.16 KN-m
Mnby = 0 KN-m
Vuy2 = 38.4 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 282.78 kN
Muy = 122.02 kNm
Vuy3 = 45.7004 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.32 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 77.55 kNm
φVcy = 78.07 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 60.42 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.04 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 543.86 kN
Mntx = 208.84 kNm
Pu Bottom = 525.76 kN
Mnbx = 208.45 kNm
Vux1 = 114.32 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = 123.91 KN-m
Mnbx = 0 KN-m
Vux2 = 33.95 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 277.61 kN
Mux = 127.32 kNm
Vux3 = -47.9976 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 114.32 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 83.67 kNm
φVcx = 77.16 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 61.93 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.58 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C22
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 421
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 140.73 kN
Muxt = -1.16 kNm
Muyt = 75.61 kNm
Vuxt = -41.47 kN
Vuyt = -0.6 kN
Pub = 150.92 kN
Muxb = 0.64 kNm
Muyb = -48.78 kNm
Vuxb = -41.47 kN
Vuyb = -0.6 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 2.326
Top 71.111 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 2.658
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 0.64 kNm
M2 = -1.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -48.78 kNm
M2 = 75.61 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -1.16 - -1.16
Major Axis Mux (bottom) 0.64 - 0.64
Minor Axis Muy (top) 75.61 - 75.61
Minor Axis Muy (bottom) -48.78 - -48.78

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 140.73 kN
Mux = -1.16 kNm
Muy = 75.61 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu = 288.39 kN
Mux = 0.1 kNm
Muy = -5.32 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 288.39 kN
φ Pn = 288.39 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.12 deg
MRes = 75.62 kNm
( φ ) MCap = 158.56 kNm
Capacity Ratio = MRes/ MCap
= 0.477 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 66.72 597.68 603.18 67.29 6.22 270 314.16 36.2 67.29 0 36.2 0
300 x 350 90 -0.34 58.35 518.07 603.18 67.29 22.58 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 66.68 597.31 603.18 67.29 6.24 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.29 70.23 631.51 804.24 87.71 8.75 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 67.29 67.29 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 103.49 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.53 82.95 756.54 804.24 87.71 22.7 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.53 74.17 669.88 804.24 87.71 38.38 333.96 339.3 39 0 87.71 0 39
300 x 350 180 -0.53 82.91 756.09 804.24 87.71 22.73 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.41 87.75 804.65 942.48 101.16 26.87 300.64 314.16 36.2 0 101.16 0 36.2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 101.16 87.71
Bottom 36.2 36.2 36.2 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 140.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 288.39 kN
Mnty = 199.01 kNm
Pu Bottom = 274.82 kN
Mnby = 197.67 kNm
Vuy1 = 149.69 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 123.91 KN-m
Mnby = 140.16 KN-m
Vuy2 = 99.65 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 143.63 kN
Muy = 62.17 kNm
Vuy3 = -31.893 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 149.69 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 39.58 kNm
φVcy = 97.49 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 86.99 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 48.75 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 363.39 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 363.39 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 288.39 kN
Mntx = 199.01 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 274.82 kN
Mnbx = 197.67 kNm
Vux1 = 149.69 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 103.49 KN-m
Mnbx = 123.91 KN-m
Vux2 = 85.81 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 140.73 kN
Mux = 75.61 kNm
Vux3 = -41.4736 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 149.69 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 53.48 kNm
φVcx = 89.22 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 100.78 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 44.61 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 420.98 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 420.98 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C22
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 448
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 17.34 kN
Muxt = -0.5 kNm
Muyt = 33.28 kNm
Vuxt = -12.96 kN
Vuyt = -0.17 kN
Pub = 27.52 kN
Muxb = 0 kNm
Muyb = -5.58 kNm
Vuxb = -12.96 kN
Vuyb = -0.17 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 2.658
Top 71.111 4000 x 300 x 350 4000 x 300 x 350 26.797 26.797 1.329
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 1.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M1 = 0 kNm
M2 = -0.5 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.88
22.95 < 33.88, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -5.58 kNm
M2 = 33.28 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.01
22.95 < 36.01, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.5 - -0.5
Major Axis Mux (bottom) 0 - 0
Minor Axis Muy (top) 33.28 - 33.28
Minor Axis Muy (bottom) -5.58 - -5.58

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 17.34 kN
Mux = -0.5 kNm
Muy = 33.28 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 43.74 kN
Mux = 0 kNm
Muy = -7.26 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 43.74 kN
φ Pn = 43.74 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 89.13 deg
MRes = 33.29 kNm
( φ ) MCap = 143.99 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.231 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.16 17.73 270 314.16 36.18 10.28 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.15 19.84 270 314.16 36.18 13.87 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.16 17.77 270 314.16 36.18 10.26 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 -0.12 21.98 270 314.16 36.18 13.69 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
300 x 350 0 -0.34 66.72 597.68 603.18 67.29 6.22 270 314.16 36.2 67.29 0 36.2 0
300 x 350 90 -0.34 58.35 518.07 603.18 67.29 22.58 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 66.68 597.31 603.18 67.29 6.24 270 314.16 36.2 67.29 0 36.2 0
300 x 350 270 -0.29 70.23 631.51 804.24 87.71 8.75 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 67.29 67.29 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 103.49 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 43.74 kN
Mnty = 174.19 kNm
Pu Bottom = 27.9 kN
Mnby = 172.5 kNm
Vuy1 = 130.83 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 123.91 KN-m
Vuy2 = 74.07 KN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 17.93 kN
Muy = 27.48 kNm
Vuy3 = 8.5875 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 130.83 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.66 kNm
φVcy = 110.31 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 34.2 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 55.15 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 43.74 kN
Mntx = 174.19 kNm
Pu Bottom = 27.9 kN
Mnbx = 172.5 kNm
Vux1 = 130.83 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 103.49 KN-m
Vux2 = 66.37 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 17.34 kN
Mux = 33.28 kNm
Vux3 = -12.9591 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 130.83 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 30.56 kNm
φVcx = 101.7 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 48.54 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 50.85 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C23
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 385
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 279.4 kN
Muxt = -62.57 kNm
Muyt = 2.75 kNm
Vuxt = -0.38 kN
Vuyt = -46.39 kN
Pub = 292.97 kN
Muxb = 122.93 kNm
Muyb = 1.23 kNm
Vuxb = -0.38 kN
Vuyb = -46.39 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.579
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = -62.57 kNm
M2 = 122.93 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 1.23 kNm
M2 = 2.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.62
27.5 < 28.62, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -62.57 - -62.57
Major Axis Mux (bottom) 122.93 - 122.93
Minor Axis Muy (top) 2.75 - 2.75
Minor Axis Muy (bottom) 1.23 - 1.23

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 292.97 kN
Mux = 122.93 kNm
Muy = 1.23 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 599.89 kN
Mux = 5.46 kNm
Muy = -1.37 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 599.89 kN
φ Pn = 599.89 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 0.57 deg
MRes = 122.93 kNm
( φ ) MCap = 175.37 kNm
Capacity Ratio = MRes/ MCap
= 0.701 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.56 100.96 940.36 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.54 72.28 651.43 804.24 87.71 36.49 316.93 339.3 39 0 87.71 0 39
300 x 350 180 -0.53 86.07 787.76 804.24 87.71 21.39 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.58 85.86 785.67 804.24 87.71 24.93 278.38 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 101.16 87.71 87.71
Bottom 36.2 36.2 36.2 39
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 137.36 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 485.33 kN
Mnty = 207.58 kNm
Pu Bottom = 467.23 kN
Mnby = 207.2 kNm
Vuy1 = 113.64 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 126.7 KN-m
Mnby = 0 KN-m
Vuy2 = 34.71 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 292.97 kN
Muy = 122.93 kNm
Vuy3 = -46.387 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.64 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 76.86 kNm
φVcy = 78.11 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 59.22 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.05 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 485.33 kN
Mntx = 207.58 kNm
Pu Bottom = 467.23 kN
Mnbx = 207.2 kNm
Vux1 = 113.64 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 137.36 KN-m
Mnbx = 0 KN-m
Vux2 = 37.63 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 302.94 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 122.47 kNm
Vux3 = -46.1769 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.64 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 74.84 kNm
φVcx = 78.44 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 58.66 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 39.22 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C23
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 422
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 153.75 kN
Muxt = -10.13 kNm
Muyt = 73.2 kNm
Vuxt = -40.25 kN
Vuyt = -6.69 kN
Pub = 163.93 kN
Muxb = 9.93 kNm
Muyb = -47.51 kNm
Vuxb = -40.25 kN
Vuyb = -6.69 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.579
Top 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.948
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.305
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 9.93 kNm
M2 = -10.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -47.51 kNm
M2 = 73.2 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -10.13 - -10.13
Major Axis Mux (bottom) 9.93 - 9.93
Minor Axis Muy (top) 73.2 - 73.2
Minor Axis Muy (bottom) -47.51 - -47.51

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 153.75 kN
Mux = -10.13 kNm
Muy = 73.2 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 316.6 kN
Mux = 21.04 kNm
Muy = -5.29 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 316.6 kN
φ Pn = 316.6 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 82.12 deg
MRes = 73.9 kNm
( φ ) MCap = 158.56 kNm
Capacity Ratio = MRes/ MCap
= 0.466 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 87.47 801.88 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.34 57.12 506.53 603.18 67.29 21.35 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 69.19 621.49 804.24 87.71 4.91 270 314.16 36.2 87.71 0 36.2 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
300 x 350 270 -0.46 69.1 620.65 804.24 87.71 7.55 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.56 100.96 940.36 942.48 101.16 0 270 314.16 36.2 101.16 0 36.2 0
300 x 350 90 -0.54 72.28 651.43 804.24 87.71 36.49 316.93 339.3 39 0 87.71 0 39
300 x 350 180 -0.53 86.07 787.76 804.24 87.71 21.39 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.58 85.86 785.67 804.24 87.71 24.93 278.38 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 101.16 87.71 87.71
Bottom 36.2 36.2 36.2 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 137.36 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 126.7 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 316.6 kN
Mnty = 201.79 kNm
Pu Bottom = 303.02 kN
Mnby = 200.45 kNm
Vuy1 = 151.79 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 123.91 KN-m
Mnby = 126.7 KN-m
Vuy2 = 94.57 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 149.27 kN
Muy = 67.85 kNm
Vuy3 = -35.3229 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 151.79 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 44.38 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcy = 94.45 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 95.56 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 47.23 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 399.18 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 399.18 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 316.6 kN
Mntx = 201.79 kNm
Pu Bottom = 303.02 kN
Mnbx = 200.45 kNm
Vux1 = 151.79 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 123.91 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 137.36 KN-m
Vux2 = 98.59 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 153.75 kN
Mux = 73.2 kNm
Vux3 = -40.2467 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 151.79 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 49.02 kNm
φVcx = 91.72 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 100.11 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 45.86 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 418.18 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 418.18 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C23
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 449
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Top Joint
Put = 18.15 kN
Muxt = -2.75 kNm
Muyt = 32.19 kNm
Vuxt = -12.6 kN
Vuyt = -2.76 kN
Pub = 28.33 kN
Muxb = 5.53 kNm
Muyb = -5.61 kNm
Vuxb = -12.6 kN
Vuyb = -2.76 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 2.948
Top 71.111 5000 x 300 x 350 4000 x 300 x 350 21.438 26.797 1.474
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 2.634
Top 71.111 4139 x 300 x 350 3811 x 300 x 350 25.897 28.126 1.317
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = -2.75 kNm
M2 = 5.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.97
22.95 < 39.97, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
r = 115.47 mm
Klux /r = 22.95
M1 = -5.61 kNm
M2 = 32.19 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.09
22.95 < 36.09, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -2.75 - -2.75
Major Axis Mux (bottom) 5.53 - 5.53
Minor Axis Muy (top) 32.19 - 32.19
Minor Axis Muy (bottom) -5.61 - -5.61

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 18.15 kN
Mux = -2.75 kNm
Muy = 32.19 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 45.04 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 8.67 kNm
Muy = -7.25 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 45.04 kN
φ Pn = 45.04 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 85.12 deg
MRes = 32.31 kNm
( φ ) MCap = 143.06 kNm
Capacity Ratio = MRes/ MCap
= 0.226 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
300 x 350 0 -0.19 17.75 270 314.16 36.18 6.37 270 314.16 36.2 36.18 0 36.2 0
300 x 350 90 -0.16 19.28 270 314.16 36.18 13.31 270 314.16 36.2 0 36.18 0 36.2
300 x 350 180 -0.16 17.08 270 314.16 36.18 10.85 270 314.16 36.2 36.18 0 36.2 0
300 x 350 270 0.04 21.4 270 314.16 36.18 13.1 270 314.16 36.2 0 36.18 0 36.2

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 36.18 36.18 36.18 36.18
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 72.38 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 72.38 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
300 x 350 0 -0.34 87.47 801.88 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
300 x 350 90 -0.34 57.12 506.53 603.18 67.29 21.35 270 314.16 36.2 0 67.29 0 36.2
300 x 350 180 -0.34 69.19 621.49 804.24 87.71 4.91 270 314.16 36.2 87.71 0 36.2 0
300 x 350 270 -0.46 69.1 620.65 804.24 87.71 7.55 270 314.16 36.2 0 87.71 0 36.2

Effective Moment for Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 87.71 87.71 67.29
Bottom 36.2 36.2 36.2 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 123.91 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 123.91 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 45.04 kN
Mnty = 174.32 kNm
Pu Bottom = 29.2 kN
Mnby = 172.64 kNm
Vuy1 = 130.93 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 72.38 KN-m
Mnby = 123.91 KN-m
Vuy2 = 74.07 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 22.61 kN
Muy = 28.65 kNm
Vuy3 = -11.2465 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 130.93 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 25.09 kNm
φVcy = 109.58 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 35.58 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 54.79 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 45.04 kN
Mntx = 174.32 kNm
Pu Bottom = 29.2 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnbx = 172.64 kNm
Vux1 = 130.93 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 72.38 KN-m
Mnbx = 123.91 KN-m
Vux2 = 74.07 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 18.15 kN
Mux = 32.19 kNm
Vux3 = -12.6041 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 130.93 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 29.34 kNm
φVcx = 103.23 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 46.17 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 51.61 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C24
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3600 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 364
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 277.18 kN
Muxt = 53.49 kNm
Muyt = 7.46 kNm
Vuxt = -4.5 kN
Vuyt = 43 kN
Pub = 290.76 kN
Muxb = -118.45 kNm
Muyb = -10.55 kNm
Vuxb = -4.5 kN
Vuyb = 43 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 5000 x 300 x 350 - 21.438 5.788
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 1.324
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.5
M1 = 53.49 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M2 = -118.45 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.42
27.5 < 39.42, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.12
M1 = 7.46 kNm
M2 = -10.55 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 53.49 - 53.49
Major Axis Mux (bottom) -118.45 - -118.45
Minor Axis Muy (top) 7.46 - 7.46
Minor Axis Muy (bottom) -10.55 - -10.55

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 290.76 kN
Mux = -118.45 kNm
Muy = -10.55 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 450.67 kN
Mux = -13.53 kNm
Muy = -0.16 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 450.67 kN
φ Pn = 450.67 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 5.09 deg
MRes = 118.92 kNm
( φ ) MCap = 173.58 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.685 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.1 92.67 757.56 804.24 97.98 47.8 402.5 452.4 56.86 0 97.98 0 56.86
300 x 350 180 -1.66 102.03 951.54 1472.61 148.34 3.2 270 314.16 36.2 148.34 0 36.2 0
350 x 400 270 -0.46 97.49 799.91 804.24 97.98 51.53 408.85 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 148.34 - 97.98 97.98
Bottom 36.2 - 56.86 56.86
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 148.34 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 154.84 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3650 mm
Pu Top = 450.67 kN
Mnty = 206.84 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 432.57 kN
Mnby = 206.46 kNm
Vuy1 = 113.23 kN
Shear from Beam Capacity at Joint:
Luy = 3650 mm
Mnty = 154.84 KN-m
Mnby = 0 KN-m
Vuy2 = 42.42 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 290.76 kN
Muy = 118.45 kNm
Vuy3 = 42.9957 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.23 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 72.73 kNm
φVcy = 78.77 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 57.44 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 39.38 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3600 mm
Pu Top = 450.67 kN
Mntx = 206.84 kNm
Pu Bottom = 432.57 kN
Mnbx = 206.46 kNm
Vux1 = 114.81 kN
Shear from Beam Capacity at Joint:
Lux = 3600 mm
Mntx = 148.34 KN-m
Mnbx = 0 KN-m
Vux2 = 41.21 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 254.79 kN
Mux = 116.75 kNm
Vux3 = -46.4726 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 114.81 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mm = 76.69 kNm
φVcx = 78.26 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 60.9 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 39.13 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C24
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 392
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 195.1 kN
Muxt = 36.66 kNm
Muyt = 80.9 kNm
Vuxt = -48.33 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyt = 25.18 kN
Pub = 208.68 kN
Muxb = -38.86 kNm
Muyb = -64.06 kNm
Vuxb = -48.33 kN
Vuyb = 25.18 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 5000 x 300 x 350 - 21.438 5.788
Top 71.111 No Beam 5000 x 300 x 350 - 21.438 6.615
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 1.324
Top 71.111 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 1.513
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 36.66 kNm
M2 = -38.86 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = -64.06 kNm
M2 = 80.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 36.66 - 36.66
Major Axis Mux (bottom) -38.86 - -38.86
Minor Axis Muy (top) 80.9 - 80.9

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minor Axis Muy (bottom) -64.06 - -64.06

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 195.1 kN
Mux = 36.66 kNm
Muy = 80.9 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 247.64 kN
Mux = -52.42 kNm
Muy = -0.39 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 247.64 kN
φ Pn = 247.64 kN
Pt min for φ Pn = 0.5 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 65.62 deg
MRes = 88.82 kNm
( φ ) MCap = 152.37 kNm
Capacity Ratio = MRes/ MCap
= 0.583 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.67 75.22 606.97 804.24 97.98 30.44 345 392.7 49.6 0 97.98 0 49.6
300 x 350 180 -0.72 86.44 791.42 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
350 x 400 270 0 76.08 614.28 804.24 97.98 28.4 345 392.7 49.6 0 97.98 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 - 97.98 97.98
Bottom 36.2 - 49.6 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 87.71 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 147.58 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.1 92.67 757.56 804.24 97.98 47.8 402.5 452.4 56.86 0 97.98 0 56.86
300 x 350 180 -1.66 102.03 951.54 1472.61 148.34 3.2 270 314.16 36.2 148.34 0 36.2 0
350 x 400 270 -0.46 97.49 799.91 804.24 97.98 51.53 408.85 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 148.34 - 97.98 97.98
Bottom 36.2 - 56.86 56.86
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 148.34 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 154.84 kNm

Design Of Shear
Design for shear along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 247.64 kN
Mnty = 194.99 kNm
Pu Bottom = 234.06 kN
Mnby = 193.65 kNm
Vuy1 = 146.66 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 147.58 KN-m
Mnby = 154.84 KN-m
Vuy2 = 114.12 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 213.01 kN
Muy = 78.3 kNm
Vuy3 = 39.9807 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 146.66 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 44.8 kNm
φVcy = 93.21 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 89.07 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Check for Minimum Shear Reinforcement
0.5 x φVcy = 46.61 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 372.06 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 372.06 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 247.64 kN
Mntx = 194.99 kNm
Pu Bottom = 234.06 kN
Mnbx = 193.65 kNm
Vux1 = 149.48 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 87.71 KN-m
Mnbx = 148.34 KN-m
Vux2 = 90.79 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 133.33 kN
Mux = 81.05 kNm
Vux3 = -48.4165 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 149.48 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 60.09 kNm
φVcx = 86.6 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 104.79 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 43.3 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 437.73 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 437.73 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C24
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 395
Critical Analysis Load Combination : 12
Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Put = 35.38 kN
Muxt = 8.05 kNm
Muyt = 42.27 kNm
Vuxt = -19.44 kN
Vuyt = 10.28 kN
Pub = 48.95 kN
Muxb = -22.78 kNm
Muyb = -16.02 kNm
Vuxb = -19.44 kN
Vuyb = 10.28 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 5000 x 300 x 350 - 21.438 6.615
Top 71.111 No Beam 5000 x 300 x 350 - 21.438 3.307
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 1.513
Top 71.111 4139 x 350 x 400 3811 x 350 x 400 45.099 48.981 0.757
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Minor axis = 0.84

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.95
M1 = 8.05 kNm
M2 = -22.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.24
22.95 < 38.24, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.84
r = 115.47 mm
Klux /r = 18.91
M1 = -16.02 kNm
M2 = 42.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.55
18.91 < 38.55, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
A B C
Major Axis Mux (top) 8.05 - 8.05
Major Axis Mux (bottom) -22.78 - -22.78
Minor Axis Muy (top) 42.27 - 42.27
Minor Axis Muy (bottom) -16.02 - -16.02

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35.38 kN
Mux = 8.05 kNm
Muy = 42.27 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 57.63 kN
Mux = -22.42 kNm
Muy = -2.27 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 57.63 kN
φ Pn = 57.63 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 79.21 deg
MRes = 43.03 kNm
( φ ) MCap = 144.16 kNm
Capacity Ratio = MRes/ MCap
= 0.299 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.33 29.54 345 392.7 49.57 14.53 345 392.7 49.6 0 49.57 0 49.6
300 x 350 180 -0.81 19.48 270 314.16 36.18 7.36 270 314.16 36.2 36.18 0 36.2 0
350 x 400 270 -1.13 32.9 345 392.7 49.57 16 345 392.7 49.6 0 49.57 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 36.18 - 49.57 49.57
Bottom 36.2 - 49.6 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 36.2 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 99.17 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.67 75.22 606.97 804.24 97.98 30.44 345 392.7 49.6 0 97.98 0 49.6
300 x 350 180 -0.72 86.44 791.42 804.24 87.71 0 270 314.16 36.2 87.71 0 36.2 0
350 x 400 270 0 76.08 614.28 804.24 97.98 28.4 345 392.7 49.6 0 97.98 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 87.71 - 97.98 97.98
Bottom 36.2 - 49.6 49.6
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 87.71 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 147.58 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2650 mm
Pu Top = 57.63 kN
Mnty = 175.66 kNm
Pu Bottom = 41.79 kN
Mnby = 173.98 kNm
Vuy1 = 131.94 kN
Shear from Beam Capacity at Joint:
Luy = 2650 mm
Mnty = 99.17 KN-m
Mnby = 147.58 KN-m
Vuy2 = 93.11 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 44.52 kN
Muy = 37.57 kNm
Vuy3 = 10.9628 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 131.94 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 30.57 kNm
φVcy = 101.99 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 49.91 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 51 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 57.63 kN
Mntx = 175.66 kNm
Pu Bottom = 41.79 kN
Mnbx = 173.98 kNm
Vux1 = 134.48 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 36.2 KN-m
Mnbx = 87.71 KN-m
Vux2 = 47.66 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 26.43 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 42.21 kNm
Vux3 = -19.4477 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 134.48 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 38.05 kNm
φVcx = 95.41 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 65.12 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 47.7 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C25
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3600 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 358
Critical Analysis Load Combination : 17
Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z)
Critical Location = Bottom Joint
Put = 89.16 kN
Muxt = -14 kNm
Muyt = 54.72 kNm
Vuxt = -48.41 kN
Vuyt = -6.6 kN
Pub = 102.74 kN
Muxb = 12.38 kNm
Muyb = -138.87 kNm
Vuxb = -48.41 kN
Vuyb = -6.6 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 350 x 400 No Beam 37.333 - 3.341
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 4139 x 350 x 400 - 45.099 2.765
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = 12.38 kNm
M2 = -14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.12
M1 = 54.72 kNm
M2 = -138.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.73
27.12 < 38.73, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -14 - -14
Major Axis Mux (bottom) 12.38 - 12.38
Minor Axis Muy (top) 54.72 - 54.72
Minor Axis Muy (bottom) -138.87 - -138.87

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 102.74 kN
Mux = 12.38 kNm
Muy = -138.87 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 344.74 kN
Mux = 0.36 kNm
Muy = 147.03 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 344.74 kN
φ Pn = 344.74 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 84.91 deg
MRes = 139.42 kNm
( φ ) MCap = 153.6 kNm
Capacity Ratio = MRes/ MCap
= 0.908 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 1.12 109.21 904.39 1005.3 120.31 37.12 379.1 392.7 49.6 120.31 0 49.6 0
350 x 400 90 -1.31 117.54 979.86 1005.3 120.31 66.28 531.33 565.5 70.41 0 120.31 0 70.41

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 120.31 - 120.31
Bottom - 49.6 - 70.41
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 120.31 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 120.31 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 344.74 kN
Mnty = 204.57 kNm
Pu Bottom = 326.64 kN
Mnby = 202.78 kNm
Vuy1 = 113.15 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 120.31 KN-m
Mnby = 0 KN-m
Vuy2 = 33.42 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 142.61 kN
Muy = 113.12 kNm
Vuy3 = 38.0681 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.15 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 90.69 kNm
φVcy = 76.16 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 61.65 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.08 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3600 mm
Pu Top = 344.74 kN
Mntx = 204.57 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Bottom = 326.64 kN
Mnbx = 202.78 kNm
Vux1 = 113.15 kN
Shear from Beam Capacity at Joint:
Lux = 3600 mm
Mntx = 120.31 KN-m
Mnbx = 0 KN-m
Vux2 = 33.42 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 102.74 kN
Mux = 138.87 kNm
Vux3 = -48.4101 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.15 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 122.71 kNm
φVcx = 73.42 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 66.21 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 36.71 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C25
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 398
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 179.62 kN
Muxt = -22.3 kNm
Muyt = -85.26 kNm
Vuxt = 45.01 kN
Vuyt = -16.19 kN
Pub = 193.2 kN
Muxb = 26.26 kNm
Muyb = 49.72 kNm
Vuxb = 45.01 kN
Vuyb = -16.19 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 No Beam 37.333 - 3.341
Top 71.111 5000 x 350 x 400 No Beam 37.333 - 3.818
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 350 x 400 - 45.099 2.765
Top 71.111 No Beam 4139 x 350 x 400 - 45.099 3.16
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
M1 = -22.3 kNm
M2 = 26.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = 49.72 kNm
M2 = -85.26 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -22.3 - -22.3
Major Axis Mux (bottom) 26.26 - 26.26
Minor Axis Muy (top) -85.26 - -85.26
Minor Axis Muy (bottom) 49.72 - 49.72

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 179.62 kN
Mux = -22.3 kNm
Muy = -85.26 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Φ Pn, Max Check
Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 193.2 kN
Mux = 26.26 kNm
Muy = 49.72 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 193.2 kN
φ Pn = 193.2 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 75.34 deg
MRes = 88.13 kNm
( φ ) MCap = 158.86 kNm
Capacity Ratio = MRes/ MCap

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 0.555 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 0.43 85.66 696.59 804.24 97.98 11.77 345 392.7 49.6 97.98 0 49.6 0
350 x 400 90 -1.1 90.42 737.95 804.24 97.98 39.78 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 97.98 - 97.98
Bottom - 49.6 - 56.86
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 97.98 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 1.12 109.21 904.39 1005.3 120.31 37.12 379.1 392.7 49.6 120.31 0 49.6 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
350 x 400 90 -1.31 117.54 979.86 1005.3 120.31 66.28 531.33 565.5 70.41 0 120.31 0 70.41

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 120.31 - 120.31
Bottom - 49.6 - 70.41
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 120.31 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 120.31 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 193.2 kN
Mnty = 189.62 kNm
Pu Bottom = 179.62 kN
Mnby = 188.28 kNm
Vuy1 = 145.35 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 97.98 KN-m
Mnby = 120.31 KN-m
Vuy2 = 83.96 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 158.96 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 76.85 kNm
Vuy3 = -40.1725 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 145.35 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 51.85 kNm
φVcy = 89.26 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 93.48 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 44.63 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 390.49 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 390.49 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu Top = 193.2 kN
Mntx = 189.62 kNm
Pu Bottom = 179.62 kN
Mnbx = 188.28 kNm
Vux1 = 145.35 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 97.98 KN-m
Mnbx = 120.31 KN-m
Vux2 = 83.96 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 141.64 kN
Mux = 80.22 kNm
Vux3 = 41.532 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 145.35 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 57.95 kNm
φVcx = 86.77 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 97.62 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 43.39 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 407.77 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 407.77 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C25
Level : 7m To 10m
Design Code = ACI 318M - 2014

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 425
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 45.49 kN
Muxt = -11.52 kNm
Muyt = -38.4 kNm
Vuxt = 15.06 kN
Vuyt = -10.05 kN
Pub = 59.06 kN
Muxb = 18.61 kNm
Muyb = 6.77 kNm
Vuxb = 15.06 kN
Vuyb = -10.05 kN

Effective Length Calculation


Calculation Along Major Axis Of Column

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 No Beam 37.333 - 3.818
Top 71.111 5000 x 350 x 400 No Beam 37.333 - 1.909
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 350 x 400 - 45.099 3.16
Top 71.111 No Beam 4139 x 350 x 400 - 45.099 1.58
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 22.52
M1 = -11.52 kNm
M2 = 18.61 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = 6.77 kNm
M2 = -38.4 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.12
22.52 < 36.12, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -11.52 - -11.52
Major Axis Mux (bottom) 18.61 - 18.61
Minor Axis Muy (top) -38.4 - -38.4
Minor Axis Muy (bottom) 6.77 - 6.77

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 45.49 kN
Mux = -11.52 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = -38.4 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 59.06 kN
Mux = 18.61 kNm
Muy = 6.77 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 59.06 kN
φ Pn = 59.06 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 73.3 deg
MRes = 40.09 kNm
( φ ) MCap = 145.31 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.276 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.08 33.93 345.71 392.7 49.57 9.29 345 392.7 49.6 49.57 0 49.6 0
350 x 400 90 0.57 37.68 384.95 392.7 49.57 19.74 345 392.7 49.6 0 49.57 0 49.6

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 49.57 - 49.57
Bottom - 49.6 - 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 49.6 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 49.6 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
350 x 400 0 0.43 85.66 696.59 804.24 97.98 11.77 345 392.7 49.6 97.98 0 49.6 0
350 x 400 90 -1.1 90.42 737.95 804.24 97.98 39.78 402.5 452.4 56.86 0 97.98 0 56.86

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top - 97.98 - 97.98
Bottom - 49.6 - 56.86
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 97.98 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 59.06 kN
Mnty = 175.82 kNm
Pu Bottom = 45.49 kN
Mnby = 174.37 kNm
Vuy1 = 134.69 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 49.6 KN-m
Mnby = 97.98 KN-m
Vuy2 = 56.76 KN
Critical Analysis Load Combination : 11
Critical Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 38.89 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 32.35 kNm
Vuy3 = -13.8503 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.69 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 26.24 kNm
φVcy = 108.87 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 43.02 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 54.44 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Lux = 2600 mm
Pu Top = 59.06 kN
Mntx = 175.82 kNm
Pu Bottom = 45.49 kN
Mnbx = 174.37 kNm
Vux1 = 134.69 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 49.6 KN-m
Mnbx = 97.98 KN-m
Vux2 = 56.76 KN
Critical Analysis Load Combination : 10
Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 45.49 kN
Mux = 38.4 kNm
Vux3 = 15.0597 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 134.69 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 31.24 kNm
φVcx = 101.95 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 54.57 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.5 x φVcx = 50.97 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C26
Level : 0m To 4m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 371
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 228.87 kN
Muxt = 80.44 kNm
Muyt = -10.79 kNm
Vuxt = 5.18 kN
Vuyt = 53.49 kN
Pub = 242.45 kN
Muxb = -133.49 kNm
Muyb = 9.92 kNm
Vuxb = 5.18 kN
Vuyb = 53.49 kN

Effective Length Calculation

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.481
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 4139 x 300 x 350 - 25.897 4.786
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = 80.44 kNm
M2 = -133.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 9.92 kNm
M2 = -10.79 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 80.44 - 80.44
Major Axis Mux (bottom) -133.49 - -133.49
Minor Axis Muy (top) -10.79 - -10.79
Minor Axis Muy (bottom) 9.92 - 9.92

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pu = 242.45 kN
Mux = -133.49 kNm
Muy = 9.92 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 442.9 kN
Mux = -2.3 kNm
Muy = 8.57 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 442.9 kN
φ Pn = 442.9 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 4.25 deg

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
MRes = 133.85 kNm
( φ ) MCap = 168.73 kNm
Capacity Ratio = MRes/ MCap
= 0.793 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.96 103.39 852.22 1005.3 120.31 51.18 405.94 452.4 56.86 120.31 0 56.86 0
300 x 350 90 -0.04 95.4 882.73 942.48 101.16 29.19 315 339.3 39 0 101.16 0 39
350 x 400 180 1.12 108.7 899.77 1005.3 120.31 29.67 345 392.7 49.6 120.31 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 - 101.16
Bottom 49.6 56.86 - 39
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Luy = 3600 mm
Pu Top = 442.9 kN
Mnty = 206.68 kNm
Pu Bottom = 424.79 kN
Mnby = 206.29 kNm
Vuy1 = 114.71 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 101.16 KN-m
Mnby = 0 KN-m
Vuy2 = 28.1 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 242.45 kN
Muy = 133.49 kNm
Vuy3 = 53.4946 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.71 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 95.36 kNm
φVcy = 75.79 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 64.88 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.5 x φVcy = 37.89 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 442.9 kN
Mntx = 206.68 kNm
Pu Bottom = 424.79 kN
Mnbx = 206.29 kNm
Vux1 = 113.14 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 177.17 KN-m
Mnbx = 0 KN-m
Vux2 = 48.54 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 207.86 kN
Mux = 126.39 kNm
Vux3 = -41.2733 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.14 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 93.7 kNm
φVcx = 75.83 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 62.19 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 37.91 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C26
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 399
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 189.26 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muxt = 88.98 kNm
Muyt = -26.29 kNm
Vuxt = 17.21 kN
Vuyt = 51.77 kN
Pub = 202.84 kN
Muxb = -66.3 kNm
Muyb = 25.32 kNm
Vuxb = 17.21 kN
Vuyb = 51.77 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.481
Top 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.693
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 4.786
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -66.3 kNm
M2 = 88.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 25.32 kNm
M2 = -26.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
A B C
Major Axis Mux (top) 88.98 - 88.98
Major Axis Mux (bottom) -66.3 - -66.3
Minor Axis Muy (top) -26.29 - -26.29
Minor Axis Muy (bottom) 25.32 - 25.32

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 189.26 kN
Mux = 88.98 kNm
Muy = -26.29 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 244.83 kN
Mux = -8.58 kNm
Muy = 33.29 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 244.83 kN
φ Pn = 244.83 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 16.46 deg
MRes = 92.78 kNm
( φ ) MCap = 158.31 kNm
Capacity Ratio = MRes/ MCap
= 0.586 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.62 79.72 645.42 804.24 97.98 28.09 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 0.11 77.05 698.02 804.24 87.71 10.93 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 0.43 86.91 707.42 804.24 97.98 8.35 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.96 103.39 852.22 1005.3 120.31 51.18 405.94 452.4 56.86 120.31 0 56.86 0
300 x 350 90 -0.04 95.4 882.73 942.48 101.16 29.19 315 339.3 39 0 101.16 0 39
350 x 400 180 1.12 108.7 899.77 1005.3 120.31 29.67 345 392.7 49.6 120.31 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 - 101.16
Bottom 49.6 56.86 - 39
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 244.83 kN
Mnty = 194.71 kNm
Pu Bottom = 231.25 kN
Mnby = 193.37 kNm
Vuy1 = 149.26 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 101.16 KN-m
Vuy2 = 72.64 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 128.48 kN
Muy = 87.16 kNm
Vuy3 = 50.4932 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 149.26 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 66.96 kNm
φVcy = 84.43 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 108.06 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.21 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 451.39 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 451.39 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 244.83 kN
Mntx = 194.71 kNm
Pu Bottom = 231.25 kN
Mnbx = 193.37 kNm
Vux1 = 146.45 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 177.17 KN-m
Vux2 = 122.55 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 164.04 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 67.7 kNm
Vux3 = 31.9894 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 146.45 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 41.9 kNm
φVcx = 95.08 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 85.62 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 47.54 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 357.63 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 357.63 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C26
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 437
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 35.64 kN
Muxt = 42.14 kNm
Muyt = -5.84 kNm
Vuxt = 6.54 kN
Vuyt = 19.09 kN
Pub = 49.21 kN
Muxb = -15.11 kNm
Muyb = 13.77 kNm
Vuxb = 6.54 kN
Vuyb = 19.09 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.693
Top 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 0.847
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 2.735
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = -15.11 kNm
M2 = 42.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.3
19.14 < 38.3, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -5.84 kNm
M2 = 13.77 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.09
22.95 < 39.09, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 42.14 - 42.14
Major Axis Mux (bottom) -15.11 - -15.11
Minor Axis Muy (top) -5.84 - -5.84
Minor Axis Muy (bottom) 13.77 - 13.77

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35.64 kN
Mux = 42.14 kNm
Muy = -5.84 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 60.26 kN
Mux = -7.15 kNm
Muy = 0.31 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 60.26 kN
φ Pn = 60.26 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 7.89 deg
MRes = 42.54 kNm
( φ ) MCap = 144.82 kNm
Capacity Ratio = MRes/ MCap
= 0.294 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.31 29.96 345 392.7 49.57 13.04 345 392.7 49.6 49.57 0 49.6 0
300 x 350 90 -0.4 22.33 270 314.16 36.18 14.2 270 314.16 36.2 0 36.18 0 36.2
350 x 400 180 -0.08 32.39 345 392.7 49.57 7.15 345 392.7 49.6 49.57 0 49.6 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 - 36.18
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.62 79.72 645.42 804.24 97.98 28.09 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 0.11 77.05 698.02 804.24 87.71 10.93 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 0.43 86.91 707.42 804.24 97.98 8.35 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 60.26 kN
Mnty = 175.94 kNm
Pu Bottom = 46.69 kN
Mnby = 174.5 kNm
Vuy1 = 134.79 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 26.16 kN
Muy = 41.16 kNm
Vuy3 = 18.3144 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.79 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 37.05 kNm
φVcy = 96.29 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 64.17 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 48.14 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 60.26 kN
Mntx = 175.94 kNm
Pu Bottom = 46.69 kN
Mnbx = 174.5 kNm
Vux1 = 132.24 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vux2 = 93.11 KN
Critical Analysis Load Combination : 12
Critical Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 42.76 kN
Mux = 28.58 kNm
Vux3 = 4.7083 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.24 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 21.86 kNm
φVcx = 116.59 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 26.09 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 58.29 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C27
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 372
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 220.33 kN
Muxt = -78.82 kNm
Muyt = -7.11 kNm
Vuxt = 1.92 kN
Vuyt = -52.89 kN
Pub = 233.9 kN
Muxb = 132.69 kNm
Muyb = 0.55 kNm
Vuxb = 1.92 kN
Vuyb = -52.89 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.481
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 4139 x 300 x 350 - 25.897 4.786
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = -78.82 kNm
M2 = 132.69 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Klux /r = 27.5
M1 = 0.55 kNm
M2 = -7.11 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.93
27.5 < 34.93, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -78.82 - -78.82
Major Axis Mux (bottom) 132.69 - 132.69
Minor Axis Muy (top) -7.11 - -7.11
Minor Axis Muy (bottom) 0.55 - 0.55

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 233.9 kN
Mux = 132.69 kNm
Muy = 0.55 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 441.11 kN
Mux = 2.35 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 8.61 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 441.11 kN
φ Pn = 441.11 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 0.24 deg
MRes = 132.69 kNm
( φ ) MCap = 169.47 kNm
Capacity Ratio = MRes/ MCap
= 0.783 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
350 x 400 0 -1.08 103.97 857.43 1005.3 120.31 26.92 345 392.7 49.6 120.31 0 49.6 0
300 x 350 90 -0.89 94.31 871.5 942.48 101.16 27.31 305.7 314.16 36.2 0 101.16 0 36.2
350 x 400 180 -0.96 103.49 853.16 1005.3 120.31 51.63 409.66 452.4 56.86 120.31 0 56.86 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 - 101.16
Bottom 56.86 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 441.11 kN
Mnty = 206.64 kNm
Pu Bottom = 423 kN
Mnby = 206.25 kNm
Vuy1 = 114.69 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 101.16 KN-m
Mnby = 0 KN-m
Vuy2 = 28.1 KN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 233.9 kN
Muy = 132.69 kNm
Vuy3 = -52.8914 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.69 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 95.91 kNm
φVcy = 75.73 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 64.94 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 37.86 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 441.11 kN
Mntx = 206.64 kNm
Pu Bottom = 423 kN
Mnbx = 206.25 kNm
Vux1 = 113.12 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 177.17 KN-m
Mnbx = 0 KN-m
Vux2 = 48.54 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 205.82 kN
Mux = 121.57 kNm
Vux3 = -39.4712 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.12 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 89.2 kNm
φVcx = 76.34 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 61.31 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.17 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C27
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 400
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 185.56 kN
Muxt = -87.92 kNm
Muyt = -23.03 kNm
Vuxt = 16.06 kN
Vuyt = -50.7 kN
Pub = 199.13 kN
Muxb = 64.13 kNm
Muyb = 25.14 kNm
Vuxb = 16.06 kN
Vuyb = -50.7 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.481
Top 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.693
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 4.786
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = 64.13 kNm
M2 = -87.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -23.03 kNm
M2 = 25.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -87.92 - -87.92
Major Axis Mux (bottom) 64.13 - 64.13
Minor Axis Muy (top) -23.03 - -23.03
Minor Axis Muy (bottom) 25.14 - 25.14

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 185.56 kN
Mux = -87.92 kNm
Muy = -23.03 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 244.33 kN
Mux = 8.51 kNm
Muy = 33.49 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 6
Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4: LL)
Pu = 244.33 kN
φ Pn = 244.33 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 14.68 deg
MRes = 90.88 kNm
( φ ) MCap = 159.38 kNm
Capacity Ratio = MRes/ MCap
= 0.57 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.65 85.04 691.21 804.24 97.98 7.66 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.77 76.37 691.37 804.24 87.71 9.56 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.62 79.66 644.89 804.24 97.98 28.12 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.08 103.97 857.43 1005.3 120.31 26.92 345 392.7 49.6 120.31 0 49.6 0
300 x 350 90 -0.89 94.31 871.5 942.48 101.16 27.31 305.7 314.16 36.2 0 101.16 0 36.2
350 x 400 180 -0.96 103.49 853.16 1005.3 120.31 51.63 409.66 452.4 56.86 120.31 0 56.86 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 - 101.16
Bottom 56.86 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 244.33 kN
Mnty = 194.66 kNm
Pu Bottom = 230.75 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnby = 193.32 kNm
Vuy1 = 149.23 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 101.16 KN-m
Vuy2 = 72.64 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 124.89 kN
Muy = 86.04 kNm
Vuy3 = -49.395 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 149.23 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 66.41 kNm
φVcy = 84.58 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 107.75 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.29 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 450.08 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 450.08 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 244.33 kN
Mntx = 194.66 kNm
Pu Bottom = 230.75 kN
Mnbx = 193.32 kNm
Vux1 = 146.41 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 177.17 KN-m
Vux2 = 122.55 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 163.94 kN
Mux = 65.76 kNm
Vux3 = 31.0259 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 146.41 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 39.98 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcx = 96.49 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 83.2 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 48.24 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 347.55 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 347.55 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C27
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 438
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 34.55 kN
Muxt = -41.34 kNm
Muyt = -4.46 kNm
Vuxt = 6.47 kN
Vuyt = -18.67 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pub = 48.13 kN
Muxb = 14.65 kNm
Muyb = 14.96 kNm
Vuxb = 6.47 kN
Vuyb = -18.67 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.693
Top 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 0.847
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 2.735
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = 14.65 kNm
M2 = -41.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.25
19.14 < 38.25, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -4.46 kNm
M2 = 14.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.58
22.95 < 37.58, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -41.34 - -41.34
Major Axis Mux (bottom) 14.65 - 14.65
Minor Axis Muy (top) -4.46 - -4.46
Minor Axis Muy (bottom) 14.96 - 14.96

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 34.55 kN
Mux = -41.34 kNm
Muy = -4.46 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 60.46 kN
Mux = 5.61 kNm
Muy = 0.57 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 60.46 kN
φ Pn = 60.46 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 6.16 deg
MRes = 41.58 kNm
( φ ) MCap = 145.06 kNm
Capacity Ratio = MRes/ MCap
= 0.287 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.33 31.54 345 392.7 49.57 6.19 345 392.7 49.6 49.57 0 49.6 0
300 x 350 90 0.16 21.51 270 314.16 36.18 13.91 270 314.16 36.2 0 36.18 0 36.2
350 x 400 180 -0.31 30.15 345 392.7 49.57 13.13 345 392.7 49.6 49.57 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 - 36.18
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.65 85.04 691.21 804.24 97.98 7.66 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.77 76.37 691.37 804.24 87.71 9.56 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.62 79.66 644.89 804.24 97.98 28.12 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Luy = 2600 mm
Pu Top = 60.46 kN
Mnty = 175.96 kNm
Pu Bottom = 46.88 kN
Mnby = 174.52 kNm
Vuy1 = 134.8 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 24.96 kN
Muy = 40.35 kNm
Vuy3 = -17.8931 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.8 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 36.42 kNm
φVcy = 96.81 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 63.31 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.5 x φVcy = 48.41 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 60.46 kN
Mntx = 175.96 kNm
Pu Bottom = 46.88 kN
Mnbx = 174.52 kNm
Vux1 = 132.26 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 12
Critical Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 42.84 kN
Mux = 28.41 kNm
Vux3 = 4.9322 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.26 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 21.68 kNm
φVcx = 117.02 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 25.4 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 58.51 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C28
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 373
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 223.91 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muxt = 78.36 kNm
Muyt = -8.95 kNm
Vuxt = 3.53 kN
Vuyt = 52.72 kN
Pub = 237.49 kN
Muxb = -132.46 kNm
Muyb = 5.19 kNm
Vuxb = 3.53 kN
Vuyb = 52.72 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.481
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 4139 x 300 x 350 - 25.897 4.786
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = 78.36 kNm
M2 = -132.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 5.19 kNm
M2 = -8.95 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
A B C
Major Axis Mux (top) 78.36 - 78.36
Major Axis Mux (bottom) -132.46 - -132.46
Minor Axis Muy (top) -8.95 - -8.95
Minor Axis Muy (bottom) 5.19 - 5.19

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 237.49 kN
Mux = -132.46 kNm
Muy = 5.19 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 414.34 kN
Mux = -10.38 kNm
Muy = 126.25 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 414.34 kN
φ Pn = 414.34 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 2.24 deg
MRes = 132.56 kNm
( φ ) MCap = 169 kNm
Capacity Ratio = MRes/ MCap
= 0.784 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.09 101.8 838.11 1005.3 120.31 50.56 402.5 452.4 56.86 120.31 0 56.86 0
300 x 350 90 -0.28 89.36 821.01 942.48 101.16 25.12 280.65 314.16 36.2 0 101.16 0 36.2
350 x 400 180 -1.08 103.91 856.85 1005.3 120.31 26.8 345 392.7 49.6 120.31 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 120.31 120.31 - 101.16
Bottom 49.6 56.86 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 414.34 kN
Mnty = 206.07 kNm
Pu Bottom = 396.24 kN
Mnby = 205.68 kNm
Vuy1 = 114.37 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 101.16 KN-m
Mnby = 0 KN-m
Vuy2 = 28.1 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 237.49 kN
Muy = 132.46 kNm
Vuy3 = 52.7184 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.37 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 95.12 kNm
φVcy = 75.78 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 64.32 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 37.89 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 414.34 kN
Mntx = 206.07 kNm
Pu Bottom = 396.24 kN
Mnbx = 205.68 kNm
Vux1 = 112.81 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 177.17 KN-m
Mnbx = 0 KN-m
Vux2 = 48.54 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 212 kN
Mux = 115.91 kNm
Vux3 = -37.5007 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 112.81 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 82.57 kNm
φVcx = 77.16 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 59.41 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.58 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C28
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 406
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 181.39 kN
Muxt = 88.36 kNm
Muyt = -23.31 kNm
Vuxt = 15.71 kN
Vuyt = 50.95 kN
Pub = 194.97 kN
Muxb = -64.44 kNm
Muyb = 23.81 kNm
Vuxb = 15.71 kN
Vuyb = 50.95 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.481
Top 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.693
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 4.786
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -64.44 kNm
M2 = 88.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 40

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -23.31 kNm
M2 = 23.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 88.36 - 88.36
Major Axis Mux (bottom) -64.44 - -64.44
Minor Axis Muy (top) -23.31 - -23.31
Minor Axis Muy (bottom) 23.81 - 23.81

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 181.39 kN
Mux = 88.36 kNm
Muy = -23.31 kNm

Φ Pn, Max Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 230.65 kN
Mux = -13.39 kNm
Muy = 34.66 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 230.65 kN
φ Pn = 230.65 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 14.78 deg
MRes = 91.38 kNm
( φ ) MCap = 158.93 kNm
Capacity Ratio = MRes/ MCap
= 0.575 < 1

Beam Capacity At Joint:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.66 77.88 629.61 804.24 97.98 27.5 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.13 72.21 650.69 804.24 87.71 8.25 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.65 84.95 690.39 804.24 97.98 7.57 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.09 101.8 838.11 1005.3 120.31 50.56 402.5 452.4 56.86 120.31 0 56.86 0
300 x 350 90 -0.28 89.36 821.01 942.48 101.16 25.12 280.65 314.16 36.2 0 101.16 0 36.2
350 x 400 180 -1.08 103.91 856.85 1005.3 120.31 26.8 345 392.7 49.6 120.31 0 49.6 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 - 101.16
Bottom 49.6 56.86 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 101.16 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 230.65 kN
Mnty = 193.31 kNm
Pu Bottom = 217.07 kN
Mnby = 191.98 kNm
Vuy1 = 148.19 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 101.16 KN-m
Vuy2 = 72.64 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 126.5 kN
Muy = 85.44 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy3 = 48.9443 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 148.19 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 65.55 kNm
φVcy = 84.69 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 105.83 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.35 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 442.05 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 442.05 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 230.65 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = 193.31 kNm
Pu Bottom = 217.07 kN
Mnbx = 191.98 kNm
Vux1 = 145.39 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 177.17 KN-m
Vux2 = 122.55 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 162.18 kN
Mux = 63.73 kNm
Vux3 = 30.271 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 145.39 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 38.22 kNm
φVcx = 97.68 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 79.52 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 48.84 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C28
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 439
Critical Analysis Load Combination : 9
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 35 kN
Muxt = 41.61 kNm
Muyt = -4.98 kNm
Vuxt = 6.21 kN
Vuyt = 18.93 kN
Pub = 48.57 kN
Muxb = -15.15 kNm
Muyb = 13.66 kNm
Vuxb = 6.21 kN
Vuyb = 18.93 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 1.693
Top 71.111 4000 x 350 x 400 5000 x 350 x 400 46.667 37.333 0.847
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 2.735
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 19.14
M1 = -15.15 kNm
M2 = 41.61 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.37
19.14 < 38.37, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -4.98 kNm
M2 = 13.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.38
22.95 < 38.38, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 41.61 - 41.61
Major Axis Mux (bottom) -15.15 - -15.15
Minor Axis Muy (top) -4.98 - -4.98
Minor Axis Muy (bottom) 13.66 - 13.66

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35 kN
Mux = 41.61 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = -4.98 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 60.28 kN
Mux = -7.38 kNm
Muy = 14.61 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 60.28 kN
φ Pn = 60.28 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 6.83 deg
MRes = 41.91 kNm
( φ ) MCap = 144.97 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.289 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.34 30.13 345 392.7 49.57 13.14 345 392.7 49.6 49.57 0 49.6 0
300 x 350 90 -0.31 20.64 270 314.16 36.18 13.37 270 314.16 36.2 0 36.18 0 36.2
350 x 400 180 -0.33 31.64 345 392.7 49.57 6.25 345 392.7 49.6 49.57 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 - 36.18
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
350 x 400 0 -0.66 77.88 629.61 804.24 97.98 27.5 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.13 72.21 650.69 804.24 87.71 8.25 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.65 84.95 690.39 804.24 97.98 7.57 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 59.92 kN
Mnty = 175.91 kNm
Pu Bottom = 46.35 kN
Mnby = 174.46 kNm
Vuy1 = 134.76 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 14

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 25.32 kN
Muy = 40.37 kNm
Vuy3 = 17.8279 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.76 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 36.39 kNm
φVcy = 96.83 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 63.21 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 48.42 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 59.92 kN
Mntx = 175.91 kNm
Pu Bottom = 46.35 kN
Mnbx = 174.46 kNm
Vux1 = 132.22 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 12
Critical Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 43.72 kN
Mux = 27.06 kNm
Vux3 = 4.7311 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.22 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 20.19 kNm
φVcx = 120.78 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 19.05 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.39 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C29
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 374
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 224.55 kN
Muxt = -78.89 kNm
Muyt = -8.99 kNm
Vuxt = 3.58 kN
Vuyt = -52.92 kN
Pub = 238.13 kN
Muxb = 132.73 kNm
Muyb = 5.31 kNm
Vuxb = 3.58 kN
Vuyb = -52.92 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 1.335
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 4139 x 300 x 350 - 25.897 4.786
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = -78.89 kNm
M2 = 132.73 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 5.31 kNm
M2 = -8.99 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -78.89 - -78.89
Major Axis Mux (bottom) 132.73 - 132.73
Minor Axis Muy (top) -8.99 - -8.99
Minor Axis Muy (bottom) 5.31 - 5.31

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 238.13 kN
Mux = 132.73 kNm
Muy = 5.31 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 380.91 kN
Mux = -7.8 kNm
Muy = 121.74 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 380.91 kN
φ Pn = 380.91 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 2.29 deg
MRes = 132.84 kNm
( φ ) MCap = 169.05 kNm
Capacity Ratio = MRes/ MCap
= 0.786 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.09 97.67 801.52 804.24 97.98 51.76 410.68 452.4 56.86 97.98 0 56.86 0
300 x 350 90 -0.41 87.55 802.63 804.24 87.71 23.3 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -1.09 97.62 801.05 804.24 97.98 51.81 411.14 452.4 56.86 97.98 0 56.86 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 56.86 56.86 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 154.84 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 380.91 kN
Mnty = 205.35 kNm
Pu Bottom = 362.81 kN
Mnby = 204.97 kNm
Vuy1 = 113.98 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 87.71 KN-m
Mnby = 0 KN-m
Vuy2 = 24.36 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 237.34 kN
Muy = 132.71 kNm
Vuy3 = 52.9079 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 113.98 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 95.39 kNm
φVcy = 75.72 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 63.76 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 37.86 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 380.91 kN
Mntx = 205.35 kNm
Pu Bottom = 362.81 kN
Mnbx = 204.97 kNm
Vux1 = 112.42 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 154.84 KN-m
Mnbx = 0 KN-m
Vux2 = 42.42 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 189.25 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 111.41 kNm
Vux3 = -35.9458 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 112.42 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 81.65 kNm
φVcx = 77.25 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 58.61 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.63 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C29
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 407
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Top Joint
Put = 125.31 kN
Muxt = -83.91 kNm
Muyt = -15.97 kNm
Vuxt = 10.72 kN
Vuyt = -48.36 kN
Pub = 135.49 kN
Muxb = 61.14 kNm
Muyb = 16.19 kNm
Vuxb = 10.72 kN
Vuyb = -48.36 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 1.335
Top 71.111 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 1.525
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 4.786
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = 61.14 kNm
M2 = -83.91 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -15.97 kNm
M2 = 16.19 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -83.91 - -83.91
Major Axis Mux (bottom) 61.14 - 61.14
Minor Axis Muy (top) -15.97 - -15.97
Minor Axis Muy (bottom) 16.19 - 16.19

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 125.31 kN
Mux = -83.91 kNm
Muy = -15.97 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 212.36 kN
Mux = -3.64 kNm
Muy = 34.37 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 212.36 kN
φ Pn = 212.36 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 10.77 deg
MRes = 85.42 kNm
( φ ) MCap = 154.7 kNm
Capacity Ratio = MRes/ MCap
= 0.552 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.66 75.11 606.01 804.24 97.98 28.75 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.29 71.07 639.68 804.24 87.71 7.09 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.66 75.07 605.7 804.24 97.98 28.77 345 392.7 49.6 97.98 0 49.6 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.09 97.67 801.52 804.24 97.98 51.76 410.68 452.4 56.86 97.98 0 56.86 0
300 x 350 90 -0.41 87.55 802.63 804.24 87.71 23.3 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -1.09 97.62 801.05 804.24 97.98 51.81 411.14 452.4 56.86 97.98 0 56.86 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 56.86 56.86 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 154.84 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 212.36 kN
Mnty = 191.51 kNm
Pu Bottom = 198.78 kN
Mnby = 190.17 kNm
Vuy1 = 146.8 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 87.71 KN-m
Vuy2 = 67.47 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 124.93 kN
Muy = 83.89 kNm
Vuy3 = 48.3429 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 146.8 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 64.24 kNm
φVcy = 84.9 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 103.17 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.45 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 430.96 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 430.96 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 212.36 kN
Mntx = 191.51 kNm
Pu Bottom = 198.78 kN
Mnbx = 190.17 kNm
Vux1 = 144.03 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 154.84 KN-m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vux2 = 114.12 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 149.24 kN
Mux = 62.05 kNm
Vux3 = 29.6419 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 144.03 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 38.58 kNm
φVcx = 97.09 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 78.24 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 48.54 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C29
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 440
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Top Joint
Put = 25.79 kN
Muxt = -39.8 kNm
Muyt = -3.57 kNm
Vuxt = 4.27 kN
Vuyt = -17.07 kN
Pub = 35.97 kN
Muxb = 11.39 kNm
Muyb = 9.25 kNm
Vuxb = 4.27 kN
Vuyb = -17.07 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 1.525
Top 71.111 4000 x 350 x 400 4000 x 350 x 400 46.667 46.667 0.763
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation Along Minor Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 2.735
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = 11.39 kNm
M2 = -39.8 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.43
19.14 < 37.43, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Klux /r = 22.95
M1 = -3.57 kNm
M2 = 9.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.63
22.95 < 38.63, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -39.8 - -39.8
Major Axis Mux (bottom) 11.39 - 11.39
Minor Axis Muy (top) -3.57 - -3.57
Minor Axis Muy (bottom) 9.25 - 9.25

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 25.79 kN
Mux = -39.8 kNm
Muy = -3.57 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 56.08 kN
Mux = -0.85 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = 0.9 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 56.08 kN
φ Pn = 56.08 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 5.13 deg
MRes = 39.96 kNm
( φ ) MCap = 144.02 kNm
Capacity Ratio = MRes/ MCap
= 0.277 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B
(kNm)
350 x 400 0 -0.34 29.6 345 392.7 49.57 13.12 345 392.7 49.6 49.57 0 49.6 0
300 x 350 90 -0.12 20.12 270 314.16 36.18 12.82 270 314.16 36.2 0 36.18 0 36.2
350 x 400 180 -0.34 29.6 345 392.7 49.57 13.11 345 392.7 49.6 49.57 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 - 36.18
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.66 75.11 606.01 804.24 97.98 28.75 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.29 71.07 639.68 804.24 87.71 7.09 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.66 75.07 605.7 804.24 97.98 28.77 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 56.08 kN
Mnty = 175.5 kNm
Pu Bottom = 42.51 kN
Mnby = 174.05 kNm
Vuy1 = 134.44 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 25.66 kN
Muy = 39.82 kNm
Vuy3 = 17.0737 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.44 kN
λ = 1
φ = 0.6

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 35.78 kNm
φVcy = 97.29 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 61.93 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 48.64 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 56.08 kN
Mntx = 175.5 kNm
Pu Bottom = 42.51 kN
Mnbx = 174.05 kNm
Vux1 = 131.91 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 12
Critical Load Combination = [8] : 1.2 (LOAD 3: DL) -(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN
Nu = 40.04 kN
Mux = 26.53 kNm
Vux3 = 4.7539 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 131.91 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 20.23 kNm
φVcx = 120.54 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 18.95 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.27 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C30
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 375
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 224.39 kN
Muxt = -78.29 kNm
Muyt = -9.83 kNm
Vuxt = 4.32 kN
Vuyt = -52.7 kN
Pub = 237.97 kN
Muxb = 132.43 kNm
Muyb = 7.43 kNm
Vuxb = 4.32 kN
Vuyb = -52.7 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 53.333 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.481
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 4139 x 300 x 350 - 25.897 4.786
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = -78.29 kNm
M2 = 132.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 7.43 kNm
M2 = -9.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -78.29 - -78.29
Major Axis Mux (bottom) 132.43 - 132.43
Minor Axis Muy (top) -9.83 - -9.83
Minor Axis Muy (bottom) 7.43 - 7.43

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 237.97 kN
Mux = 132.43 kNm
Muy = 7.43 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 412.48 kN
Mux = -5.13 kNm
Muy = 117.26 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 412.48 kN
φ Pn = 412.48 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 3.21 deg
MRes = 132.64 kNm
( φ ) MCap = 168.65 kNm
Capacity Ratio = MRes/ MCap
= 0.786 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.17 103.51 853.28 1005.3 120.31 27.78 345 392.7 49.6 120.31 0 49.6 0
300 x 350 90 -0.58 85.7 784.02 804.24 87.71 21.46 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -1.09 101.61 836.37 1005.3 120.31 50.58 402.5 452.4 56.86 120.31 0 56.86 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 - 87.71
Bottom 56.86 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 412.48 kN
Mnty = 206.03 kNm
Pu Bottom = 394.38 kN
Mnby = 205.64 kNm
Vuy1 = 114.35 kN
Shear from Beam Capacity at Joint:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Luy = 3600 mm
Mnty = 87.71 KN-m
Mnby = 0 KN-m
Vuy2 = 24.36 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 237.97 kN
Muy = 132.43 kNm
Vuy3 = -52.6952 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.35 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 95.01 kNm
φVcy = 75.79 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 64.26 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 37.9 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 412.48 kN
Mntx = 206.03 kNm
Pu Bottom = 394.38 kN
Mnbx = 205.64 kNm
Vux1 = 112.79 kN
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 177.17 KN-m
Mnbx = 0 KN-m
Vux2 = 48.54 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 212.03 kN
Mux = 106.92 kNm
Vux3 = -34.3976 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 112.79 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 73.58 kNm
φVcx = 78.57 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx = (Vux - φVcx) / φ
= 57.04 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 39.28 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
General Data
Column No. : C30
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 393
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 181.45 kN
Muxt = -88.19 kNm
Muyt = -24.03 kNm
Vuxt = 15.94 kN
Vuyt = -50.82 kN
Pub = 195.03 kN
Muxb = 64.24 kNm
Muyb = 23.79 kNm
Vuxb = 15.94 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuyb = -50.82 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.481
Top 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.693
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 4.786
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = 64.24 kNm
M2 = -88.19 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 23.79 kNm
M2 = -24.03 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -88.19 - -88.19
Major Axis Mux (bottom) 64.24 - 64.24
Minor Axis Muy (top) -24.03 - -24.03
Minor Axis Muy (bottom) 23.79 - 23.79

Where
A = Moments from analysis
B = Moment due to slenderness effect

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 181.45 kN
Mux = -88.19 kNm
Muy = -24.03 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 229.8 kN
Mux = 6.36 kNm
Muy = 34.21 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 229.8 kN
φ Pn = 229.8 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 15.24 deg
MRes = 91.4 kNm
( φ ) MCap = 158.6 kNm
Capacity Ratio = MRes/ MCap
= 0.576 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.68 84.55 687 804.24 97.98 8.18 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.46 69.9 628.31 804.24 87.71 5.94 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.66 77.79 628.85 804.24 97.98 27.53 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Bottom Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.17 103.51 853.28 1005.3 120.31 27.78 345 392.7 49.6 120.31 0 49.6 0
300 x 350 90 -0.58 85.7 784.02 804.24 87.71 21.46 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -1.09 101.61 836.37 1005.3 120.31 50.58 402.5 452.4 56.86 120.31 0 56.86 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 - 87.71
Bottom 56.86 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 177.17 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 229.8 kN
Mnty = 193.23 kNm
Pu Bottom = 216.23 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mnby = 191.89 kNm
Vuy1 = 148.12 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 87.71 KN-m
Vuy2 = 67.47 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 126.7 kN
Muy = 85.29 kNm
Vuy3 = -48.8464 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 148.12 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 65.37 kNm
φVcy = 84.74 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 105.65 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 42.37 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 441.31 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s required = max (Av/s minimum , Av/s shear)
= 441.31 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 229.8 kN
Mntx = 193.23 kNm
Pu Bottom = 216.23 kN
Mnbx = 191.89 kNm
Vux1 = 145.33 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 177.17 KN-m
Vux2 = 122.55 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 161.47 kN
Mux = 60.37 kNm
Vux3 = 29.0272 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 145.33 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 34.98 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φVcx = 100.63 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 74.5 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 50.32 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of Ductile links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C30
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 396
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 35.07 kN
Muxt = -41.56 kNm
Muyt = -5.34 kNm
Vuxt = 6.23 kN
Vuyt = -18.85 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pub = 48.65 kN
Muxb = 14.97 kNm
Muyb = 13.36 kNm
Vuxb = 6.23 kN
Vuyb = -18.85 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 1.693
Top 71.111 5000 x 350 x 400 4000 x 350 x 400 37.333 46.667 0.847
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.85

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 2.735
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.85
r = 115.47 mm
Kluy /r = 19.14
M1 = 14.97 kNm
M2 = -41.56 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.32
19.14 < 38.32, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -5.34 kNm
M2 = 13.36 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.79
22.95 < 38.79, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -41.56 - -41.56
Major Axis Mux (bottom) 14.97 - 14.97
Minor Axis Muy (top) -5.34 - -5.34
Minor Axis Muy (bottom) 13.36 - 13.36

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35.07 kN
Mux = -41.56 kNm
Muy = -5.34 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 60.22 kN
Mux = 7.18 kNm
Muy = 14.62 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 60.22 kN
φ Pn = 60.22 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 7.31 deg
MRes = 41.9 kNm
( φ ) MCap = 144.88 kNm
Capacity Ratio = MRes/ MCap
= 0.289 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.33 31.56 345 392.7 49.57 6.28 345 392.7 49.6 49.57 0 49.6 0
300 x 350 90 0.04 19.54 270 314.16 36.18 12.27 270 314.16 36.2 0 36.18 0 36.2
350 x 400 180 -0.34 30.16 345 392.7 49.57 13.12 345 392.7 49.6 49.57 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 - 36.18
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.68 84.55 687 804.24 97.98 8.18 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.46 69.9 628.31 804.24 87.71 5.94 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.66 77.79 628.85 804.24 97.98 27.53 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Luy = 2600 mm
Pu Top = 59.68 kN
Mnty = 175.88 kNm
Pu Bottom = 46.11 kN
Mnby = 174.44 kNm
Vuy1 = 134.74 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 25.43 kN
Muy = 40.36 kNm
Vuy3 = -17.7938 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.74 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 36.36 kNm
φVcy = 96.85 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 63.14 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
0.5 x φVcy = 48.43 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 59.68 kN
Mntx = 175.88 kNm
Pu Bottom = 46.11 kN
Mnbx = 174.44 kNm
Vux1 = 132.2 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 20.6 kN
Mux = 13.09 kNm
Vux3 = 2.8744 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.2 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 9.85 kNm
φVcx = 121.22 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 18.3 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.61 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C31
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 376
Critical Analysis Load Combination : 16
Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 274.88 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muxt = -72.17 kNm
Muyt = -10.85 kNm
Vuxt = 5.23 kN
Vuyt = -50.41 kN
Pub = 288.46 kN
Muxb = 129.42 kNm
Muyb = 10.06 kNm
Vuxb = 5.23 kN
Vuyb = -50.41 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 1.665
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 4139 x 300 x 350 - 25.897 4.786
Sway Condition (as per Stability Index) = Non Sway

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = -72.17 kNm
M2 = 129.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.12 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.5
M1 = 10.06 kNm
M2 = -10.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
27.5 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
A B C
Major Axis Mux (top) -72.17 - -72.17
Major Axis Mux (bottom) 129.42 - 129.42
Minor Axis Muy (top) -10.85 - -10.85
Minor Axis Muy (bottom) 10.06 - 10.06

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 288.46 kN
Mux = 129.42 kNm
Muy = 10.06 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 440.53 kN
Mux = -7.4 kNm
Muy = 111.83 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 440.53 kN
φ Pn = 440.53 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 4.45 deg
MRes = 129.81 kNm
( φ ) MCap = 173.48 kNm
Capacity Ratio = MRes/ MCap
= 0.748 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -2.72 111.79 927.62 1005.3 120.31 29.71 345 392.7 49.6 120.31 0 49.6 0
300 x 350 90 -0.44 83.27 759.71 804.24 87.71 19.03 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -1.17 106.68 881.68 1005.3 120.31 26.41 345 392.7 49.6 120.31 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 120.31 120.31 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 169.92 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 440.53 kN
Mnty = 206.63 kNm
Pu Bottom = 422.43 kN
Mnby = 206.24 kNm
Vuy1 = 114.69 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 87.71 KN-m
Mnby = 0 KN-m
Vuy2 = 24.36 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 276.07 kN
Muy = 129.13 kNm
Vuy3 = 50.1972 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 114.69 kN
λ = 1

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 85.72 kNm
φVcy = 76.92 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 62.94 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.46 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3650 mm
Pu Top = 440.53 kN
Mntx = 206.63 kNm
Pu Bottom = 422.43 kN
Mnbx = 206.24 kNm
Vux1 = 113.11 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Shear from Beam Capacity at Joint:
Lux = 3650 mm
Mntx = 169.92 KN-m
Mnbx = 0 KN-m
Vux2 = 46.55 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 237.88 kN
Mux = 101.55 kNm
Vux3 = -32.6435 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 113.11 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 64.14 kNm
φVcx = 80.51 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 54.35 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 40.25 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C31
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 408
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 212.32 kN
Muxt = -75.49 kNm
Muyt = -24.66 kNm
Vuxt = 16.11 kN
Vuyt = -41.97 kN
Pub = 225.89 kN
Muxb = 50.4 kNm
Muyb = 23.64 kNm
Vuxb = 16.11 kN
Vuyb = -41.97 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Bottom 71.111 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 1.665
Top 71.111 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 1.903
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 4.786
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = 50.4 kNm
M2 = -75.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 40

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = 23.64 kNm
M2 = -24.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.95 < 40, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -75.49 - -75.49
Major Axis Mux (bottom) 50.4 - 50.4
Minor Axis Muy (top) -24.66 - -24.66
Minor Axis Muy (bottom) 23.64 - 23.64

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 212.32 kN
Mux = -75.49 kNm
Muy = -24.66 kNm

Φ Pn, Max Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 248.97 kN
Mux = 0.69 kNm
Muy = 24.87 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 248.97 kN
φ Pn = 248.97 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 18.09 deg
MRes = 79.42 kNm
( φ ) MCap = 158.38 kNm
Capacity Ratio = MRes/ MCap
= 0.501 < 1

Beam Capacity At Joint:

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -1.54 88.72 723.15 804.24 97.98 7.8 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.32 68.44 614.23 804.24 87.71 4.5 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.68 86.91 707.35 804.24 97.98 7.09 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -2.72 111.79 927.62 1005.3 120.31 29.71 345 392.7 49.6 120.31 0 49.6 0
300 x 350 90 -0.44 83.27 759.71 804.24 87.71 19.03 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -1.17 106.68 881.68 1005.3 120.31 26.41 345 392.7 49.6 120.31 0 49.6 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 120.31 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 169.92 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 248.97 kN
Mnty = 195.12 kNm
Pu Bottom = 233.13 kN
Mnby = 193.56 kNm
Vuy1 = 149.49 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 87.71 KN-m
Mnby = 87.71 KN-m
Vuy2 = 67.47 KN
Critical Analysis Load Combination : 14
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 147.32 kN
Muy = 74.62 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vuy3 = 41.3126 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 149.49 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 51.45 kNm
φVcy = 90.12 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 98.96 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 45.06 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 413.36 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 413.36 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 248.97 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mntx = 195.12 kNm
Pu Bottom = 233.13 kN
Mnbx = 193.56 kNm
Vux1 = 146.67 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 147.58 KN-m
Mnbx = 169.92 KN-m
Vux2 = 119.81 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 172.09 kN
Mux = 58.37 kNm
Vux3 = 28.4274 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 146.67 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 31.31 kNm
φVcx = 105.1 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 69.29 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 52.55 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C31
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 436
Critical Analysis Load Combination : 11
Load Combination = [7] : 1.2 (LOAD 3: DL) -(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 42.92 kN
Muxt = -34.97 kNm
Muyt = -6.13 kNm
Vuxt = 6.39 kN
Vuyt = -13.6 kN
Pub = 56.5 kN
Muxb = 5.82 kNm
Muyb = 13.03 kNm
Vuxb = 6.39 kN
Vuyb = -13.6 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 1.903
Top 71.111 5000 x 350 x 400 5000 x 350 x 400 37.333 37.333 0.951
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.86

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 300 x 350 - 25.897 5.47
Top 71.111 No Beam 4139 x 300 x 350 - 25.897 2.735
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.86
r = 115.47 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Kluy /r = 19.36
M1 = 5.82 kNm
M2 = -34.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 36
19.36 < 36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.95
M1 = -6.13 kNm
M2 = 13.03 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.65
22.95 < 39.65, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -34.97 - -34.97
Major Axis Mux (bottom) 5.82 - 5.82
Minor Axis Muy (top) -6.13 - -6.13
Minor Axis Muy (bottom) 13.03 - 13.03

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 42.92 kN
Mux = -34.97 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Muy = -6.13 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Critical Location = Bottom Joint kN
Pu = 64.59 kN
Mux = 0.18 kNm
Muy = 14.62 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 5
Load Combination = [1] : 1.4 (LOAD 3: DL)
Pu = 64.59 kN
φ Pn = 64.59 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 9.95 deg
MRes = 35.51 kNm
( φ ) MCap = 145.25 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Capacity Ratio = MRes/ MCap
= 0.244 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 0 -0.38 33.01 345 392.7 49.57 7.25 345 392.7 49.6 49.57 0 49.6 0
300 x 350 90 -0.12 18.79 270 314.16 36.18 11.52 270 314.16 36.2 0 36.18 0 36.2
350 x 400 180 -0.33 31.93 345 392.7 49.57 6.13 345 392.7 49.6 49.57 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 49.57 - 36.18
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 99.17 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 36.2 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D Bot @
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm) B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
(kNm)
350 x 400 0 -1.54 88.72 723.15 804.24 97.98 7.8 345 392.7 49.6 97.98 0 49.6 0
300 x 350 90 -0.32 68.44 614.23 804.24 87.71 4.5 270 314.16 36.2 0 87.71 0 36.2
350 x 400 180 -0.68 86.91 707.35 804.24 97.98 7.09 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 97.98 - 87.71
Bottom 49.6 49.6 - 36.2
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 147.58 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 87.71 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 64.59 kN
Mnty = 176.4 kNm
Pu Bottom = 48.75 kN
Mnby = 174.72 kNm
Vuy1 = 135.05 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 36.2 KN-m
Mnby = 87.71 KN-m
Vuy2 = 47.66 KN
Critical Analysis Load Combination : 14

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X) kN
Nu = 30.25 kN
Muy = 35.04 kNm
Vuy3 = 13.537 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 135.05 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 30.29 kNm
φVcy = 103.19 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 53.09 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 51.6 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design for shear along B
Shear from Moment Capacity:
Lux = 2650 mm
Pu Top = 64.59 kN
Mntx = 176.4 kNm
Pu Bottom = 48.75 kN
Mnbx = 174.72 kNm
Vux1 = 132.5 kN
Shear from Beam Capacity at Joint:
Lux = 2650 mm
Mntx = 99.17 KN-m
Mnbx = 147.58 KN-m
Vux2 = 93.11 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 23.95 kN
Mux = 12.41 kNm
Vux3 = 2.8262 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 132.5 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 8.64 kNm
φVcx = 121.57 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 18.21 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 60.79 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Special confining reinforcement as per ACI
Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Column No. : C32
Level : 0m To 4m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3600 mm
Clear Floor Height @ luy = 3600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 359
Critical Analysis Load Combination : 14
Load Combination = [10] : 0.9 (LOAD 3: DL) +(LOAD 1: SL X)
Critical Location = Bottom Joint
Put = 218.64 kN
Muxt = 60.5 kNm
Muyt = -2.59 kNm
Vuxt = -0.75 kN
Vuyt = 46.05 kN
Pub = 232.21 kN
Muxb = -123.66 kNm
Muyb = -5.6 kNm
Vuxb = -0.75 kN
Vuyb = 46.05 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Length Calculation
Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 5000 x 350 x 400 - 37.333 3.341
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 53.333 No Beam No Beam - - 1
Top 53.333 No Beam 4139 x 350 x 400 - 45.099 2.765
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
Q = 0.031
0.031< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.033
0.033< 0.05, Column shall be designed as non-sway frame (Braced)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 27.12
M1 = 60.5 kNm
M2 = -123.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.87
27.12 < 39.87, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 27.12
M1 = -2.59 kNm
M2 = -5.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.45
27.12 < 28.45, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 60.5 - 60.5
Major Axis Mux (bottom) -123.66 - -123.66
Minor Axis Muy (top) -2.59 - -2.59
Minor Axis Muy (bottom) -5.6 - -5.6

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 232.21 kN
Mux = -123.66 kNm
Muy = -5.6 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 327.66 kN
Mux = -14.49 kNm
Muy = 109.1 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 327.66 kN
φ Pn = 327.66 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 2.59 deg
MRes = 123.79 kNm
( φ ) MCap = 168.32 kNm
Capacity Ratio = MRes/ MCap
= 0.735 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.46 96.39 790.2 804.24 97.98 43.75 402.5 452.4 56.86 0 97.98 0 56.86
350 x 400 180 -2.72 108.96 902.09 1005.3 120.31 38.25 390.95 392.7 49.6 120.31 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 - - 97.98
Bottom 49.6 - - 56.86
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 120.31 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 3600 mm
Pu Top = 327.66 kN
Mnty = 202.89 kNm
Pu Bottom = 309.56 kN
Mnby = 201.1 kNm
Vuy1 = 112.22 kN
Shear from Beam Capacity at Joint:
Luy = 3600 mm
Mnty = 97.98 KN-m
Mnby = 0 KN-m
Vuy2 = 27.22 KN
Critical Analysis Load Combination : 16
Critical Load Combination = [12] : 0.9 (LOAD 3: DL) -(LOAD 1: SL X) kN
Nu = 141.19 kN
Muy = 113.32 kNm
Vuy3 = -38.2208 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 112.22 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 91.12 kNm
φVcy = 76.03 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ
= 60.31 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 38.01 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 3600 mm
Pu Top = 327.66 kN
Mntx = 202.89 kNm
Pu Bottom = 309.56 kN
Mnbx = 201.1 kNm
Vux1 = 112.22 kN
Shear from Beam Capacity at Joint:
Lux = 3600 mm
Mntx = 120.31 KN-m
Mnbx = 0 KN-m
Vux2 = 33.42 KN
Critical Analysis Load Combination : 17
Critical Load Combination = [13] : 0.9 (LOAD 3: DL) -(LOAD 2: SL Z) kN
Nu = 117.62 kN
Mux = 100.97 kNm
Vux3 = -34.5177 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 112.22 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 82.47 kNm
φVcx = 77.12 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 58.5 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 38.56 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links
Links in the zone where special confining links are not required
Normal Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C32
Level : 4m To 7m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 409
Critical Analysis Load Combination : 9

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 158.65 kN
Muxt = 76.92 kNm
Muyt = -12.13 kNm
Vuxt = 9.36 kN
Vuyt = 40.25 kN
Pub = 172.22 kN
Muxb = -43.8 kNm
Muyb = 15.96 kNm
Vuxb = 9.36 kN
Vuyb = 40.25 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 5000 x 350 x 400 - 37.333 3.341
Top 71.111 No Beam 5000 x 350 x 400 - 37.333 3.818
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 350 x 400 - 45.099 2.765

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Top 71.111 No Beam 4139 x 350 x 400 - 45.099 3.16
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.024
0.024< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.027
0.027< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = -43.8 kNm
M2 = 76.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = -12.13 kNm
M2 = 15.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 76.92 - 76.92
Major Axis Mux (bottom) -43.8 - -43.8
Minor Axis Muy (top) -12.13 - -12.13
Minor Axis Muy (bottom) 15.96 - 15.96

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 158.65 kN
Mux = 76.92 kNm
Muy = -12.13 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 185.05 kN
Mux = -28.93 kNm
Muy = 41.85 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Minimum Ast Calculation

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 185.05 kN
φ Pn = 185.05 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 8.96 deg
MRes = 77.87 kNm
( φ ) MCap = 158.87 kNm
Capacity Ratio = MRes/ MCap
= 0.49 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 0 76.56 618.34 804.24 97.98 24.73 345 392.7 49.6 0 97.98 0 49.6
350 x 400 180 -1.54 85.2 692.57 804.24 97.98 12.36 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Left Right Left Right
Top 97.98 - - 97.98
Bottom 49.6 - - 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 97.98 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -0.46 96.39 790.2 804.24 97.98 43.75 402.5 452.4 56.86 0 97.98 0 56.86
350 x 400 180 -2.72 108.96 902.09 1005.3 120.31 38.25 390.95 392.7 49.6 120.31 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 120.31 - - 97.98
Bottom 49.6 - - 56.86
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 120.31 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 97.98 kNm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 185.05 kN
Mnty = 188.82 kNm
Pu Bottom = 171.47 kN
Mnby = 187.48 kNm
Vuy1 = 144.73 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 97.98 KN-m
Mnby = 97.98 KN-m
Vuy2 = 75.37 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 158.65 kN
Muy = 76.92 kNm
Vuy3 = 40.2513 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 144.73 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 51.97 kNm
φVcy = 89.1 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D


Vsy = (Vuy - φVcy) / φ

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 92.71 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 44.55 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 387.26 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 387.26 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 185.05 kN
Mntx = 188.82 kNm
Pu Bottom = 171.47 kN
Mnbx = 187.48 kNm
Vux1 = 144.73 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 97.98 KN-m
Mnbx = 120.31 KN-m
Vux2 = 83.96 KN
Critical Analysis Load Combination : 15
Critical Load Combination = [11] : 0.9 (LOAD 3: DL) +(LOAD 2: SL Z) kN
Nu = 133.59 kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Mux = 62.49 kNm
Vux3 = 33.0488 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 144.73 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 41.48 kNm
φVcx = 95.03 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 82.83 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 47.52 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 345.99 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 345.99 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design Of Links

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

General Data
Column No. : C32
Level : 7m To 10m
Design Code = ACI 318M - 2014
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Analysis Reference No. = 427
Critical Analysis Load Combination : 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Top Joint
Put = 43.27 kN
Muxt = 14.17 kNm
Muyt = -31.31 kNm
Vuxt = 13.13 kN
Vuyt = 10.76 kN
Pub = 56.84 kN
Muxb = -18.1 kNm
Muyb = 8.06 kNm
Vuxb = 13.13 kN
Vuyb = 10.76 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 71.111 No Beam 5000 x 350 x 400 - 37.333 3.818
Top 71.111 No Beam 5000 x 350 x 400 - 37.333 1.909
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness ψ
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
N-M mm mm N-M N-M
Bottom 71.111 No Beam 4139 x 350 x 400 - 45.099 3.16
Top 71.111 No Beam 4139 x 350 x 400 - 45.099 1.58
Sway Condition (as per Stability Index) = Non Sway
Effective Length Factor along Minor axis = 1

Check For Stability Index


Along D
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame (Braced)

Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 22.52
M1 = 14.17 kNm
M2 = -18.1 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.52 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 22.52
M1 = 8.06 kNm
M2 = -31.31 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.09
22.52 < 37.09, Column not slender along B

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Calculation of Design Moment
Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 14.17 - 14.17
Major Axis Mux (bottom) -18.1 - -18.1
Minor Axis Muy (top) -31.31 - -31.31
Minor Axis Muy (bottom) 8.06 - 8.06

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 43.27 kN
Mux = 14.17 kNm
Muy = -31.31 kNm

Φ Pn, Max Check


Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Critical Location = Bottom Joint kN
Pu = 56.84 kN
Mux = -18.1 kNm
Muy = 8.06 kNm
Pt Calculated = 1.51
φ Pn, Max = 2268.28 kN
Pu < φ Pn, Max Hence, OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Minimum Ast Calculation
Critical Analysis Load Combination = 10
Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL)
Pu = 56.84 kN
φ Pn = 56.84 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.51
Reinforcement Provided = 12-#16
Load Angle = Tan-1(Muy/Mux)
= 65.65 deg
MRes = 34.37 kNm
( φ ) MCap = 143.01 kNm
Capacity Ratio = MRes/ MCap
= 0.24 < 1

Beam Capacity At Joint:


Beams at Level: Top Joint
Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 -1.13 30.71 345 392.7 49.57 13.58 345 392.7 49.6 0 49.57 0 49.6
350 x 400 180 -0.38 33.93 345.8 392.7 49.57 9.39 345 392.7 49.6 49.57 0 49.6 0

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Effective Moment for Column
Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 49.57 - - 49.57
Bottom 49.6 - - 49.6
Moment Along D:
Mntx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 49.6 kNm

Moment Along B:
Mnty = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))
= 49.6 kNm

Beams at Level: Bottom Joint


Beam Size Beam angle Torsion Moment Capacity Beam at Top Moment Capacity Beam at Bottom Resultant Moment
w.r.t. moment
column Ly
Bot @
Mu Ast req Ast pro Mu cap Mu Ast req Ast pro Mu cap Top @ D Top @ B Bot @ D
B
(mm) (deg) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (sqmm) (sqmm) (kNm) (kNm) (kNm) (kNm)
(kNm)
350 x 400 90 0 76.56 618.34 804.24 97.98 24.73 345 392.7 49.6 0 97.98 0 49.6
350 x 400 180 -1.54 85.2 692.57 804.24 97.98 12.36 345 392.7 49.6 97.98 0 49.6 0

Effective Moment for Column


Mu Major (Along D) (kNm) Mu Minor (Along B) (kNm)
Left Right Left Right
Top 97.98 - - 97.98
Bottom 49.6 - - 49.6
Moment Along D:
Mnbx = MAX((left,Bot + Right,Top), (left,Top + Right,Bot))
= 97.98 kNm

Moment Along B:
Mnby = MAX((Left,Top + Right,Bot), (Right,Top + Left,Bot))

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
= 97.98 kNm

Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Luy = 2600 mm
Pu Top = 56.84 kN
Mnty = 175.58 kNm
Pu Bottom = 43.27 kN
Mnby = 174.14 kNm
Vuy1 = 134.51 kN
Shear from Beam Capacity at Joint:
Luy = 2600 mm
Mnty = 49.6 KN-m
Mnby = 97.98 KN-m
Vuy2 = 56.76 KN
Critical Analysis Load Combination : 9
Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 1: SL X) +0.5 (LOAD 4: LL) kN
Nu = 39.1 kN
Muy = 32.23 kNm
Vuy3 = 13.8089 kN
Design Shear, Vuy = Maximum(Vuy1, Vuy2, Vuy3)
= 134.51 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 26.08 kNm
φVcy = 109.07 kN
Vuy > φVcy Hence, Shear links required

Design of Shear Links Along D

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Vsy = (Vuy - φVcy) / φ
= 42.39 kN
Vsy Permissible = 0.66 x sqrt(f'c) x b x deff
= 451.44 kN
Vsy < Vsy permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcy = 54.54 kN
Vuy > 0.5 x φVcy Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Design for shear along B


Shear from Moment Capacity:
Lux = 2600 mm
Pu Top = 56.84 kN
Mntx = 175.58 kNm
Pu Bottom = 43.27 kN
Mnbx = 174.14 kNm
Vux1 = 134.51 kN
Shear from Beam Capacity at Joint:
Lux = 2600 mm
Mntx = 49.6 KN-m
Mnbx = 97.98 KN-m
Vux2 = 56.76 KN
Critical Analysis Load Combination : 10
Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 2: SL Z) +0.5 (LOAD 4: LL) kN

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Nu = 43.27 kN
Mux = 31.31 kNm
Vux3 = 13.1268 kN
Design Shear, Vux = Maximum(Vux1, Vux2, Vux3)
= 134.51 kN
λ = 1
φ = 0.6
deff = 342 mm
ρw (50% of As provided) = 0.018
Mm = 24.51 kNm
φVcx = 111.85 kN
Vux > φVcx Hence, Shear links required

Design of Shear Links Along B


Vsx = (Vux - φVcx) / φ
= 37.75 kN
Vsx Permissible = 0.66 x sqrt (f'c) x d x beff
= 451.44 kN
Vsx < Vsx permissible Hence OK
Check for Minimum Shear Reinforcement
0.5 x φVcx = 55.93 kN
Vux > 0.5 x φVcx Hence , Minimum Shear reinforcement required
Av/s minimum = 333.33 sqmm/m
Av/s shear = 333.33 sqmm/m
Av/s required = max (Av/s minimum , Av/s shear)
= 333.33 sqmm/m
Diameter of link = 10 mm
Numbers of legs provided = 4
Spacing of Link Provided = 200 mm
Av/s provided = 1570.8 sqmm/m
Av/s required < Av/s provided Hence OK

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Criterion for spacing of Ductile links:


Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 100 mm
So = 150 mm
Spacing = 150 mm
Provided Spacing = 75 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 4
S1 = 75 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshD1 = 241.07 sqmm
AshD2 = 128.57 sqmm
AshD (Max (AshD1, AshD2)) = 241.07 sqmm
AshD Provided = 314.16 sqmm
Along B
No of bars along B = 4
S1 = 75 mm
Ag = 160000 sqmm
dc2 = 320 mm

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Ach = 102400 sqmm
AshB1 = 241.07 sqmm
AshB2 = 128.57 sqmm
AshB (Max (AshB1, AshB2)) = 241.07 sqmm
AshB Provided = 314.16 sqmm

Provided Links = #10@75 c/c

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 10 10 10
Spacing 200 --- 75 200 75

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD