You are on page 1of 4

TRANSMISSION AND DISTRIBUTION

Short-circuit current limitation


by series reactors
by Oswald Mendrock, Trench, Austria

Safe and reliable supply of electric power is a prerequisite for continuation and growth of prosperity in any country.

As shown in the past there are


circumstances which require a substantial
adaptation of the power systems to new
conditions. For example, changes in the
political conditions in Europe at the end
of the 1980s have resulted in a massive
restructuring of the power systems in
Central and Eastern Europe. In addition,
the liberalisation of the power industr y,
which started globally in the nineties of the
last century, caused substantial changes
to the power systems because of new
reference conditions, in particular by
intensifying electric power trading. A further
important factor influencing extension of
power grids is the growing imperatives for
electric power which is increasingly being
met by renewable energy sources. The
integration of new energy sources, e.g.
wind energy with large block units into Fig. 1: Relationship between system voltage drop, reactor short circuit voltage, and power factor.
the grid, or the connection of distributed
small power producers into the distribution
network, will lead to major changes in the voltage drop in the network. In general, this with time, and it decays due to the
infrastructure of power systems. Changes does not represent a particular problem armature reaction of the generators. The
of sites for large power production and for the grid operation since the voltage AC component reduces towards the end
consumption may result in the need to drop at the reactor is geometrically of the short-circuit duration to become:
completely change the original grid plans. subtracted from the supply voltage, and
These new system conditions result in the is therefore a function of the power factor. Steady-state short-circuit current: I KD
need to extend the existing network and The system voltage drop as the result of a T h e r e l a t i o n s h i p b e t w e e n I K" a n d I KD
coordinatenew networks withexisting ones. series reactor is calculated as a function depends (among other factors) on the
Management and control of increased of cosφ as follows: type of the fault, the location of the fault,
short-circuit currents resulting from these
conditions is a major requirement. οܷ ͳ and the type of generator. The steady-state
ฬ ฬ ൌ ͳ െ
ܷே short-circuit current determines the thermal
In many cases the use of series reactors ටͳ ൅ ʹ ȉ  ‫ݑ‬௞ ξͳ െ ܿ‫ ݏ݋‬ଶ ߮ ൅ ܷ௞ଶ (1)
loading of the system components in the
to limit the short-circuit power is not where U k is the short-circuit voltage of the event of a short circuit.
only economical, but the only possible reactor
technical solution to the problem for a Peak short-circuit current: l KS
given plant design, as this allows the use For example, a short-circuit voltage of
a reactor of 5% and a power factor of If the short-circuit begins at an instant
of existing equipment without modification
0,9 leads to a drop insystem voltage of near to the voltage zero crossing, a DC
and without replacement of switchgear.
only 2,23%. Fig. 1 shows the relationship component is present in addition to the
Grid planning has to integrate the networks
between the system voltage drop, the AC current. This,together with the initial
of low-power consumers with high-power
short-circuit voltage of the reactor, and symmetrical short-circuit current form
networks. It is not economical to design the
the power factor. the peak short-circuit current, which is
equipment of such consumers to cater for
the short-circuit current of the high power reached at the first maximum of the
Main parameters of short-circuit current
network, but the use of current-limiting AC current after the short-circuit has
and of the current-limiting reactor
reactors allows the equipment to be rated occurred. The peak short-circuit current
for nominal current and this is usually the Short-circuit current parameters are given determines the dynamic loading of the
best and most economical solution. in national and international standards system components through which the
(e.g. IEC 60909-0 or DIN EN 60909-0) and
short-circuit current passes.
The function of a current-limiting reactor is are listed briefly here
to increase the impedance in a possible Peak factor: k
short-circuit loop. The short-circuit current Initial symmetrical short-circuit current: IK"
driven by the voltage source in the faulty This is the ratio between IKS and √2.IK" and is
The AC component of the current flowing
circuit is reduced by the reactance of the at the beginning of a short-circuit is called the peak factor. It depends on the
coil. During normal operation, any increase called the initial symmetrical short-circuit ratio of the reactance to the resistance
in reactance results in an increase of the current. The AC component is not constant in the short-circuit loop and is usually

energize - October 2009 - Page 45


TRANSMISSION AND DISTRIBUTION
the short-circuit and the generators,
the armature reaction is not significant
This situation is refered to as a far-from-
generator short-circuit.
Single or multiple fault
In contrast to single faults, multiple faults
have at least two fault locations which
result in a short circuit. One type of multiple
fault is the double earth fault. As long
as both fault locations are on the same
side of the current-limiting reactor the
short-circuit currents can be expected
to be smaller than for the three-phase
short-circuits (at the same location). If the
Fig. 2: Example calculation.
two fault locations are at different sides of
the reactor, the short-circuit current of the
double earth fault can exceed that for a Fig. 3: Short-circuit current-limiting reactor.
three-phase fault.
assumed to have a value of 1,8.
Short-circuit power: N K Reactor parameters for current-limiting
The three-phase short-circuit is usually the phase AC systems – Part 0, Calculation of
The short-circuit power in a network is
only case considered in the specification currents". For this calculation the relevant
calculated by:
of parameters for a current-limiting reactor. components of the network, including
 ൌξ͵ȉ ȉ  (2) The starting point for the specification all power sources, are modeled in the
is the initial short-circuit current I K". With form of impedances. At the fault location
Short-circuit voltage of a reactor – U K the exception of reactors installed in the an equivalent voltage source c.U N/√3 is
The short-circuit voltage of a reactor, immediate vicinity of a generator, the inserted. The voltage factor which covers
which is usually given as a percentage is initial short-circuit current is considered various uncertainties in the calculation is
calculated by: to be equal to the steady-state short- usually assumed to be 1,1. Using this the
circuit current for practical purposes. The short-circuit current is determined from the
ͳͲͲ ȉ ξ͵  ȉ ‫ܫ‬ே ȉ ܺ (3) short-circuit duration depends mainly equivalent voltage and the impedances
ܷ௞ ൌ  Ψ on the protection system and the type of the equivalent system.
ܷே 
of switchgear. In most standards the
where A problem with this method is the necessity
maximum duration is assumed to be two
X is the reactance of the reactor. seconds. Peak current is determined from of converting the impedances to a
the initial symmetrical short-circuit current reference voltage level (usually the voltage
UN is the rated voltage of the network (see by applying the peak factor k, usually at the fault location). This is avoided in
IEC 60038: IEC Standard voltages). assumed to be 1,8. The peak short-circuit a more simple procedure, called the
current is then calculated by: "Method of calculation with reduced
IN is the rated continuous current of
percentage short-circuit voltages" [1]. This
the coil. ‫ܫ‬௄ௌ ൌ  ξʹ  ȉ ͳǡͺ ȉ  ‫ܫ‬௄ ̶ ൌ ʹǡͷͷ ȉ  ‫ܫ‬௄ ̶ 4) method uses the network voltage drops
Once the inductance L, the initial or the of the impedances, i.e. the short-circuit
Types of fault
steady-state short-circuit current, I K" or I KD, voltages which are arbitrarily related to a
For the calculation of short-circuit currents, the short-circuit duration and the peak rated transmission power of 1 MVA . The
information on the type of the fault short-circuit current l KS are set, the design formulae used for this method are:
is required in addition to the network of the series reactor is fully determined. ܷ௄
parameters. Faults are classified into ‫ݑ‬ᇱ ൌ  (6)
Reactors are designed according to
various types: IEC 60076-6: "Reactors" and they must
ܰ௡
Symmetrical or asymmetrical fault withstand the rated short-circuit currents. ͳͲͲ

ᇱ (7)
‫ ݑ‬ൌ
An asymmetrical fault is present when If the short-circuit power of the supply ܰ௄
the symmetrical short-circuit current is network is large compared to the short-
of a different magnitude in the three circuit power after the coil, the symmetrical where
phases. All single and two-phase faults short-circuit current is solely determined by
the reactance of the coil and is calculated u' = reduced, percentage voltage drop
a r e a s y m m e t r i c a l f a u l t s, w h e r e a s a
three-phase short-circuit is a symmetrical by: U K =short-circuit voltage in percent
fault. This is the most easily calculated
‫ܫ‬ே ȉ ͳͲͲ
‫ܫ‬௄஽ ൌ  (5) Nn =rated transmission power in MVA
case and is specifically considered for ܷ௄
network planning and dimensioning of If the short-circuit power of the supply N K =short-circuit power in MVA
the current-limiting reactor. For networks network is of the same order of magnitude
with an isolated or resonance grounded as that of the network to be protected, Values of the reduced percentage voltage
neutral the three-phase short-circuit results the short-circuit impedance of the supply drop in series are summed, values in
in the highest short-circuit current (except network may be taken into consideration par al l el are cal cu l ated l i ke parallel
for special cases of double line-to-ground for dimensioning the reactor. Precise connected resistors.
faults.) calculation of short-circuit currents is
not particularly easy because of several Series connection
Near–to–generator or far–from–generator
system parameters which may have an
short-circuit
influence, and for this reason simplified
‫ݑ‬ᇱ ൌ  ‫ݑ‬Ԣଵ ൅  ‫ݑ‬Ԣଶ (8)

Armature reaction of the generators results c a l c u l a t i o n m e t h o d s a r e u s e d. T h e Parallel connection


in a reduction of the AC current provided approximate calculation of the short-
‫ݑ‬Ԣଵ ȉ ‫ݑ‬Ԣଶ (9)
by the generator. If there is sufficient circuit current is described in detail in IEC ‫ݑ‬ᇱ ൌ 
impedance between the location of 60909-0: "Short-circuit currents in three- ‫ݑ‬Ԣଵ ൅‫ݑ‬Ԣଶ

energize - October 2009 - Page 46


TRANSMISSION AND DISTRIBUTION

Fig. 5a and Fig. 5b Reactor in the supply feeder.

Applying equation (6) for the transformer:


ܷ௄் ͳͲ
ܷԢଶ ൌ  ൌ ൌ ͲǡʹͷΨ
ܰ௡் ͶͲ

For calculation of the short-circuit power at


the 30 kV busbar u'1 and u'2 are added:
‫̶ݑ‬ଷ ൌ Ͳǡͳͳ ൅ Ͳǡʹͷ ൌ Ͳǡ͵͸Ψ
ͳͲͲ ͳͳͲ
Fig. 4: Stacked three-phase reactor. ܰ௄ଶ ൌ  ൌ ൌ ͵Ͳͷ‫ܣܸܯ‬ Fig. 6: Feeder reactors.
‫̶ݑ‬ଷ Ͳǡ͵͸
using equation (7)
The following example illustrates the The short-circuit power at the feeder after of winding which can withstand the forces
calculation of the design parameters of the reactor must not exceed 200 MVA; thus: occurring during a short-circuit.
a current-limiting reactor by this method. ͳͳͲ ͳͳͲ
‫ݑ‬Ԣହ ൌ ൌ ൌ ͲǡͷͷΨ Fig. 3 shows the layout of a typical air-core
(See Fig. 2).
ܰ௄ଷ ʹͲͲ dry-type current-limiting reactor.
The short-circuit power of a 30 kV feeder The percentage voltage drop of the The main advantages of an air-core
at a 30 kV busbar (Fig. 2) must not exceed reactor is: reactor are as follows:
200 MVA. The short-circuit power of the
u'4 (coil) = U' 5 - U'3 = 0,55 - 0,36 = 0,19% l Constant inductance, even for the
220 kV system is 1000 MVA, the transformer
short-circuit current, with no saturation
has a rated power of 40 MVA and a The required short-circuit voltage for the
effects
short-circuit voltage of 10%. The required reactor, using equation (6) is:
l No insulating oil and therefore no risk
short-circuit voltage of the reactor is UKD =U'4 • NnD= 0.19 • 20,8=3,95% of a possible contamination of the
unknown, the rated current of the feeder is
A 4 % c o i l i s u s e d. T h e s y m m e t r i c a l ground, and negligible fire hazard
400 A corresponding to 20,8 MVA . when compared to oil immersed
short-circuit current I KD of the reactor is
The following symbols are used: calculated by equation (2): reactors
l Simple insulation to ground, provided
U n = nominal voltage, in kV ͵ ʹͲͲ
 ൌ ൌ ൌ3,85 A by support insulators
NK1 220 kV network short-circuit power, in  ȉξ͵ ͵Ͳȉξ͵
Since dry type reactors do not have an iron-
MVA
This corresponds to 3850/400 = 9,65 times core or an iron screen, the magnetic field
N nT rated power of the transformer, in the rated current. spreads into the surrounding environment.
MVA This must be taken into account particularly
Design of current-limiting reactors for three-phase air-core reactance coils
U KT transformer short-circuit voltage, in with stacked phase windings.
percent Air-core, dry-type current-limiting reactors,
being robust and having a simple design Three-phase stacked reactors will exhibit
NK2 short-circuit power at the 30 kV busbar,
time var ying axial forces between the
in MVA have been used almost exclusively for
phase coils during a two-phase or three-
decades. Compared to oil-immersed phase short-circuit. As the short-circuit
UKD short-circuit voltage of the reactor, in
percent coils with an iron-core, an air-core reactor force depends on the distance between
requires considerably lower investment the coils, the force from the center to
NnD rated through-put power of the reactor, the outward coils is much higher than
costs.
in MVA between the two outward coils. Reversing
An air-core reactor is a cylindrical winding the winding direction of the center coil
N K3 short-circuit power after the reactor,
in MVA mounted on a number of insulators. with respect to the outward coils, causes
Since windings made of copper are the neighboring coils to be attracted to
u' 1 ...u' 5 reduced percentage voltage heavier and more expensive and do each other when the time varying force
drop at the corresponding locations, in not offer any technical advantages vs. reaches its maximum during a three-
percent phase short-circuit. This contraction force
aluminum windings, aluminum is used
Applying equation (7) for the 220 kV almost exclusively as the material for the is absorbed by the supporting insulators
network: windings. The turn's insulation consists of a between the coils.

ͳͳͲ ͳͳͲ combination of insulation film and glass Further, the magnetic coupling between
‫ݑ‬Ԣଵ ൌ  ൌ ൌ ͲǡͳͳΨ cloth tape. Impregnation with epoxy the coils results in an increase of the
ܰ௄ଵ ͳͲͲͲ
resin results in a compact, self-supporting effective inductance of the center coil. This

energize - October 2009 - Page 48


TRANSMISSION AND DISTRIBUTION
are loaded symmetrically, the magnetic
coupling in the two half coils will reduce
the effective reactance and therefore
the voltage drop. In the event of a short-
circuit the full reactance of the half coil
is effective.

Fig. 7a: Bus tie reactors. Fig. 7b: Duplex reactor. If each busbar is supplied by a separate
transformer, the reliability of voltage
supply may be improved by coupling
can be compensated for by a reduction feeder, the same reactance (not the same the two busbars with a bus tie reactor.
of the self inductance of the center short-circuit voltage) must be provided in Assuming that the two busbars are loaded
phase by reducing the number of turns each short-circuit path, i.e. the inductance symmetrically, no current flows in the
accordingly. of the reactor in the incoming feeder bus tie reactor and therefore no losses
and that of each outgoing feeder must and voltage drops occur. If one of the
Examples of application of current-limiting be the same. As the unit power rating of transformers fails, the associated busbar is
reactors a reactor is proportional to the square of
still live but it is supplied at reduced power
The application of current-limiting reactors the current (N = X • IN2), the total power of
through the bus tie reactor. The short-circuit
is illustrated in a simple circuit. Three n reactors (of identical power) is only the
power of each busbar is of course higher
arrangements of the reactor are shown nth part of the unit power rating of a single
due the connection via the bus tie reactor
(Fig. 5a, 5b, 6, 7a, 7b). reactor applied in the incoming feeder.
as compared to fully separated busbars.
Furthermore, splitting into several reactors
with lower current but the same reactance It is, however, less than the short-circuit
The short-circuit power at the outgoing power of firmly connected busbars. Usually
leads to lower voltage variations at the
feeders of the simple circuit consisting of the specified current rating of the bus tie
consumers, and less impact by one feeder
a feeder transformer and a busbar with reactors is approx. 50% of the rated current
eight outgoing feeders should be reduced on the voltage of other feeders.
of the transformers.
accordingly. Depending on the location Coils in busbars (Fig. 7a and 7b).
of the reactor, the following cases are References
classified: A further option for reducing the short-
circuit power in the sample circuit is the [1] P Steglich, "Kurzschlussberechnung mit Hilfe von
The reactor in the supply feeder reduzierten prozentualen Spannung-sabfällen"
installation of bus tie reactors (Fig. 7a). If (Short-circuit calculation by means of reduced
This has the lowest investment cost, as a the two coils are combined to form a joint percentage voltage drops), in German, ETZ Nr.
large unit is cheaper than several smaller reactor with the center terminal connected 63, Heft 43/44
units. Further advantages are a lower space to the supply transformer, one obtains a so- Contact Oswald Mendrock, Trench Austria,
requirement and thus less installation cost. called duplex-coil. If the busbar sections oswald.mendrock@trench-group.com v
A disadvantage compared to the other
options is higher losses and larger voltage
variations at the busbar between full load
and reduced load. This option should not
be employed if a large power consumer
with strongly varying load is connected
at one of outgoing lines, which would
reduce the voltage quality for all other
consumers.
The options shown in Fig. 5a and Fig. 5b
only differ in the location of the reactor,
either upstream or downstream of the
transformer. If a possible fault between the
coil and the transformer is considered and
the transformer is not short-circuit-proof
(e.g. autotransformer), the reactor has to
be installed upstream of the transformer.
If the transformer is short-circuit-proof the
choice of location of the coil is open and
be may be made according to space or
best price conditions.
Reactors in outgoing feeders (Fig. 6)
The possible impact on the quality of
the busbar voltage can be avoided
by providing reactors in the individual
outgoing feeders. However, it must be
ensured that the equipment before the
feeder reactors is short-circuit-proof.

Further it may be noted that the unit power


of all feeder reactors together is less than
the unit power rating of one single reactor
at the incoming line. If the short-circuit
power should be the same at any outgoing

energize - October 2009 - Page 49

You might also like