You are on page 1of 57

 

 
 
 

LIKHU KHOLA‐ A 
HEP 
Under sluice bay design 
report 

 
Prepared by Entura Hydro Tasmania India 
Pvt Ltd ‐ Corporate identification number‐ 
U74140DL2006FTC156829 

Unit 3A, 3rd Floor, Plot No. FC‐24, Film City, 
Sector‐16A, Noida, District Gautam Budh 
Nagar,  Uttar Pradesh‐201301, India 

 
 

Entura in Australia is certified to the latest version of ISO9001,  ISO14001, and OHSAS18001. 
 
 
 
 
©Entura. All rights reserved. 
Entura has prepared this document for the sole use of the client and for a specific purpose, as expressly stated in the document. Entura 
undertakes no duty nor accepts any responsibility to any third party not being the intended recipient of this document. The information 
contained in this document has been carefully compiled based on the client’s requirements and Entura’s experience, having regard to 
the assumptions that Entura can reasonably be expected to make in accordance with sound professional principles. Entura may also 
have relied on information provided by the client and/or other parties to prepare this document, some of which may not have been 
verified. Subject to the above conditions, Entura recommends this document should only be transmitted, reproduced or disseminated 
in its entirety. 

 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Document information 

Document title  LIKHU KHOLA‐ A HEP 
  Under sluice bay design report 
Client organisation  Numbur Himalayan Hydropower Private Limited 
Client contact  Sujan Ghimire/Subodh Paudel 
ConsultDM number   
Project Manager  Kavish Bibra 
Project number  P513678 

Revision history 
Revision 0 

Revision description   

Prepared by  Pradipta Kumar Swain     
Reviewed by  Abhay P Singh     
Approved by  Kavish Bibra     
  (name)  (signature)  (date) 

Distributed to  Sujan Ghimire  Numbur Himalayan 


 
Hydropower Private Limited 
  (name)  (organisation)  (date) 

   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Contents 
1.  Under sluice bay  1 
1.1  Purpose of the structure  1 
1.2  Description  1 
1.3  Design philosophy  4 
1.4  Design drawings  5 

2.  Material properties  7 
2.1  System of units  7 
2.2  Materials  7 
2.2.1  Structural concrete (M25)  7 
2.2.2  Reinforcement steel  7 
2.2.3  Backfill material  7 
2.2.4  Foundation material  8 

3.  Geotechnical design data  9 

4.  Main undersluice bay  11 


4.1  Loads and load combinations  11 
4.1.1  Design loads  11 
4.1.2  Load combinations  14 
4.2  FEM (finite element analysis)  15 
4.3  Main under sluice components design  15 
4.3.1  Pier  15 
4.3.2  Raft  16 
4.3.3  Top slab  16 
4.3.4  Breast wall  16 
4.4  Reinforcement summary  16 

5.  Extended pier  17 


5.1  Load & load combinations  17 
5.1.1  Design loads  17 
5.1.2  Load combinations  17 
5.2  FEM (finite element analysis)  18 
5.3  Reinforcement summary  18 

6.  Undersluice bay Stilling basin portion  21 


6.1  Load & load combinations  21 
6.1.1  Design loads  21 
6.1.2  Load combinations  21 
6.2  FEM (finite element analysis)  22 
6.3  Reinforcement summary  22 

7.  References  23 

  v 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Appendices 

A  Stress diagrams‐main under sluice bay 

B  Bending moment & shear force‐main under sluice bay 
B.1  Raft 
B.2  pier 
B.3  Top slab 
B.4  Breast wall 

C  Stress diagram –extended pier 

D  Bending moment & shear force‐extended pier 
D.1  Raft 
D.2  Stem 

E  Stress diagram –undersluice bay stilling basin portion 

F  Bending moment & shear force‐ undersluice bay stilling basin portion 
F.1  Raft 
F.2  Stem 

Annexure 

List of figures 

Figure 1.1: Under sluice bay top plan  2 

Figure 1.2: Cross section of main undersluice bay  2 

Figure 1.3: Undersluice bay section in stilling basin  3 

Figure 1.4: Under sluice longitudinal section  3 

Figure 1.5: extended pier plan  4 

Figure 1.6: Extended pier section with top at EL1451.0  4 

Figure 4.1: Hydrostatic pressure‐water level at EL1451.0  12 

Figure 4.2: Hydrostatic pressure‐water level at EL1453.75  12 

Figure 4.3: active earth pressure‐saturated  13 

Figure 4.4: uplift below raft‐Normal case  13 

   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 4.5: Three dimensional Strand7 model of main undersluice Structure  15 

Figure 5.1: 3D model of extended pier  18 

Figure 7.1: Brick stress contour sYY  25 

Figure 7.2: Brick stress contour sZZ  25 

Figure 7.3:  Brick stress contour sXX  26 

Figure 7.4:  Design bending moment‐raft  27 

Figure 7.5: Design shear force‐raft  27 

Figure 7.6:  design bending moment‐pier  28 

Figure 7.7: design shear force‐pier  28 

Figure 7.8: design bending moment‐top slab  29 

Figure 7.9: design shear force –top slab  29 

Figure 7.10:  design bending moment‐breast wall  30 

Figure 7.11: design shear force –breast wall  30 

Figure 7.12: Brick stress contour sYY  31 

Figure 7.13: Brick stress contour sXX  31 

Figure 7.14: Brick stress contour sZZ  32 

Figure 7.15: design bending moment‐raft  32 

Figure 7.16: design shear force ‐raft  33 

Figure 7.17: design bending moment‐stem  35 

Figure 7.18: design shear force‐stem  35 

Figure 7.19: Brick stress contour sYY  36 

Figure 7.20: Brick stress contour sXX  36 

  vii 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 7.21: Brick stress contour sZZ  37 

Figure 7.22: design bending moment‐raft  38 

Figure 7.23: design shear force‐raft  38 

Figure 7.24: design bending moment‐stem  39 

Figure 7.25: design shear force‐stem  39 

List of tables 

Table 2.1: structural concrete M25  7 

Table 2.2: reinforcement steel Fe500  7 

Table 2.3: backfill material  7 

Table 2.4: foundation material  8 

Table 4.1: load combinations‐main undersluice bay  14 

Table 4.2:  Reinforcement summary  16 

Table 5.1: load combinations‐extended pier  17 

Table 5.2:  Reinforcement summary  19 

Table 6.1: load combinations‐undersluice bay stilling basin portion  21 

Table 6.2:  Reinforcement summary  22 

   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

1. Under sluice bay 
1.1 Purpose of the structure 

Under sluice bay is provided on the left bank and is located adjacent to the overflow weir. It is a 
gated structure with breast wall provided above EL 1445.30. Vertical lift gate proposed has a opening 
of size 4.0m (w) x 3.8m (h). Stilling basin is located downstream of the main undersluice structure. 
Top level of the piers on both sides of the stilling basin portion is at EL 1447.0. Similarly the pier is 
extended upstream and infront of the Intake structure to facilitate discharge into the intake and 
through undersluice when gates are open. Top level of the extended pier is fixed at EL1451.0. Main 
purpose of the undersluice bay is as following. 
 Facilitate discharge of part of the design flood if required 
 Flushing of bed load during flood. 
 Maintaining silt/debris free in front of the Intake by operating the gate intermittently or as per 
operation manual. 

1.2 Description 

 Proposed under sluice opening can discharge maximum 122 cumecs for reservoir water level at 
EL1453.75, which is the maximum water level. Top level of the structure is fixed at EL1455.0 with a 
freeboard of 1.25m. Gate shall be operated from the top slab at EL 1453.75. Total length of the 
structure is 7.0m, which includes two no’s of 1.5m wide pier and 4m wide clear bay. Length of the 
structure along the flow is 19m. Invert level of the under sluice is fixed at EL 1441.50. Breast wall is 
provided to restrict the height of the gate to 3.8m. All the components of the main under sluice 
structure such as raft, piers, breast wall, top slab are fixed to each other to make it behave as single 
unit. 

Undersluice bay consists of main undersluice bay structure, upstream extended pier and 
downstream stilling basin with piers on both sides. Undersluice bay is reinforced concrete structure 
constructed out of concrete of grade M25. To reduce erosion due to flow of high velocity of silt laden 
water, top surface is laid with 500mm (minimum) thick high performance concrete og grade M60. 

The structure is founded on river bed material having safe bearing capacity of 250kn/m2.  Adjacent 
structures Intake on the left and spillway on the right are not connected to under sluice, however the 
joints between them are proposed to be provided with two layers of waterstops. All hydraulic 
calculation have been presented in hydraulic report. This report includes analysis and design of the 
components of the under sluice bay structure. 

Some of the sketches of the under sluice bay are presented below. 

  1 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 1.1: Under sluice bay top plan 

Figure 1.2: Cross section of main undersluice bay 

2   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 1.3: Undersluice bay section in stilling basin 

Figure 1.4: Under sluice longitudinal section 

  3 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 1.5: extended pier plan 

Figure 1.6: Extended pier section with top at EL1451.0 

1.3 Design philosophy 

Main under sluice structure including top slab, raft, piers and breast wall, undersluice bay in stilling 
basin portion and extended pier have been analysed against all possible external loads. The results of 
analysis obtained for different components of the structure have been used to design the 
components by limit state method. Flexural and shear reinforcement have been calculated against 
maximum bending moment and shear force for each component of the structure by using in house 
spread sheets.    

4   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

1.4 Design drawings 

Concrete drgs:‐EHTLKA‐DD‐C‐W‐101, 102, 103 & 105 

Reinforcement drgs: EHTLKA‐DD‐C‐W‐204, 205 & 206 

  5 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

2. Material properties 
2.1 System of units 

The design is presented in units defined in the standard ISO 1000. SI units and their recommended 
multiples are applied. 

2.2 Materials 

2.2.1 Structural concrete (M25) 

Table 2.1: structural concrete M25 

S. No.  Property  Value 


1  Concrete Grade  M25 
2  Concrete Modulus  25 GPa 
3  Poisson’s ratio   0.2 
5  Unit weight (reinforced)  24 kN/m3 

2.2.2 Reinforcement steel 

 Table 2.2: reinforcement steel Fe500 

S. No.  Property  Value 


1  Steel Grade  Fe500 
2  Steel Modulus  200 GPa 
3  Unit weight (reinforced)  7850 kN/m3 

2.2.3 Backfill material 

Backfill material should be self draining and cohesion less. Properties of the material considered are 
presented below. 

Table 2.3: backfill material 

S.No.  Parameter  Values 


1  Unit weight  20 kN/m3 
2  Angle of internal friction  30° 
3  Active Earth pressure coeff.  0.33 

  7 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

2.2.4 Foundation material 

Foundation material is consisted of river borne material which is matrix of sand and boulders. Safe 
bearing capacity of the foundation is considered as 250kn/m2. Accordingly modulus and poisson’s 
ratio of the strata has been worked out by the standard formula as given in Bowles book and 
adopted values are presented below. 

Table 2.4: foundation material 

S. No.  Property  Value 


2  Modulus  150Mpa 
3  Poisson’s ratio   0.25 
5  Unit weight (reinforced)  20 kN/m3 

8   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

3. Geotechnical design data 
The foundation of Likhu khola A undersluice structure is kept on the overburden. The foundation 
strata (overburden) is made up of gravel/boulders in sandy matrix. The terrace was earlier 
investigated through drill holes up to 25 m depth and no bedrock has been encountered. Thus, it is 
apprehended that the foundation strata would be overburden comprising loose sand admixed with 
gravels, boulders and pebbles of calcium sillicates, phyllite, schist etc.  

The engineering property of these type of materials is assumed to be cohesion less with low angle of 
internal friction.  Further, the material is expected to be very permeable. From visual examination of 
the material the following engineering parameter may be considered: 

Cohesion (C) = 0 

Angle of internal friction (Ø) = 30ᴼ 

Safe bearing capacity = 250kn/m2 

  9 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

4. Main undersluice bay  
4.1 Loads and load combinations 

4.1.1 Design loads 

Following loads and forces are considered for the design of Under sluice Structure: 
 Dead load 
 Live load 
 Hydrostatic pressure 
 Active earth pressure 
 Uplift pressure 
 Earthquake load 

4.1.1.1 Dead load 

It consists of self‐weight of the structure including the weight of end piers, intermediate piers, raft, 
top slab and wall etc. Dead load is applied in the strand7 as gravity load considering density of 
concrete as 24kn/m3. 

4.1.1.2 Live load 

A uniformly distributed live load of 10 kN/m2 is assumed to be acting on the top slab.  

4.1.1.3 Hydrostatic pressure 

Hydrostatic pressure is calculated corresponding to the full supply level of 1451.0 and high flood level 
of 1453.75. Figure below presents hydrostatic pressure diagram for A) Full supply level and B) High 
flood level. Hydrostatic pressure varies linearly from top to bottom as shown in the figures. 

  11 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

 
Figure 4.1: Hydrostatic pressure‐water level at EL1451.0 

Figure 4.2: Hydrostatic pressure‐water level at EL1453.75 

4.1.1.4 Active earth pressure 

Active earth Earth pressure is applied on left abutment/pier upto top of the backfill (EL. 1445.5 m). It 
is proposed to use self‐draining material for the backfill. The properties of the backfill material used 
for design is presented in the table above. 

12   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

 
Figure 4.3: active earth pressure‐saturated 

4.1.1.5 Uplift 

Results of subsurface flow analysis has been used for calculation of uplift pressure. Linearly varying 
pressure from upstream to downstream acts below the raft. Uplift is different for both normal and 
flood case. 

Figure 4.4: uplift below raft‐Normal case 

4.1.1.6 Earthquake load 

Nepal is located in high‐risk seismic zone. Therefore, it is considered that Project site is located in 
Zone – V seismic zone (most severe earthquake zone as per IS 1893‐2016). Accordingly, seismic 
parameters for zone V has been adopted for the design of the Under sluice structure.  

Following values of seismic coefficients have been adopted for the design of Under sluice structure 

Horizontal seismic coeff. ah = 0.22 

  13 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Vertical seismic coeff. av = 2/3 x ah = 0.15 

4.1.1.7 Dynamic increment of earth pressure 

Dynamic increment of earth pressure is calculated as per Indian Standard, cl. 8.1 of IS: 1893 – 1984. 

4.1.2 Load combinations 

Following load combinations have been adopted for the design of main undersluice bay. 

Table 4.1: load combinations‐main undersluice bay 

Combination  Combination type  Loads and Partial Load Factors (F)  Remarks 


no. 
(As per Table 18 of IS 456 & cl.6.3 IS 1893) 
Load  Description  (F) 
1  Construction case  DL  Dead load  1.5  No water in Reservoir 
EP  Earth pressure (sat)  1.5 
2  Normal case  DL  Dead load  1.5  Water level at FSL 1451.0 
LL  Live load  1.5 
EP  Earth pressure (sat)  1.5 
UP  Uplift  1.5 
WP  Hydrostatic pressure  1.5 
3  Normal case +  DL  Dead load  1.2  Water level at FSL 1451.0 
Earthquake 
LL  Live load  1.2 
EP  Earth pressure (sat)  1.2 
WP  Hydrostatic pressure  1.2 
UP  Uplift  1.2 
EQ  Earthquake  1.2 
DYN  EP dynamic  1.2 
increment 
4  High flood case  DL  Dead load  1.2  Water level at MWL 1453.75 
LL  Live load  1.2 
EP  Earth pressure (sub.)  1.2 
WP  Hydrostatic pressure  1.2 
UP  Uplift  1.2 

14   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

4.2 FEM (finite element analysis)  

Main under sluice structure is modelled as three dimensional solid finite element model in strand7. 
All the components such as raft, piers, breast wall and top slab are modelled to the actual dimension. 
However the curved portion at the upstream end of the piers are not modelled to avoid complicated 
model. The structure is founded on the river borne material. The left bank of the under sluice is filled 
with compacted backfill up to EL1445.50. On the right bank movement of the structure is restrained 
by the spillway. FEM 3‐D model is presented below. 

Figure 4.5: Three dimensional Strand7 model of main undersluice Structure 

4.3 Main under sluice components design 

Under sluice structure primarily consists of piers, raft, top slab and breast wall. Each component is 
designed based on the results of Strand 7 FEM analysis. All the components of under sluice are 
designed by Limit state method conforming to IS456:2000. 

Output of Strand 7 is presented in Appendix. Typical reinforcement calculations are presented as 
Annexure. Design summary of each components of the under sluice structure are presented below. 

4.3.1 Pier 

Pier is subjected to earth pressure and seismic load in addition to self‐weight and forces transferred 
from adjacent components. Earth pressure is considered saturated during normal operation and 
submerged up to EL1444.50 during flood. Accordingly submerged earth pressure is applied on the 
pier for flood case. Thickness of the pier is 1500mm.  

Design forces (bending moment and shear force) are derived from Strand 7 cut section tool and 
reinforcement worked out as per IS456:2000 using in house spread sheets. Reinforcement of 20T @ 
150mm c/c have been provided on both faces vertically and 20T @ 150mm c/c horizontally.. 

  15 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

4.3.2 Raft 

Raft is subjected to uplift, seismic load in addition to self‐weight and forces transferred from adjacent 
components. Thickness of the raft is 1500mm.  

Design forces (bending moment and shear force) are derived from Strand 7 cut section tool and 
reinforcement worked out as per IS456:2000 using in house spread sheets. Reinforcement of 20T @ 
150mm c/c have been provided on both faces across the flow and 20T @ 150mm c/c along the flow. 

4.3.3 Top slab 

Top slab is subjected to live load, seismic load in addition to self‐weight and forces transferred from 
adjacent components. Thickness of the top slab is 500mm.  

Design forces (bending moment and shear force) are derived from Strand 7 cut section tool and 
reinforcement worked out as per IS456:2000 using in house spread sheets. Reinforcement of 16T @ 
150mm c/c have been provided on both faces across the flow and 16T @ 150mm c/c along the flow. 

4.3.4 Breast wall 

Breast wall is subjected to hydrostatic load, seismic load in addition to self‐weight and forces 
transferred from adjacent components. Thickness of the breast wall is 850mm.  

Design forces (bending moment and shear force) are derived from Strand 7 cut section tool and 
reinforcement worked out as per IS456:2000 using in house spread sheets. Reinforcement of 20T @ 
150mm c/c have been provided on both faces across the flow and 16T @ 150mm c/c along the flow. 

4.4 Reinforcement summary 

Summary of reinforcement details is presented below. 

Table 4.2:  Reinforcement summary 

S. No.  Main under sluice  Direction  Face  Dia. (mm)  c/c spacing (mm) 


component 
1  Raft  Across the flow   Each  20  150 
Along the flow  20  150 
2  Piers  Vertical  Each  20  150 
     Horizontal  20  150 
3  Top slab  Across the flow  Each  16  150 
     Along the flow  16  150 
4  Breast wall  Horizontal  Each  20  150 
     Vertical  16  150 

16   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

5. Extended pier 
Extended pier is 1.5m thick and resting over 2m thick raft. Top of the pier is proposed at EL1451.0. 
Main purpose of the pier is to divide the flow and facilitate flow into the intake. 

5.1 Load & load combinations 

5.1.1  Design loads 

Following loads and forces are considered for the design of the Structure: 
 Dead load 
 Hydrostatic pressure 
 Uplift pressure 
 Earthquake load 

All the loads list above are explained in chapter 4. Only specific loads are explained below. 

5.1.1.1 Hydrostatic pressure 

Net force on the stem due to Hydrostatic pressure during normal case is zero. However during flood 
case 2m differential load has been considered which may arise due to turbulence and layout of the 
headworks. 

5.1.1.2 Uplift 

Uplift load has been calculated by Khosla theory and presented in hydraulics report. Average uplift 
5.0 m of water head or 0.049kn/m2 uplift pressure acts below raft for normal case.  

5.1.2 Load combinations 

Table 5.1: load combinations‐extended pier 

Combination  Combination type  Loads and Partial Load Factors (F)  Remarks 


no. 
(As per Table 18 of IS 456 & cl.6.3 IS 1893) 
Load  Description  (F) 
1  Construction case  DL  Dead load  1.5  No water in Reservoir 
2  Normal case  DL  Dead load  1.5  Water level at FSL 1451.0 on 
both sides 
UP  Uplift  1.5 
WP  Hydrostatic pressure  1.5 

  17 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

3  Normal case +  DL  Dead load  1.2  Water level at FSL 1451.0 on 


Earthquake  both sides 
WP  Hydrostatic pressure  1.2 
UP  Uplift  1.2 
EQ  Earthquake  1.2 
4  High flood case  DL  Dead load  1.2  Water level at MWL 1453.75 
on overflow weir side and 
WP  Hydrostatic pressure.  1.2 
1451.75 on undersluice side. 
(2m differential 
head) 
UP  Uplift  1.2 

5.2   FEM (finite element analysis)  

Extended pier is modelled as three dimensional solid finite element model in strand7. All the 
components such as raft and stem are modelled to the actual dimension. The structure is founded on 
the river borne material. FEM 3‐D model is presented below. 

Figure 5.1: 3D model of extended pier

Output of Strand 7 is appended in appendix. The reinforcement summary is presented below. 

5.3 Reinforcement summary 

Summary of reinforcement details is presented below. 

18   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Table 5.2:  Reinforcement summary 

S. No.  Extended pier  Direction  Face  Dia. (mm)  c/c spacing (mm) 


component 
1  Raft  Across the flow   Each  25  150 
Along the flow  16  150 
2  Stem  Vertical  Each  32  150 
     Horizontal  16  150 

  19 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

6. Undersluice bay Stilling basin portion 
The bay is 4m wide flanked by piers each of 1.5m thick. Raft of the stilling basin varies from 2.5m to 
1.5m. The structure is a reinforced concrete structure with concrete of grade M25. High performance 
concrete of grade M60 is laid at the surface to resist possible erosion due to high velocity of silt laden 
water. 

6.1 Load & load combinations 

6.1.1 Design loads 

Following loads and forces are considered for the design of the Structure: 
 Dead load 
 Earthfill load 
 Hydrostatic pressure 
 Uplift pressure 
 Earthquake load 

All the loads list above are explained in chapter 4.1. Only specific load cases are described below. 

6.1.1.1 Uplift 

Uplift load has been calculated by Khosla theory and presented in hydraulics report. Uplift varies 
from 3.37m to 2.14m of water head which comes out to be 2.755m of water head or 0.027kn/m2 
uplift pressure below raft. 

6.1.2 Load combinations 

Table 6.1: load combinations‐undersluice bay stilling basin portion 

Combination  Combination type  Loads and Partial Load Factors (F)  Remarks 


no. 
(As per Table 18 of IS 456 & cl.6.3 IS 1893) 
Load  Description  (F) 
1  Construction case  DL  Dead load  1.5  No water in Reservoir 
2  Normal case  DL  Dead load  1.5  No water on downstream. 
Earth fill upto EL1445.5 on 
EP  Earth pressure(Sat)  1.5 
left bank. 
UP  Uplift  1.5 
WP  Hydrostatic pressure  1.5 

  21 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

3  Normal case +  DL  Dead load  1.2  No water on downstream. 


Earthquake  Earth fill upto EL1445.5 on 
EP  Earth pressure(Sat)  1.2 
left bank. 
WP  Hydrostatic pressure  1.2 
UP  Uplift  1.2 
EQ  Earthquake  1.2 
4  High flood case  DL  Dead load  1.2  Water level at EL1444.5. 
Earth fill upto EL1445.5 on 
EP  Earth pressure(Sat)  1.2 
left bank. 
WP  Hydrostatic pressure  1.2 
UP  Uplift  1.2 

6.2 FEM (finite element analysis) 

Sluice bay in stilling portion is modelled as three dimensional solid finite element model in strand7. 
Components such as raft and stem are modelled to the actual dimension. The structure is founded 
on the river borne material. FEM 3‐D model is presented below. 

6.3 Reinforcement summary 

Summary of reinforcement details is presented below. 

Table 6.2:  Reinforcement summary 

S. No.  Under sluice bay stilling  Direction  Face  Dia. (mm)  c/c spacing (mm) 


basin portion component 
1  Raft  Across the flow   Each  25  150 
Along the flow  25  150 

22   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

2  Stem  Vertical  Each  25  150 


     Horizontal  25  150 

7. References 

IS 1893:1984   :  “Criteria for Earthquake Resistant Design of Structures”, Fourth Revision 
“Criteria  for  Earthquake  Resistant  Design  of  Structures”,  Part  I  –  General 
IS 1893:2002  : 
Provisions for Buildings, Fifth Revision 
IS 456:2000  :  “Code of Practice for Plain and Reinforced Concrete”, Fourth Revision 

      Bowles, foundation analysis and design 
      SP 16, design aids for reinforced concrete 

  23 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Appendices 

24   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

A Stress diagrams‐main under sluice bay 

Figure 7.1: Brick stress contour sYY 

Figure 7.2: Brick stress contour sZZ 

  25 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 7.3:  Brick stress contour sXX 

26   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

B Bending moment & shear force‐main under sluice bay 
B.1 Raft 

 
Figure 7.4:  Design bending moment‐raft 

Figure 7.5: Design shear force‐raft 

  27 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

B.2 pier 

Figure 7.6:  design bending moment‐pier 

Figure 7.7: design shear force‐pier 

28   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

B.3 Top slab 

 
Figure 7.8: design bending moment‐top slab 

Figure 7.9: design shear force –top slab 

  29 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

B.4 Breast wall 

 
Figure 7.10:  design bending moment‐breast wall 

Figure 7.11: design shear force –breast wall 

30   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

C Stress diagram –extended pier 

Figure 7.12: Brick stress contour sYY 

Figure 7.13: Brick stress contour sXX 

  31 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 7.14: Brick stress contour sZZ 

D Bending moment & shear force‐extended pier 
D.1 Raft 

Figure 7.15: design bending moment‐raft 

32   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 7.16: design shear force ‐raft 

D.2 Stem 

  33 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 7.17: design bending moment‐stem 

Figure 7.18: design shear force‐stem 

  35 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

E Stress diagram –undersluice bay stilling basin portion 

Figure 7.19: Brick stress contour sYY 

Figure 7.20: Brick stress contour sXX 

36   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 7.21: Brick stress contour sZZ 

F Bending moment & shear force‐ undersluice bay 
stilling basin portion 
F.1 Raft 

  37 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Figure 7.22: design bending moment‐raft 

Figure 7.23: design shear force‐raft 

38   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

F.2   Stem 

Figure 7.24: design bending moment‐stem 

Figure 7.25: design shear force‐stem 

  39 
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Annexure 

Reinforcement calculation‐main undersluice bay 

    
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Member pier Raft bridge Breast wall


Input data
Depth of the section mm 1500 2000 500 750
Factored Bending moment knm 372.643 562.80 56.92 231.75
Shear force kn 297.028 435.90 78.43 241.42
2
Concrete grade N/mm 25 25 25 25
2
Reinforcement steel N/mm 500 500 500 500
Cover to reinforcement mm 75 75 40 40
Dia of bar mm 25 25 25 25
Effective depth d mm 1412.5 1912.5 447.5 697.5
Main reinforcement
Factored bending moment knm 372.64 562.80 56.92 231.75
M u lim =0.133*fck*b*d^2 knm 6633.89 12161.71 665.85 1617.63
Factored bending moment < Limiting moment FBM < LM FBM < LM FBM < LM
To be designed as Single reinforced beam S R B S R B S R B 
2
Mu/bd 0.18677 0.15 0.28 0.48
Required percentage of reo from table 3 of SP16 % 0.07 0.07 0.07 0.11
For thick structures >1000mm, depth considered is mm 250 250 500 750
Minimum required reinforcement in surface
zone(as per IS 3370-Part 2:2009) % 0.35 0.35 0.35 0.35
Provided dia of bar mm 25 25 25 25
Spacing of bars mm 200 200 200 200
Reinforcement percentage in surface zone % 0.98175 0.98 0.98 0.98
ok, Provided reinforcement is more than min. reinforcement in surface zone
hence acceptable ok ok ok
2
Total sectional area of reo mm 2454.37 2454.37 2454.37 2454.37
Percentage of reinforcement % 0.17 0.13 0.55 0.35
ok, Provided reinforcement is more than min. & required reinforcement hence
acceptable ok ok ok

   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Shear reinforcement'
Factored shear force Kn 297.03 435.90 78.43 241.42
Depth at the section considered m 1.5 2 0.5 0.75
2
Shear stress N/mm 0.21 0.23 0.18 0.35
pt provided % 0.17376 0.13 0.55 0.35
b 16.7055 22.62 5.29 8.25
t 0.31075 0.27 0.51 0.42
2
Permissible shear stress sc N/mm 0.31075 0.27 0.51 0.42
Shear reinforcement
Not reqd.,as shear stress is less than permissible shear stress of concrete Not reqd. Not reqd. Not reqd.
Vs= V-tc*B*d kn -169.1 -106.46 -148.72 -53.20
Dia of stirrups mm 12 12 12 12
No of legs no 5 5.00 5.00 5.00
req Spacing of shear stirrups mm No No No No
provided spacing of stirrups 'cl 7.3.2 IS 13920 mm 200 200 200 200  
No of rows of single legged stirrups
check for min shear
Asv/(b*sv)>0.4/(0.87*fy)
Max spacing mm 300 300 300 300

ok, provided shear reinforcement is more than minimum required ok ok ok


Transverse reinforcement
For thick structures >1000mm depth considered is mm 250 250 500 750
Minimum required reinforcement in surface zone(as per
IS 3370-Part 2:2009)/sectional area as per IS456:2000 % 0.35 0.35 0.12 0.12
Provided dia of bar mm 20 20 16 16
Spacing of bars mm 200 200 200 200
2
Total sectional area of reo mm 1570.8 1570.80 1005.31 1005.31
Reinforcement percentage in surface zone/sectional area % 0.63 0.63 0.20 0.13
ok, provided reinforcement is more than minimum required ok ok ok

    
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

 
 
 
 
 
 
 
Reinforcement calculation‐extended pier 

   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

Member stem Raft


Input data
Depth of the section mm 1500 2000
Factored Bending moment knm 440.19 914.29
Shear force kn 200.00 267.71
2
Concrete grade N/mm 25 25
2
Reinforcement steel N/mm 500 500
Cover to reinforcement mm 75 75
Dia of bar mm 20 20
Effective depth d mm 1415 1915
Main reinforcement
Factored bending moment knm 440.19 914.29
M u lim =0.133*fck*b*d^2 knm 6657.4 12193.52
 
FBM < LM FBM < LM
To be designed as S R B S R B
2
Mu/bd 0.21985 0.25
Required percentage of reo from table 3 of SP16 % 0.07 0.07
For thick structures >1000mm, depth considered is mm 250 250
Minimum required reinforcement in surface
zone(as per IS 3370-Part 2:2009) % 0.35 0.35
Provided dia of bar mm 20 20
Spacing of bars mm 150 150
Reinforcement percentage in surface zone % 0.84 0.84
ok ok
2
Total sectional area of reo mm 2094.4 2094.40
Percentage of reinforcement % 0.15 0.11

    
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

 
Shear reinforcement'
Factored shear force Kn 200 267.71
Depth at the section considered m 1.5 2
2
Shear stress N/mm 0.14 0.14
pt provided % 0.14801 0.11
b 19.6114 26.54
t 0.28922 0.25
2
Permissible shear stress sc N/mm 0.29 0.29
Shear reinforcement
Not reqd. Not reqd.
Vs = V-tc*B*d kn -210.35 -287.64
Dia of stirrups mm 12 12
No of legs no 6.67 6.67
req Spacing of shear stirrups mm No No  
provided spacing of stirrups 'cl 7.3.2 IS 13920 mm 150 150
check for min shear
Asv/(b*sv)>0.4/(0.87*fy)
Max spacing mm 300 300

ok, provided shear reinforcement is more than minimum required ok


Transverse reinforcement
For thick structures >1000mm depth considered is mm 250 250
Minimum required reinforcement in surface zone(as per IS 337% 0.35 0.35
Provided dia of bar mm 20 20
Spacing of bars mm 150 150
2
Total sectional area of reo mm 2094.4 2094.40
Reinforcement percentage in surface zone % 0.84 0.84
ok ok

   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

 
Reinforcement calculation‐Undersluice bay stilling basin portion 
Member pier Raft
Input data
Depth of the section mm 1500 2000
Factored Bending moment knm 818.4 774.80
Shear force kn 255.8 444.20
2
Concrete grade N/mm 25 25
2
Reinforcement steel N/mm 500 500
Cover to reinforcement mm 75 75
Dia of bar mm 20 20
Effective depth d mm 1415 1915
Main reinforcement
Factored bending moment knm 818.40 774.80
M u lim =0.133*fck*b*d^2 knm 6657.4 12193.52
 
Factored bending moment < Limiting moment FBM < LM
To be designed as Single reinforced beam S R B
2
Mu/bd 0.40875 0.21
Required percentage of reo from table 3 of SP16 % 0.1 0.07
For thick structures >1000mm, depth considered is mm 250 250
Minimum required reinforcement in surface
zone(as per IS 3370-Part 2:2009) % 0.35 0.35
Provided dia of bar mm 20 20
Spacing of bars mm 150 150
Reinforcement percentage in surface zone % 0.84 0.84
ok ok
2
Total sectional area of reo mm 2094.4 2094.40
Percentage of reinforcement % 0.15 0.11

    
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

 
Shear reinforcement'
Factored shear force Kn 255.80 444.20
Depth at the section considered m 1.5 2
2
Shear stress N/mm 0.18 0.23
pt provided % 0.14801 0.11
b 19.61 26.54
t 0.29 0.25
2
Permissible shear stress sc N/mm 0.29 0.29
Shear reinforcement
Not reqd. Not reqd.
Vs = V-tc*B*d kn -179.2 -135.80
Dia of stirrups mm 12 12
No of legs no 6.66667 6.67
req Spacing of shear stirrups mm No No
provided spacing of stirrups 'cl 7.3.2 IS 13920 mm 150 150
No of rows of single legged stirrups
check for min shear
Asv/(b*sv)>0.4/(0.87*fy)
Max spacing mm 300 300

ok ok
Transverse reinforcement
For thick structures >1000mm depth considered is mm 250 250
Minimum required reinforcement in surface zone(as
per IS 3370-Part 2:2009)/sectional area as per % 0.35 0.35
Provided dia of bar mm 20 20
Spacing of bars mm 150 150
2
Total sectional area of reo mm 2094.4 2094.40
Reinforcement percentage in surface zone/sectional area % 0.84 0.84
ok ok

   
LIKHU KHOLA‐ A HEP ‐ Under sluice bay design report  Revision No: 0 
   

    