3-Phase, 50Hz@1500RPM
Voltage kW kVA Amps
380 500 625 949.6
400 500 625 902.1
Prime Power
415 500 625 869.5
440 500 625 820.1
380 555.6 694.4 1055.1
400 555.6 694.4 1002.4
Standby Power
415 555.6 694.4 966.1
440 555.6 694.4 911.2
Noise Level at 7 Open Type 99
meters (dBA) Silent Type 74
Notes:
1) Ambient reference conditions: 1,000 mbar, 27℃, 30% relative humidity;
2) Standby Power: the maximum power available under varying loads. Only for standby and emergency use. No overload is permissible. Prime
Power: the maximum power available under varying loads for continuous operation. A 10% overload is permissible for 1 hour every 12 hours.
Features Benefits
With all the advantages of the soundproofed Easy to transport
generators Easy operation
Optimal unit protection with minimum size No need of installation
Fluid containment design for greater environmental Suitable for outdoor usage
protection
Sound attenuated to minimize impact on local
environment
Keeps all spillages contained inside enclosure
avoiding external site
PLC-5220
DES-5220 control pannel is applied
Microprocessor control, with high stability and credibility
Mains supply and generator operation monitoring
Indicating operation status and fault conditions
Multiple protections; multiple parameters display, like pressure, temp.
Manual and automatic work mode selectable
Real time clock for time and date display, overall runtime display, 99
log entries
Overall power output display
Integral speed/frequency detecting, telling status of start, rated
operation, overspeed
Communication with PC via RS485 OR RS232 interface, using
MODBUS protocol.
Optional
Lubricating
Exhaust System Cooling System Control Panel Voltages
System
● Oil with the ● Protection board from hotness ● Front heat protection ● Remote control panel ● 415/240V
machine ● Low frequency silencer ● 50℃ radiator ● Automatic paralleling ● 400/230V
● Coolant (-30OC) control panel ● 380/220V
● Automatic Transfer ● 220/127V
Switch (ATS) ● 200-115V
Air Switch Paralleling Control ATS Mobile Trailer
System