Rangoli Block D Typ.

Floor DEFLECTION CHECK


PANEL DETAILS REINFMNT. SPACING REQUIRED DEFLECTION CHECK AS PER IS-456

panel panel condition Lx Ly w D DIA AREA Sx+


Sy+ Sx- Sy-
mkd. (as per table 26, Annex D : IS 456) M M T/M 2
mm Ly/Lx mm mm2 mm c/c mm c/c mm c/c mm c/c STATUS

S1 4 TWO ADJ EDGE DISCONT. 3.78 3.78 1.0000 115 1.000 8 50.3 250 250 225 225 SAFE
S2 4 TWO ADJ EDGE DISCONT. 3.17 3.78 1.0000 110 1.193 8 50.3 250 250 225 250 SAFE
S3 2 ONE SHORT EDGE DISCONT. 2.14 3.18 1.0000 110 1.487 8 50.3 250 250 250 250 SAFE
S4 9 ALL EDGE DISCONT. 0.68 2.14 2.0000 110 3.140 8 50.3 250 250 NMNL NMNL SAFE
S5 9 ALL EDGE DISCONT. 1.83 2.29 2.0000 110 1.249 8 50.3 250 250 NMNL NMNL SAFE
S6 3 ONE LONG EDGE DISCONT. 3.28 4.39 1.0000 115 1.337 8 50.3 250 250 225 250 SAFE
S7 3 ONE LONG EDGE DISCONT. 1.77 3.89 1.0000 110 2.198 8 50.3 250 250 250 250 SAFE
S8 9 ALL EDGE DISCONT. 1.83 1.91 1.0000 110 1.044 8 50.3 250 250 NMNL NMNL SAFE
S9 7 ONE LONG EDGE CONT. 1.92 3.51 1.0000 110 1.833 8 50.3 250 250 250 NMNL SAFE
S10 6 TWO LONG EDGE DISCONT. 6.06 6.22 1.0000 180 1.026 8 50.3 175 200 NMNL 150 SAFE
S11 5 TWO SHORT EDGE DISCONT. 1.41 2.5 1.0000 110 1.773 8 50.3 250 250 250 NMNL SAFE
S12 7 ONE LONG EDGE CONT. 2.00 2.23 2.0000 110 1.118 8 50.3 250 250 250 NMNL SAFE

concrete 20
reinforcement 415
clear cover 20
minm. %age 0.12