GUIDE BOOK
ACSON Service Guide Book
Table of Contents
Appendix
Resistance – Temperature Characteristic ............................... 88
1
ACSON Service Guide Book
2
ACSON Service Guide Book
1.2 Nomenclature
Indoor Unit
AA : Revision
Connection Type
F : Flare
X : Not Applicable
Electrical
A : 220-240V/1Ph/50Hz
F : 380-415V/3Ph/50Hz
A WM 10 G W - A X A A
Piping
H : 4 Pipes System
Omitted if 2 pipes system
Model Type
R : Heat Pump
W : Chilled Water Fan Coil
Omitted if DX Cooling Only
Series
G : G Series
Capacity
10 : 10,000 Btu/h
Inverter Series
X: X-Series
Y: Y-Series
Omitted if Non-inverter
Model Name
WM : Wall Mounted
CK : Ceiling Cassette
Refrigerant
5 : R410A
Omitted if R22
Brand
A : Acson
3
ACSON Service Guide Book
Outdoor Unit
Others
A : First Issue
Specifications Variation
O : Standard Unit
I : Gold Fins
G : Low Ambient Unit
H : High Ambient Unit
Compressor
P : Panasonic
M : Mitsubishi
Market Region
C : Export with CE mark
Electrical
A : 220-240V/1Ph/50Hz
F : 380-415V/3Ph/50Hz
A LC 10 C R - A C P O A
Model Type
R : Heat Pump
Omitted if Cooling Only
Series
C : C Series
Capacity
10 : 10,000 Btu/h
Inverter Series
X : X - series
Y : Y – series
Omitted if non-inverter
Model Name
LC : Single Split Condensing Unit
MC : Modular Split Condensing Unit
Refrigerant
5 : R410A
Omitted if R22
Brand
A : Acson
4
ACSON Service Guide Book
Capacity
Btu/hr MBH kCal/Hr kW
1 0.001 0.252 0.293 x 10-3
1000 1 252 0.293
-3
3.968 0.004 1 1.162 x 10
3412 3.412 860.04 1
Pressure
2 W.G. Pascal
PSI kg/cm
(in.) (ft.) (Pa)
4
1 0.07 27.7 2.309 0.69 x 10
4
14.22 1 394.08 32.84 9.81 x 10
3.61 x 10-2 2.538 x 10-3 1 0.083 248.84
1.45 x 10-4 0.1 x 10-4 0.004 3.349 x 10-4 1
Flow Rate
3 3
L/s m /hr m /s U.S. GPM CFM
1 3.6 0.001 15.85 2.119
0.278 1 0.278 x 10-3 4.403 0.588
1000 3600 1 15850 2119
-3
0.063 0.227 0.063 x 10 1 0.1337
-3
0.472 1.7 0.472 x 10 7.481 1
Temperature Velocity
°F = (18 x °C) + 32 fps m/s fpm
1 0.305 60
° F − 32
°C = 3.281 1 196.9
1.8 0.017 0.005 1
Volume
3 3
L m U.S. G.P.M. ft
1 0.001 0.264 0.0353
1000 1 264 35.3
3.785 3.785 x 10-3 1 0.134
28.315 0.028 7.48 1
Area
2 2 2 2
in ft m cm
-3 -4
1 6.94 x 10 6.452 x 10 6.452
144 1 0.093 929.03
1550.06 10.764 1 1 x 104
-3 -4
0.155 1.076 x 10 1 x 10 1
5
ACSON Service Guide Book
6
ACSON Service Guide Book
7
ACSON Service Guide Book
8
ACSON Service Guide Book
Handset Model
Year Main Board Remarks
Wireless Wired Cooling Heating
SLM3 / Valveless application
2002 Chilled Water W1V3 G6 WM-FW / CE-DW / CC-CW / CK-AW / CK-BW
Netware 2 (optional) only
2002 Multi Split Indoor, MS10.0 G8 - - WMS (10-20)FR Auto random restart
2003 Mini Chiller MCH03A - SC302 AC/4AC(80-150)C AC/4AC (80-150)CR Cooling & heatpump
SB (125/150) SB (125/150)
2003 Universal U1SB125 - SLM3 – single speed B1/C1/D1 BR1/CR1/DR1 Cooling & heatpump
RT/4RT (60-120)A RT/4RT (60-120)AR
RT/4RT (150-
RT/4RT (150-300)A
300)AR
2003 Sequential Controller, SQ - SQ-LCD Cooling & heatpump
SB 150B2-600B4 SB 150BR2-600BR4
SB 125D2-500D4 SB125DR2-500DR2
2004 U1.4 G8 - CK (10-20)C CK (10-20)CR Cooling & heatpump
WM (07-15)G WM (07-15)GR
2004 L2.0 G12 - Cooling & heatpump
WM (20-25)G WM (20-25)GR
MC01 - Chiller Panel AC (80-150)C AC (80-150)CR Cooling & heatpump
2004
MCH01 - Chiller Panel AC (20-60)C AC (20-60)CR Cooling & heatpump
G12 - CE (15-28)E CE (15-28)ER Cooling & heatpump
2005 L208A
- Netware 3 CC (75-100)D CC (75-100)DR Cooling & heatpump
U1.4 - SLM3 SB (75-100)ER
2005 Universal U1SB125 - SLM3 – single speed SB (125-150)ER1 Heatpump only
Sequential Controller, SQ - SQ-LCD SB 125ER2-600ER4
Inverter
2005 VA2.0 G12 - 5WMX (10-25)GR In set form only
5SLX (10-25)CR
2005 MC01 - Chiller Panel 5AC (030-055)CR Heatpump only
CE-D / CK-A/B/C / CE-DR / CK-
G8 & G12 SLM3 / Netware 3
2006 L208A CC-C AR/BR/CR / CC-CR Cooling & Heatpump
- SLM3 SB (75-100)B/D SB (75-100)BR/ER
2006 Sequential Controller, SQ - SQ-LCD RT (360-420)A RT (360-420)AR Cooling & Heatpump
WM-GW / CE-DW / CE-EW / CC-CW / CK-
2006 Chilled Water W2 G8 & G12 SML3 / Netware 3
AW/AWH/CW / SB-BW
2008 L2GSN G18 - (5)WM-J/JR Cooling & Heatpump
2009 W_2_03A G18 - 5WMY-J/JR Cooling & Heatpump
9
ASCON Service Guide Book
5.1 G6
Outlook
Operation Guide
1. “ON/OFF” Switch
• Press to start the air conditioner unit.
• Press again to stop the unit.
2. Temperature Setting
• Set the desire room temperature.
• Press button to increase or decrease the set temperature. Setting range are between 16°C to
30°C setting (60°F to 80°F) (Optional setting from 20°C to 30°C).
• Press ▲ or ▼ button simultaneously will toggle the temperature setting between °C and °F.
4. “SLEEP” MODE
• Press the button to activate sleep mode. This mode can only be activated while in cooling or
heating mode operation. If it is activated in “COOL” mode, the set temperature will be
increase 0.5°C after 30 minutes, 1°C after 1 hour and 2°C after 2 hours. Whereas in “HEAT”
mode, the set temperature will decrease by 1°C after 30mins, 2°C after 1 hour and 3°C after 2
hours.
• This function is available under COOL, HEAT & AUTO mode.
10
ASCON Service Guide Book
5. Timer Setting
Press set button to activate the timer setting (from 1 hour to 15 hour) of the air conditioning
unit. It will be in “On” or “Off” condition after the set time depending to the current condition
(either from “On” to Off” or vise versa)
To cancel the timer setting, press the button continuously until the timer display goes off.
6. Operation Modes
• Press the “mode” button for select the type of operating mode.
• Cooling only unit:
Cool → Dry → Fan.
• Heatpump unit:
Auto → Cool → Dry → Fan → Heat
11
ASCON Service Guide Book
5.2 G8
Outlook
Operation Guide
1. Transmission Source
• The source where the signal will be transmitted.
3. On/Off Button
• Press once to start the air conditioner.
• Press again to stop the unit.
4. Temperature Setting
• To set the desired room temperature, press the button to increase or decrease the set
temperature.
• The temperature setting range is from 16°C to 30°C (Optional setting 18°C to 30°C).
• Press both buttons simultaneously to toggle the temperature setting between °C and °F.
12
ASCON Service Guide Book
5. Operation Mode
• Press the MODE button to select the type of operating mode.
• For cooling only unit, the available modes are: COOL, DRY & FAN.
• For heat pump unit, the available modes are: AUTO, COOL, DRY, FAN & HEAT.
7. On Timer Setting
• Press the SET button will activate the on timer function.
• Set the desired on time by pressing the SET button continuously. If the timer is set to 7.30am,
the air conditioner will turn on at 7.30 sharp.
• Press the CLR button to cancel the on timer setting.
13
ASCON Service Guide Book
5.3 G12
Outlook
Operation Guide
1. “ON/OFF” Button
• Press once to start the air conditioner unit.
• Press again to stop the unit.
2. Temperature Setting
• To set the desired room temperature, press ▲ the button to increase or ▼ button to decrease
then set temperature.
• The temperature setting range is from 16°C to 30°C.
• Press both buttons simultaneously to toggle and from ▲ °C to▼ °F setting.
3. Operation Mode
• Press the MODE button to select the type of operating mode.
• For cooling only unit, the available modes are: COOL ( ), DRY ( ) and FAN ( ).
• For heat pump unit, the available modes are: AUTO, COOL ( ), DRY ( ), FAN ( ) and
HEAT ( ).
14
ASCON Service Guide Book
5. ON Timer Setting
• Press the SET button will activate the on timer function.
• Set the desired on time by pressing the SET button continuously. If the timer is set to 7.30am,
the air conditioner will turn on at 7.30am sharp.
• Press the CLR button to cancel the on timer setting.
11. Ionizer
• Press the Ionizer ( ) button to activate the negative Ion function, which will refresh the
indoor air effectively.
15
ASCON Service Guide Book
5.3 G18
Outlook
Operation Guide
1. Transmission Source
• The source where the signal will be transmitted.
2. Signal Transmission Indication
• Blink to confirm that the last setting has been transmitted to the unit.
3. Temperature Setting
• To set the desired room temperature, press the ▲ or ▼ button to increase or decrease
the set temperature.
• Temperature setting range is from 16°C to 30°C (optional setting 20°C to 30°C).
4. Personalize Setting
• Press and hold for 3s, then will blink. Press again to cycle between and .
• Set the desire setting, then leave the handset for 4s without pressing any key and it will save
the setting into the program.
• Press once to activate the P1 setting, press again to cycle between P1 and P2.
• Press any key to deactivate the personalize setting.
16
ASCON Service Guide Book
8. Operating Mode
• Press the MODE button to select the type of operating mode.
• For cooling only unit, the available modes are: COOL ( ), DRY ( ) and FAN ( ).
17
ASCON Service Guide Book
5.4 GS02
1
6 4
7
13
9
12
11 8
10
Operation Guide
1. Transmission Source
• The source where the signal will be transmitted.
3. ON/OFF Button
• Press once to start the air conditioner unit.
• Press again to stop the unit.
• Stop pressing when the desired fan speed appears on the display screen.
18
ASCON Service Guide Book
5. Operation mode
• Press the MODE button to select the type of operating mode.
• For cooling only unit, the available modes are: COOL , DRY and FAN .
• For heat pump unit, the available modes are: AUTO , COOL , DRY , FAN
and HEAT .
• The AUTO mode is unavailable for chilled water system.
•
6. Automatic air swing
• Press the SWING button to activate the automatic air swing function.
• To distribute the air to a specific direction, press the SWING button and wait until the
louver move to the desired direction and press the button once again.
19
ASCON Service Guide Book
20
ASCON Service Guide Book
5.5 APJ2
5
6
7 8
3 9
4 10
12 13
2
11
Operation Guide
1. Transmission Source
• The source where the signal will be transmitted.
2. LCD Display
• It displays the current settings.
• (In this illustration, each section is shown with its displays on for the purpose of explanations)
3. ECONO button
• ECON operation is a function which enables efficient operation by limiting the maximum
power consumption value.
• This function is useful for cases which attention should be paid to ensure a circuit breaker will
not trip when the product runs along side other appliances.
• Press button to start ECONO operation. The symbol is displayed on the LCD.
• Press button to cancel ECONO operation. The symbol button disappears from
the LCD.
21