You are on page 1of 40

Knowledge

Heating technology

Heat pump knowledge


in 4 modules.

Understanding heat pumps. Basic principles and main


components. Planning and measuring correctly. Sound. 1
Table of contents

Module 1: Understanding heat pumps_____________________________________________________________ 4


1. Heat source – heat sink – system boundary_______________________________________________________ 6
2. Designs________________________________________________________________________________________________________________ 8
Monobloc____________________________________________________________________________________________________________ 8
Split design__________________________________________________________________________________________________________ 9
3. Modes of operation___________________________________________________________________________________________ 10
4. Practicable refrigerants_____________________________________________________________________________________ 12
5. GWP value_________________________________________________________________________________________________________ 14
6. P
 arameters for the efficiency of heat pumps_____________________________________________________ 15
COP – Coefficient of Performance____________________________________________________________________ 15
Heating seasonal performance factor_______________________________________________________________ 15

Module 2: Basic principles and main components______________________________________ 17


1. Thermodynamics_______________________________________________________________________________________________ 17
2. T
 he four main components of the compression refrigeration circuit_________________ 18
The evaporator__________________________________________________________________________________________________ 18
The condenser___________________________________________________________________________________________________ 21
The compressor_________________________________________________________________________________________________ 21
The expansion unit____________________________________________________________________________________________ 23
3. Other important components in the refrigerant circuit______________________________________ 24

2
Table of contents

Module 3: Planning and measuring correctly_______________________________________________ 26


1. Planning heat pump systems____________________________________________________________________________ 26
2. P
 ractical knowledge for working in the field______________________________________________________ 27
Preparation________________________________________________________________________________________________________ 27
Initial commissioning_________________________________________________________________________________________ 28
Service and maintenance__________________________________________________________________________________ 31
3. R
 ecording and evaluating important parameters______________________________________________ 32
Subcooling________________________________________________________________________________________________________ 32
Superheating_____________________________________________________________________________________________________ 32

Module 4: Sound_________________________________________________________________________________________________ 35
1. T
 he installation site____________________________________________________________________________________________ 35
Inside_________________________________________________________________________________________________________________ 35
Outside______________________________________________________________________________________________________________ 36
2. Structure-borne sound______________________________________________________________________________________ 36
3. S
 ound measurement_________________________________________________________________________________________ 37
Sound power_____________________________________________________________________________________________________ 37
Sound pressure_________________________________________________________________________________________________ 37
Sound radiation_________________________________________________________________________________________________ 37
Sound emission_________________________________________________________________________________________________ 37
Sound immission_______________________________________________________________________________________________ 37
4. Optical sound____________________________________________________________________________________________________ 38

3
Module 1:
Understanding heat pumps

Heat pumps are becoming increasingly Heat pumps are mainly used in
important in everyday life. They heat residential buildings. Depending on
buildings, they can cool if required the building’s heat requirement, the
and heat tap water for sanitary use. heating output of a unit is between 5
Heat pumps are able to demonstrate and 20 kW. This practical guide deals
their advantages over alternative or with these types of applications. Heat
fossil heating systems as long as they pumps are the largest segment among
are ideally dimensioned, the entire heating systems and the segment
system is optimally planned and the that shows the highest growth rates.
occupant of the residence operates Larger systems for heat or for process
them correctly. If they are regularly cooling up to the megawatt range
maintained and run on green electricity are used in trade and industry, in
– preferably from their own PV system shopping centres, in hotels, office and
– heat pumps not only protect the administrative buildings or in leisure
environment, but also the customer's facilities such as swimming pools or
wallet. multi-purpose facilities. There are also
pure hot-water heat pumps, which are
used exclusively for sanitary purposes.

4
Heat pumps work according to the operating fluids are the refrigerant, the
following principle: A hermetically oil in the compressor and the brine
sealed piping system, the refrigeration or groundwater as the heat transfer
circuit, operates internally. In split medium. The choice of refrigerant
systems, this is extended via copper depends on the available supply,
pipes to the external unit. In it, a ecological and safety aspects, subsidy
refrigerant circulates. This is an options, but above all on the decision
operating fluid that absorbs heat at of the customer.
low temperature and low pressure and
releases it again at higher temperature
and higher pressure. These so-called
compression refrigeration circuits
consist of four main components,
which are briefly described in more
detail below. The heat pump’s

Outdoor unit of a heat pump

5
1. Heat source - heat sink - Each heat source has its advantages
system boundary and disadvantages, which are
Heat pumps take heat from different described in the following table.
sources at a low temperature level However, air-to-water heat pumps
and raise it to the required flow seem to be gaining acceptance in
temperature. The following heat new constructions for detached
sources are used in private buildings: houses and apartment buildings,
• Air mainly because of their unlimited
• Ground (brine) availability and lower investment
• Water costs. A similar trend is emerging for
The most frequently used heat source existing buildings. This is because air
with high rates of growth is air. is the easiest heat source to develop.
Trailing way behind it is geothermal And: New generations of modulating
heat via brine in probes, ground heat pumps now deliver acceptable
collectors or other techniques such as seasonal performance factors for older
geothermal baskets. Groundwater or buildings.
well water is used quite rarely.

(Source: Maximize Market Research PVT. LTD.)

6
Heat source Advantages Disadvantages
Air Available everywhere Defrosting necessary
Easy to develop Propagation of airborne sound
Also suitable for renovations Temperature fluctuations
Low investment costs Very good planning necessary
Ground/brine High temperature (approx. 10 °C) Cumbersome to develop
Constant temperature High development costs
High yield (heat transfer) Space requirement for collectors
Very good seasonal performance Cooling of the soil
factors
Water Relatively constant temperature High development costs
Relatively high temperature Not available everywhere
Possibility of passive cooling Risk of well ageing
Good seasonal performance Observe environmental regulations
factors

(Source: ©NutzWort)

A heat sink is the point of transfer of The smaller the temperature difference
thermal energy from the refrigeration between the heat source and the
circuit. In practice, this usually means heat sink, and thus the lower the flow
a buffer storage tank. From this, the temperatures, the more efficiently a
heat is then transferred via a hydraulic heat pump can work. Heat sinks and
system to radiators, underfloor, the hydraulic supply of the building
wall or ceiling heating in the rooms along with heat exchangers (heat
of the building. Alternatively, it is distribution and storage system) are
possible to heat the air in the room not examined in any detail on the
using convectors, although this is following pages, but are essential for
rarely done in detached houses and the energy planning of a heat pump
apartment buildings. The hot water for heating system. The system boundary
use in the bathroom or kitchen can be is drawn around the heat pump and
connected to the same storage tank or heat source system. The main focus
a separate storage tank, depending on is on air, as this is by far the most
the design, or it can be produced by a frequently used heat source.
pure hot-water heat pump.

7
2. Designs Placement in the building is practised
There are two basic types of heat for all known heat sources. In the
pumps: case of air, two ducts for supply
• Monobloc and exhaust air connect the heat
• Split design pump to the environment. Short-
circuiting of the air flows must be
Monobloc prevented. Likewise, cold bridges
Monobloc means that the complete must be prevented via professional
refrigerant circuit is located inside duct insulation. Heat is extracted
the heat pump. There are monobloc from the ground using probes, ground
heat pumps for indoor and outdoor collectors or baskets. Connection to
installation. the heat pump inside is implemented
via a brine circuit sealed off from the
environment. However, if water is
used, the system is open. From the

Functional principle of the heat pump

Drive energy
Thermal energy
Environmental energy

Air Hot water


Compress-
ing

Soil Radiator

Evapo- Con-
rator denser

Expansion Surface
Groundwater heating

Heat source system Heat pump Heat distribution and storage


system

Heat pump system (Source: BWP)

8
suction well, the groundwater enters Advantages:
the heat pump directly and is returned • No intervention in the refrigerant
via the absorption well. circuit necessary
• Low refrigerant fill level
Outdoor installation of a monobloc • No sound emissions from the
is often used in detached houses compressor when installed indoors
and apartment buildings for air as a
heat source. The recovered heat then Disadvantages:
enters the building via a well-insulated • Loss of efficiency due to the
brine circuit to the buffer storage tank. additional heat exchanger of the
This is why various manufacturers also brine circuit
refer to this variant as split technology • Sound decoupling from the building
with a split refrigerant circuit. There and distribution network is necessary
are various points to consider for for indoor installation
the unit installed outside. It should • With outdoor installation, icing up
be placed as close as possible to and noise emissions to neighbouring
the indoor unit in order to keep heat buildings possible
losses via the brine pipes low. In
winter, the evaporator can ice up and
will therefore be defrosted regularly.
The thawed water must be able to
drain off and must not result in any
hazardous areas under the heat pump
due to black ice. In addition, the sound
emissions of the compressor must not
cause any noise nuisance.

9
Split design An expert technician requires
The split design with closed refrigerant refrigeration expertise for installing
circuit is a special design of air-to- sealed connecting pipes between
water heat pumps. Compressor, the outdoor and indoor unit, for
evaporator and expansion valve evacuation and for filling as well as for
are located in the outdoor unit. The commissioning.
condenser is inside, often combined
with the hydraulics and small buffer Advantages:
tank in one housing. You can also get • Closed refrigeration circuit inside
units that have only the evaporator and and outside
fan in the outdoor unit, with the rest • Better coefficient of performance of
of the refrigerant circuit in the indoor the heat pump
section. In both cases, however, the • All sound-emitting components
outdoor and indoor units must be mostly outside the building
connected with refrigerant-carrying
pipes, which all together make up Disadvantages:
the refrigeration circuit. The outdoor • Larger fill quantity of refrigerant
unit should be placed as close as • Refrigeration expertise necessary
possible to the indoor unit to keep the • Noise emissions and icing up of the
refrigerant fill level low. With regard outdoor unit
to icing up and noise emissions, the
same requirements apply as for a
monobloc installed outside.

10
3. Modes of operation Another possibility is bivalent
If a heat pump undertakes the operation of a heat pump. This is
complete heat and hot water supply where, in addition to electricity,
of a building, it is referred to as a another primary energy source covers
monovalent system. The drive energy the heat requirement. Thus, when a
used is then exclusively electricity. building is renovated, the existing
A variant of this is mono-energetic heating system can continue to be
operation. This is when, for example, operated in parallel with the new
the integrated heating element, as heat pump, for example only for hot
direct heating, becomes part of the water preparation, or to compensate
heat requirement planning. This for peak loads. Another variant is the
can be useful, so that a heat pump coupling of environmental energy to
works with the optimum coefficient cover the heat requirement. Examples
of performance during the main are the use of a solar thermal system,
operating hours, but then cannot a pellet or log stove, or where the
handle the peak load at very low heat building is supplied via a cold district
source temperatures. Nevertheless, heating network as a heat source.
the system achieves a better seasonal These are often referred to as hybrid
performance factor over a year than heat pump systems. In addition, there
is the case in monovalent operation. are hybrid units that combine heat
A second possibility can be short- pump and gas boiler in one housing.
term heating of the hot water tank for They are primarily intended for the
reasons of hygiene. Working out which renovation market and can ascertain
of these two modes of operation a whether electricity or gas is the more
type of heat pump provides and is the environmentally friendly or economical
right choice for a customer, in addition mode of operation.
to the CO2 emissions with regard to
operating costs, requires experience
during planning and, in the event
of any doubt, consultation with the
manufacturer.
11
If the owner of a home also wants 4. Practicable refrigerants
to cool with the heat pump, there Theoretically, a variety of refrigerants
are solutions for this on the market can be used for refrigeration circuits.
too. These are reversible systems, However, not everything on the
i.e. systems that can be switched market is suitable for a heat pump:
over. For planning purposes, these Thermodynamics, various safety
place additional demands on the requirements in the building, available
expert technician, especially when equipment, environmental aspects
it comes to heat absorption in the and also customer intention all limit
building and also for the control the choice for heating. Currently,
aspects. For example, surfaces such there is no refrigerant that covers
as floors, walls and ceilings can also all requirements. This means that
be used for room cooling if they are compromise is always necessary.
designed correctly from the outset.
Alternatively, convectors are good In recent years, natural refrigerants
solutions for heating and cooling. The for heating have greatly increased
flow temperature in each room must in significance – and not just since
be closely monitored. If it is too low, stricter regulations came into force
condensate and moisture can form in worldwide (such as the EU F-Gas
the building fabric. Reversible systems Regulation 517/2014). For heat pumps,
are also more expensive to invest in these not only include carbon dioxide
than pure heat pumps. (R 744) but also hydrocarbon gases
such as propene (R 1270) and in
particular propane (R 290). Both in
terms of thermodynamics and in terms
of their carbon footprint, these natural
refrigerants are long-term and climate-
friendly working media. Moreover, they

12
are not halogenated gases and are pump manufacturers offer various
therefore not regulated by the F-Gas solutions using synthetic transitional
Ordinance. refrigerants. The market is divided into
two parts: Firstly, there are suppliers
Due to the highly flammable nature of Asian origin and R32 as a solution.
of halogenated hydrocarbon gases Secondly, many manufacturers have
(safety class A3), particular emphasis included different refrigerant mixtures
must be placed on “safety” during in their product range. With reduced
planning, installation and operation. global warming potential, these are
However, since heat pumps usually either still non-flammable (safety class
only require small quantities of A1), or with very low GWP values they
refrigerant, or in split design the belong to safety class A2L “mildly
refrigeration circuit can also be flammable”. Therefore, the specified
installed outside, the potential risk is safety requirements must also be
put into perspective, but must not be followed for these substances.
disregarded. Refrigeration expertise is
a prerequisite for handling refrigerants
such as propane.

Thus far, the synthetic refrigerant


R410A has been the most widely
used in heat pumps. However, its
high GWP value of 2088, expected
price hikes and potential supply
bottlenecks make it an increasingly
unattractive option for new heat
pumps. As bridging technologies with
significantly lower GWP values, heat

13
5. GWP value This value expresses how much 1
The Global Warming Potential (GWP) kg of a refrigerant in the atmosphere
is a numerical value which describes contributes to global warming in
the impact of a substance on the comparison to 1 kg of CO2. This
atmosphere and thus its contribution means the GWP value represents a
to the greenhouse effect and to CO2 equivalent.
global warming. CO2 with a numerical
value of 1 is used as the baseline.

Refrigerant GWP Safety class


Synthetic
R410A
2088 A1
(50% R32 / 50% R125)*
R407C
1774 A1
(23% R32 / 25% R125 / 52% R134a)
R466A 733
A1
(49%R32 / 11.5%R125 / 39.5% CF3l)* (Low ODP value)
R32
675 A2L
(pure substance)
R513A
631 A1
(44% R134a / 56% R1234yf)*
R454B
466 A2L
(68.9% R32 / 31.1 % R1234yf)*
R454C
148 A2L
(21.5% R32 / 78.5% R1234yf)*
R455A
148 A2L
(21,5% R32 / 75,5% R1234yf / 3% CO2)*
Natural
R290
3 A3
(propane)
R1270
3 A3
(propene)
R744
1 A1
(CO2)
*: Mixture components; table not exhaustive
(Table: ©NutzWort)

14
Sunlight
(short wave)
Greenhouse effect
Stratosphere H2O, CO2, N2O, CH4,
HFC,
(long wave)
HFC mixtures
Earth surface
Troposphere

GWP values of well-known refrigerants and their effect on the atmosphere

6. Parameters for the efficiency of Something that is important but often


heat pumps confused: The COP relates exclusively
COP – Coefficient of Performance to the heat pump and not to the
A good comparative value for heat entire heating system. This becomes
pumps is the COP (Coefficient Of important in the case of the annual
Performance). This value describes electricity bill, when the heating
the heat output at the operating point energy recorded by the heat meter is
in comparison to the electrical energy considered in relation to the electricity
consumed. It is determined under consumption. This is the heating
laboratory conditions. seasonal performance factor.

15
Heating seasonal performance circuit coming from the heat source
factor and also for distributing the heat in
The heating seasonal performance the building. The heating element for
factor portrays the real operating emergency operation or peak load
scenario over a period of 12 months. It coverage is also included. The graph
records the thermal energy emitted by shows all influencing factors that
the entire heating system – measured are crucial to the heating seasonal
via the heat meter – and compares performance factor.
this to the real power consumption,
including all auxiliary energy. This
includes, for example, the circulation
pumps in the brine or groundwater

Factors influencing the efficiency of heat pumps

Mode of Real source


operation temperature

Can be influenced by...


Heating Real hot
threshold water the manufacturer
temperature content
Measured the tradesman/planner

heating seasonal
Real the consumer
system performance Flexibility
temperatures the weather
factor
the energy supplier

COP values Ventilation


behaviour

Installation
quality

(Source: BWP)

16
Module 2:
Basic principles and main components

Heat pumps use the functional source and 1 part energy from the
principle of a compression compressor, converted from electrical
refrigeration system. In this process, to thermal. The entire amount of
waste heat accumulates as a energy is then released again on the
“waste product” in the refrigeration high-pressure side of the refrigeration
technology. Whenever possible, circuit at the condenser at a higher
however, this should be recovered temperature level for heating or for hot
or, as in the case of heat pumps, put water.
to intentional use. To understand the
thermodynamic process behind this, The second law of thermodynamics
here are a few simple basics. is no less crucial when it comes to
refrigeration technology. It states
1. Thermodynamics that (thermal) energy is only ever
In simplified terms, the first law of transferred naturally from a hotter
thermodynamics states that energy body to a colder body. If additional
is not lost, but simply converted into a energy (compressor) is used, this
new form. This principle is particularly effect can also be used for heating.
important when considering the energy This is because the energy flow of
flows in refrigeration, air conditioning a heat pump in winter is from the
and heating technology. The energy cold heat source to the even colder
balance sheets must therefore be refrigerant in the evaporator. Thus,
coherent. thermal energy can be extracted even
from 10-degree soil or from very cold
Looking at this more simply, it can be air outside. The transfer of energy
seen that the drive power from the then also follows the principle: “from
compressor is added to the thermal warm to cold!”
energy absorbed in the evaporator
from the heat source. With a COP of
4, this means 3 parts heat from the

17
The third law of thermodynamics 2. The four main components of
is derived from the second law. If the compression refrigeration
heat always naturally “flows” from circuit
warm to cold, this means: absolute In general, the compression
zero can never be achieved, at least refrigeration circuit can be defined via
via thermodynamic means. This is 4 main components:
defined at 0 K or -273.15°C and 1) Evaporator
describes a state where the particles 2) Condenser
are motionless. 3) Compressor
4) Expansion unit

The graphic shows these main


components in the refrigerant circuit
of a heat pump. A cycle is shown
in which the refrigerant circulates
in a closed circuit and in doing so
undergoes two changes of state.

ΠEvaporator ΠEvaporator
 Condenser  Scroll compressor

Ž Condenser
Œ Ž  Expansion valve
 Expansion
unit Liquid
Ž Compressor
Gaseous

Refrigerant Ambient heat Thermal heat


receiver

Refrigerant circuit of a heat pump

18
The evaporator ensures that no quantities of liquid
The evaporator is a very important get into the compressor, when there
component. It virtually forms the are for instance load fluctuations.
“interface” from the heat source side The evaporator and expansion unit
to the brine or refrigerant circuit. components must therefore be very
There are two main types used in heat well coordinated.
pumps:
• Finned heat exchanger, when heat is This coordination has a significant
extracted from the medium air influence on the efficiency and
• Plate heat exchanger for heat reliability of the system. The
transfer between two fluids appropriate evaporation temperature
and evaporator superheating serve as
With both options, the heat flow is a measure of effective evaporation.
the same: from “hot” to “cold”. At Both values can be reliably determined
low pressure (suction pressure), the with the digital manifolds testo 557s or
refrigerant enters the evaporator testo 550s.
still largely in liquid form from the
expansion valve. There, it evaporates The entire process is automatically
while absorbing heat from the heat monitored and controlled via the
source. heating control. Under certain
The aim is to inject so much refrigerant conditions (temperature, humidity),
into the evaporator that the thermal finned heat exchangers can ice
energy absorbed is sufficient for up outdoors. The defrosting of the
the complete phase transition from evaporator that is necessary when that
liquid to vapour. In addition to happens represents an interruption of
sensible energy, latent energy is also the heat transfer. Defrosting is also
absorbed. The smallest possible carried out automatically by an icing
superheating of the vapour in the sensor. Nevertheless, knowledge of
last part of the evaporator serves as the defrosting process is necessary
a necessary control process for the because it affects the efficiency of the
injection unit. At the same time, this heat pump.
19
Knowledge about defrosting Another possibility is hot gas
defrosting. Then, the compressed
• Not too early: Because no build- and hot refrigerant does not reach
up of frost or too little build-up of the condenser, but reaches the
frost means unnecessary power evaporator via a bypass. However,
consumption and interruption of the constructional work is more
the heat extraction coming from the complex with this method. On the
source side. other hand, defrosting is very fast
and efficient.
• Not too late: Because heavy frost
on the evaporator significantly • Controlled: Defrosting is
impairs the heat transfer. automatic via intelligent controllers;
however, it is advisable to check
• No longer than necessary: occasionally, including checking
Because too much heat from the the probe position in the outdoor
defrosting process decreases the unit, in order to rule out any
efficiency of the heating system. malfunctions that may have gone
unnoticed. Intelligent heat pumps
• As efficiently as possible: The alert you to faults by means of
most common defrosting method remote monitoring.
for heat pumps is to use heat from
the buffer tank. To do this, the  ell planned: Adjustment of
•W
circuit is briefly reversed and energy the defrosting requires some
is extracted from the storage tank experience, but should be done
to defrost the fins in the outdoor conscientiously, because otherwise
unit. In some cases, defrosting the seasonal performance factor
is also carried out directly using will be affected and this will go
heating water. unnoticed.

20
The condenser Condensing of the refrigerant takes up
The condenser inside a heat pump the greatest space. After compression,
is a brazed or welded plate heat the first step involves the superheated
exchanger. This transfers thermal refrigerant vapour being cooled down
energy on the high-pressure side to the appropriate condensation
behind the compressor to the medium temperature. At this point, the first
of the connected buffer tank. During drop of liquid refrigerant occurs in the
this process, the refrigerant in the condenser. As the heat dissipation to
condenser liquefies, which not only the surroundings continues, this drop
releases the sensible heat energy but gets larger and larger, until there is no
also the latent heat energy absorbed longer any refrigerant vapour present.
during evaporation. If this all happens It is now possible for there to be a
while flowing through the condenser slight subcooling of the refrigerant,
and there is low desuperheating, where the design of the condenser is
optimum heat transfer is achieved. appropriate.
In principle, a condenser has three
sections:
• the desuperheating zone
• the condensing zone
• the subcooling zone

Approx. 1 to 2% Approx. 75% Approx. 23%

Subcooling Condensing Desuperheating


Process and proportions of the individual zones in the condenser

21
The compressor Fully hermetic compressor:
The task of a compressor in the These compressors are hermetically
refrigerant circuit is to draw in sealed. They are used in large
the superheated vapour from the quantities for smaller capacities. The
suction line (suction pressure) and electric motor and the inside of the
to compress this vapour to the high- compressor are not accessible from
pressure level. This level results from the outside. The electric motor is
the performance ratio of condenser cooled via the cold suction vapour
and evaporator when there is a heat (suction vapour cooling) and/or via
requirement in the building and the the oil (oil cooling). Two compression
ambient conditions on the heat source principles are used in heat pumps:
side. Both are subject to seasonal
fluctuations due to day/night or higher/ Scroll: Two interlocking spirals
lower annual temperatures. User compress the refrigerant as it flows
behaviour also plays an important role. through. To do this, one stands
still, while the other rotates at high
The compressor is the component speed, creating increasingly narrow
in the refrigerant circuit that requires chambers. The pressure increases,
the most electrical energy. Heat the gas is compressed, heated
pumps almost exclusively use fully and discharged at the end. Scroll
hermetic compressors. Semi-hermetic compressors are the most common
designs are also used for systems type of construction in classic heat
with a higher output in commercial or pumps. They work quietly and
industrial applications. efficiently. For the heat source air,
speed-controlled operation with a
frequency converter is preferred
because it allows the fluctuating
ambient conditions to be balanced
in an energy-optimized manner. For
temporarily higher flow temperatures,
output control also pays off.
22
Twin rolling pistons: In this design, electric motor can be replaced and
the pistons fully rotate. Another the valve plates of the compressor
designation for this is therefore a are freely accessible for servicing.
rotary compressor. Rotary piston This mode of operation usually
compressors are not quite as efficient, involves reciprocating compressors, or
but they are somewhat cheaper. They screw units for very large capacities.
can exploit this advantage particularly However, neither of these plays
in the small output range below 5 a major role in heat pumps in the
kW heating output. As the heating output range for detached houses or
requirements of highly insulated apartment buildings. The reasons for
homes are becoming ever smaller, this are the significantly higher costs
there has also been increased interest or noise emissions.
in this type of construction ever since.
For heating and hot water, but also, The expansion unit
for example, for coupling houses The expansion unit in a refrigerant
with a high source temperature from circuit has the important task of
cold district heating networks, or for injecting the right quantity of liquid
domestic ventilation systems with a refrigerant into the evaporator to
heat pump module. enable as much refrigerant as possible
to evaporate in its pipe contents.
Semi-hermetic compressor: Evaporating refrigerant requires a lot
Semi-hermetic compressors are of energy for this, which is extracted
used for medium and very high from the heat source. There are
capacities in chillers or heat pumps. various designs:
The electric motor and compressor • Capillary tube
are securely connected to each • Automatic expansion valve
other in the housing, and the motor • Thermostatic expansion valve
is cooled via the cold suction vapour • Electronic expansion valve
or via an attached fan. In contrast
to fully hermetic compressors, the

23
For heat pumps, the last two types 3. Other important components in
play a role almost exclusively. The the refrigerant circuit
thermostatic expansion valve is In addition to providing sufficient
currently the standard for refrigerant liquid refrigerant to the expansion
circuits. Its task is to keep the units, the refrigerant receiver also
superheating section in the evaporator has the task of separating any vapour
constant. The exact setting of the bubbles that may be present in the
thermostatic expansion valve is condensate pipe from the liquid.
particularly important to ensure the When selecting the design, the vertical
fewest possible failures here. receiver is preferable to the horizontal
receiver. Vertical receivers have a
The electronic expansion valve has higher liquid column and thus a better
the highest quality of control of the possibility of fill level monitoring and
expansion elements mentioned. The also a subcooling gain.
aim is to keep the superheating ratio
in the evaporator constant using the The refrigerant dryer – built into the
auxiliary energy (electrical actuation) liquid line – is intended to bind the
and to adjust it quickly in the event of residual moisture from the system. In
load fluctuations. Since the supplier combination with refrigerant, oil and
market has been developing cost- heat, the residual moisture that may
effective variants for some years now, be present may give rise to an acid
the electronic expansion valve is also which can attack the compressor's
becoming increasingly popular for heat enamelled copper wire, amongst other
pumps. Its precise controllability has a things. Furthermore, it is possible
particularly positive effect on the COP to minimize the acid content in the
of a heat pump and especially on the circuit with appropriate additives.
seasonal performance factor. An additional filter prevents foreign
particles, such as chips or scale,
from reaching the solenoid valve or
expansion valve. If any procedure is

24
carried out on the refrigerant circuit, The low-pressure switch monitors
this filter dryer must be replaced. the refrigerant pressure on the heat
source side. If this drops too much,
The sight glass enables a “view” of for example due to a leak, it switches
the flowing refrigerant. If the sight off the heat pump for safety reasons.
glass is incorporated immediately The task of the high-pressure switch
before the expansion valve, pre- is to protect the compressor. If
evaporation due to high pressure the pressure becomes too high, it
drops in the liquid line and too low a switches off the compressor. This
subcooling or a lack of refrigerant can happens when not enough heat is
easily be seen. being absorbed by the condenser.

Drive motor
Low-pressure switch High-pressure switch

Heat source,
e.g. ground-
water
Compressor
Evaporator Condenser
10 °C 35 °C

6 °C 30 °C
Heat dissipation,
Evaporator
e.g. underfloor
probe
heating

Expansion Inspec- Dryer


Refrigerant
valve tion glass
receiver

The components of the simple refrigerant circuit of a heat pump (source: DIN “Heat Pump Manual”;
Jürgen Bonin; 3rd edition 2017, Beuth Verlag; Figure 3.5, page 11)

25
Module 3:
Planning and measuring correctly

Heat pumps are industrially 1. Planning heat pump systems


prefabricated in large quantities. The However, everyday practice often
refrigerant circuit is then already pre- demands even more from a specialist
installed in a monobloc – whether company. In contrast to combustion
for indoor or outdoor installation. technology with energy sources such
In the case of split units, the expert as oil, gas, wood or pellets, each
technician must close the refrigerant degree Celsius in the thermodynamic
circuit. The next task is to properly cycle of a heat pump by and large
connect the heat pump to the thermal plays a major role in the use of
storage tanks or the distribution electrical energy. For example, 1 K
network in the building and to the higher evaporation temperature on
heat source. No mistakes must the heat source side or 1 K lower
be made here, because this will condensation temperature at the
inevitably have a negative impact heat sink bring about a 2 to 3 percent
on the seasonal performance factor improvement in the COP of the heat
and thus the overall efficiency of pump. Expert knowledge is therefore
the heating system. The final step is required.
commissioning.
2. Practical knowledge for work in
the field
Exact measuring values and expert
knowledge form the basis for
comprehensive system evaluation and
correct adjustment of the refrigerant
circuit of a closed split heat pump.
This is the only way to record and
evaluate crucial operating conditions
or parameters.

26
Preparation This is different with the digital
For commissioning and, primarily, manifold. Here, the pressures of
in the event of servicing, it is crucial the system and the associated
that the expert technician quickly temperatures can be recorded in
obtains the most important system parallel and very accurately
parameters of a refrigerant circuit. It to enable the superheating and
is true that, to some extent, pressures subcooling to be determined. It is
and temperatures can be read out on impossible to make either a parallax
modern heat pumps. However, it is error or a mathematical error.
only possible to be certain whether
the displayed values are correct The display illumination, ambient
after a check. A manifold and a pressure adjustment and also
temperature measuring instrument measurement data storage are useful
are therefore indispensable tools additions, allowing servicing work to
when it comes to commissioning. be carried out quickly and efficiently.
However, measuring instruments are This is why electronic refrigeration
often exposed to mechanical and measuring instruments, such as the
thermal stress in vehicles and on new wireless generation of digital
construction sites. The analog version, manifolds testo 557s, testo 550s or
i.e. a manometer with mechanical testo 550i, are now an indispensable
pointers, has the disadvantage that part of the toolbox of any expert
crucial values such as subcooling technician for heat pumps.
and superheating cannot be read off
directly. When calculating these values
manually, there is always the risk
of mathematical errors. In addition,
so-called parallax errors, i.e. pressure
value readout errors, can occur when
interpreting the pointer position.

27
Initial commissioning pressure or leakage test. It is also
Once the heat pump has arrived and perfectly legitimate to remove the
been installed, the cooling circuit of existing air from the pipelines and
split systems must be completed. The the heat exchanger beforehand using
correct choice of pipes to be used is a vacuum pump and then introduce
taken from the current standards. This the dried nitrogen into the evacuated
is because the material, wall thickness, system. Important subsequently:
toughness, corrosion and pressure Gradually raise the test pressure to the
resistance must be selected to match calculated permissible overpressure.
the refrigerant used. All soldered joints Only in this way can leaks due to
are connected leak-tight by brazing pores or fine cracks in materials,
under inert gas (nitrogen) with copper weld seams and soldered joints be
or silver solder. detected and eliminated in good
time during subsequent operation.
This is followed by commissioning Other weak points for leaks are screw
of the refrigerant circuit. The expert connections, valve stuffing boxes,
technician connects his/her digital measuring and monitoring devices
manifold to the corresponding and, paradoxically, seals of all kinds.
high-pressure and low-pressure
connections of the heat pump. The Digital manifolds from Testo have
red and blue hoses help the expert their own measurement program for
technician to keep track of where the leakage test, whereby checks
the pressure measurement is being are carried out over a certain period
taken. The third hose, which is usually of time to ascertain whether the
yellow, is connected to the service applied pressure in the system
port of the manifold. It is used initially remains constant. The leakage test
to introduce dried nitrogen for the is also carried out along the system

28
using foaming agent or a Testo leak measurement, the digital manifold or a
detector from the 316 series. Once vacuum probe such as the testo 552i,
the tests have been completed and which is attached to the system and
documented successfully, the nitrogen transmits the measurement results to
can be drained from the system. the manifold or app, is suitable. Once
Here again, the digital manifold helps the final vacuum has been reached
the expert technician to release the and the vacuum testing has been
nitrogen only to the extent that a successfully documented again, the
slight overpressure remains in the heat pump valves can be opened and
system. A vacuum pump is then the refrigerant, already pre-filled by the
connected to the yellow hose and the manufacturer, can be introduced into
system is evacuated. On the other the system. If the pre-filled refrigerant
hand, for even more accurate vacuum

Digital manifold testo 557s in use

29
quantity is not sufficient, top this up the electrical values such as supply
via the yellow service hose. voltage and current consumption (e.g.
The heat pump is now ready for with the testo 770-3). The system can
use, so series of measurements can be handed over to its owner.
follow for the commissioning. For
this, high and low pressures can be Service and maintenance
read directly from the manifold. If a Depending on the refrigerant, heat
temperature probe is connected for pumps are subject to mandatory
this, subcooling and superheating maintenance. In order to avoid
can be easily determined in real time. creeping refrigerant losses or
Using another temperature measuring malfunctions, for example due to
instrument, the flow and return dirty heat exchanger surfaces, it also
temperatures to the building as well as makes sense to have a maintenance
the intake and output temperatures at contract between the operator and
the evaporator can be determined. the expert technician. Testo also
offers the right measuring instruments
Once the heat pump has been running for the refrigerant circuit. To prevent
in trial operation for some time, refrigerant escaping when connecting
the expert technician checks the measuring instruments, the testo 549i
refrigerant circuit again during the pressure transmitters can be used.
precision checking with an electronic This is because, for pure control
leak detector. This ensures that even measurements, no hoses are required
the smallest leaks are detected. for connection. The pressure is
The measurements are rounded off displayed on a smartphone or tablet.
during commissioning by measuring The same applies to temperature

30
measurements with the clamp 3. Recording and evaluating
thermometer testo 115i. In the case important parameters
of servicing and maintenance, the Subcooling
electronic leak detector is always on In principle, it is best to determine the
the job. It helps the expert technician subcooling of the liquid refrigerant
to detect even the smallest refrigerant before the expansion unit. Subcooling
losses. This prevents a lack of calculations after the condenser or
refrigerant from causing the heat after the (vertical) receiver are only
pump to fail. relevant for the consideration of
subsections. However, what state the
refrigerant is in before the expansion
unit is crucial.

Subcooling is a very important


evaluation parameter when it comes to
the efficiency of the refrigerant circuit.
On the one hand, subcooling leads
to an enthalpy gain, thus increasing
the amount of heat which can be

1 Evaporator
2 Condenser

4 Expansion unit 3

Compressor

Refrigerant
receiver
Determination of subcooling before the expansion valve

31
absorbed by the evaporator. On the Regarding 1)
other hand, it is required in order to Evaporator superheating is
be able to overcome the pressure determined immediately after the
drops in the liquid line without pre- evaporator and at the start of the
evaporation. suction line. The probe element of the
thermostatic expansion valve or the
Superheating superheating sensor of electrically
Just like subcooling, superheating is actuated expansion valves is located
one of the most important parameters in the same place.
for assessing the current efficiency
of the heat pump. In principle, a Regarding 2)
distinction has to be made here as Superheating in the suction line
to the point in the refrigerant circuit generally occurs due to the heat
where the superheating should be impact of the environment through
calculated: the insulation on the suction line. This
1) Evaporator superheating heat impact is normally not desired
2) Superheating in the suction line in systems that are optimally planned
3) Intake superheating and designed, because this heat also
4) Superheating in the compressor has to be absorbed by the refrigerant
circuit.

32
Regarding 3)
Intake superheating, determined
immediately before the intake of the
superheated suction vapour into the
compressor, is based on the sum
of the evaporator and suction line
superheating, including any internal
heat exchanger that may be present.

Regarding 4)
In practice, it is virtually impossible
to determine the additional
superheating present in the
compressor, so this has hardly any
role to play in terms of servicing.
This superheating is predominantly
caused by the compressor's suction
vapour cooling and is specific to the
manufacturer.

33
1 Evaporator
2 Condenser

4 Expansion unit
3 Compressor

Refrigerant
receiver

Determination of evaporator superheating

1 Evaporator
2 Condenser

4 Expansion unit
3 Compressor

Refrigerant
receiver

Determination of intake superheating

34
Module 4: Sound level

When planning the installation site 1. The installation site


of a heat pump, its sound emissions Inside
must be taken into account as early If the heat pump is installed indoors,
as possible. This applies both to the complete refrigerant circuit and
monoblocs installed indoors and to thus also the compressor are located
units with integrated compressors within the building. The units are
installed outdoors. usually well insulated. However, sound
transmission cannot be ruled out.
Reverberant floors or empty rooms
can make this even worse. This should
be taken into account when planning
the installation site. Effective insulation

Air-to-water heat pump installed outside

35
can be achieved, for example, with a The outdoor installation location must
concrete foundation slab and rubber also not impair the efficiency of the
mat. In the case of an air-to-water heat pump. A floor depression, for
heat pump, the air ducts to the outside example, is not a good place because
must be thermally insulated and cold outside air can accumulate there,
also soundproofed. Moreover, when which will affect the COP. Since
connecting each heat pump to pipes heat pump designs vary widely, it is
and electrical cables, care must be advisable to consult the manufacturer
taken to ensure acoustic decoupling if in doubt.
from the building installation, for
example via compensators. 2. Structure-borne sound
In buildings, sound is usually
Outside propagated due to structure-borne
Air-to-water heat pumps installed sound through the floor and walls.
outdoors should be placed at a The sound is then transmitted to the
sufficient distance from and facing ambient air. In this way, noise can
away from neighbouring properties. spread from the basement to the entire
The air flow must not be obstructed building, or even to the surrounding
from any side. When placed on a area.
foundation or base, condensate
can flow off unhindered even in
snow. The housing must be installed
professionally in this case. Buffers or
plastic elements, which are usually
included, decouple the outdoor unit
from the ground. This prevents sound
transmission. Correct installation then
prevents unwanted noise transmission.
Sound-absorbing surrounding surfaces
or greenery are also helpful.

36
3. Sound measurement Sound radiation
If necessary, an approved test The radiation of sound or noises is
measurement can be carried out for expressed in decibels, or dB for short.
heat pumps. Minimum requirements In the case of airborne sound, the unit
for the sound measurement of is given the additional abbreviation
heat pumps can be found in the dB(B). In the case of structure-borne
Ecodesign Regulation (EU) 813/2013/ or liquid-borne sound, the unit is
EC, for example. Precise measuring dB(A).
instruments such as the testo
816-1 are available for accurate Sound emission
determination of the sound level. For a Sound emission is the term used
sound measurement, it is advisable to to describe the sound emitted by a
differentiate between some technical source. It is expressed as a sound
terms. power level with the indication dB.

Sound power Sound immission


Sound power is a theoretical The sound impact on a location is
calculated value. It describes the total called sound immission, measured as
sound energy emitted by a sound a sound pressure level in dB.
source. The greater the distance, the
greater the area over which the sound
power can spread.

Sound pressure
Sound pressure occurs where a noise
source causes air to vibrate. The
greater the change in air pressure, the
louder the perception of a sound.

37
4. Optical sound or facing the street has the same
The growing number of air-to-water effect. In case of any doubt, a sound
heat pumps installed outside is level measurement implemented
increasingly resulting in a curious by an expert technician using the
problem: optical sound. This is when testo 816 measuring instrument and
neighbours feel annoyed by noise in conjunction with the neighbour
because they see the fan blade can help to eliminate the problem of
turning. However, there is actually no optical noise.
noise at all because the heat pump is
not running, but the wind is driving the
fan. The remedy is a heat pump design
that hides the fan. Choosing a location
away from the neighbouring property

This prevents optical noise and makes a heat pump almost invisible.

38
Tips on sound • It is advisable to ensure sufficient
• Take the heat pump manufacturer's distance from neighbouring
noise emission data on the energy buildings for an outdoor unit
label into account • Out of sight, out of mind – a privacy
• Carefully decouple the heat pump screen can help and act as a
installed indoors from the building, preventive measure
supply lines and air ducts
• The TA-Lärm lists guideline values
for noise immissions. Important
to know: The system operator is
responsible for compliance

Fields for name or


trademark or model Space heating function,
identifier of the supplier indicated by radiator
symbol, for medium and low
temperature applications

Energy efficiency classes


for medium and low
temperature applications
Scale of efficiency
classes

Sound power
Nominal heat output for
level LWA indoors (if
average, colder and warmer
applicable)
climates and for medium and
low-temperature applications

Sound power level LWA


outdoors
European temperature
zones with three indicative
temperatures

The energy label for heat pumps (source: BWP)

39
Subject to change, including technical modifications.
© Copyright 2021
2980 XXXX/msp/08.2021

Hassellunden 11A, 2765 Smørum


Tel. 45 95 04 10
info@buhl-bonsoe.dk
www. buhl-bonsoe.dk
www.testo.com

You might also like