You are on page 1of 12

Samada, S., Martínez, A. & Pozo, O. (2018).

Web Client and SCADA Applications for Monitoring the “Cayo Santa María”
Isolated Electric System, Sistemas & Telemática, 16(47), 59-70. doi:10.18046/syt.v16i47.3216

Original research / Artículo original / Pesquisa original - Tipo 1

Web Client and SCADA Applications for


Monitoring the “Cayo Santa María” Isolated
Electric System
Sergio Emil Samada Rigó / ssamada88@gmail.com
Alain Sebastián Martínez Laguardia / amguardia@uclv.edu.cu
Universidad Central Marta Abreu de Las Villas, Santa Clara-Cuba
Osniel Pozo Mederos / osnielpm@gmail.com
Universidad Tecnológica del Perú - San Isidro, Perú

ABSTRACT In modern society, monitoring and control every industrial process are essentials requirements to achieve an
adequate efficiency. This work is focused on the implementation of a Supervisory Control and Data Acquisition [SCADA]
system integrating the generating groups and the electric substation of the “Cayo Santa María” isolated electrics y stem
located in Cuba. For its design, we employed the Eros development platform on its version 5.9 and we collected the field
variables via the Modbus protocol and the OPC standard. We also defined the communicatons network between the tech-
nological targets at the physical level by configuring a report system with the most relevant measurements and we coded a
web client to monitor the SCADA parameters from the cooperative network. The obtained solution entails to considerable
economical savings by complaining the pre-established functional and operational requirements; furthermore, it provides
a considerable flexibility towards future modifications.

KEYWORDS Eros; Modbus; OPC; SCADA; Web client.

Aplicaciones SCADA y cliente Web para Sistemas SCADA e cliente Web para
la monitorización del sistema eléctrico a supervisão do sistema elétrico iso-
aislado “Cayo Santa María” lado "Cayo Santa María"
RESUMEN En la sociedad actual, la monitorización y el con- RESUMO Na sociedade atual, a supervisão e controle de to-
trol de todo proceso industrial son requisitos indispensables para dos os processos industriais são requisitos essenciais para alcançar
lograr una eficiente productividad. Este trabajo se enmarca en uma produtividade eficiente. Este trabalho faz parte da imple-
la implementación de un Sistema de Control Supervisorio y Ad- mentação de um Sistema de Controle Supervisório e Aquisição
quisición de Datos [SCADA] que integra los grupos de genera- de Dados (SCADA) que integra os grupos de geração e a sub-
ción y la subestación eléctrica del sistema eléctrico aislado Cayo estação elétrica do sistema elétrico isolado Cayo Santa María
Santa María (Cuba). Para su diseño se utilizó la plataforma de (Cuba). Para o desenho, foi utilizada a plataforma de desenvol-
desarrollo Eros v.5.9 y para la adquisición de las variables de vimento Eros v.5.9 e para a aquisição das variáveis de campo: o
campo: el protocolo Modbus y el estándar OPC. Como parte de protocolo Modbus e o padrão OPC. Como parte desse sistema,
este sistema se diseñó también la red de comunicaciones entre também foi projetada a rede de comunicações entre os objeti-
los objetivos tecnológicos a nivel físico, se configuró un sistema vos tecnológicos no nível físico, foi configurado um sistema de
de reportes con las mediciones más significativas y se codificó relatórios com as medições mais significativas e foi codificado um
un cliente web para la monitorización de los parámetros del cliente web para o monitoramento dos parâmetros SCADA da
SCADA desde la red corporativa. La solución obtenida supone rede corporativa. A solução obtida supõe uma considerável re-
un ahorro económico considerable, satisface los requerimientos dução de custos, satisfaz os requisitos funcionais e operacionais
funcionales y de operación preestablecidos, y brinda una elevada pré-estabelecidos e fornece uma alta flexibilidade diante de futu-
flexibilidad frente a modificaciones futuras. ras modificações.

PALABRAS CLAVE SCADA; Eros; Modbus; OPC; Cliente PALAVRAS-CHAVE Eros; SCADA; Modbus; OPC; cliente
Web. Web.

Received / Recepción: June. 27, 2018 - Accepted / Aceptación: August 12, 2018 doi:10.18046/syt.v16i47.3216
59
Samada, S., Martínez, A. & Pozo, O. (2018).

I. Introduction I.Introducción
A SCADA system is, basically, a software tool permitting re- Básicamente, un sistema SCADA es una herramienta de sof-
tware que posee acceso a datos remotos de un proceso tecnoló-
mote data in a technological process that can be controlled
gico, la cual, mediante herramientas de comunicación, puede
through communication tools (Padrón-Ramos, 2011;Rodrí-
controlarlo (Padrón-Ramos, 2011; Rodríguez-Penin, 2013).
guez-Penin, 2013). Its main advantages are: it minimizes
Sus principales ventajas son: minimizan las tareas de los opera-
the operators tasks, achieves superior performance, increa- dores, logran un mayor rendimiento, aumentan la productivi-
ses the productivity, and offers higher security. dad y ofrecen mayor seguridad.
Currently, the SCADA systems are practically emplo- En la actualidad, los SCADA se emplean prácticamente en
yed in every aspect of society including the automotive, todos los sectores de la sociedad, incluyendo: las industrias: au-
railway, aerospace, chemical, petrochemical, food and be- tomotriz, ferroviaria, aeroespacial, química, petroquímica, de
verages, textile, pharmaceutical, and electrical industries. alimentos y bebidas, textil, farmacéutica y eléctrica. En este
Consequently, several companies around the world —such sentido, diversas compañías en todo el mundo, tales como
las multinacionales Siemens, Schneider Electric, ABB, Won-
as Siemens, Schneider Electric, ABB, Wonderware, and
derware y Alstom, comercializan sus propias plataformas de
Alstom— commercialize their own development platforms
desarrollo, tanto para su uso en un proceso particular, como
both for their usage in a punctual process and for their ge-
para uso general o uso en varios procesos.
neral usage in several processes.
La automatización de su sector industrial constituye un reto
The automation of the industrial sector is an important importante para Cuba, debido a los costos elevados que impli-
challenge in Cuba because of the elevated costs entailed in ca la instalación y puesta en marcha de proyectos que incluyen
the installation and launching of projects using applications aplicaciones de este tipo. Por ello, se han priorizado aquellos
related with this. For this reason, the objectives creating objetivos que tributan positivamente a la economía de la Na-
benefits for the nation economy are prioritized such as the ción, como es el casos del Sistema Eléctrico Cayo Santa María,
Cayo Santa María electrical system. This latter guarantees el cual garantiza la generación, transmisión y distribución de
the generation, transmission, and distribution of all the toda la energía que se consume en este importante polo turís-
tico ubicado en la región central del país. Este sistema no está
electrical energy used in this important touristic area loca-
conectado a la red nacional, por lo que constituye un sistema
ted in the center of the country. This system is not connec-
de suministro eléctrico aislado (Elices & Rouco, 2001). Su ener-
ted to the national network, so it is an isolated power su-
gía se produce a partir de un esquema de baterías de grupos
pply system (Elices & Rouco, 2001). Its energy is produced electrógenos, distintos en cuanto a: su tecnología (Hyundai,
through a scheme of batteries in engine-generators (gen-set) Mtu y Man) y su capacidad de generación (1700, 1800 y 3850
different on their technology(Hyundai, Mtu, and Man) and kW, respectivamente). Además de la central de generación,
its generation capacity(1,700, 1,800, and 3,850 kW, respec- el sistema incluye una subestación eléctrica de 13.8 kV, con
tively). Apart from the generation power plant, the system tecnología de Alstom, que puede ser telecomandada de forma
includes an electrical substation with 13.8 kV using Alstom local o remota.
technology, which can be remotely or locally commanded. En la última década, el aumento de la capacidad de genera-
In the last decade, the increase in the installed generation ción instalada, debido a la continua construcción de instalacio-
nes para el turismo, conlleva a un desafío considerable, incluso
capacity due to the continuous construction of installations
para los operadores más experimentados. Por ser un sistema
related to the tourism entails a considerable challenge, even
aislado, es importante subrayar que un incidente menor podría
for the most experienced operators. The fact of being an desatar una reacción en cadena que culminaría en un apagón
isolated system is important to highlight that, when a minor generalizado, lo que afectaría significativamente de la calidad
incident arises, it might cause a chain reaction ending in del servicio eléctrico ofrecido a los clientes. Para la gestión del
a generalized power outage, affecting the quality of servi- sistema no se dispone de un centro de despacho energético de-
ce provided to the clients. For the system management, an finido, donde esté integrada toda la información, tanto de la
energetic control center where the information is integra- generación, como de la subestación, en un sistema SCADA
ted from both the generation and the electric substation in único. Cada tecnología de generación, así como la subestación
a unique SCADA system is not available. Each generation eléctrica, cuenta con un supervisor independiente; además, los
technology —such as the electric substation— has an inde- centros de control de la generación y la subestación están geo-
pendent supervisor; further, the generation control centers gráficamente desplazados, lo que produce ineficiencias en la
operación.
of the substation are geographically moved, resulting in in-
La situación descrita provocó que se llevara a cabo la in-
efficiencies in the operation.
vestigación que se reporta en este documento, cuyo objetivo
The situation previously described was the trigger for the fue: implementar un sistema SCADA que integre la central de
investigation described in this document, where the main ob- generación y la subestación eléctrica, que brinde elementos de

60 http://www.icesi.edu.co/revistas/index.php/sistemas_telematica
Web Client and SCADA Applications for Monitoring the “Cayo Santa María” Isolated Electric System, Sistemas & Telemática, 16(47), 59-70.

flexibilidad de cara a los proyectos futuros y que permita mejo- jective is to implement a SCADA system by integrating the
rar la operación del sistema eléctrico. generation power plant and the electric substation and also
El artículo continúa con la siguiente estructura. En la sec- providing flexible elements relative to the future projects,
ción II se expone un marco teórico relacionado con la imple- allowing to improve the operation of the electric system.
mentación de sistemas SCADA para monitorizar sistemas eléc-
The structure of this article is as follow: section II pre-
tricos; en la sección III se exhibe el diseño de la red local; en la
sents a general background related with the implementation
sección IV se expone la arquitectura del sistema de adquisición
de datos; en la sección V se describe la configuración de los of SCADA systems to monitor electric systems; in section
reportes y la codificación del cliente Web; en la sección VI se III, we describe the design of the local network. Section
presentan y discuten los resultados; y por último, en la sección IV presents the architecture of the data gathering system,
VII se presentan las conclusiones. section V details the configuration of the reports and the
II. Antecedentes coding of the web client. Section VI presents the results and
Varios trabajos en la literatura científica abordan temas rela- their corresponding discussion and section VII finalizes the
cionados con el diseño y la implementación de sistemas SCA- document with the conclusions.
DA para la monitorización y supervisión de sistemas eléctricos, II. Background
tanto aislados, como sincronizados con una red. A continua-
ción se presentan algunos de ellos. Several research works in the scientific literature address to-
Villegas (2015) exhibe el diseño e implementación de un pics related with the design and implementation of SCADA
sistema de adquisición de datos y monitorización para los systems for monitoring and supervising electrical systems.
generadores síncronos del simulador experimental de siste- These systems are both isolated and synchronized in the
mas eléctricos de potencia de la SEPI-ESIME. El simulador network. We present a brief summary of the most impor-
está compuesto por cuatro áreas de control y se utiliza para tant for us.
fines de docencia e investigación. Desde el punto de vista de Villegas (2015) presents the design and implementation
equipamiento, contiene todos los tipos de máquinas eléctricas: of a data gathering and monitoring system for the synchro-
especiales, escaladas y no escaladas, incluso pretende interco-
nous generators of the power experimental simulator for
nectar fuentes de energía renovables. La adquisición de datos
electrical systems of the SEPI-ESIME. This simulator is
se realiza en tiempo real, con tiempos de muestreo configura-
bles; el conjunto de variables a monitorizar incluye, tanto las
composed of four control areas and it is mainly used for
eléctricas, como las mecánicas de los generadores, para lo que research and teaching purposes. From the equipment point
se emplea un arreglo de compuertas programables [Field Pro- of view, it contains all the types of electrical machinery:
grammable Gate Array, FPGA]. Emplea LabVIEW y MAT- special, escalated, and not escalated. It is even able to inter-
LAB como herramientas de software para la monitorización y connect renewable energy sources. Data gathering is per-
el análisis de señales formed in real-time with configurable sampling times; the
Weber (2011) y Lanas (2011) presentan la implementación set of variables to monitor includes both the electrical and
de una plataforma SCADA, así como un programa especiali- the mechanical variables of the generators. For this, a Field
zado en la gestión de los recursos energéticos. Ambos trabajos Programmable Gate Array [FPGA] is employed together
persiguen optimizar el despacho y minimizar los costos de ope- with LabVIEW and MATLAB as software tools for moni-
ración del sistema de electrificación sustentable aislado de la toring and analyzing the signals.
localidad de Huatacondo (Chile). El sistema eléctrico en cues-
tión está conformado por un grupo electrógeno diesel y unida- Weber (2011) and Lanas (2011) present the implementa-
des de generación distribuida basadas en energías renovables tion of a SCADA platform and a specialized program for
no convencionales, tales como: paneles fotovoltaicos, sistemas the energy resources management. Both works pursue the
de almacenamiento con baterías y una planta eólica. Para la optimization in the dispatch and the minimization of the
interconexión de estos elementos de generación se manejan los operational costs in the isolated sustainable electrification
estándares Ethernet, RS-485 e IEEE 802.15.4 [ZigBee], a tra- system of Huatacondo (Chile). The electrical system is for-
vés de los protocolos OPC y Modbus. El flujo de información med by some diesel gen-sets and distributed generation units
se centraliza en un servidor que incluye un enlace seguro a based on renewable and non-conventional energies such as
través de Internet, mediante una red privada virtual [Virtual photovoltaic panels, storage systems based on batteries, and
Private Network, VPN], para monitorizar de forma remota el
a wind power plant. For the interconnection of these ge-
sistema aislado.
neration elements, Ethernet, RS-485, and IEEE 802.15.4
Manassero, Torres, López, Furlani, Regalini y Orué (2012)
(ZigBee) are employed through the OPC and Modbus pro-
proponen un Sistema Integral de Supervisión [SIS], para mo-
tocols. The information flow is centralized in a server in-
nitorizar, en tiempo real, las variables físicas del sistema de
combustible, así como las variables eléctricas de los grupos
cluding a secure link through Internet via a Virtual Private
Network [VPN] to remotely monitor the isolated system.

61
Samada, S., Martínez, A. & Pozo, O. (2018).

Manassero et al., (2012) propose an Integral Supervision de generación de las centrales térmicas que administra la fir-
System [ISS] to monitor in real-time both the physical varia- ma Energía Argentina S.A [ENARSA]. El SIS se basa en un
bles of the gasoline system and the electrical variables of the sistema de control distribuido con controladores lógicos pro-
engine-generators in the thermal power plants managed by gramables [Programmable Logic Controller, PLC] a partir
the Energía Argentina company. The ISS is based on a distri- de una red física con topologías en estrella y en bus; especí-
ficamente, la adquisición de datos se maneja en tres niveles:
buted control system with Programmable Logic Controllers
un nivel de campo, con enlaces RS-485 a través del protocolo
[PLC] through a physical network with star and bus topolo-
Modbus RTU; un segundo nivel, que utiliza Modbus TCP so-
gies. Specifically, the data gathering is handled in three levels: bre Ethernet entre los autómatas, así como módulos de E/S
a field level with RS-485 links through the Modbus RTU distribuidos, interfaz de usuario [Human-Machine Interface,
protocol; a second level using Modbus TCP over Ethernet HMI] y un gateway que concentra todas las mediciones para
in the automatons such as input/output distributed modules, luego transmitirlas al centro de control [Control Operativo de
Human-Machine Interfaces [HMI], and a gateway proces- Generación, COG] de ENARSA; y un tercer nivel, basado en
sing all the measurements to transmit them to the control una interfaz satelital entre el concentrador y el COG.
center in the company; and a third level based on a satellite En Silupú (2016) se muestra el diseño de un sistema SCADA
interface between the controller and the control center. para integrar las subestaciones de 66 kV del interconectado
eléctrico denominado “Lote 1AB”, al SCADA distribuido que
Silupú (2016) shows the design of a SCADA system to in-
opera la compañía Pluspetrol Norte S.A. La interconexión de
tegrate the 66 kV substations of the electric interconnection
las subestaciones se fundamenta en una red Ethernet sobre fi-
called “Lote 1AB” to the distributed SCADA operated by
bra óptica; la adquisición de las variables de campo en cada
the Pluspetrol Norte company. The substations interconnec- subestación utiliza el protocolo Modbus (tanto RTU, como
tion is supported by an Ethernet network over optical fiber; TCP) y la norma IEC 61850; en el centro de control se ma-
the field variables gathering in each substation employs the nejan interfaces de seguridad, tales como cortafuegos, zona
Modbus (both RTU and TCP) protocol and the IEC61850 desmilitarizada [DeMilitarized Zone, DMZ,] y VPN, con el
standard. Security interfaces such as firewall, DeMilitari- fin de independizar la red industrial, de la corporativa. Como
zed Zones [DMZ], and VPN are handled in the control herramienta de software se emplea la plataforma de desarrollo
center seeking to separate the industrial network from the de Wonderware.
corporate one. The development platform of Wonderware En general, las tecnologías empleadas en el desarrollo de
is employed as the software tool for this project. sistemas SCADA son diversas y dependen en gran medida de
los recursos económicos disponibles para invertir en equipa-
In general terms, the most employed technologies in
miento. En los casos de sistemas conformados por fuentes de
the development of SCADA systems are several and they
generación con energías renovables o grupos electrógenos de
mainly depend of the available economical resources to pequeña potencia, la tendencia es utilizar plataformas, como
be invested in equipment. In the case of systems made by Arduino, y microcontroladores PIC (Fernández & Duarte,
sources powered by renewable energies or low scale gen- 2015; Guamán, Vargas, Nogales, Guevara, García & Ríos,
sets, the trend is to use platforms such as Arduino and PIC 2016), elección que se fundamenta en el ahorro considerable
microcontrollers (Fernández & Duarte, 2015; Guamán et en la adquisición del hardware que procesa la información de
al., 2016).This choice is substantiated by the considerable la instrumentación de campo, y en las pocas variables que se
savings in the hardware processing the information gathe- tienen en cuenta para la monitorización de estos sistemas.
red in the field and in the few variables to consider when Las microredes aisladas, por su parte, enlazan subestaciones
monitoring these systems. eléctricas con grupos electrógenos de potencia elevada para
régimen de trabajo continuo. En este sentidos, se opta por
The isolated micro-networks connect electrical substa-
instalar sistemas SCADA comerciales y de control distribuidos
tions with high-power engine-generators for continuous apoyados en PLC, y paralelamente se implementan sistemas
operation plans. For this reason, SCADA commercial and de gestión distribuidos [Distribution Management System,
control systems supported in PLC are generally installed DMS], que permiten integrar los SCADA con aplicaciones
and concurrently, the so-called Distribution Management orientadas a la operación de las redes eléctricas.
Systems [DMS] are also installed to allow the integration La decisión de uso de soluciones propietarias se basa en la
of the SCADA with applications oriented to the operation complejidad de los procesos de conversión de energía, en la
of electrical networks. extensa cantidad de variables que se tienen en cuenta y en
Choosing to use proprietary solutions is a decision based las condiciones medioambientales a las que está sometido el
equipamiento. Sus ventajas radican en que se optimizan la
on the complexity of the energy conversion processes, in
operación y el control, y se brinda la información necesaria
the large number of variables to consider, and in the en-
para llevar a cabo el mantenimiento de los equipos; como des-
vironmental conditions that the equipment will deal with.
ventaja cabe destacar que ofrecen poca flexibilidad a la hora

62 http://www.icesi.edu.co/revistas/index.php/sistemas_telematica
Web Client and SCADA Applications for Monitoring the “Cayo Santa María” Isolated Electric System, Sistemas & Telemática, 16(47), 59-70.

de incluir nuevos dispositivos, pues para hacerlo es necesario Their advantages are related with the optimization in the
invertir nuevamente recursos monetarios para la contratación control and operation processes; furthermore, the neces-
de servicios de ingeniería. sary information to perform the equipment maintenance is
Para implementar la aplicación SCADA se propone Eros provided. One of the main disadvantages of these systems
v.5.9, entorno de desarrollo comercializado por la empresa cu- relies in the fact of offering low flexibility when new devices
bana SERCONI, dotado de funciones fiables y probadas en el are added; this requires investment to hire specialized engi-
ámbito de la producción, que aún cuando ofrece menos presta-
neering services.
ciones que otros como: WinCC, Intouch y Movicon, cumple con
los requisitos funcionales y de operación esenciales para integrar In order to implement the proposed SCADA application
la diversidad de tecnologías existentes, a un costo mínimo. we used Eros v.5.9, a development environment commer-
cialized by the SERCONI Cuban company. It has reliable
III. Diseño de la red local
and tested functions in the production environments, al-
La arquitectura de la red física (ver Figura 1) se basa en una to-
pología de estrella a partir de cables de fibra óptica multimodo though it does not offer all the solutions provided by other
de 50/125 μm. El enlace redundante de seis hilos entre ambos solutions such as WinCC, Intouch, and Movicon. Never-
centros de control se fundamenta en el beneficio de una vía theless, Eros complies with the essential operational and
de comunicación alternativa entre los dos sitios donde mayor functional requirements to integrate the diversity of exis-
información fluye. ting technologies at a fraction of the cost.
Dentro de la red local convergen dos subredes virtuales [Vir-
tual Local Area Network, VLAN], una operativa, otra corpo-
III. Design of the Local Network
rativa. Además, la comunicación con el Despacho Provincial The architecture of the physical network (see Figure 1) is
de Carga [DPC] se respalda a través de un contrato con la based on a star topology using multimode fiber optics with
Compañía de Telecomunicaciones de Cuba [ETECSA], a 50/125 μm of diameter. The redundant link with six yarns
partir de dos enlaces mediante modem, uno para cada VLAN. between both control centers is seeking the benefit of an
En cada nodo de la fibra coexisten: una caja de distribu- alternate communication way between the two sites with
ción [Optical Distribution Frame, ODF], un conversor de larger information exchange.
medio de fibra a cobre, y un conmutador. Los conmutadores
Within the local Networks, two Virtual Local Area Ne-
en dependencia de la funcionalidad son dispositivos capa 2
tworks [VLAN] converge: an operative and a corporate
o capa 3 del modelo de interconexión de sistemas abiertos
one. Furthermore, the communication with the load dis-
[Open System Interconnection, OSI]. Para el manejo de las
subredes virtuales se emplean dos conmutadores capa 3, ubi- patcher is backed up through a contract with the Cuban te-
cados en ambos centros de control. lecommunications company [ETECSA] by using two links
via modem, one for each VLAN.
IV. Arquitectura del sistema de adquisición de datos
In every node of the fiber there exists: an Optical Dis-
Subestación
tribution Frame [ODF], a media converter from fiber to
La subestación eléctrica de 13.8 kV se opera mediante DS
copper, and a switch. These switches depending on the
Agile de Alstom [Figura 2]. Esta solución se basa en una red
functionality are layer 2 and 3 devices of the Open System
principal IEC 61850 sobre Ethernet con topología de anillo re-
Interconnection [OSI] model. In order to manage the vir-
dundante. A la red principal se conectan dispositivos electróni-
cos inteligentes [IED, IntelligentElectronicDevice] tales como tual subnetworks, two layer-3 switches located in both con-
controladores de bahía, analizadores de redes, protecciones trol centers are employed.
digitales entre otros.
IV. Data Gathering System Architecture
Substation
The 13.8 kV electrical substation is operated through DS
Agile of Alstom (Figure 2). This solution is based on a main
IEC 61850 network over Ethernet with redundant ring to-
pology. Some Intelligent Electronic Devices [IED] such as
bay controllers, network analyzers, digital protections, etc.,
are connected to the main network.
For the remote control of the substation, three gateways
based on Alstom devices are employed. These devices
are configured with the IEC 60870-5-101/104 protocols,
Figure 1. Architecture of the local network Dnp3, and the OPC [OLE for Process Control] standard.
Arquitectura de la red local

63
Samada, S., Martínez, A. & Pozo, O. (2018).

Para el control remoto de la subestación se manejan tres ga-


teways basados en dispositivos de la firma Alstom, configura-
dos con los protocolos IEC 60870-5-101/104, Dnp3 y el están-
dar OPC [OLE for Process Control]. Igualmente, está incluido
el controlador DAPServer (Alstom, 2013), que intrínsecamente
contiene una base de datos de tiempo real para colectar datos
y luego servirlos, en este caso particular, mediante el protoco-
lo de comunicación Modbus sobre Ethernet. Precisamente, la
integración de los parámetros de la subestación se lleva a cabo
mediante el controlador DAPServer.
Generación Mtu
Estructuralmente, los grupos electrógenos Mtu están ubicados
Figure 2. DS Agile automation system dentro de contenedores y, a su vez, todos tributan a un con-
Sistema de automatización DS Agile tenedor adicional, denominado de media tensión, en el cual
Likewise, the DAPServer controller(Alstom, 2013) is inclu- están instalados los interruptores de salida a la subestación.
Para el régimen de trabajo de cada grupo los motores de com-
ded; this one has an intrinsic real-time database to collect
bustión interna operan con combustible diesel.
data and then transmit them —in this particular case—
El control y protección de cada par motor-generador lo ejerce
using the Modbus communications protocol over Ethernet.
el Controlador para Motores Diesel Mtu [Mtu Diesel Engine
The integration of the substation parameters is carried out
Controller, MDEC] acoplado al Controlador Avanzado de Gru-
via the DAPServer controller. pos Electrógenos [Advanced Gen-set Controller, AGC]. El AGC
Mtu Generation es un IED basado en microprocesador, y consta de un sistema
de medición trifásico que constituye la base para realizar todas
Structurally, the Mtu engine-generators are located inside
las funciones de control y protección al generador (DEIF, 2008).
containers and —at the same time— all of them are within
La integración de estos grupos se realiza mediante los proto-
an additional container called mid voltage container. In this colos industriales Can Bus [J1939] y Modbus [Figura 3]. Cada
one, the output switches to the substation are located. For AGC se enlaza al servidor de puerto serie Moxa Nport5600
the working regime of each gen-set, the internal combus- y este se acopla al SCADA a través de TCP/IP Ethernet. El
tion engines work with diesel fuel. servidor Nport concentra todas las variables y, mediante mane-
The control and protection of each engine-generator jadores COM [Component Object Model], establece la cone-
pair is performed by the Mtu Diesel Engine Controller xión de forma transparente entre los puertos series y el puerto
local COM de la computadora host (Moxa, 2010).
[MDEC] coupled to the Advanced Gen-set Controller
[AGC]. The ACG is an IED based on a microprocessor Generación Hyundai y Man
and it has a triphasic measurement system, which is the El proceso de generación de energía eléctrica de estas dos tec-
base to perform all the control and protection functions of nologías de grupos electrógenos difiere del de los grupos Mtu
the generator (DEIF, 2008). debido a que los motores de combustión utilizan fuel-oil como
combustible. A ser este, viscoso y pesado, es imprescindible un
The integration of these groups is performed via the
calentamiento previo para que pueda ser consumido por el
Can Bus J1939 and Modbus (Figure 3) industrial protocols.
motor, para lo cual se emplea una unidad de tratamiento de
Each AGC is linked to the Moba Nport5600 serial port ser- combustible, una caldera de vapor y una planta de tratamiento
ver and this latter is coupled to the SCADA via TCP/IP químico de agua.
Ethernet. The Nport server gathers all the variables and Ambos procesos se controlan a través de un sistema de auto-
using Component Object Model [COM] handlers, it es- matización distribuido a base de PLC y sistemas SCADA. En
tablishes the connection in a transparent way between the el caso de los Hyundai los PLC son Siemens S7-300, además
serial ports and the COM local port of the host computer
(Moxa, 2010).

Hyundai and Man Generation


The generation process of electrical energy used by these
engine-generator technologies differs from the Mtu groups
due to the fact that the combustion engines use fuel-oil as
combustible. This fuel-oil is viscous and heavy, so it requires
a previous heating in order the engine can use it. For this, Figure 3. Data gathering of the Mtu groups
Adquisición de datos de los grupos Mtu

64 http://www.icesi.edu.co/revistas/index.php/sistemas_telematica
Web Client and SCADA Applications for Monitoring the “Cayo Santa María” Isolated Electric System, Sistemas & Telemática, 16(47), 59-70.

del Controlador de Conexión en Paralelo al Generador [Gene- a combustible treatment unit, a steam boiler, and a water
rator Paralell Controller, GPC] de DEIF. Como SCADA, ope- chemical treatment plant are utilized.
ra SIMATIC WinCC, versión 6.2, también de Siemens. Los
Both processes are controlled through a distributed auto-
grupos Man, por su parte, manejan PLC de la serie AC800 y el
mation system based on PLC and SCADA systems. In the
SCADA Industrial 800xA versión 5.0, ambos de ABB.
case of the Hyundai technology, the employed PLC is a Sie-
La unificación de los parámetros de estos grupos a la apli-
mens S7-300 plus the Generator Parallel Controller [GPC]
cación se emplea a través del estándar abierto OPC. Este pro-
tocolo ofrece elevada fiabilidad en la comunicación y un aho- of DEIF. For SCADA we have the SIMATIC WinCC ver-
rro considerable de tiempo para su configuración. Para lograr sion 6.2, also from Siemens. On the other hand, the Man
este propósito es imprescindible emplear la tecnología DCOM groups handle the series AC800 PLC and the industrial
[Distributed Component Object Model] y el buscador de ser- SCADA 800xA version 5.0, both from ABB.
vidores OPC, OPCENUM.exe, debido a que el intercambio The unification of the parameters in these groups to the
entre los servidores y el cliente se realiza de forma remota. En application is employed through the OPC open standard.
la Figura 4 se muestra, de forma general, la arquitectura de
This protocol offers high reliability in the communications
la red industrial para integrar la generación Hyundai y Man.
and considerable time savings in its configuration. In order
to achieve this purpose, it is essential to use the Distributed
Component Object Model [DCOM] technology and the
OPC server finder —OPCENUM.exe— because the ex-
change between the servers and the client is remotely perfor-
med. Figure 4 shows the general architecture of the indus-
trial network to integrate the Hyundai and Man generation.

V. Reporting System and Web Client


The Eros report system [SREros] allows the generation of
reports from data and measurements obtained from the
connection between Eros and its clients; they are presented
as a web page or as a Microsoft Excel report. Specifically
for this system, reports related with the generation, loads in
the output circuits, energies, and the reserves are configured
using 1-hour intervals and configured as Excel outputs.
On the other hand, the need of monitoring the electrical
Figure 4. Data gathering in the Hyundai and Man groups system parameters from the corporate network are based
Adquisición de datos de los grupos Hyundai y Man on a web client. Normally, the proprietary solutions inte-
V. Sistema de reportes y cliente web grate web servers and only a web browser is required. Once
El Sistema de Reportes Eros [SREros] permite generar repor-
SCADA is in execution mode, it is possible to visualize the
tes a partir de datos y mediciones obtenidas mediante la cone- desired synoptics through this interface. In the Eros parti-
xión al Eros como su cliente y son presentados en formato de cular case, this is not directly available; however, dynamic
página web o de MSExcel. Específicamente para este sistema, web pages can be created via EROSNet for this purpose.
se configuran reportes relacionados con la generación, las car- EROSNet is a COM server presented as Dynamic Link
gas de los circuitos de salida, las energías y la reserva rodante, Library [DLL]. In general, this library exports the basic
con intervalos de una hora, los cuales se presentan en formato functionalities of Eros throughout the interaction with other
MSExcel.
systems supporting the COM technology. The applications
Por otra parte, la necesidad de monitorización de los pará-
based on EROSNet are the ones following the client-ser-
metros del sistema eléctrico desde la red corporativa se basa
ver paradigm, where Eros is the server and the client is the
en un cliente web. Normalmente, las soluciones propietarias
application developed by the user. Hence, only the creation
integran servidores web y solo se necesita de un navegador;
una vez que el SCADA esté en modo de ejecución, es posible of instances of the EROSClient class is required to deploy
visualizar los sinópticos deseados a través de esta interfaz. En el a client(Rodríguez-Hidalgo, 2010).
caso particular del Eros, esta herramienta no está directamen- The client coding to acquire the variables included in the
te disponible, sin embargo, mediante la EROSNet se pueden SCADA is developed employing the JavaScript language
crear páginas web dinámicas con este propósito. by using two fundamental methods: the first one is associa-
La EROSNet es un servidor COM presentado como una bi- ted with the connection with Eros; the second one returns
blioteca de enlace dinámico [Dynamic-Link Library, DLL]. En

65
Samada, S., Martínez, A. & Pozo, O. (2018).

the variables directly as a character string. From the design general, esta biblioteca exporta las funcionalidades básicas del
point of view, the graphical interface is coded by using the Eros a través de la interacción con otros sistemas que soportan
Bootstrap front-end framework. This set of open code tools la tecnología COM. Las aplicaciones basadas en la EROSNet
is compatible with most of the web browsers, it has design son del tipo de arquitectura cliente-servidor, en la que se puede
templates based on HTML and CSS and optional JavaS- discernir como servidor al Eros y como cliente a la aplicación
que desarrolla el usuario. Por tanto, para desplegar un cliente
cript extensions. Other features are related with the fact
solo se precisa crear instancias de la clase EROSClient (Rodrí-
that the Bootstrap applications are responsive or adaptable;
guez-Hidalgo, 2010).
i.e., the pages are dynamically adapted according to the fea-
La codificación del cliente para adquirir las variables inclui-
tures of the employed device.
das en el SCADA se desarrolla empleando el lenguaje JavaS-
The representation of the system relevant information cript; se utilizan dos métodos fundamentales: el primero está
in the client is performed via tables by using the DataTa- asociado con la conexión con el Eros; el segundo devuelve las
bles component of the JQuery library in JavaScript. Da- variables, directamente, como una cadena de caracteres. Des-
taTables provides controls and advanced interactions with de el punto de vista de diseño, la interfaz gráfica se codifica
HTML tables such as searching filters and paging elements utilizando el framework front-end Bootstrap. Este conjunto de
(“JQuery…”, 2015). herramientas de código abierto es compatible con la mayoría
de los navegadores, contiene plantillas de diseño basadas en
VI. Results and Discussion HTML [Hyper Text Markup Language] y CSS [Cascading
The data gathering system validation was performed using Style Sheets], y extensiones de JavaScript opcionales adiciona-
the ModbusPoll tool and the OPC client integrated in Eros. les. Otra de sus características destacadas es que las aplicacio-
nes con Bootstrap son responsivas o adaptables, es decir que
We performed three real tests with the sampling times de-
las páginas se ajustan de manera dinámica de acuerdo con las
fining the functional and operational requirements of the
características del dispositivo utilizado.
SCADA: 250 ms for variables related with the generation
La representación de la información relevante del sistema en
and 1,000 ms for the remaining ones.
el cliente se realiza en forma de tablas, para lo que se maneja el
The first test assessed the Modbus TCP link with the Dap complemento DataTables de la librería JQuery de JavaScript.
server. As pointed before, this controller congregates the DataTables proporciona controles e interacciones avanzadas
substation variables through the IEC61850 standard. The con tablas en formato HTML, como por ejemplo: filtros de
direct connection with the device is achieved after configu- búsqueda y elementos de paginación (“JQuery…”, 2015).
ring the IP address, the identifier, and the port —by default, VI. Resultados y discusión
Modbus TCP uses the port 502—. The addressed variables La validación del sistema de adquisición de datos se realizó uti-
are input registers [function 04] and discrete output regis- lizando la herramienta ModbusPoll y el cliente OPC integrado
ters [function 02]. en el Eros. Se realizaron tres pruebas reales con los tiempos de
Figure 5 shows the satisfactory reading of the selected muestreo que definen los requisitos funcionales y de operación
del SCADA: 250 ms para las variables relacionadas con la ge-
variables. Several polls are performed [TX] providing re-
neración y 1000 ms para las restantes.
sults without error [Err]. The variables corresponding to
La primera prueba evaluó el enlace Modbus TCP con el
discrete inputs represent states in a switch of the substation,
servidor Dap. Como se señaló, este controlador concentra las
whilst the input registers —the floating type ones— are the
variables de la subestación a través de la norma IEC 61850.
measurements of a switching cell. Finally, the part of the La conexión directa con el dispositivo se logra luego de confi-
frame reading is illustrated. gurar la dirección IP, el identificador y el puerto –por defecto
The second experiment assessed the communication with Modbus TCP emplea el 502–. Las variables que se direccionan
the AGC controllers, specifically the one operating the Mtu1 son registros de entrada [Función 04] y registros de entrada
group. The test was performed similarly to the previous case, discreta [Función 02].
the only difference is that now the link is serial Modbus. In or- La Figura 5 muestra satisfactoriamente la lectura de las varia-
der to establish connection, we defined the serial port to use, bles seleccionadas. Se realizan varias encuestas [TX] que arro-
the speed and transmission mode, the datum length, parity, jan resultados sin errores [Err]. Las variables que corresponden
a entradas discretas representan estados de un interruptor de la
and the stop bit. The addressed variables are the input and
subestación, mientras que los registros de entrada, del tipo flo-
discrete input registers; the first ones are measurements of the
tante, constituyen las mediciones de una celda de conmutación.
generator electrical parameters, whilst the discrete input one
Finalmente se ilustra parte de la trama de la lectura.
is a 16-bit register, where each bit represents an alarm trigge-
El segundo experimento evalúa la comunicación con los
red to protect the generator in case of a short circuit. If none controladores AGC, específicamente el que opera en el grupo
alarm is triggered, the register value is zero. Figure 6 presents “Mtu1”. La prueba se efectuó de la misma forma, solo que en
the successful connection and a fraction of the frame. este caso el enlace es Modbus Serie. Para lograr la conexión se

66 http://www.icesi.edu.co/revistas/index.php/sistemas_telematica
Web Client and SCADA Applications for Monitoring the “Cayo Santa María” Isolated Electric System, Sistemas & Telemática, 16(47), 59-70.

Figure 6. Measurements of discrete input and output registers as-


sociated to the AGC controller / Lecturas de registros de entrada
Figure 5. Measurements of input and discrete input registers y entrada discreta asociados al controlador AGC
associated to the Dap server / Lecturas de registros de entrada y
entrada discreta asociados al servidor Dap
The third experiment [Figure 7] visualizes the communi-
definen: el puerto serie a emplear; la velocidad y el modo de cation with the Hyundai engine-generators through OPC.
transmisión; la longitud del dato; la paridad; y el bit de para- The link is performed after enabling and defining the au-
da. Las variables direccionadas son los registros de entrada y thentication and security levels for both the DCOM and OP-
entrada discreta, los registros de entrada constituyen medicio- Cenum.exe. The test shows a representative number of total
nes de los parámetros eléctricos del generador, mientras el de variables handled —in this case, Boolean variables— symbo-
entrada discreta constituye un registro de 16 bit, donde cada lizing the stop/operation states of these engine-generators.
bit representa una alarma por disparo de una protección al
From the user interface point of view, the operator in-
generador. Al no existir en este instante ninguna activa, el va-
lor del registro es cero. La Figura 6 exhibe de forma exitosa la teracts with 4 main synoptics from a total of 29 confor-
conexión y una sección de la trama. ming the supervisor. The so-called begin is precisely where
El tercer experimento [Figura 7] visualiza la comunicación the application starts after the register data are introduced
con los grupos Hyundai a través de OPC. El enlace es realizado [login]. This interface has the general or total system me-
luego de habilitar y definir los niveles de autenticación y se- asurements and the synoptic called generation allows the
guridad, tanto para el DCOM, como para OPCenum.exe. La operator to supervise the state of every group and access
prueba muestra un número representativo de las variables tota- to specific parameters of each one of them. The synoptic
les que se manejan, en este caso, variables booleanas, que sim- substation is conformed with the variables of each swit-
bolizan los estados de parada/funcionamiento de estos grupos. ching cell and the input and energy distribution circuits.
Desde el punto de vista de interfaces de usuario, el operador Lastly, the interface related with the energetic consumption
interactúa con cuatro sinópticos principales, de un total de 29 calculates the possible losses from the exported and billed
que conforman el supervisor. El denominado Inicio es precisa- energies. The SCADA also includes synoptics associated
mente donde la aplicación comienza, una vez introducido los
with the handling of alarms and trend graphs with histo-
datos de registro [login]. Esta interfaz contiene las mediciones
rical data for posterior analysis. In Figure 8, the interface
generales o totales del sistema. El sinóptico Generación le per-
associated with the generation is displayed, whilst Figure 9
mite al operador supervisar el estado de todos los grupos, así
como la acceder a los parámetros específicos de cada uno. El shows a section of the web client.
sinóptico Subestación, por su parte, está conformado con las
variables de cada celda de conmutación, así como los circuitos
de entrada y distribución de la energía. Por último, la inter-

Figure 7. Registers reading of the Hyundai groups through OPC Figure 8. Interface related with the generation
Lecturas de registros de los grupos Hyundai a través de OPC Interfaz relacionada con la generación

67
Samada, S., Martínez, A. & Pozo, O. (2018).

faz relacionada con el consumo energético calcula las posibles


pérdidas a partir de las energías exportadas y facturadas. El
SCADA además incluye sinópticos asociados con el tratamien-
to de alarmas y gráficas de tendencia, con salva en históricos,
para análisis posteriores. En la Figura 8 se visualiza la interfaz
relacionada con la generación, y en la Figura 9 se muestra una
sección del cliente web.
VII. Conclusiones
La implementación del sistema SCADA satisfizo los requisitos
funcionales y de operación preestablecidos en su concepción.
La puesta en marcha, desde 2015, ha contribuido a perfeccio-
nar la operación del sistema eléctrico.
El diseño de la red propició de forma exitosa la interco-
Figure 9. Hyundai section of the web client nexión de todos los objetivos a nivel físico; la creación de las
Sección Hyundai del cliente web subredes virtuales hizo posible aislar la red tecnológica de la
corporativa, aportando con ello mayor seguridad.
VII. Conclusions La ejecución del proyecto constituyó una solución econó-
The implementation of the SCADA system complied the micamente factible debido a que resolvió la problemática vin-
culada a la adquisición de un software de alta complejidad y
functional and operational requirements preestablished in
valor. La utilización del Eros permitió integrar la diversidad
its conception. The initial launch —started in 2015— has
de tecnologías y equipos existentes, sin la necesidad de apostar
contributed to polish the operation of the electrical system.
por otras plataformas de mayores prestaciones y mayor costo.
The network design entailed in a successful interconnec- La codificación del cliente web favoreció la monitorización
tion of all the objectives at a physical level; the creation of del sistema desde la red corporativa, teniendo acceso a toda la
virtual subnetworks made possible to isolate the technolo- información incluida en el supervisor.
gical network from the corporate, increasing the security. La aplicación, en general, garantiza elevada flexibilidad ha-
The project execution was an economically viable solution cia posibles modificaciones y proyectos futuros, como son la in-
due to the fact that it solved the problem associated to the tegración de nuevos grupos Mtu y las mediciones relacionadas
con el control de combustibles.
purchasing of a high complexity and value software. The use
of Eros allowed us to integrate several technologies and equi-
pment currently in use without the need of betting to other
platforms with higher features but also higher associated cost.
The coding of the web client helped in the system moni-
toring from the corporate network by easing the access to
all the information included in the supervisor.
The application —in general terms— guarantees high
flexibility towards future modifications for other projects
such as the integration of new Mtu groups and measure-
ments related with the fuel control.

68 http://www.icesi.edu.co/revistas/index.php/sistemas_telematica
Web Client and SCADA Applications for Monitoring the “Cayo Santa María” Isolated Electric System, Sistemas & Telemática, 16(47), 59-70.

References / Referencias
Alstom.(2013). DAPServer multifunction platform [technical specification]. Paris, France: Alstom.
DEIF. (2008). Designers reference handbook: Automatic gen-set controller multi-line2. Retrieved from: http://www.deif.com
Elices, A. & Rouco, L. (2001). Análisis fundamental del impacto de la reserva primaria en sistemas eléctricos aislados. In:
7as Jornadas Hispano-Lusas de Ingeniería Eléctrica, (Vol. 2, pp. 335-340). Available at: http://www.mat.ucm.es/~aelices/
conferences/Elices_2000_Analisis_fundamental_Impacto_Reserva_Primaria_Sistemas_Electricos_aislados.pdf
Fernández, F. H. & Duarte, J. E. (2015). Automatismo para el monitoreo y control de un grupo electrógeno con arranque eléc-
trico. Entramado, 11(2), 262-271. http://dx.doi.org/10.18041/entramado.2015v11n2.22241
Guamán, J., Vargas, C., Nogales, R., Guevara, D., García, M., & Ríos, A. (2016). Solar manager: plataforma cloud de adqui-
sición, tratamiento y visualización de información de sistemas fotovoltaicos aislados. Ingenius, 15, 5-16. doi:10.17163/
ings.n15.2016.01
JQueryDataTables. (2015). Retrieved from: https://www.jquery.com.
Lanas, F. (2011). Planeamiento de optimización del sistema de coordinación Ge-Vi [thesis]. Universidad de Chile: Santiago
de Chile.
Manassero, U., Torres, J. L., López, D., Furlani, R., Regalini, R., & Orué, M. (2011). Instrumentación, control y telesupervisión
de centrales térmicas de pequeña potencia. Iberoamerican Journal of Industrial Engineering, 3(2), 70-86.
Moxa. (2010). NPort 5600 Series: User’s Manual. Retrieved from: http://www.moxa.com/product
Padrón-Ramos, J. O. (2011). Diseño de sistema SCADA para la supervisión de grandes consumidores de energía eléctrica.
[thesis]. Universidad Central “Marta Abreu” de Las Villas: Santa Clara, Cuba.
Rodríguez-Hidalgo, R. (2010). Especificación del Servidor COM EROSNet para la comunicación con el SCADA EROS. Holguín,
Cuba.
Rodríguez-Penin, A. (2013). Sistemas SCADA [3ª ed.]. Ciudad de México: Alfaomega-Marcombo.
Silupú, I. (2016). Diseño de un sistema SCADA usando Wonderware System Platform para el monitoreo del interconectado
eléctrico del Lote 1AB de Pluspetrol Norte S.A. [thesis]. Universidad Nacional Pedro Ruiz Gallo: Lima, Perú.
Villegas, A. (2015). Diseño e implementación de un sistema de adquisición de datos y monitoreo de los generadores de un
simulador experimental de laboratorio [thesis]. Instituto Politécnico Nacional (IPN): Ciudad de México.
Weber, P. A. (2011). Diseño e implementación de plataforma SCADA para sistema de electrificación sustentable en la locali-
dad de Huatacondo [thesis]- Universidad de Chile: Santiago de Chile.

69
Samada, S., Martínez, A. & Pozo, O. (2018).

CURRICULUM VITAE
Sergio Emil Samada Rigó Automation Engineer from the Universidad Central “Marta Abreu” de Las Villas
[UCLV] (Santa Clara- Cuba, 2012) institution where he currently studies the Master in Automation and Infor-
matics Systems and develops his research works focused on the automation of electrical substations and engine
generators. He participated in the installation and initial launching of the ALSPA P320 system of Alstom in the
“Antonio Guiteras” thermoelectric in Cuba and he supervised the factory acceptance tests of engine generators
and MTU technology with the PACiS system of Schneider Electric in China / Ingeniero en Automática de la Uni-
versidad Central “Marta Abreu” de Las Villas [UCLV] (Santa Clara, Cuba – 2012) entidad donde actualmente
cursa la Maestría en Automática y Sistemas Informáticos y desarrolla trabajos vinculados a la ejecución de pro-
yectos de automatización de subestaciones eléctricas y grupos electrógenos. Participó en la instalación y puesta
en servicio del sistema ALSPA P320 de Alstom en la Termoeléctrica “Antonio Guiteras” [Cuba] y supervisó las
pruebas de aceptación de fábrica [Factory Acceptance Test, FAT] de grupos electrógenos, tecnología MTU, con el
sistema PACiS de Schneider Electric en la República Popular de China.

Alain Sebastián Martínez Laguardia Ingeniero en Automática (2001) y Máster en Telemática (2005) de
la Universidad Central “Marta Abreu” de Las Villas [UCLV] (Santa Clara, Cuba), con un doctorado conjunto en
Ingeniería de la Université Libre de Bruxelles (Bélgica) y la UCLV (2015). Desde 2001 es miembro del Departa-
mento dé Automática y Sistemas Computacionales de la UCLV, donde actualmente es profesor titular e imparte
docencia en varios campos de la computación-programación. Desde 2003 es miembro fundador del Grupo de
Automatización, Robótica y Percepción, donde investiga acerca del diseño de sistemas empotrados y el desa-
rrollo y aplicación de vehículos autónomos. Ha participado en varios proyectos de investigación internacionales
y cuenta con más de una decena de publicaciones científicas asociadas a los temas de la automatización /
Automation Engineer (2001) and Master in Telematics (2005) from the Universidad Central “Marta Abreu” de
Las Villas [UCLV], (Santa Clara, Cuba), with a PhD in Engineering from both, the Université Libre de Bruxelles
(Bélgica) and the UCLV (2015). Since 2001, he is a member of the Automation and Computational Systems
Department of the UCLV, where he is a full time professor of several programming fields. Since 2003, he is a
founding member of the Sensing, Robotics and Automation Group, where he performs researches about the de-
sign of embedded systems and autonomous vehicles. He has participated in international research projects and
he has over a dozen of scientific publications related with automation topics.

Osniel Pozo Mederos Telecommunications and Electronics Engineer of the Universidad Central “Marta Abreu”
de Las Villas [UCLV] (Santa Clara, Cuba – 2008); he currently studies the Master in Business Administration in
the Postgraduate School of the Universidad Tecnológica del Perú [UTP] (San Isidro). He has developed research
works focused on the execution of telecommunications and automation projects of electrical substations and engine
generators. From 2016, he is a member of the Electronics Academic Department at the UTP, where he is a full time
professor in several fields of electronics / Ingeniero en Telecomunicaciones y Electrónica en la Universidad Central
“Marta Abreu” de Las Villas [UCLV] (Santa Clara, Cuba – 2008); actualmente cursa la Maestría en Administración
de Empresas en la Escuela de Postgrado de la Universidad Tecnológica del Perú [UTP] (San Isidro). Ha desarro-
llado trabajos vinculados a la ejecución de proyectos de telecomunicaciones y automatización de subestaciones
eléctricas y grupos electrógenos. Desde 2016 es miembro del Departamento Académico de Electrónica de la UTP,
donde es profesor a tiempo completo en varios campos de la electrónica.