Professional Documents
Culture Documents
This article will analyse some of the most important safety issues related to
design and use of LV electrical installations. Besides explanation of relevant
terms in this field defined by IEC standards, some misinterpretations and
confusions which may be seen in practice will be illustrated and clarified.
When can we say that earthing arrangement is safe for people? (on photo:
An old earthing bar in LV switchgear; photo credit: Richard Cadena)
Table of contents:
1. Introduction and basic terms
1. Lightning strike
2. Electric arc
3. Direct contact
4. Indirect contact
2. Earthing arrangements and efficiency of protection
1. TN earthing arrangement
2. TT earthing arrangement
3. IT earthing arrangement
3. Additional comments and FAQs
Safety risk: If galvanic connection (short circuit) between live part and
exposed conductive part is established because of a fault, electric shock
may be caused by increased voltage which is a consequence of potential
difference between faulty conductive part and earth. In the case of LV
networks, usually touch voltage is critical.
See Figure 1.
Figure 1 – Illustration
of TN earthing arrangement
If protective conductor has, in the same time, the role of neutral conductor,
designation TN-C shall be used (four wire system), while if protective and
neutral functions are separated, designation TNS shall be used (five wire
system). Both systems may be used together within power supply system
from the same source, TN-C system up to the one point, and TN-S system
downstream of that point.
This practically means that, for the purpose of protection efficiency checking,
no real touch voltage calculation is necessary, which significantly simplifies a
method for efficiency checking.
(Equation 1)
where:
Ia is the value of current which will cause overcurrent protective device
to trip within time specified in Table 1,
U0 is rated voltage to earth, and
Zs is fault loop impedance.
For example, in the case of 3×400/230 LV network, 230/Zs ratio shall be
greater or equal to the current which will cause protective device to trip
within 0.4 s.
See Figure 2.
Figure 2 – Illustration
of TT earthing arrangement
Fault loop is consisting of phase conductors from the source up to the point
of fault, and protective conductors together with earthing resistance from the
point of fault back to transformer’s neutral. Fault loop impedance is not so
low as in the case of TN system, because earthing resistance of
underground electrodes is also part of this impedance.
(Equation 2)
where:
Ia is the value of current which will cause overcurrent protective device
to trip, and
RA is the sum of protective conductors and earthing resistance
connected to faulty exposed conductive part.
If RCD is used as protective device , rated sensitivity current ∆I n shall be
used for efficiency checking in Equation 2.
In other words, protective device shall disconnect a circuit in such a way that
current flowing through protective conductors and earthing electrodes does
not cause a potential difference between exposed conductive part and
reference earth greater than 50V, which is the upper limit for safe AC
voltage.
See Figure 3.
Figure 3 – Illustration
of IT earthing arrangement
Fault loop is consisting of phase conductors from the source up to the point
of fault, and parasitic capacities between phase conductors and earth. Since
these capacities are very low, fault loop impedances are high, and fault
currents are also very low, significantly lower than working currents.
However, voltage of two phase conductors not affected by the fault are
higher than nominal during that period, which may increase the possibility for
insulation breakdown and dangerous direct contact.
FAQ № 2
Since earthing connections inside TN arrangement are
also common, how can we distinguish TN from TT system
for sure?
Answer: Inside TN arrangement, return path of fault current, from the point
of fault back to the system’s neutral, is consisted of galvanic connections
(conductors) exclusively.
So, if exposed conductive parts are connected with neutral point via earthing
electrodes galvanically, we are actually talking about TN system. This would
be the common case, for example, in large facilities where several rooms or
even buildings share the same earthing mesh.
However, if fault current flows through the earth even partially, we are talking
about TT arrangement.
For example, if 16A rated MCB shall trip in the case of fault, and we assume
that at least 20A will cause a certain trip, earthing resistance shall be lower
or equal than 50/20= 2.5 Ω. On the other side, if RCD with sensitivity
current of 30mA is used, the same earthing resistance shall be lower or
equal than 50/0.03= 1667 Ω, which is much less demanding requirement.
So, the use of RCD is not mandatory in the case of TT system. However,
requirement for efficiency of protection against indirect contact will be much
easier to fulfil if RCD is used.
Even if this requirement can be achieved without the use of RCD at the moment of
installation start up, it may still be a good idea to use it, because earthing resistance may
More about understanding of earth (ground) resistance testing you can learn
below: