Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: In this paper, a novel beam-to-column steel moment connection, named “double reduced beam section (DRBS)”
Received 18 April 2017 is introduced and the seismic performance of the connection is assessed using finite element modeling. The
Received in revised form 10 July 2017 connection is composed of double dog bone sections close to the column face to widen the plastic hinge region;
Accepted 18 July 2017
consequently, reducing the resultant equivalent plastic strain. The region between the two reduced beam sec-
Available online 28 July 2017
tions is laterally connected to the slab to protect the plastic hinge from lateral torsional buckling. A parametric
Keywords:
study was conducted on the influence of cut parameters on the connection's seismic behavior. The results
Steel moment connections showed that, following the limitations and guidelines stated in this research, the DRBS connection exhibits
Reduced beam section outstanding hysteresis behavior. The deformation capacity of the connection was increased up to 40% in the
Seismic DRBS connection, compared to the common reduced beam section (RBS) connection. Plasticization of both
Hysteresis behavior reduced beam sections postponed the failure buckling modes, resulting in 50 to 75% increase in the absorbed
Finite element analysis seismic energy before buckling, compared to the traditional RBS connection. Moreover, adding a second cut to
the ordinary RBS connection distributed the strains over the two reduced sections, leading to 35 to 60% reduction
in the equivalent plastic strain at the reduced sections, at 6% inter-story drift.
© 2017 Elsevier Ltd. All rights reserved.
1. Introduction been the subject of experimental and theoretical studies [23]. Among
all these suggestions, the radius cut for reducing the beam flanges has
Extensive brittle damage at the beam-to-column flange groove shown a better seismic performance [24,25] and is known as the re-
welds in numerous steel moment resisting frames were observed duced beam section (RBS) connection. Guidelines for the design of
during the 1994 Northridge and 1995 Kobe earthquakes [1,2]. Conse- RBS connection are given in FEMA-350 [26] and also AISC-358 [27].
quently, for improving the seismic performance of the “pre-Northridge” The common failure modes of RBS connection are the web local buck-
steel connections, new strategies, such as changing the weld access hole ling (WLB), flange local buckling (FLB) and lateral-torsional buckling
(WAH) geometry [3,4], strengthening the beam at the column face by (LTB) of the beam. Testing of 55 full-scale specimens showed that the
adding a haunch [5], using side plates [6–8], utilizing external T- strength degradation of the RBS connection is dominantly due to the
stiffeners [9–11], using vertical and inclined rib plates [12,13] and weak- beam WLB and the slenderness ratio for LTB has a weak influence on
ening the beam section at a proper distance from the column face were the connection's response parameters [28]. However, an experimental
proposed and evaluated under cyclic loadings. Providing structural research by Chi and Uang [29] showed although the beam WLB is still
shear [14] and flexural fuses utilizing welded and bolted splice plates the dominant failure mode, deep columns in the RBS connection are
[15,16], trimming the beam flanges [17], reducing the beam web prone to LTB because of the concentric forces imposed from the beam
[18,19] and reducing both the beam flanges and the web simultaneously as a result of LTB of the beam. Later experiments in 2005 showed that
[20] are among different techniques used with the objective of weaken- controlling the beam LTB reduces both post-earthquake damage and
ing the beam section. Moreover, in a recent study [21], design recom- the tendency for beam flanges to fracture [30].
mendations for a new energy dissipation system, containing three In this research, a new cut profile consisting of two adjacent radius
different types of flexural fuses is provided. By using flexural fuses cuts in the beam flanges is proposed with the aim of postponing the
in such frames, the post-earthquake repair is merely limited to the WLB, FLB and LTB of the beam, leading to more ductile behavior, higher
replacement of the beams with reduced sections. energy absorption, and less post-earthquake damage to the connection.
The concept of reducing the beam flanges was first introduced and The seismic moment resisting steel connection is named double
implemented by a trapezoidal cut profile in the beam flanges by Plumier reduced beam section or DRBS in short. A comparison between the
in 1990 [22]. After that, various configurations for the cut profile have traditional RBS and the proposed DRBS connections has been made
using verified nonlinear finite element models. Based on the numerical
study results, the performance of DRBS connection is assessed. Details
⁎ Corresponding author. of the finite element analyses and a design procedure assuring the
E-mail address: dolatshahi@sharif.edu (K.M. Dolatshahi). balanced plasticization of both reduced sections are presented.
http://dx.doi.org/10.1016/j.jcsr.2017.07.013
0143-974X/© 2017 Elsevier Ltd. All rights reserved.
284 M.A. Morshedi et al. / Journal of Constructional Steel Research 138 (2017) 283–297
2. Methodology
Nomenclature
were set to the values that satisfy the strong column-weak beam limita- for the value of the reduction in beam flanges in the second cut (C2),
tion according to the AISC seismic provisions [31]. The details of which had no upper extreme. The details of the shear plate and WAH
modeled connections are summarized in Table 1. geometry also followed the AISC-358 guidelines for the RBS moment
The beam section in each of the aforementioned subassemblies was connection. According to this code, the WAH geometry shall conform
reduced at two sections with various cut parameters. Both cut profiles to the requirements of both the AISC specification [32] and American
satisfied the AISC-358 [27] limitations for the RBS connection except Welding Society's [33] limitations. Thickness of the continuity plate
was set equal to the beam flange thickness. The details of the connection
of IPE500 beam to BOX330 × 25 (connection C) is shown in Fig. 3 as a
Table 1 sample.
Modeled subassemblies (units in mm). Connections A, B and C of Table 1 with different values of parameters
Connection Column Beam Hbeam bbf tw tf Lb (half C1, b and d were modeled and the optimum value of C2 that guarantees
section section span) the balanced formation of the plastic hinge at both reduced sections of
A BOX 300 × 15 IPE330 330 160 7.5 11.5 2500 the beam was determined through finite element analysis as described
B BOX 330 × 15 IPE400 400 180 8.6 13.5 2500 in the following section. The influence of parameters C1, b and the exis-
C BOX 330 × 25 IPE500 500 200 10.2 16 3600 tence of the auxiliary lateral bracing between the two reduced sections
on the connections having the optimum value of C2 is also evaluated and
reported.
3. Numerical study
15
10
5
Drift (%)
-5
-10
-15
0 5 10 15 20 25 30 35 40 45
Number of cycles
Fig. 3. WAH geometry and a sample cut profile of connection C (units in mm). Fig. 4. Loading protocol [26,31].
286 M.A. Morshedi et al. / Journal of Constructional Steel Research 138 (2017) 283–297
Table 2
Nominal and tensile coupon test results of beam flange steel [35].
240 MPa 252 MPa 360 MPa 399.6 Mpa 30.8 210 GPa 0.3
Fig. 6. The DC-S specimen tested by Nia et al. [35] (units in mm).
M.A. Morshedi et al. / Journal of Constructional Steel Research 138 (2017) 283–297 287
200
100
Load (kN)
0
-100
Test
ABAQUS
-200
-8 -4 0 4 8
Drift (%)
model was ST-37-2 with the nominal and the coupon test results, The combined hardening parameters of the materials were deter-
shown in Table 2. mined based on the coupon test results performed by Lee et al. [30]
Hysteresis responses are compared between the finite element on SS400 and SM490 steels as shown in Table 3.
model and the test results [35] in Fig. 7(a). Fig. 7(b) shows the local The normalized moment-rotation hysteresis responses of the
buckling of the beam flanges at 6% inter-story drift in the tested speci- modeled connection and the tested specimen are compared in
men. The PEEQ index and the local buckling of the beam flanges of the Fig. 9(a). The moment was calculated at the reduced beam section and
modeled specimen at 6% inter-story drift ratio are also shown in normalized by the plastic moment of the reduced beam based on the
Fig. 7(c) and (d), respectively. As can be seen in these figures, the results
of finite element analysis and the test data are in a very good agreement.
Table 3
Dimensions and tensile coupon test results of specimen DB700-SW [30].
M/Mpn
0
-1
Test
ABAQUS
-2
-8 -4 0 4 8
Drift (%)
(c) PEEQ index at 6% drift (d) local buckling of the beam at 6% drift
Fig. 9. Comparison of the FE model and test results of specimen DB700-SW tested by Lee et al. [30].
measured yield strength. The local behavior of the beam in the tested reduction of the beam flanges in the second reduced section was in-
specimen [30] is shown in Fig. 9(b). The equivalent plastic strain creased gradually till the location of plastic hinge shifted from the first
(PEEQ) and the local buckling of the beam web and flanges of the to the second reduced section. Since the moment in the second reduced
modeled assembly are also shown at 6% inter-story drift ratio in section, which is farther from the column face, is less than the first re-
Fig. 9(c) and (d). According to Fig. 9, there is a very good agreement be- duced section, the initial value of parameter C2 was assumed to be
tween the FE analysis results and the test data. The FE model accurately equal to C1. As expected, the results showed that there was an optimum
predicted significant yielding of the beam web, the plastic hinge forma- state behavior, standing between the two limit states of Fig. 2 for the
tion and the strength degradation of the RBS connection due to the DRBS connection. The proper distribution of deformations between
beam FLB. the two reduced sections due to the stress redistribution mechanism
in the optimum state, led to a balanced yielding and plasticization of
4. Parametric study results both reduced sections from the early to the last cycles of loading. The
yielding of the beam initiated from the beam flanges at the center of
In the conducted numerical study, different values were considered both reduced sections and propagated to the beam web at these sec-
for C1 and b for each of the modeled subassemblies of Table 1. The tions and beam flanges near the column face. During the last cycles,
plastic strain increased at the center of both reduced sections, leading
Table 4
to a balanced plasticization of these sections. Further increase of plastic
Optimum range of parameter C2. strains led to the WLB accompanied by FLB at the centerline of both re-
duced sections resulting in the strength degradation of the connection.
Connection C1 b C2
The optimum value of parameter C2 was determined for the connec-
Exact value Optimum range tions A, B and C of Table 1. The considered values for C1, b and a summary
A1 0.2 0.85 0.260 0.255–0.265 of C2 optimum values are shown in Table 4.
A2 0.225 0.65 0.270 0.265–0.275 From here on, the connections are referred to with the designations
A3 0.225 0.85 0.275 0.270–0.280 of Table 4. Note that the values presented for parameters C1, C2 and b are
A4 0.25 0.65 0.285 0.280–0.290
A5 0.25 0.85 0.290 0.285–0.295
dimensionless and are normalized with respect to the beam flange
B1 0.205 0.85 0.270 0.265–0.275 width (bbf) for C1 and C2, and beam section height (Hbeam) for parameter
B2 0.225 0.65 0.275 0.270–0.280 b. The normalization approach of these parameters is similar to that of
B3 0.225 0.85 0.2825 0.2775–0.2875 AISC 358-16 [26], as shown in Fig. 1.
B4 0.25 0.65 0.290 0.285–0.295
Fig. 10 displays the described limit states and the location of the
B5 0.25 0.85 0.290 0.285–0.295
C1 0.197 0.85 0.265 0.260–0.270 plastic hinge in a subassembly of connection A3, B3 and C3 of Table 4
C2 0.225 0.65 0.275 0.270–0.280 as a few samples. From Fig. 10, choosing C2 according to Table 4 led to
C3 0.225 0.85 0.280 0.275–0.285 the optimum behavior of the connection and selecting values less than
C4 0.25 0.65 0.290 0.285–0.295 0.225 and more than 0.35 for parameter C2 resulted in a behavior similar
C5 0.25 0.85 0.290 0.285–0.295
to the limit states 1 and 2, respectively. Note that due to the selection of
M.A. Morshedi et al. / Journal of Constructional Steel Research 138 (2017) 283–297 289
Connection A3
C1 as the initial of C2, the limit state (I) did not practically take place and regardless of the beam section size; however, as the beam size increased
a localization of deformation in the first reduced section was observed in connections A to C, the DRBS connection exhibited an earlier strength
instead. degradation. This can be explained by the fact that the slenderness ratio
of the beam web (Hbeam/tw) is higher for deeper beam sections, resulting
4.1. Comparison of DRBS and RBS connections in an earlier buckling of deeper beam sections. Moreover, this trend also
held for single RBS connections for the same reasons and did not pertain
Fig. 11 compares the hysteresis behavior of RBS and DRBS configura- to any particular defect in the DRBS connection.
tion of connections A1, B1 and C1 of Table 4. Note that the point “A” Comparison between the distribution of plastic strain through the
marks the cycle of loading at which LWB and LFB took place and the beam section, the buckling modes and the cycle of buckling incidence
dashed lines depict the 20% drop in the peak strength. In most of the and the energy absorption capacity is also made in the following sections.
cases, using the DRBS connection instead of the traditional RBS connec-
tion postponed the connection's strength deterioration for 2% more of 4.1.1. PEEQ index
inter-story drift. The modeled DRBS connections with the optimum The main advantage of the DRBS over the RBS connection is the re-
value of C2 exhibited stable hysteresis behavior and did not experience duction of the equivalent plastic strain (PEEQ) due to the balanced dis-
strength degradation until 7% inter-story drift ratio. tribution of the deformations between the two reduced sections,
According to Fig. 11, changing the size of the beam had no consider- thereby delaying the beam local failure at the reduced sections. Fig. 12
able influence on the global and local response of the DRBS connection. compares the PEEQ index values between connection A1, B1 and C1
The balanced participation of both reduced sections was guaranteed, with one and two reduced sections at 6% inter-story drift ratio. Using
290 M.A. Morshedi et al. / Journal of Constructional Steel Research 138 (2017) 283–297
Load (kN)
Load (kN)
50 50 50
0 0 0
-50 -50 -50
-100 -100 -100
-150 WLB+FLB -150 -150
A WLB+FLB WLB+FLB
-200 -200 -200
-12 -6 0 6 12 -12 -6 0 6 12 -12 -6 0 6 12
Drift (%) Drift (%) Drift (%)
Load (kN)
50
Load (kN)
50 50
0 0 0
-50 -50 -50
-100 -100 -100
A
-150 -150 -150
WLB+FLB A WLB+FLB A WLB+FLB
-200 -200 -200
-12 -6 0 6 12 -12 -6 0 6 12 -12 -6 0 6 12
Drift (%) Drift (%) Drift (%)
the DRBS connection results in a considerable reduction in the maxi- of parameter C2 according to Table 4. The values and the percent of
mum PEEQ index of the connection, obviously. the reduction in the maximum PEEQ index are summarized in Table 5.
Fig. 13 also shows the maximum value of PEEQ index at the end of 1% From Fig. 13 and Table 5, the maximum value of the PEEQ index at the
to 6% drift ratios in connections A, B and C with one and two reduced reduced sections is reduced by 35–60% in the DRBS compared to the RBS
sections. The DRBS connections of this figure have the optimum value connection. The sudden increases in the PEEQ of RBS connections in the
Fig. 12. Equivalent plastic strain of connections A1, B1 and C1 at 6% drift ratio.
M.A. Morshedi et al. / Journal of Constructional Steel Research 138 (2017) 283–297 291
PEEQ index
PEEQ index
PEEQ index 1.5 A3-DRBS 1.5 B3-DRBS 1.5 C3-DRBS
A5-RBS B5-RBS C5-RBS
1 A5-DRBS 1 B5-DRBS 1 C5-DRBS
0 0 0
0 1 2 3 4 5 6 0 1 2 3 4 5 6 0 1 2 3 4 5 6
Drift (%) Drift (%) Drift (%)
graphs of Fig. 13 are due to the local buckling of the beam that was post- 30–40% in the DRBS connection, compared to RBS connection, according
poned as a result of the second cut in the DRBS connections. to Table 6.
The effect of adding the extra lateral bracing at the conjunction of the
4.1.2. Lateral torsional buckling reduced sections on the hysteresis behavior of connection A1 is present-
According to AISC-358, RBS connections that satisfy the normal lat- ed in Fig. 15 as a sample. As depicted, more stable hysteresis loops and
eral bracing requirements of AISC-341 [31] for beams in special moment delayed strength deterioration were observed in the connection A1
frame systems, can achieve inter-story drift angles of 0.04 rad. However, when the auxiliary lateral brace was provided.
adding a supplemental lateral brace at or just beyond the end of the RBS
that is farther from the column face (beyond the protected zone) 4.1.3. Energy absorption capacity
improves the performance of RBS connection [27]. In the modeled Cumulative energy dissipation before buckling of the beam web was
subassemblies, lateral bracing was provided by restraining the beam also compared between the connections of Table 4, having one and two
flanges against lateral movements at the end of both reduced sections, reduced sections. The cumulative absorbed seismic energy is presented
Such bracing is shown in Fig. 5. in Table 7. Participation of both reduced sections in energy absorption in
A comparison between buckling modes and the story drift at which addition to the delayed buckling modes, increased the dissipated seis-
WLB and FLB occurred has been made for connections A1, B1 and C1 of mic energy of the DRBS connection by 50 to 75% compared to RBS
Table 4 with one and two reduced sections in Fig. 14. In the RBS connec- connection.
tions of Fig. 14(a), the lateral bracing was provided at the end of the Results of Table 7 show that connections with higher and lower
reduced section, while two different states were considered for the values of b and a, respectively, have more energy absorption capacity.
location of the lateral braces in the DRBS connections: the beam flanges Fig. 16 also depicts the cumulative dissipated energy of connections A,
in the DRBS connections of Fig. 14(b) and (c), were laterally braced at B and C having: constant C1 and different values of b (part a) and con-
the end of only the second or both reduced sections, respectively. stant b = 0.85 and different values of C1 (part b). It is worth mentioning
Fig. 14(b) shows that the first considered state for lateral bracing of that since the optimum value of C2 is a function of parameters C1 and b,
the beam in the DRBS connection does not satisfactory control the all connections of Fig. 16 have the optimum value of C2. The objective of
lateral-torsional buckling of the beam. This is due to the large unbraced the figure is to propose the optimum value of C1 and b, in order to have
length of the beam flanges of connections A1, B1 and C1 with two re- the best performance in terms of energy dissipation and displacement
duced sections. Thus, the unbraced length of the flanges was reduced capacity.
in the second considered state by providing an auxiliary set of lateral According to Fig. 16(a), in the subassemblies with higher reduced
braces. According to Fig. 14(c), the failure mode that caused strength section length (b), plasticization of a wider region of the beam web
degradation of the DRBS connections with two sets of lateral braces and flanges, increases the DRBS connection energy dissipation capacity.
was the beam WLB near the center of both reduced sections. In most Thus, it is recommended to set b to the upper limit suggested by AISC-
of the models, this failure mode was accompanied by FLB. The buckling 358 [27], to achieve a higher energy absorption capacity. It is worth
mode was similar in the beams with one or two reduced sections; how- mentioning that, increasing b and the unbraced length of the beam
ever, as summarized in Table 6, due to lower amounts of plastic strain as flanges, as a result, does not negatively affect the performance of the
a result of strain redistribution in the DRBS connection, the beam web DRBS connections, due to the existence of the auxiliary lateral bracing.
buckling occurred at 2% more inter-story drift ratio compared to Fig. 16(b) shows that the DRBS connections, having lower values of
that of the RBS connection. The deformation capacity was increased C1, have higher energy absorption capacity. This can be explained by
comparing the hysteresis loops of connections A, B and C, having the
highest and lowest values of C1, shown in Fig. 17. According to Fig. 17,
Table 5 changing C1 has no considerable influence on the global and local re-
Reduction in the maximum PEEQ index at 6% inter-story drift ratio. sponse of the DRBS connection, except for the peak plastic moment.
Selecting lower values of C1, results in higher maximum plastic
Connection PEEQ index Reduction in the PEEQ index (%)
moments and a higher energy absorption capacity, consequently. More-
DRBS RBS over, lower values of C1 result in the optimum consumption of materials
A1 0.687 1.060 64.81 and less reduction in the stiffness of the connection. Thus, it is recom-
A3 0.762 1.800 42.33 mended to select the values of C1 close to the lower limit suggested by
A5 0.855 1.573 54.35
AISC-358 [27].
B1 0.690 1.571 43.92
B3 0.795 1.763 45.09
B5 0.985 1.889 52.14 5. Design procedure
C1 0.767 1.779 43.11
C3 0.769 2.193 35.07 Based on the results of the numerical study, a two-phase design pro-
C5 1.046 2.487 42.06
cedure is introduced for the design of DRBS connection. In the first and
292 M.A. Morshedi et al. / Journal of Constructional Steel Research 138 (2017) 283–297
(a) RBS
(b) DRBS with one lateral brace
(c) DRBS with two lateral braces
second phases of the design procedure, the parameters of the first and beam section and the plastic hinge location moves toward the second
second cuts are determined, respectively. The first design phase con- cut; thus, there is an optimum value for C2 to have the most desirable be-
forms to the AISC-358 design procedure for the RBS connection; however, havior. Although the most important parameter is C2, this parameter is a
based on the parametric study conducted in this research, in order to have multi-variable function of other parameters such as C1, b, gravity loads
the best performance for the DRBS connection, it is recommended to and span length, rather than being an explicit function of either of these
choose lower and higher values for parameters C1 and b, respectively. parameters. Hence, two dimensionless parameters Mf/Mpe and Mpr2/
As discussed, the most important parameter is the value of C2. Low values Mpr1 are introduced to account for all influential parameters, as follows:
of C2 have no considerable influence on the connection's hysteresis be-
havior. On the other hand, high values of C2 weaken the second reduced Z RBS1 ¼ Z beam −2 C 1 t bf Hbeam −t bf ð1Þ
Table 6
Mpr1 ¼ C pr Ry F y Z RBS1 ð2Þ
Drift ratio at which WLB occurs in the RBS and DRBS connections. 2
wSh
Connection Drift (%) Increased deformation capacity (%)
M f ¼ M pr1 þ V RBS1 Sh þ ð3Þ
2
RBS DRBS
150 150
75 75
Load (kN)
Load (kN)
0 0
-75 -75
WLB+FLB WLB+FLB
-150 -150
-12 -6 0 6 12 -12 -6 0 6 12
Drift (%) Drift (%)
(a) One lateral brace at the farthest end of the (b) Added auxiliary lateral brace at the conjuction
second RBS of reduced sections
Fig. 15. Effect of adding the auxiliary braces on the hysteresis response of connection A1.
Table 7 capacity of the beam, added for normalization so that the results can be
Cumulative energy dissipation before beam web buckling. expanded to all beam sections. Table 8 shows the average of the
Connection Dissipated energy (MJ) Variation (%) optimum ranges suggested for C2 in Table 4 and the resultant Mpr2/Mpr1.
RBS DRBS
A plot of Mpr2/Mpr1 versus Mf/Mpe for the connections of Table 8, is
depicted in Fig. 18 and a function with the least square sum has been
A1 219.7 376.1 71
introduced for the relation of the defined dimensionless parameters.
A2 181.2 315.2 74
A3 196.4 336.8 71 This function is stated through Eq. (5) as follows:
A4 179.1 303.8 70
A5 190.3 322.2 69 Mpr2 Mf
¼ −0:4312 þ 1:2949 ð5Þ
B1 272.6 452.6 66 Mpr1 M pe
B2 270.2 414.5 53
B3 268.8 439.3 63
B4 216.5 368.7 70
Eq. (5) is used in the determination of C2 in the second phase of the
B5 259.6 390.0 50 design procedure. The two phases of the design procedure are as follows:
C1 410.1 643.9 57 Phase (I): Determine C1:
C2 360.4 613.1 70
C3 356.4 614.5 72 Step 1: assume a trial value for parameter C1 close to the AISC-358
C4 318.2 556.5 75 lower limit.
C5 354.1 599.0 69
800 1000
b=0.65 C1=0.2
Dissipated energy (MJ)
Dissipated energy(MJ)
b=0.85 800
600 C1=0.225
600 C1=0.25
400
400
200
200
0 0
A2,A3 A4,A5 B2,B3 B4,B5 C2,C3 C4,C5 A1 A3 A5 B1 B3 B5 C1 C3 C5
Connection Connection
(a) Connections A, B and C with C1=0.225,0.25 (b) Connections A, B and C with b=0.85
Fig. 16. Effect of parameters (a) C1 (b) b on the cumulative energy dissipated before buckling.
75 100 100
Load (kN)
Load (kN)
Load (kN)
0 0 0
Table 8
Best cut parameters.
Step 2: compute the plastic section modulus of the first reduced section
using Eq. (1).
Step 3: calculate the probable maximum plastic moment at the first cut
through Eq. (2).
Step 4: calculate the shear at the first cut using Eq. (6). This equation is Fig. 19. Free body diagram of the beam with two reduced sections.
derived from the free-body diagram of the beam under factored
gravity loads, shown in Fig. 19, while two plastic hinges have
been formed in the first reduced sections of both beam ends. Phase 2: Determine C2:
The second phase is to determine the value of C2 based on the first
cut configuration through a three-step process:
2M pr1 wLh
V RBS1 ¼ þ ð6Þ Step 1: calculate the value of Mpr2 by substituting Mf/Mpe and Mpr1 into
Lh 2
Eq. (5).
Step 2: compute the value of ZRBS2 based on Eq. (8):
Step 5: calculate the resultant moment at the column face due to the
probable maximum plastic moment at the first cut through Mpr2 ¼ C pr Ry F y Z RBS2 ð8Þ
Eq. (3)
Step 6: check the flexural capacity of the non-reduced beam section to
carry the moment at the column face and repeat steps 1 to 6 till
Eq. (7) is satisfied: Step 3: calculate the value of C2 using Eq. (9):
Z beam −Z RBS2
Mf C2 ¼ ð9Þ
≤ φd ð7Þ 2t bf H beam −t bf
M pe
0.9 As Table 9 shows, Eq. (5) is quite accurate and the error in predicting
Mpr2/Mpr1 and C2, as a result, is negligible, therefore Eq. (9) used in
0.88 the second phase of the design procedure is reliable in predicting the
optimum values of C2.
FEM best result A new fourth connection, specimen DB600-MW tested by Lee et al.
0.86
Best fit
[30], with different material behavior and column section is also evalu-
ated to double check the accuracy of the developed procedure. The
0.84 beam and column dimensions and the considered cut parameters of
0.86 0.895 0.93 0.965 1 connection DB600-MW are summarized in Table 10. Since the material
Mf/Mpe behavior used for the beam and column is the same as DB700-SW
connection, discussed in the verification section, the same material
Fig. 18. Relation between Mf/Mpe and Mpr2/Mpr1 for connections with optimum value of parameters as of the second verification model are used in modeling
C2. DB600-MW connection.
M.A. Morshedi et al. / Journal of Constructional Steel Research 138 (2017) 283–297 295
Table 9
Accuracy of the presented function in predicting the value of Mpr2/Mpr1.
Connection Mf/Mpe C1 b Mpr2/Mpr1 model* Mpr2/Mpr1 predicted** Error (%) C2 model* C2 predicted** Error (%)
The DRBS configuration for connection DB600-MW is designed The results indicated that:
based on the proposed equations of section “Design procedure”. The
optimum value of C2 is set to 0.3025 according to Eq. (9). The geometry • Adding the second cut to the RBS connection diminished the
of the optimum DRBS connection is shown in Fig. 20. The cyclic perfor- maximum equivalent plastic strain index at the reduced sections by
mance of specimen DB600-MW (Fig. 20) is assessed in Abaqus, under 35 to 60% at 6% inter-story drift ratio.
loading protocol of Fig. 4. The equivalent plastic strain distribution and • It is necessary to brace both beam flanges at the end of both reduced
the maximum PEEQ are then compared between DRBS and RBS connec- sections against lateral movements in the DRBS connection to control
tions in Figs. 21 and 22. the early lateral torsional buckling of the beam.
According to Fig. 21, setting C2 = 0.3025 in DB600-MW connection • Using the DRBS connection instead of RBS connection postpones the
leads to the simultaneous formation of plastic hinges in both reduced beam web local buckling that considerably causes strength degrada-
sections. The plastic strains are obviously lower in the same cycles of tion of the connection. This, in turn, reduces the post-earthquake
loading in the DRBS connection (Fig. 21(II)), compared to the RBS con- damage and beam the flanges fracture tendency.
nection (Fig. 21(I)). Thus, the plastic hinge formation is postponed for • Formation of a distributed plastic zone and participation of a relatively
1% inter-story drift ratio in the DRBS, compared to the RBS connection. large portion of the beam web and flanges in the deformations
From Fig. 22, using DRBS instead of RBS connection, results in almost increased energy absorption (before beam WLB occurs) from 50 to
50% reduction in the PEEQ at different drift ratios. All of the aforemen- 75% compared to the RBS connection.
tioned advantages of the DRBS over RBS configuration hold for connec- • The reduction of the beam flanges in the first cut (C1) is determined by
tion DB600-MW. Therefore, the proposed design procedure is reliable in the first phase of the proposed design procedure, which conforms to
predicting the optimum values of C2 in DRBS connection. AISC-358 for the RBS connection. The reduction of the beam flanges
in the second cut (C2), assuring the balanced formation of plastic
6. Conclusions
Table 10
Dimensions and cut parameters of connection DB600-MW [30].
hinges at both reduced sections, is determined using the derived Further studies should be conducted to evaluate the performance
equation based on the numerical study results. and the optimum values of the parameters of DRBS connections having
• The parametric study showed that setting the reduction of the beam different span lengths and gravity loads and in multistory frames. In
flanges in the first cut (C1) and the length of the reduced sections addition, the proposed connection should be assessed experimentally
(b) to the lower and upper limits of AISC-358, respectively, results prior to application in real structures.
in the most desirable cyclic performance. The location of the start of
the first cut (a) was also set to the lowest limit proposed by AISC-
358, since increasing this parameter increases the moment at the References
column face. Moreover, the distance between the cut profiles (d) [1] D.K. Miller, Lessons learned from the Northridge earthquake, Eng. Struct. 20 (4–6)
was set to zero to prevent the formation of the plastic hinge in either (1998) 249–260.
of the reduced sections. [2] M. Nakashima, K. Inoue, M. Tada, Classification of damage to steel buildings
observed in the 1995 Hyogoken-Nanbu earthquake, Eng. Struct. 20 (4–6) (1998)
271–281.
[3] J.M. Ricles, C. Mao, L.W. Lu, J.W. Fisher, Inelastic cyclic testing of welded unrein-
forced moment connections, J. Struct. Eng. 128 (4) (2002) 429–440.
[4] C. Mao, J. Ricles, L.W. Lu, J. Fisher, Effect of local details on ductility of welded
moment connections, J. Struct. Eng. 127 (9) (2001) 1036–1044.
2 [5] Q.S.K. Yu, C.M. Uang, J. Gross, Seismic rehabilitation design of steel moment connec-
tion with welded haunch, J. Struct. Eng. 126 (1) (2000) 69–78.
[6] C.C. Chou, K.C. Tsai, Y.Y. Wang, C.K. Jao, Seismic rehabilitation performance of steel
DB600-RBS side plate moment connections, Earthq. Eng. Struct. Dyn. 39 (1) (2010) 23–44.
1.5 [7] M. Shiravand, A. Deylami, Application of full depth side plate to moment connection
DB600-DRBS
PEEQ index
[15] M. Valente, C.A. Castiglioni, A. Kanyilmaz, Numerical investigations of repairable [26] FEMA, Recommended Seismic Design Criteria for new Steel Moment Frame Buildings,
dissipative bolted fuses for earthquake resistant composite steel frames, Eng. Struct. FEMA 350, Federal Emergency Management Agency (FEMA), Washington, DC, 2000.
131 (2017) 275–292. [27] AISC, Prequalified Connections for Special and Intermediate Steel Moment Frames
[16] M. Valente, C.A. Castiglioni, A. Kanyilmaz, Welded fuses for dissipative beam-to- for Seismic Applications, AISC/ANSI 358-16, American Institute of Steel Construction
column connections of composite steel frames: numerical analyses, J. Constr. Steel (AISC), Chicago, IL, 2016.
Res. 128 (2017) 498–511. [28] C.M. Uang, C.C. Fan, Cyclic stability criteria for steel moment connections with
[17] N.R. Iwankiw, C.J. Carter, The dogbone: a new idea to chew on, Mod. Steel Constr. 36 reduced beam section, J. Struct. Eng. 127 (9) (2001) 1021–1027.
(4) (1996) 18–23. [29] B. Chi, C.M. Uang, Cyclic response and design recommendations of reduced beam
[18] S.S. Kumar, D.P. Rao, RHS beam-to-column connection with web opening— section moment connections with deep columns, J. Struct. Eng. 128 (4) (2002)
experimental study and finite element modelling, J. Constr. Steel Res. 62 (8) 464–473.
(2006) 739–746. [30] C.H. Lee, S.W. Jeon, J.H. Kim, C.M. Uang, Effects of panel zone strength and beam web
[19] S. Wilkinson, G. Hurdman, A. Crowther, A moment resisting connection for earth- connection method on seismic performance of reduced beam section steel moment
quake resistant structures, J. Constr. Steel Res. 62 (3) (2006) 295–302. connections, J. Struct. Eng. 131 (12) (2005) 1854–1865.
[20] S. Maleki, M. Tabbakhha, Numerical study of slotted-web–reduced-flange moment [31] AISC, Seismic Provisions for Structural Steel Buildings, AISC/ANSI 341-16, American
connection, J. Constr. Steel Res. 69 (1) (2012) 1–7. Institute of Steel Construction (AISC), Chicago, IL, 2016.
[21] D. Dimakogianni, G. Dougka, I. Vayas, Seismic behavior of frames with innovative [32] AISC, Specification for Structural Steel Buildings, AISC/ANSI 360-16, American
energy dissipation systems (FUSEIS1-2), Eng. Struct. 90 (2015) 83–95. Institute of Steel Construction (AISC), Chicago, IL, 2016.
[22] A. Plumier, New idea for safe structures in seismic zones, IABSE symposium, Mixed [33] AWS, Structural Welding Code-Seismic Supplement, ANSI/AWS D1.8/D1.8M,
Structures Including New Materials-Brussels 1990, pp. 431–436. American Welding Society, Miami, FL, 2015.
[23] D. Sophianopoulos, A. Deri, Parameters affecting response and design of steel [34] SIMULIA, Abaqus user's Manual, Version 6.13, SIMULIA, The Dassault Systemes,
moment frame reduced beam section connections: an overview, Int. J. Steel Struct. Realistic Simulation, USA, 2013.
11 (2) (2011) 133–144. [35] Z.S. Nia, M. Ghassemieh, A. Mazroi, WUF-W connection performance to box column
[24] C.J. Carter, N.R. Iwankiw, Improved ductility in seismic steel moment frames with subjected to uniaxial and biaxial loading, J. Constr. Steel Res. 88 (2013) 90–108.
dogbone connections, J. Constr. Steel Res. 1 (46) (1998) 448.
[25] M.D. Engelhardt, T. Winneberger, A.J. Zekany, T.J. Potyraj, The dogbone connection:
part II, Mod. Steel Constr. 36 (8) (1996) 46–55.