Note: the user IDs and passcodes noted in these job aids are for example only.
Enter Passcode
1. To access the panel, turn the Keyswitch ON.
2. To enter your Passcode, press F3 on the controller.
3. To enter your User ID, press “7” using the keypad.
4. Now press Enter using the F5 key.
5. Now enter your four-digit passcode, “3256”, followed by pressing Enter (F5).
Walk Test
! Note: The Walk Test task should only be performed by advanced operators.
Alternative Weekly Test
To carry out a statutory weekly fire alarm test, follow the steps listed in the “Fire Alarm Event”
simulation (page 10) of this course. Before carrying out a fire alarm test, ensure you carry out
the following:
Note: The test can be conducted by activating a call point using the supplied test key.
Removal of the test key will reset the call point allowing the system to be reset on
completion of the test. Revisit steps 1, 2 and 3 above if any of these operations has been
implemented.
Walk Test
1. To select Walk Test, enter the Service Menu by pressing “7” on the keypad.
2. Press “1” (Walk Test) on the keypad.
3. Using the F3/F4 (-/+) keys, select the Area. Press F3 once; press F4 twice.
4. Press F2 (>>) to move the cursor to highlight the Zone Number.
5. To enter the Zone Number, press 001 on the keypad.
6. Press F2 (>>) to move the cursor to highlight the Device Type.
7. Using the F3/F4 keys select the Device Type (Detectors). Press F4 once.
8. Press F2 (>>) to move the cursor to highlight the Loop.
9. Using the F3/F4 (-/+) keys select the Loop (A).
10. Press F2 (>>) to move the cursor to highlight the Test Mode.
11. Using the F3/F4 (-/+) keys select Auto or Manual. Let’s select Manual for physical
testing. Press F4 twice.
12. Press F2 (>>) to move the cursor to highlight the Multisensor Device to test only a part of
the device or the complete device. Note: testing of fire detectors is best left to a trained
operator and unless training has been given, this function should not be tested.
13. Using the F3/F4 (-/+) keys select Full. Press F4 once.
14. Once your selection is complete, press F5 (Start) to start your test. The L-C-D display
will show the number of elements that are to be tested.
15. If all devices haven’t responded before ending the test, use the F1 key (Back) to return
to the Main Menu. Press F1 twice.
16. Select option “6” from the Main Menu, View/Print Data, and then option “2” to display
Points Untested or Failed.