You are on page 1of 4

MX Online Training Simulation Steps 1-4

MX Basic Operation Online Training Simulation Steps

Note: the user IDs and passcodes noted in these job aids are for example only.

Enter Passcode
1. To access the panel, turn the Keyswitch ON.
2. To enter your Passcode, press F3 on the controller.
3. To enter your User ID, press “7” using the keypad.
4. Now press Enter using the F5 key.
5. Now enter your four-digit passcode, “3256”, followed by pressing Enter (F5).

Accept an Incoming Event


1. With any Incoming Event, the panel buzzer will sound. Turn the keyswitch to position “1”.
Silence the buzzer by pressing the “SILENCE BUZZER” button.
2. The information regarding the incoming event will be shown clearly on the LCD display.
Make a note of the displayed event and take appropriate action.
3. Enter your User ID. Press F3 (Passcode); press 7; now press Enter (F5).
4. Enter your passcode. Press "3256". Press Enter (F5).
5. Select "1" (Accept Events) from the Main Menu to accept the event.
6. Press F3 (Accept) to accept the event.
7. Press F1 (Back) to return to the Main Menu.
8. Turn the keyswitch to the "0" position and remove the key. This will log you off the
system.

Fire Alarm Event


1. With a Fire Alarm Event, the fire lights will illuminate and the panel buzzer and external
sounders will sound.
2. Silence the panel buzzer by pressing the “SILENCE BUZZER” button.
3. Silence the external sounders by pressing the “SILENCE/RESOUND” button. Note: the
external sounders should only be silenced when it is safe to do so.

Tyco Safety Products-Europe


MX Online Training Simulation Steps 2-4

View Status of a Loop Device


1. To View the Status of a Loop Device, select “2” (View Status) from the Main Menu.
2. Now select Option “1” (Point) as shown on the LCD using the keypad.
3. Select Option “1” (Loop Point) as shown on the LCD using the keypad.
4. Use the F4/F3 (+/-) keys to select the Loop: press F4, then F3.
5. Now move the cursor by pressing F2 once to highlight the device address.
6. Using the keypad, enter the device address: 64.
7. Press Enter (F5).

Isolate a Loop Device


1. To enter the Isolate Menu, select “3” (Isolate/De-Isolate) from the Main Menu. The nine
options are displayed on the LCD.
2. For Loop Devices, select “1” (Point) as shown on the LCD from the keypad.
3. Select Option “1” (Loop Point) as shown on the LCD using the keypad.
4. Use the F4/F3 (+/-) keys to select the Loop: press F4, then F3.
5. Now move the cursor by pressing F2 once to highlight the loop device.
6. Using the keypad, enter the device address: 64.
7. Press Enter (F5). The device is now displayed.
8. Select “1” (Isolate) as shown on the LCD, using the alphanumeric keypad, to isolate.
9. The number of isolations is now shown in the General window on the LCD display.

View the Event Log


1. To enter the Event Log Menu, select “5” from the Main Menu. Three options display on the
LCD.
2. To view the Event Log, press “1” on the keypad. The most recent Event is now displayed on
the LCD.
3. Use the F2/F3/F4 keys (<</>>) to scroll through the log: Press F3 three times, then F4 once.
4. Press the F1 (Back) key to return to the Event Log menu.
5. Select “3” (Filter) from the Event Log Menu to select the event type before viewing or
printing. The nine Event Type options display. Select the options by entering the appropriate
numbers, crosses will appear alongside the events selected.
6. Now return to the Main Menu by pressing F1 repeatedly. Press F1 three times.
7. To enter the View/Print Data Menu, select “6” from the Main Menu.
8. Select “1” from the keypad to view points isolated.
9. Now return to the Main Menu by pressing F1 repeatedly. Press F1 twice.

Tyco Safety Products-Europe


MX Online Training Simulation Steps 3-4

Walk Test

! Note: The Walk Test task should only be performed by advanced operators.
Alternative Weekly Test

To carry out a statutory weekly fire alarm test, follow the steps listed in the “Fire Alarm Event”
simulation (page 10) of this course. Before carrying out a fire alarm test, ensure you carry out
the following:

1. Inform the Remote alarm receiving centre if the system is connected.


2. Inform occupants of the building of the impending test.
3. Take care to isolate any plant shutdown circuits if these are likely to effect the normal
operation of any process and/or in itself create a hazard.

Note: The test can be conducted by activating a call point using the supplied test key.
Removal of the test key will reset the call point allowing the system to be reset on
completion of the test. Revisit steps 1, 2 and 3 above if any of these operations has been
implemented.

Walk Test
1. To select Walk Test, enter the Service Menu by pressing “7” on the keypad.
2. Press “1” (Walk Test) on the keypad.
3. Using the F3/F4 (-/+) keys, select the Area. Press F3 once; press F4 twice.
4. Press F2 (>>) to move the cursor to highlight the Zone Number.
5. To enter the Zone Number, press 001 on the keypad.
6. Press F2 (>>) to move the cursor to highlight the Device Type.
7. Using the F3/F4 keys select the Device Type (Detectors). Press F4 once.
8. Press F2 (>>) to move the cursor to highlight the Loop.
9. Using the F3/F4 (-/+) keys select the Loop (A).
10. Press F2 (>>) to move the cursor to highlight the Test Mode.
11. Using the F3/F4 (-/+) keys select Auto or Manual. Let’s select Manual for physical
testing. Press F4 twice.
12. Press F2 (>>) to move the cursor to highlight the Multisensor Device to test only a part of
the device or the complete device. Note: testing of fire detectors is best left to a trained
operator and unless training has been given, this function should not be tested.
13. Using the F3/F4 (-/+) keys select Full. Press F4 once.
14. Once your selection is complete, press F5 (Start) to start your test. The L-C-D display
will show the number of elements that are to be tested.
15. If all devices haven’t responded before ending the test, use the F1 key (Back) to return
to the Main Menu. Press F1 twice.
16. Select option “6” from the Main Menu, View/Print Data, and then option “2” to display
Points Untested or Failed.

Tyco Safety Products-Europe


MX Online Training Simulation Steps 4-4

17. Press F1 (Back) to return to the Main Menu.


18. Return to the Walk Test menu by entering the Service Menu. Press “7” on the keypad.
19. Press End (F5) to end your test.

Tyco Safety Products-Europe