You are on page 1of 5

12C x 2.

5mm2
Cu/XLPE/PVC/CuT/PVC

TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev.02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR


ALUMINUM CONDUCTOR, 600/1000V RATING

Enquiry No. Date:

Purchase Order No. or Date:


Contract No.

PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS

Standards to which material shall conform * IEC 60502-1

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General

Cable application (Power or Control) Control Cable

Cable installation * As required


(conduit, duct, trays, direct burial, GIS)

Voltage rating (kV) * 0.6/1

Fault current duration (sec.) * 1

Available ground fault current (kA) * 0.28


(when shielded cable is required)

Conductor DC resistance at 20°C (Ω/km) * 7.41

'A'- NATIONAL GRID SAUDI ARABIA SPECIFIED DATA/PARAMETER.


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS.
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO. 9 OF 13


TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev.02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR


ALUMINUM CONDUCTOR, 600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)

Conductor AC resistance per km at 20°C


* ≈ 7.411
(Ω)

Minimum Insulation resistance per km at


*
20°C (M) 84.12

Maximum permissible continuous


*
conductor temperature (°C) 90

Maximum rated temperature of


*
insulation material (°C) 90

Maximum permissible continuous


* 90
jacket temperature (°C)

4.3.1 Conductor Material Cu / Al Cu

Conductor cross sectional area (mm²) * 2.5

For conductors 4mm² and larger:


Number of strands per conductor * NA

Diameter of compacted strand (mm) * NA

Number of cores * NA

For conductors below 4mm²:


Stranding required ? Yes / No Yes

Number of strands per conductor * 7

Diameter of compacted strand (mm) * 0.67

Number of conductors * 12

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO. 10 OF 13


TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev.02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR


ALUMINUM CONDUCTOR, 600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)

Outer diameter of conductor (mm) * ≈ 2.01

Is conductor tinning required? Yes / No NO

4.3.2 Insulation Material PVC / XLPE XLPE

Nominal thickness of insulation (mm) * 0.7 (Nom.)

Outer diameter over insulation (mm) * ≈ 3.41

Insulation shield material, if any * NA

Thickness of insulation shield (mm) * NA

4.3.3 Binder required ? Yes / No Yes (Extruded PVC)

4.3.4 Metallic shield required ? Yes / No ** Yes (Copper Tape)

Thickness of metallic shield (mm) * 0.05

4.3.5 Armor material, if any * NA

4.3.6 Jacket Material PVC PVC-ST2-FR

Nominal thickness (mm) * 1.8 (Nom.)

Overall diameter of cable (mm) * 18.5 (Approx.)

4.4.7 Reference standard for core As per 01-TMSS-01, Rev.03


*
identification (IEC, ICEA) Clause 7.0

4.4.8 Color of single core cable/wire (if Black cores with


* each core numbered
applicable)

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO. 11 OF 13


TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev.02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR


ALUMINUM CONDUCTOR, 600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

5.0 TESTS
None
5.3 List of special tests, if required

6.0 PACKING AND SHIPPING

6.3 Cable weight (kg/km) * 570 (Approx.)

Reel and cable weight (kg) * 625 (Approx.)

Cable length per Reel (m) * 1000

Total quantity required (m) * 100

Cable reel diameter (mm) * 1100

Cable reel width (mm) * 650

Maximum pulling tension (kN) * 1.5

Minimum bending radius (mm) * 223

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO. 12 OF 13


TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev.02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR


ALUMINUM CONDUCTOR, 600/1000V RATING

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


NATIONAL GRID SAUDI ARABIA:

B ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR:

C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR:

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company TEKAB CO. LTD.


Location and address P.O. Box 40474, Industrial Area No. 13,

Sharjah, United Arab Emirates

Name and Signature of


authorized
representative MAJID EQBAL
and date 21 March 2019

Official Seal/Stamp 21-Mar-19


of the Company &
Date

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO. 13 OF 13