Professional Documents
Culture Documents
11 NOVEMBER 1967
Abstract-This paper deals with the use of the insulating prop- Using design procedures based on these and similar methods,
erties of wood in transmission line practice. The electrical prop- shielded lines using wood insulation have been commonly
erties-impulse strength and arc quenching-and the possible operated1]' [9] up to 160 kV. Such lines have also been con-
damaging effects of surge currents and power frequency leakage structed for 220 and even 345 kV as given by Darvenizall]
currents are considered. Prediction of the lightning performance of Sect. 1(b). Experimental structures using glued, laminated
shielded and unshielded lines is discussed, and it is shown that the wood have also been tested at 460 and 650 kV. [10]
impulse strength and arc quenching properties of wood influence per-
formance, the latter property being the dominant one for unshielded
lines. A design criterion using this arc quenching property has been Unshielded Lines
developed from experimental data on arc characteristics.
It is established that wood-insulated lines up to 110 kV can be
operated with acceptable outage rates without providing over-
BACKGROUND CONSIDERATIONS OF LINE DESIGN head earth wires, and Golde,[7] Garwood,[11] and Burgsdorft121
M OST methods for predicting the lightning performance have calculated outage rates due to lightning striking phase
of power lines were developed for steel-tower lines conductors. The critical lightning currents (I*) which can cause
shielded by overhead earth wires. These are now examined with insulation flashover under these conditions are given by I1*
particular reference to the way in which the properties of wood = 2 E, -/Z and 12* = 2 E, _/Z(l - k) in which Z is the
are used in the design of wood-insulated lines. Unshielded lines surge impedance of the stricken conductor (typically 500 ohms),
with conventional earthing and Petersen coil systems are also k is the coupling factor (typically 0.25), E, - , is the phase-to-
considered. ground flashover voltage, and E, - is the phase-to-phase flash-
over voltage.
Induced Lightning Surges For normal 11-, 33-, and 66-kV structures, the minimum E, -
Golde7I] and others have shown that induced surges greater lies in the range 300-1000 kVY for seasoned, wet wood; E, - , is
than 300-kV to ground are rare on lines of conductor heights up of the order of 2000 kVY. For weak-link structures (defined later)
to 60 feet. The average height of wood-pole lines is usually limited both Ep - p and Ep - , are likely to be much smaller. Thus I*
to 60 feet; thus, if sufficient insulation is provided between the will be between 1.6 and 5.2 kA for phase-to-phase flashovers
phase conductors and ground, outages due to induced surges and of the order of 8 kA for phase-to-ground flashovers on normal
can be effectively eliminated; e.g., for an 11-kV line, sufficient structures, and less for weak-link structures. Despite the addi-
insulation can be provided by a pin insulator in series with three tional insulation provided by the wood, most direct strokes will
feet of seasoned wet wood. Adequate insulation strength to therefore cause flashover of line insulation. If unprotected by
ground is even more readily provided for higher voltages. overhead earth wires, the dominant factor determining line out-
ages is not then the impulse flashover strength of the insulation.
Lines Shielded by Overhead Earth Wires It appears that the outage rate is mainly controlled by the
arc quenching property of the line insulation, which reduces the
The usual methods[2]' [3], [71, [8] for predicting lightning probability (pi) of a lightning flashover being followed by a
performance are applicable to wood-insulated lines. Because the sustained power-frequency fault current. This probability
tall tower problem is avoided, it is reasonable to expect satis- should be optimized when designing the line.
factory prediction of outage rates by these methods. The ad- Field and laboratory experience with the arc quenching
ditional impulse strength provided by the wood is incorporated property of wood has been reviewed by Darveniza. I3' This
by determining an equivalent insulation level for the wood- indicates that p,v is influenced by line design, and that it can be
porcelain combination. In the AIEE method, an equivalent related to the power-frequency voltage gradient (gi) applied to
number of insulators must be determined with which to enter the arc path following a lightning flashover. The gradient is
the prediction curves; the insulation strength added by dry normally calculated by dividing the voltage by the combined
wood is based on the work of Lusignan and Miller, [4] a 50- length of the wood and the wet flashover path of the porcelain.
percent reduction factor being used for wet conditions. For The variation of P1 with g1 has been investigated statistically
distribution lines, Clayton and Hileman 3M use the insulation and the results of Bellaschi,[141 Burgsdorf, [12] Ekvall,111] and
level of the wood-porcelain combination as a parameter; again Andrews and McCann[16] are presented in Fig. 1. The data of
the values are derived from Lusignan and Miller, 60 percent of Ekvall have been converted from outages per 100 structure-
dry strength being recommended for calculating wet strengths. years to the probability pi by assuming an average of 13 struc-
It is generally agreed that all lightning flashovers do not tures per mile of 33-kV line and that 60 lightning flashovers
result in a sustained power-follow current and consequent line could be expected per 100 mile-years of line; these assumptions
outage. For wood-insulated lines, where the flashover path influence the slope of curve (b). While there is disagreement, par-
may include wood, the ratio of outages to lightning flashovers is ticularly for gradients above 1.0 kVrms/in., the results suggest
stated to range from 0.35 to 0.50, [21 and the latter figure is usually that an acceptable operating gradient is 0.5 kV/in. Experi-
recommended for predicting the outage rate. This characteristic ments by Burgsdorf and by Bellaschi indicate that the prob-
is discussed later. ability of a transition to a power arc is virtually zero if g1 is
less than 0.25 kY/in, [121 and 0.5 kVrms/in. [141 Discussion in
Paper 31 TP 66-94, recommended and approved by the Trans- Bellaschit[4] showed that power faults can sometimes be caused
mission and Distribution Committee of the IEEE Power Group for
presentation at the 1966 Winter Power Meeting, New York, N. Y., by lightning even if the gradient is less than 0.25 kV/in.
January 30-February 4, 1966. Manuscript submitted October 18,
1965; made available for printing December 27, 1966. Petersen Coil Systems
M. Darveniza and S. A. Prentice are with the Department of
Electrical Engineering, University of Queensland, Brisbane, Aus- As shown in the foregoing, direct strokes to unshielded lines
tralia.
G. J. Limbourn is with the Electricity Commission of New South normally result in phase-to-phase flashovers, although phase-to-
Wales, Sydney, Australia. ground flashovers may also develop if the current is sufficiently
DARVENIZA ET AL.: ELECTRICAL PROPERTIES OF WOOD 1345
4
I
I
-~~~~~~
n
v.
n.
z
Z Lj
CD Ix
L, Cc)x
oo*w _____ _____
>a
(a)
//x
m
0
0W2 v;7XI,."
_x ai woo
0 0-5 1.0 IS 2-0 2-5 3-0
9,- POWER FREQUENCY VOLTAGE GRADIENT (kv.rrslinch)
Fig. 1. Probability of lightning flashover with power arc as func- Fig. 2. Influence of internal moisture (due to seasoning and rain)
tion of power frequency voltage gradient. Curve (a) from Bel- on impulse strength of wood-porcelain insulation. Vertical or-
laschi[14]; curve (b), Ekvall[115; curve (c), Burgsdorf[12]; point dinates are approximately to scale and represent range of values
X, Andrews and McCann.[16] reported.
large. Phase-to-phase faults must be minimized, and the phase- made for wood-porcelain combinations. The reduction in strength
to-ground insulation should be deliberately lowered to ensure with increased moisture content depends on the particular
that I,* < I2*. The probability of developing a phase-to-phase combination of wood and porcelain. Rain has little effect on
flashover after a phase-to-ground flashover is a function of the unseasoned wood; it causes a reduction in the impulse strength
current magnitude and the impedance of the tower and its of seasoned wood to 60 to 70 percent of its seasoned strength. [41,
earth. The probability of phase-to-phase flashovers can be [6], [201, [21] There is general agreement that the full reduction in
estimated from the critical current I3* = E - p/P(l - k) in strength is achieved after three to five minutes of rain at pre-
which P is the voltage developed on the stricken conductor per cipitation rates of 3 and 5 mm/min and that a much longer period
unit stroke current determined from a lattice diagram. For of fine weather must elapse before original strength is restored.
shielded lines, back-flashover first involves phase-to-ground insu- Most published data on wood-porcelain combinations refer to
lation, although other phase conductors will be involved if the phase-to-ground insulation. The available data and apparent
stroke current is sufficiently large. Burgsdorf[121 gives statistics deficiencies were reviewed in 1956 by an AIEE Committee,[51
of phase-to-phase and phase-to-ground faults on wood-insulated which concluded that dry wood can add 10 to 130 kV/ft of
and steel-tower lines, with and without overhead earth wires. wood to the impulse strength of porcelain insulation, and 0 to 60
kV/ft when the wood is wet. The additional insulation (X)
ELECTRICAL PROPERTIES OF WOOD INSULATION provided by the wood depended on its condition and varied with
different of wood-porcelain combinations. A simplified
In view of the cellular structure of wood, it is not surprising impedancetypes model was developed which represented the porcelain
that the electrical properties exhibit considerable scatter; insulation as a capacitance and the wood as a resistance in
coefficients of variation from 10 to 20 percent are common, parallel with a capacitance. This was used to show that the
even with selected species and controlled conditions of moisture variability between the impulse strength of various combinations
content. Moisture content is, however, the greatest single cause was chiefly due to predictable variations in the distribution of
of variation, e.g., a change from 50 percent for unseasoned wood the impulse voltage between the wood and the porcelain. A
to 15 percent for seasoned wood changes the resistivity by at similar model, developed by Rathsman and Sandstrom, [6]
least two orders of magnitude. Less marked changes occur in enabled the 1/50 impulse flashover voltage of a wood-porcelain
permittivity and impulse strength, but moisture content re- combination to be predicted from the impedances and the
mains the most significant cause of variation of these. Moisture flashover voltages of the individual elements. The results of
content depends on the degree of seasoning and also on the such a calculation for 11-kV line insulation, together with
amount of moisture absorbed at the surface, e.g., from rain or experimental results, are given in Fig. 3(a) and (b). The vari-
humid air. of the additional impulse strength (X) provided per
Most available data have been obtained from tests on soft- abilityfoot of wood is shown, and can be explained in terms of the
woods. A few countries have taken advantage of the greater properties
structural strength of indigenous hardwoods. Electrical data on insulator, X is a function of the lengthThus,
of the individual elements. even for a particular
and the resistance of the
softwoods have been assumed to apply to hardwoods with wood, as well as its impulse strength. Figure 3 shows that X
sufficient accuracy for design purposes, and recent investiga- varies from virtually zero for short, moist lengths to 140 kV/ft
tions [18 -[21] tend to confirm this. for all lengths of dry wood. The various conditions of breakdown
involved are described by Rathsman and Sandstrom. [6] A
Impulse Strength of Wood and Porcelain Combinations simple expression for the total flashover voltage (V,) of a wood-
The most frequently used data for softwoods are those pub- porcelain combination was suggested by Thoren, viz., V, =
lished by Lusignan and Miller. [4] Data in Darveniza[ll [Sect. (V,n + Vwn)lin in which Vi is the flashover voltage of the
3(c)] refer to specific structure designs [22], [23] and are of less insulator and Vw is the flashover voltage of the wood. For
general value for line design. Similar specific tests have been comparison, values of Vt calculated using n = 2 are plotted on
made in Great Britain [21] and Australia.[18] [20] both the theoretical and experimental curves (a) and (b) of
Various workers have concluded that the impulse strength Fig. 3. Limbourn, [20] also using n = 2, suggests that agreement
of wood is not significantly reduced by repeated breakdown between calculated and measured values is better than 20
impulses. The first few breakdown paths, whether internal or percent for a wide range of wood-porcelain combinations. He
near the surface, rarely follow the path of an earlier breakdown. has also refined the impedance model and extended it to wood-
However, repeated breakdowns can lead to a reduction in porcelain combinations at higher voltages. Flashover phenomena
strength due to the ingress of moisture through splits and cracks. observed on 11-, 33-, and 66-kV insulation have been correlated
Figure 2 indicates the influence of moisture content on the with that predicted by the impedance model and following the
impulse strength of wood. [41, [20] Similar observations have been suggestion of Sandstrom, the model was extended to include the
1346 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS NOVEMBER 1967
(150 Rw
I o -TIME (10osecs) -CURRENT
X
z 500
ED
n'
Ul
>r
400
300
~ ~~
\z4 It
e'
-
10 0
I
200 O --TIME
-~Ci 16 pf B
Cw 12pf. ft
---wood alone (Vw)
- wood-porceLain6t
0 2 3
(a)
Fig. 4. Identification of processes in breakdown oscillograms:
I A-peak of voltage wave; B-instant of breakdown; C-max-
z imum discharge current; D-minimum arc voltage (MAV);
a: 400 _ _
_
/ / t I
wood
E-recovery of dielectric strength (RAV); I-sparkover of in-
U) \ zdry sulator (alone).
300I
Qti
20 ( , mit woodL
./
, 20
L
Mean 1-13
case of phase-to-phase insulation involving wood in series with L
ni ... .1-0. ."I2-5I
two units of porcelain. This is of importance for unshielded lines,
-J
0 0-5 10 1-5 2-0 3-0
gw-MINIMUM ARC VOLTAGE GRADIENT IkVp/inch)
since few previous workers [4 [5] have considered phase-to-
phase flashover voltages. Fig. 5. Histogram of minimum arc voltage gradients (gW). Points
represent individual frequencies; smooth curve is drawn through
Arcing Characteristics of Wood the results.
Most workers have observed that voltage oscillograms recorded
with impulse breakdown of wood differ markedly from normal
breakdown oscillograms of air or across porcelain. At the instant age RAV across the now nonconducting arc channel, of which
of failure, the voltage collapses to a relatively low value-but not the dielectric strength at this instant must be at least equal to
to zero, as in the case of sparkover in air or across porcelain. or greater than the RAV. Measurements by Darveniza1l3] indi-
Appreciable arc voltages can be observed in the oscillograms pre- cated that the general v equation for arcs was applicable after
sented by Darveniza, 'll' Bellaschi,[14] Ouyang and Clowes,[21] and the minimum arc voltage was established.
Clayton and Shankle.[22] In many instances, a minimum arc The properties of arcs in wood are assumed to be charac-
voltage (MAV) is established and the test object later extinguishes terized by the minimumare voltage gradient (g10) and by the
the arc and recovers in part its dielectric strength; the voltage recovery arc voltage. Table I gives data for short lengths of
across the test object at the instant of recovery is called the hardwood, for cases where the circuit conditions given by Dar-
recovery arc voltage (RAV), see Fig. 4. veniza1l3] hold. Most arcs were internal, and the data show that
The volt-ampere (v-i) characteristics of arcs in softwoods the minimum arc voltage gradients are at least an order of magni-
have been investigated by Nekrasov, [171 and tests were reported tude greater than for arcs in air. For longer lengths of wood (alone
for lengths of pine and oak up to 6 meters, creosoted and un- and in series with porcelain) the arc path tends to be near surface
creosoted. Darveniza[13] investigated the arc characteristics of but a high gradient (gw) is still observed. Many configurations
hardwoods using short lengths and uniform field electrodes. involving wood alone, seasoned and unseasoned, wet and dry,
Later tests involved lengths up to 100 inches. and in combination with 11-, 33-, and 66-kV insulation, have
Appreciable residual arc voltages are always recorded when been tested, and a histogram of the observed minimum arc
the arc path involves wood, either internally or if the arc hugs voltage gradients is given in Fig. 5. By comparison with Table I,
the surface. Internal arc paths are usual for breakdown of un- these results indicate that for longer lengths the mean value of
seasoned wood, but for partly seasoned wood, particularly g10 is lower and that the spread of results is greater. Six percent
when in combination with porcelain, flashover occurs on the exhibited gradients less than 0.1 kV,/in of wood, and were
surface, the arc having a jagged orange flame appearance, in probably associated with flashover in air rather than along the
contrast to the white-hot appearance of arcs in air. These are wood. The few tests reported by Nekrasov give 2.5 kVp/in
referred to as near surface arcs, since they probably originate for 50 cm of oak, 1.25 and 1.49 for 100 and 625 cm of pine, and
just below the surface and are blown out into the surrounding 0.65 for 475 cm of creosoted pine. These are in the range recorded
air, at the same time gouging out small slivers or chips of wood. for hardwoods. The effect of impregnants on gn,w has not yet
Negligible arc voltage is observed if flashover occurs entirely been studied widely. However, limited tests reported by Nekrasov
through the air or over porcelain surfaces, e.g., with bonded on creosoted softwoods and by the University of Queensland on
phase-to-phase insulation. copper-chrome-arsenate impregnated hardwood poles with sap-
The arc voltage is a complex function of many factors of wood, suggest that g9, is higher for impregnated wood.
which arc length and current magnitude appear to be dominant.
Oscillograms show that, some time after the instant of voltage Mechanical Damage due to Surge Currents
collapse, a minimum arc voltage condition is established. The The use of wood as an insulator implies the possibility of
arc voltage then generally increases as the discharge current mechanical damage from the disruptive effects of surge currents.
decreases. Later, the arc is extinguished leaving a recovery volt- Most workers [4] [5] infer that it is necessary to control the path
DARVENIZA ET AL.: ELECTRICAL PROPERTIES OF WOOD 1347
TABLE I
PROPERTIES OF ARCS IN WOOD['3"
of the flashover away from the wood so that mechaniical damage TABLE II
will be minimized; this is particularly recommended for un- PERCENTAGE OF SUSTAINED LIGHTNING FAULTS ON
shielded structures. However, to use the arc quenching property, WOOD LINES[12] [26]
the design of the structure should be such that the flashover
path will involve wood members. Percent
It was found that if confined to the center of the wood, 10/20 Un-
,us surge currents less than 10 kA completely shattered normal- Operating success-
sized crossarms. In general, seasoned, dry wood shattered more Voltage, ful
easily due to internal arcs than green wood and this conclusion kV Country Type of Line Reclosure
was supported by mechanical impact tests. However, the
damage due to surge currents will depend on the actual flashover 110 U.S.S.R. shielded 15
path; if internal, severe damage will result; if near surface, 110 U.S.S.R. unshielded 5
relatively minor damage will occur. Most tests on wood-porcelain 110 Australia, Queensland shielded *
combinations with seasoned or partially seasoned crossarms 35 U.S.S.R. shielded 28
33 U.S.S.R. unshielded 11
indicated near surfaces flashover paths. Similarly, near surface 33 Australia, Queensland unshielded 12
flashover paths were noted on seasoned wood poles, although the 11 Australia, Queensland unshielded 7
time for sufficient seasoning is considerably longer than for cross-
arms. For green wood, the arc path is normally internal and * Only 4 lightning incidents in 3600 mile-years of experience.
hence severe mechanical damage can result which suggests that
lines constructed with unseasoned wood will undergo an initial
period during which there is a high risk of mechanical damage due ence for each voltage) are summarized in Table II. Permanent
to lightning. This is supported by service experience with poles. faults were caused by insulator puncture or shattering, con-
After normal seasoning, little damage should be expected.'ll, ductor damage, and mechanical damage to poles and cross-
[12], [24] -[26] Wood crossarms and poles need not be protected arms. Power arcing, which is the main cause of damage, could
by air gaps and thus full use is made of the arc quenching and be reduced by greater use of high-speed protection; the data in
insulating properties. Where wood insulators are inserted in stay Table II show the advantages of automatic reclosing.
(guy) wires, the consequences of failure suggest that special
precautions, such as the use of protective air gaps, may be "Weak-Link" Structures
necessary. However, some stays are installed as a precaution
(e.g., at shackle structures) or to stabilize the line against possible Some pole-top configurations do not permit the best use of
wind or flood forces, and hence protection of the wood insert is wood insulation and result in weak-link structures such as
less vital. transpositions, pole-top supporting metal framed hardware,
and poles with staywires fixed near the crossarm. Normal wood
Power Frequency Leakage Currents insulated structures have a high impulse flashover level between
The resistivity and ignitability of wood are properties which phases and between phase and ground. In contrast weak-link
determine the effects of power frequency leakage currents in structures have reduced impulse strength and high power-
unbonded structures. Leakage currents of sufficient magnitude to frequency voltage gradients. Thus, normal wood-insulated
harm personnel or damage the components of a wood structure structures (seasoned, wet) for 33 kV can support a 500-kVp
can result from 1) complete or partial insulator failure, 2) surge on one conductor without insulation flashover, whereas a
bridging of the insulator by a conductor (wire or live object), voltage of 250 kVp would cause flashover on a structure utilizing
or 3) contamination of the insulator surface by dust, salt spray, only normal porcelain insulation (e.g., earthed metal crossarm).
or industrial pollution. Typical possibilities of shock involve Using the Foust and Menger attenuation formula (with K =
persons working on a wood structure or touching a wood pole 0.000 16), a 500-kV surge must travel over ten miles to attenuate
carrying dangerously high leakage current. Investigations to 250 kV and thus may travel up to this distance to seek out the
have been reported in the literature,t11 and currently the effect weak-link structure.
of preservative treatment on the resistivity of wood used for The influence of weak-link structures on outage rates is con-
poles is being examined in Australia. Damage to a structure can sidered later. As an example, fault records on an unshielded
result from local burning even with relatively small leakage 33-kV system indicate that weak-link structures have a dis-
currents; contamination is the most common cause. proportionate influence on the lightning outage rate. Data
from 4000 mile-years of experience indicate that 50 percent of
DESIGN FEATURES ARISING FROM FIELD EXPERIENCE identified faults were associated with such structures. The
Occurrence of Sustained Faults performance of weak-link structures should therefore be in-
corporated in predictions of lightning outage rates. Significant
The occurrence of sustained faults has been studied by Burgs- improvements to outage rates may be effected by applying
dorf, 12] Littler,[251 and Dawson.[261 The data from extensive remedial measures to these structures; often it may be more
system records (between 3000 and 9000 route mile-years experi- convenient to install lightning arresters than to modify existing
1348 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS NOVEMBER 1967
arms were painted all over with semiconducting paint with bands
of aluminum paint at the insulator attachment points. Sub- w
HI
there has not been a recurrence. Deterioration in effectiveness is m
not known; however, repainting has not been found necessary,
and, in general, is not considered to be practical. An examination
of system records since 1957 shows that of the relatively small
m
0
caI
I/
number of pole fires, most have been due to faulty insulators, --
TABLE IV
FLASHOVER AND OUTAGE RATES/100 MILE-YEARS, 138- AND 345-KV LINES, ILLINOIS POWER COMPANY[331
Reported Pi Calculated Outage Rate
Operating Voltage, kV Flashover Rate Fig. 1 (c),(x) Fig. 6(a), (y) (x) (y) Reported Outage Rate
Unshielded Lines: The critical lightning current (1*) which can The outage rate calculations accounting for the arc quenching
cause insulation flashover must be calculated and the FR ob- property of wood have also been applied to a 138-kV wood
tained from H frame construction[33] for which both calculated and actual
lightning performance data were available. The calculated
FR = N1 X P2 flashovers/100 mile-years. figures were obtained with the Monte Carlo prediction method, [81
N1 is the number of direct strokes to 100 miles of line per year and assumed that all lightning flashovers result in line outages.
(Golde[29] or Burgsdorf[12]), and P2 is the probability that I* The outage rates in Table IV were determined by multiplying
will be exceeded. The outage rate is OR = N1 X P2 X Pli the published FR figures by Pi obtained from both Burgsdorf's
For lines which are effectively shielded to protect terminal data in Fig. 1 and the data of Fig. 7. Similar calculations were
stations, it is not advisable to lower flashover voltages so as to made for the 345-kV line described in the same paper.[33] The
use the arc quenching property of wood in the lightning proof good agreement between the calculated and actual outage
zone. Here it is necessary to reduce the flashover rate rather than rates for the 138-kV line shows that predictions of line perform-
the outage rate to an acceptable minimum. For unshielded lines, ance require consideration of arc quenching.
the accuracy of OR is mainly controlled by the accuracy with
which N1 and pi are estimated. As stated by Littler, [25] it is neces- Discussion
sary to account for weak-link structures directly. Thus it is ad-
visable to calculate an outage rate OR1 for normal structures and Discussion will be confined to the prediction of the probability
an outage rate OR2 for weak-link structures. Then the outage of lightning flashover with a power arc using the design criterion
rate for the line is determined by a mean, weighted according to based on the arcing characteristics of wood. However, line
the relative abundance of the different types and their flashover performance must also be influenced by any system parameters
voltages. The probability that any stroke to the line will result which may affect the transition, e.g., any effect which tends to
in a weak-link flashover is calculated with the following assump- carbonize the arc path in the wood or to cause restrikes. One
tions: 1) that all strokes are evenly distributed along the line, possibility is carbonization due to the passage of power frequency
and 2) that for any stroke distant d feet from a weak-link, the fault currents (Isc). Arc extinction probably occurs in micro-
flashover voltage of the weak-link structure will be exceeded be- seconds and so the rise of fault current and its duration during the
fore the flashover voltage of the normal structure is reached if lightning discharge will be small. The possibility of a restrike
after arc extinction should also be considered since transient
LV1 - LV2 X 1000 system voltages, equaling Isc X Z/2, will appear at the flashover
K < K(,,it)
d
kV/Ms, point as the system voltage recovers. Since the dielectric strength
of the wood at the instant of arc extinction, RAV, is normally
K being the slope of the impressed surge voltage (= rate of larger than the MAV and since the self-quenching property of
rise of current +. Z/2) and LV the surge voltage causing either the nonconducting arc should ensure a further and rapid increase
phase-to-phase or phase-to-ground flashovers. in strength, a restrike due to the system recovery voltage seems
From the distribution of weak-link structures, and assuming a unlikely. With regard to arc extinction at the first natural current
known probability[30] for the rate of rise of lightning currents, zero, attempts to apply the dynamic arc theory[31' [321 to arcs
the probability that strokes would cause flashover at a normal across short length wood surfaces have been promising, par-
or a weak-link structure may be calculated for each portion of ticularly when the operating voltage gradient exceeds the MAV
the line. These probabilities are then averaged over the whole gradient. If the probability of extinction is a direct function of
line, and hence provide the necessary weighting values to assign the system fault current, this may be an important factor in the
to outage rates associated with the various types of structures. performance of 11- and 33-kV lines with low fault currents.
Such calculations must also account for the disposition of con- From the application of the arc quenching criterion, it could
ductors on the pole-tops, since this will decide the most likely be inferred that there is no possibility of a sustained fault if the
flashover paths to be involved. Alternatively, field experience designed minimum arc voltage is much greater than the system
may assist in weighting the various outage rates. For example, voltage. However, in practice, a small number of faults are
the performance of unshielded 11- and 33-kV systems in Queens- recorded even if the design criterion is in general exceeded.
land [25] suggests that the line OR is the mean of the individual Possible reasons are that the path of the arc can bypass portions
outage rates; however, this may not apply to other systems. Line of the wood in wood-porcelain combinations, particularly at
performance can be further improved by automatic reclosure of high overvoltages; that there are multiple lightning discharges
circuit breakers, the sustained interruption rate being then of sufficient duration; and that the criterion may not be satisfied
obtained by multiplying OR by a percentage from Table II. at weak-link structures.
Comparison of Calculated and Actual Lightning Performance of
Wood-Insulated Lines CONCLUSIONS
The application of the outage rate calculations to unshielded 1) In general, the advantages of using the insulating prop-
11- and 33-kV lines by Littler[251 gives good agreement between erties of wood to give acceptable lightning performance of lines
predicted and actual outage rates and similar calculations completely outweigh the disadvantages which may result from
for a 300-mile system of shielded 110-kV lines and a 600-mile the damaging effects of surge currents and power-frequency
system of unshielded 33-kV lines are given in the Appendix leakage currents. Such risks may be made acceptably small by
and Tables II and III. appropriate design of the wood members.
DARVENIZA ET AL.: ELECTRICAL PROPERTIES OF WOOD 1351
shielded lines up to 132 kV, and recent work indicates that a '0
+'T~ ~ ~ ~ ~ ~A
SIDE
characteristic is responsible for, and may be related directly to, CON JIIOkV
the observed arc quenching property of wood. This gives rise to a 55x120
TWIN
4p
simple criterion for line design, namely that the length of wood
insulation should be such that the power-frequency voltage STAY ATTACHMENT
gradient appearing across it after lightning flash overis suffi-
ciently small compared to the MAV gradient (g,) to ensure a CON.4. 33kV. CON. 1. 33W
small probability (Pi) of a sustained power arc.
4) Methods for the prediction of the lightning performance of Fig. 8. Constructions of 110- and 33-kV line in
both shielded and unshielded wood-insulated lines have been Southeastern Queensland.
based on the probability that a lightning stroke will cause
flashover of line insulation and the probability that such a flash- Earth resistance measurements were made on six percent of the
over will be followed by a sustained power arc; the latter mainly available structures; the sample was selected according to a
controls the performance of unshielded lines. It has also been dominant soils classification of the route areas. The average
shown that the performance of weak-link structures must be footing resistance was 21 ohms, and omitting a few high values,
accounted for directly in any calculation of outage rates. There is the distribution was: 0 to 10 ohms, 35 percent; 11 to 20 ohms,
satisfactory agreement between predicted and actual outage 33 percent; 21 to 30 ohms, 21 percent; 31 to 50 ohms, 8 percent;
rates of typical lines. 51 to 100 ohms, 3 percent. Impulse flashover tests were carried
5) Further investigation of the following is needed: the impulse out on actual structures and it was concluded that the insulation
strength of complex wood-porcelain combinations; the influence of each type was equivalent to 15 disks. For positive polarity
of preservatives on the impulse strength, leakage resistance, impulses applied to the shield wire, the flashover path on both
and the arc characteristics of wood; the switching surge strength structures was always via the air path A in Fig. 8; for negative
of wood-porcelain insulation; the detailed physics of the arc polarity, flashover occurred via the air path on construction B,
quenching properties of wood and the possible application of the whereas for construction J, the flashover followed the air or the
dynamic arc theory; and a study of the transition from impulse wood path (B in Fig. 8) with about equal probability. The mid-
to power arc using combined impulse and power-frequency test span clearances are 18 feet for construction B and 16 feet for
sources. Additional field data are also required regarding: construction J.
reduced performance of wood-insulated lines before adequate Using the distribution of measured footing resistances and
seasoning is achieved; the occurrence of lightning flashover of estimating the corresponding impulse resistances, the average
wood without a sustained power arc and outage; the permanent flashover rates for the lines were determined for T = 24, and
damage resulting from lightning incidents on wood-insulated these are given in Table VI. Outage rates in Table VI were
lines; and the influence of weak-links on line performance. calculated using Figs. 1 and 7. The outages which might be
expected as a result of direct strokes reaching the phase con-
APPENDIX ductors due to shielding failures are also given and these are
LIGHTNING PERFORMANCE OF 110- AND 33-KV based on the data of Burgsdorf.[12] The agreement between the
WOOD-INSULATED LINES IN SOUTHEASTERN QUEENSLAND calculated and actual rates is satisfactory but not conclusive,
Line Data and Service Performance[26I when it is considered that the number of lightning faults to
In the area supplied by the Southern Electric Authority of date is only two (see Table V) and that the assumption of 100
Queensland (over 17 000 square miles), the annual thunderday strokes to line/100 mile-years may not be correct. Further, the
level (T) varies between 15 and 35 (average 24). All lines are average height of the lines is less than 50 feet compared with
unbonded and unearthed. Two pole-top designs are used for 75 feet used in the AIEE method.
normal 110-kV structures, shown as constructions B and J of
Fig. 8. Termination, strain, and angle structures were designed Outage Rate Calculations for 33-kV Lines
to achieve an impulse strength not less than that of the normal The impulse flashover voltages for the 33-kV structures were
intermediate structure, using, where necessary, a 3-pole structure. taken from the data of Limbourn. [201 The minimum flashover
Wood inserts, 12 feet in length, were installed in all stay wires. voltages (E) of the most likely breakdown paths are given in
The unshielded 33-kV lines use a wishbone construction shown Table VII (wet seasoned wood), together with the associated
as 1 of Fig. 8 for normal intermediate structures, and a tri- critical surge currents (I*) and the operating gradients g1 and g2.
angular construction, 4, for strain structures. (An alternative The data for the alternative strain structure are given in brackets.
construction places the center conductor on the crossarm nine For the normal structure of construction 1, it was assumed that
inches from the pole.) Where necessary, 33-kV structures are the two top conductors could be struck with equal probability
stayed with steel wire ropes (without a wood insert) fixed to the and hence average values are given for the surge voltage on the
pole in the position shown; in the alternative construction the line (LV) required to cause flashover between phases. The aver-
staywire is attached just below the arm braces. The lightning age surge impedance of the top conductors is taken as 450 ohms,
performance is given in Table V. and the coupling factors, allowing for corona, vary between 0.3
and 0.45. The flashover data in Table VII indicate that the
Outage Rate Calculations for 1IO-kV Lines stayed strain structures (particularly the alternative) are weak-
Flashover rates were calculated using the AIEE method. [21 links compared to the normal line structures.
1352 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS NOVEMBER 1967
TABLE V
PERFORMANCE OF SEAQ 110- AND 33-KV LINES
Lightning Faults
Average Number of Faults per 100
Period Line Design Mile-Years Thunderdays All Lightning Mile-Years
1952-1963 Construction B 3029 24 57 2 0.07
1957-1963 Construction J 572 24 7 2 0.35
1957-1963 Constructions 1, 4A 4252 24 565 343 8.1
TABLE VI
FLASHOVER AND OUTAGE RATEs/100 MILE-YEARS, 110-KV STRUCTURES, SEAQ
Structure
Construction Construction
Item B J Remarks
(i) Flashover rate 0.24 0.41
(ii) Outage rate [Fig. 1(c)] 0.15 0.20 gi calculated assuming air path A, Fig. 8
(iii) Outage rate (Fig. 7) 0.13 0.31 92 calculated assuming wood path B, Fig. 8
(iv) Shielding failure rate[12] 0 0.16
(ii + iv) Total calculated OR 0.15 0.36
(iii + iv) Total calculated OR 0.13 0.47
Actual OR (Table V) 0.07 0.35
TABLE VII
FLASHOVER DATA, 33-KV STRUCTURES, SEAQ
TABLE VIII
SPECIFIC OUTAGE RATES, 33-KV LINES, SEAQ
A specific outage rate for each type of flashover listed in (construction 1), 71 percent of all strokes will cause phase-to-
Table VII was calculated from OR = N1 X p2 X P, outages/100 phase flashovers on normal structures (either type a or b), and
mile-years. When calculated according to Burgsdorf,[12] Golde, [29] 29 percent will cause a type d flashover to earth at weak-link
and the AIEE figure, [21 after allowing for height, the values of structures. Since the pole-top potential is only substantially
N1 were 37, 23, and 50, respectively. The average of 37 strokes/ reduced by a flashover to ground, then it is likely that a phase-
100 mile-years was taken as the best estimate. Using the stroke to-phase flashover will also be followed by a phase-to-ground
current probability datat2] to obtain P2 and calculating p1 from flashover. On these lines, it can be shown that of the 71 percent
both the data of Burgsdorf [12] (Fig. 1) and Fig. 7, the rates given of strokes which cause phase-to-phase flashover, 43 percent will
in Table VIII were obtained. The average rate was then obtained also cause a type e flashover at a weak-link while the likelihood
by determining a mean for the individual structure outage rates, of a type c flashover to ground at a normal structure is very
weighted according to the relative abundance and flashover small. Also, it can be expected that the phase-to-phase flashover
voltages of the various structures. For the 33-kV lines, it was would occur in air (type b) along the span as well as at the
estimated that one ninth were weak-link structures. Considering structure, where both type a and type b flashovers may occur.
strokes to either of the top conductors on the normal structures The relative proportion of type a and type b flashovers was
DARVENIZA ET AL.: ELECTRICAL PROPERTIES OF WOOD 1353
calculated using the same approach as that employed for the AIEE (Power Apparatus and Systems), vol. 75, pp. 16-21, April 1956.
weak-link calculations, but further refined to account for the [6] B. G. Rathsman and U. Sandstrom, "Fundamental principles
different impulse volt-time characteristics of the various air and for the insulation of power lines," CIGRE, Paris, France, paper 222,
1956.
wood-porcelain flashover paths. Of the 71 percent of strokes [7] R. H. Golde, "Lightning surges on overhead distribution lines
resulting in phase-to-phase flashover, 15 percent involved caused by indirect and direct lightning strokes," Trans. AIEE
only an air path. The average outage rate is given by (Power Apparatus and Systems), vol. 73, pt. III-A, pp. 437-447,
June 1954.
[8] J. G. Anderson, "Monte Carlo computer calculation of trans-
OR = 0.29 X 2.6 + 0.15 X 24 + 0.56 X 3.3 + 0.43 X 5.2 mission-line lightning performance," Trans. AIEE (Power Apparatus
and Systems), vol. 80, pp. 414-420, August 1961.
= 8.4 outages/100 mile-years using 92 and pi determined [9] "The lightning performance of typical transmission lines,"
from Fig. 7 2nd. ed, Ohio Brass Company, Ohio, Publ. 1321-H, 1955.
[10] S. D. Alpert et al., "Glued laminated wood and prestressed
concrete 650-kV tower structures for project EHV," presented at
or 1961 AIEE Winter General Meeting.
[ll] G. T. Garwood, "The operational characteristics of modern
OR = 0.29 X 2.6 + 0.15 X 2.4 + 0.56 X 4.8 + 0.43 X 6.3 H. V. wood-pole lines," J. IEE(London), vol. 94, pt. II, pp. 481-
493, 1947.
= 6.5 outages/100 mile-years [based on the Burgsdorf data [12] V. V. Burgsdorf, "Lightning protection of overhead trans-
mission lines and operating experience in the U.S.S.R.," CIGRE,
of Fig. 1 (c) ]. Paris, France, paper 326, 1958.
[13] M. Darveniza, "Some aspects of lightning flashover and power
The preceding calculations were repeated for construction 4(A) outage performance of wood-insulated transmission lines," Elect.
for strain structures and the outage rates were 11.6 and 8.9. and Mech. Trans., (Inst. Engrs., Aust.) vol. EM4, no. 11, pp. 49-60,
1962.
It was estimated that approximately one in five of the strain [14] P. L. Bellaschi, "Wood pole insulation tests," Elect. Engrg.,
structures utilized the alternative construction and hence the vol. 66, pp. 672-677, 1947.
overall outage rates are given by [15] H. N. Ekvall, "Minimum insulation level for lightning pro-
tection of medium-voltage lines," Elect. Engrg., vol. 60, pp. 128-
OR = 0.8 X 8.4 + 0.2 X 11.6 132, 1940.
[16] F. E. Andrews and G. D. McCann, "Lightning investigations
on 33-kV wood-pole lines," Elect. Engrg., vol. 64, pp. 768-777,
= 9.1 outages/100 mile-years 1945.
[17] M. N. Nekrasov, "Transition of an impulse flashover into a
or power arc on wood-pole transmission lines," Elektrichestvo, no. 3,
pp. 7-10, 1951.
OR = 0.8 X 6.5 + 0.2 X 8.9 [18] M. Darveniza, "Impulse strength of Australian hardwoods,"
University of Queensland, Brisbane, Australia, E.R.B. rept. U./Q.1,
= 7.0 outages/100 mile-years. May 1956.
[19] W. C. E. Wager, "Measurement of the internal breakdown
The agreement between the calculated value of 9.1 and the strength of timber," M.Eng.Sc. thesis, University of Queensland,
Brisbane, Australia, March 1962.
actual outage rate of 8.1 is satisfactory considering the number [20] G. J. Limbourn, "Impulse voltage distribution between wood
of assumptions involved in the calculation. The conclusions are and porcelain in transmission line insulation," M.Eng.Sc. thesis,
that: University of Queensland, Brisbane, Australia, December 1964.
[211 M. Ouyang and R. J. Clowes, "The impulse flashover char-
acteristics of keruing wood," BEAIRA Rept. S/T110, Leatherhead,
1) The outage rate for any particular type of structure is England, 1961.
mainly controlled by the probability (pi). Table VIII shows that [22] J. M. Clayton and D. F. Shankle, "Insulation characteristics of
most strokes to line will result in a flashover. wood and suspension insulators in series," Trans. AIEE (Power
2) The performance of weak-link structures can have a dis- Apparatus and Systems), vol. 74, pt. III, pp. 1305-1312, December
1955.
proportionate influence on the lightning outage rate and hence [23] J. J. Trainor and L. B. LeVesconte, "230-kV wood-pole
their performance must be specifically considered in calculations transmission-line design," Trans. AIEE (Power Apparatus and
of the overall line outage rate. The preceding calculations show Systems), vol. 73, pt. III-A, pp. 522-528, June 1954.
that about 40 percent of the outages occur on the weak-link [24] J. Beesley, "A survey of the causes of service failing of cross-
arms throughout Australia. Summary of results, conclusions, and
structures and this agrees with experience. recommendations," Aust. C.S.I.R.O. Div. Forest Products, Rept. 7,
3) Calculations of the probability of arc quenching based on a Sub-proj. P2-2, September 1954.
wood gradient g2 or on a total arc path gradient g1 give sub- [25] G. E. Littler, "High speed reclosing and protection techniques
stantially similar final results. applied to wood pole lines," Elect. Engrg. Trans., (Inst. Engrs.,
Aust.), vol. EE-1, pp. 107-116, September 1965.
[26] G. Dawson, "Lightning performance and associated design
ACKNOWLEDGMENT aspects of wood pole overhead lines in south east Queensland,"
Elect. Engrg. Trans., (Inst. Engrs, Aust.), vol. EE-1, pp. 95-106,
The authors wish to thank the Southern Electric Authority of September 1965.
Queensland and the Electricity Commission of New South Wales [27] S. A. Prentice, "Report on pole and crossarm fires," State
for their assistance in the preparation of this paper. Electricity Commission of Victoria, Australia, internal rept., August
1950.
[28] P. M. Ross, "Wood structure burning by leakage currents,"
REFERENCES Elect. Engrg., vol. 66, pt. 5, pp. 472-474, 1947.
['1 M. Darveniza and W. Wager, "A bibliography on wood- [29] R. H. Golde, "Frequency of occurrence and the distribution
insulated transmission lines," presented at the AIEE 1961 Fall of lightning flashes to transmission lines," Trans. AIEE, vol. 64, pp.
General Meeting. 902-910, 1945.
[2] AIEE Committee Report, "A method of estimating lightning [30] C. F. Wagner and A. R. Hileman, "The lightning stroke,"
performance of transmission lines," Trans. AIEE, vol. 69, pt. II, pp. Trans. AIEE (Power Apparatus and Systems), vol. 77, pp. 229-242,
1187-1196, 1950. June 1958.
[3] J. M. Clayton and A. R. Hileman, "A method of estimating [31] 0. Mayr, "Contributions to the theory of static and dynamic
lightning performance of distribution lines," Trans. AIEE (Power electric arc," Arch. Elektrotech, vol. 37, p. 588, 1943.
Apparatus and Systems), vol. 73, pt. III-B, pp. 933-945, August [32] S. G. Fraser, "The arc quenching properties of fine bore
1954.
[4] J. T. Lusignan, Jr., and C. J. Miller, Jr., "What wood may tubes," Ph.D. thesis, University of Queensland, Brisbane, Australia,
add to primary insulation for withstanding lightning," Trans. AIEE, February 1964.
vol. 59, pp. 534-540, September 1940. [33] G. P. Wilson, R. H. Sarikas, Z. J. Andracki, and R. L. Trotter,
[5] AIEE Committee Report, "Impulse flashovers of combinations "Sydney-Cayuga 345-kV wood H-frame line," IEEE Trans. Power
of line insulators, air gaps, and wood structural members," Trans. Apparatus and Systems, vol. PAS-84, pp. 93-106, February 1965.
1354 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS NOVEMBER 1967
Discussion The paper brings out several of the virtues of wood in contributing
to the electrical performance of the system. To these the writer
F. Edmondson (State Electricity Commission of Western Australia, would add the exploitation of the characteristic that the impulse
Perth, Australia): We have observed on four 66-kV lines that there time-lag curve of wood is much steeper than that of air gaps. This
have been a greater number of outages due to lightning during the gives scope to the ability to design the tower top, whether shielded
first year of operation. This, I believe, to be due to the very high or unshielded, in such fashion that flashovers occurring well along
moisture content of the timber. We have no proof that unseasoned the tail of the wave will take place over the wood path, whereas the
timber is the sole reason for this high outage rate, because on each of flashovers occurring near crest will take place over the air-strike
the lines where lightning damage occurred after the first year of path, thus protecting the wood from the larger physical damage
operation, we have erected sections of overhead earth wires. resulting from the higher impulse currents accompanying the near-
crest flashover voltages. The flashovers along the wood path at the
impulse currents accompanying tail-of-wave flashovers rarely do
more than knock some splinters out of the wood.
The arc-quenching effectiveness of wood as expressed in kV/in
sounds optimistically high to the writer in comparison with previous
impressions going back to the late 1920s. Could it be that the
parameter of the prospective fault current as brought out by Arm-
strong et al.1 accounts for the difference?
little published information is available regarding this factor; the that the flashover path is internal if the crossarm of pole is un-
work of Burgsdorf and Bellaschi being the chief references. Their seasoned; surge current tests indicate that much damage may result.
laboratory tests have sought to define the probability in terms of the Over a period of years, we have impulse tested crossarms with
overall power frequency voltage gradient of the insulation path. varying degrees of seasoning (i.e., at various times after milling and
The relationship suggested by Burgsdorf gives results under average indoor storage). Generally the flashover path is external or near-
conditions which agree well with field experience. surface when the nominal moisture content' falls below about 25
The often-quoted value of 0.85 for air should be used with caution, percent. This condition can be reached within six to 12 months after
since it has been derived from statistics on 132- and 220-kV steel milling if the crossarms are so stacked as to ensure the most effective
tower lines of a certain length. Harder and Clayton have given a air seasoning. Because of their larger cross-sectional area, poles
figure of 0.5 for lines over 200 miles in length, and there is no evidence season much more slowly and drying periods of one to two years are
to suggest that the probability of 0.85 necessarily applies to distri- recommended to ensure avoidance of an internal flashover path.
bution lines operating at, say, 11 kV.
Power system parameters: While laboratory tests are a very useful
guide, one has to apply the results with caution, because the test w
equipment may not duplicate real power system conditions. Field + _ 4
testing is less convenient and the power system parameters cannot IL~~~~~~~
always be varied; but nevertheless it could provide more detailed 00
La
information. Theoretically, one would expect such factors as the >
. OI
1
E oo-porcetoin -
X/R ratio at the fault, source resistance, and natural frequency to o- D I?~~~~
play an important part in determining the probability of power rod opI
:
0 4 8 12 16 20
tribution systems to complex EHV networks. TIME TO BREAKDOWN (p secs.)
Outage rates for 33-kV lines: There is no simple way in which the Fig. 11. Typical volt-time characteristics for wood-porcelain
individual structure and line outage rates can be combined to give and air insulation.
an overall outage rate for an unshielded line. An examination of
structure damage might be thought to give a guide to the points of I000 _ _ _ - _-
flashover which could be related to the number of structures of
each type in a line. However, as stated by Littler, [25] no direct as- 400 6*
Stoodord -
sociation could be found, due to the complex nature of the initial 1300 rod gap
X X
where finally one structure may predominate. IL 1100
severe damage during the initial year of operation. Though this dissimilar in magnitude. In general, in a practical combination, the
may have been in part due to unusually high lightning activity in flashover voltages of the wood and the porcelain will not be vastly
that particular year, the relatively unseasoned condition of the poles different, i.e., Vi will not be much greater than V. or vice versa, and
is also a likely cause. Impulse voltage tests have shown repeatedly hence Vt will generally be significantly larger than Vi or V.. We
I "Testing timber for moisture content," Aust. C.S.I.R.O., Div.
Manuscript received March 21, 1966. of Forest Products, circular no. 50, 1962.
1356 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS VOL. PAS-86, NO. 11 NOVEMBER 1967
have carried out impulse tests on insulation typical of 11-, 33-, transition from an impulse flashover to a power arc is influenced by
66-, 110-, and 132-kV structures and the preceding remarks are the fault current level, whereas the laboratory data of Bellaschi[l41
based on the results of these tests. (It is hoped to publish these and the data of Burgsdorf['ll do not support this view. Clearly more
results eventually.) The following data on the 110-kV structure, theoretical and laboratory work is required here. Mr. Littler has
construction J of Fig. 8, illustrate the point. The minimum flashover very rightly drawn attention to the fact that the probability of
voltages were 1) wood-porcelain-air path B, 1250 kV, 2) wood- power follow should be evaluated both for air and for wood flashover
porcelain (excluding the air gap), 950 kV, 3) seven porcelain disks paths. We have not examined the former case but agree that it
alone, 750 kV, and 4) wood alone, 600 kV-all values were deter- should be investigated; the results of existing work are referred to
mined with the wood soaked by artificial rain. It is interesting to by Darveniza.1131 Because the observed arc voltages for air differ
note that the flashover voltage of the wood-porcelain combination bv an order from that for wood, we would expect the two arc-
agrees closely with that predicted from the simple expression re- quenching capabilities to be very different and hence it would seem
ferred to previously, viz., Vt = (Vi2 + VW2)1/2. to us that it would be best to characterize each by the parameter
Attention was also drawn by Mr. Stewart and Mr. Littler to the best suited to the particular case. For wood, we believe this to be the
influence of weak-link structures on line performance, and we are power frequency voltage gradient along the wood alone.
grateful for the additional data. Mr. Littler has also questioned the manner in which multiple
The possible influence of prospective system fault current on the flashovers were accounted for in the calculation of the outage rate
arc-quenching capability was raised by Stewart, Dawson, and for the 33-kV system. While it is true that only one outage will
Littler, and the latter also suggested that other relevanit system result from a single lightning incident leading to multiple flashovers,
parameters should be considered. The field data reported by Dawson the final outage rate is based on a weighted average of the individual
and the recent data provided by Armstrong et al.2 suggest that the flashover rates for each path. Since the probability (pi) of arc
extinction differs for each path, the possibility of an outage arising
2 H. R. Armstrong, H. 0. Stoelting, and E. F. Veverka, "Impulse from a type e flashover, when the type a or b flashover does not occur
studies on distribution line construction," IEEE Trans. Power (because of arc extinction), must be accounted for in the averaging
Apparatus and Systems, vol. PAS-86, pp. 206-214, February 1967. process.
Abstract-The facilities of the Grand Coulee Pumping Plant and The pumping plant, located directly behind the west abutment
the original starting procedures used for the 65 000-hp synchronous of Grand Coulee Dam, is shown diagrammatically in Fig. 1. The
motor-driven pumps are briefly described, followed by a description plant was designed to accommodate a total of 12 pumps, each
and schematic diagrams of the controls now used in the automatic capable of supplying the water required to irrigate 100 000 acres
centralized power control scheme. The starting, stopping, and remote of land. Each pump will deliver up to 1600 cubic feet of water
annunciation systems associated with the pumps are described in per second at the normal operating head of 280 feet. There is
detail. A description of the control system for the 108 000-kW
generator associated with the pump unit is also included. The system approximately 800 feet of 12-foot diameter discharge pipe be-
has proved very satisfactory, and after one season of operation with tween the pump and the canal headworks structure. At the
the centralized power control scheme, only two minor modifications headworks, the water discharges into a feeder canal which flows
were made to provide greater reliability. into Banks Lake, the equalizing reservoir with a capacity of one
million acre feet of active storage.