Professional Documents
Culture Documents
Hazard Volume prior to a discharge, the unit should be shut down and/or
dampers operated to close the ducts. Sufficient time must be
In total flooding applications, the hazard area must be an allowed for the plant to stop, or dampers to close, before dis-
enclosed space with no significant openings so that the design charge occurs.
concentration can be achieved and maintained. Generally, the
calculation is based on an empty area; the subsequent furniture Dampers should be installed in both supply and return air
and fittings having little effect on the actual concentration. ducts, as close as possible to the area. The duct volume
Similarly, large equipment cabinets and control panels should between the unit and the damper must be added to the overall
not be considered in the calculation as it is assumed that the volume.
internal area is required to be filled with agent.
Hazard Temperature
Each enclosed space is considered as a hazard area and
requires at least one nozzle. A floor void, ceiling void, cable Determine as accurately as possible the anticipated minimum
duct, etc., is treated as a separate adjacent area and requires and maximum temperatures likely to be experienced within the
simultaneous discharge to occur. protected area. Minimum agent quantity requirements are
based on minimum hazard temperature. At maximum temper-
Ceiling obstructions such as beams that are less than 12 in.
ature, hazard concentration must not exceed the
(300mm) below the slab need not be considered. Obstructions
NOAEL/LOAEL values for normally occupied spaces, refer-
greater than 12 in. (300mm) can affect the distribution of agent
ence NFPA 2001, Section 1-6 “Safety.”
and may require additional nozzles. Consult Pyro-Chem if in
doubt. Please note that floor voids cannot be protected sepa-
rately from the associated room. Hazard Fuels
To determine the volume refer to the site drawings, ensuring All fuels in the hazard must be identified and the correspon-
that the scale is accurate and that heights are denoted, or make ding agent concentration requirements for each must be deter-
a sketch of the area adding dimensions and any relevant details. mined. The design concentration (percent by volume) required
Calculate the volume of each area. for the hazard will be the highest concentration required by any
one of the fuels present in the hazard.
Ventilation
Personnel Safety
If the hazard enclosure has no means of adequate venting after
discharge, consideration should be given to installing a nor- Natural Agent: To avoid possible injury, avoid any expo-
mally closed means of ventilation with extraction arrange- sure to FM-200® in volume concentrations greaterthan 9%
ments which will discharge directly to open air. unless using self contained breathing apparatus. Limit
exposure times as stated in NFPA 2001, Section 1-6
Air conditioning and/or forced ventilation can affect the sys- “Safety.”
tem performance and the quantity of agent required.
Symptoms of overexposure to concentrations greater than
(i) Self-contained air conditioning unit 10.5% may include dizziness, impaired coordination, reduced
A self-contained unit conditions the air within the enclosure mental acuity, cardiac effects or unconsciousness. In the event
and does not rely on a fresh air supply, or draw air from other of overexposure, remove to fresh air immediately and summon
parts of the building. medical assistance.
If the hazard has a self-contained unit and it is located with- Frostbite: Direct skin contact with FM-200® in the imme-
in the area without an outside air supply, no additional agent is diate area of discharge may cause frostbite.
required. It is not necessary to shut down the unit prior to a dis-
charge as the mixing effect is beneficial. Agent Quantities
(ii) Central air conditioning unit Normally the agent quantity is the weight required to produce
A central air conditioning unit relies on air from outside and is the desired concentration at the lowest temperature within the
often linked by ducts to other parts of the building, therefore, hazard enclosure.
OUT
OUT IN
10-30% 006049
30-70%
BULL TEE
IN IN
33.0 FT. 7 PORT
BULL TEE SIDE TEE
(10.05 m)
Figure 25a
Design Example – Calculations When the minimum quantity of FM-200® has been calculated
the weight is compared to the available agent tank size. The
Minimum Agent Quantity is based on the hazard volume at the tank size must be equal to or greater than the weight of agent
minimum anticipated temperature and concentration required. (see Figure 1).
To determine the minimum agent quantity the following equa-
tion is used: With the appropriate tank selected, the previous equation can
( )
be rearranged to determine the concentration based on the actu-
V C
W = _____ _____ al weight as tanks are filled to the nearest lb.
S 100–C
100 WS
C = _______
W = Weight of Agent required – lbs. WS + V
V = Hazard Volume – ft. 3 To calculate the required agent for each hazard volume as a
S = Specific Vapor Volume – ft. 3/lb. percentage of the total agent required;
S = 1.885 + 0.0046 t
% Hazard Agent = _____________________
Individual hazard Volume
t = Design Temperature in Hazard Area –°F Sum of hazard volumes
C = Required FM-200® Design Conc. (% by volume) at
Design Temperature (t) Switch Room: 4262.6/25775.1 = 16.6% of Total Agent
Computer Room: 19237.1/25775.1 = 74.6% of Total Agent
Example: Floor Void: 2275.4/25775.1 = 8.8% of Total Agent
Calculation for two rooms and floor void with the following It is determined from the above that both the Switch Room and
dimensions: the Computer Room can be fed by one manifolded system
using 3 x 180 liter tanks, each filled with 276 lb. (125.2 kg) of
Switch Room: 22.9 x 22.7 x 8.2 ft. = 4262.6 cu. ft.
Agent. The Floor Void would use 1 x 52 liter tank filled with
(7.0 x 6.92 x 2.5 m = 120.7 cu. m)
80 lb. (36.3 kg) as it requires less than 10% of the total Agent
Computer Room: 52.5 x 39.4 x 9.3 ft. = 19237.1 cu. ft. and therefore equates as follows. (Separate tank is required for
(16.0 x 12.0 x 2.83 m = 543.3 cu. m) floor void. If protected with nozzle from Computer Room sys-
tem, the piping would be outside the tee split limits.)
Floor Void: 52.5 x 39.4 x 1.1 ft. = 2275.4 cu. ft.
(16.0 x 12.0 x 0.33 m = 63.4 cu. m) Switch Room: 4262.6/23499.7 = 18.1% of Agent
Computer Room: 19237.1/23499.7 = 81.9% of Agent
t = 70 °F (21 °C) for calculation example
Floor Void: 2275.4/2275.4 = 100% of Agent
Switch Room: (7.2% required design concentration) –
example only The minimum enclosure concentrations can be calculated
based on the actual tank fill 70 °F (21 °C) minimum design
4262.6
______ 7.2
_____ temperature).
W = X = 149.9 lb.
2.207 (100-7.2)
Switch Room: C = 100 (150.2 x 2.207)
___________________ = 7.22%
Computer Room: (7.2% required design concentration) (150 x 2.207) + 4262.6
19237.1
______ 7.2
____ Computer Room: C = ____________________
100 (677.8 x 2.207)
W = X = 676.3 lb. = 7.22%
2.207 (100-7.2) (677.8 x 2.207) + 19237.1
Floor Void: (7.2% required design concentration) Floor Void: 100 (80 x 2.207)
C = ___________________ = 7.22%
2275.4
______ 7.2
_____ (80 x 2.207) + 2275.4
W = X = 80.0 lb.
2.207 (100-7.2)
After determining the minimum weight and concentration, the Piping Practices
maximum concentration can be determined by recalculating
the equation based on the maximum temperature anticipated in Due to the two phase flow of FM-200®, certain piping prac-
each enclosure 80 °F (27 °C) maximum design temperature. tices must be adhered to. Mainly that the flow split must be on
This calculation is required to determine if the maximum con- the horizontal plane. There are two types of tees used in
centration is below the NOAEL limit for normally occupied FM-200® systems, a through/side tee and a bull tee. Both have
areas. limitations on the minimum and maximum allowable flow
splits which are detailed on Page 24.
Switch Room: C = 100 (150.2 x 2.2538)
___________________ = 7.36%
(150.2 x 2.253) + 4262.6 It should also be noted that system designers shall allow a min-
imum of 10 times the nominal pipe diameter around tee splits
Computer Room: C = ____________________
100 (677.8 x 2.2538) = 7.36% before any change of direction.
(677.8 x 2.253) + 19237.1
System designers should aim to design as far as possible bal-
Floor Void: C = 100 (80 x 2.2538)
_________________ = 7.34% anced pipe networks, use minimum lengths of pipe, use mini-
(80 x 2.253) + 2275.4 mum numbers of elbows, maximize pipe volume before the
first tee and incorporate similar pipe run lengths to nozzles.
004844