Professional Documents
Culture Documents
SOURCE DESTINATION
MEASURED 10% Tolerance TOTAL
Core
S.No CABLE ID TYPE FUNCTION LENGTH on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT
(Mtr) Length (mt) LENGTH (mt)
1S1 1S1(R) 1 1S1(R) TB1:1
1S2 1S2(R) 2 1S2(R) TB1:2
6c 4.0mm2
1S3 1S3(R) 3 1S3(R) TB1:3
1 D1 C01 D1CT1_R D1CT1_JB Cu/PVC/SWA/PVC CT CONNECTIONS 5 0.5 6.00 9
2S1 2S1(R) 4 2S1(R) TB2:1
CABLE
2S2 2S2(R) 5 2S2(R) TB2:2
2S3 2S3(R) 6 2S3(R) TB2:3
Page 1 of 7
ANIMALA PSS_33kV LINE-1 (D1) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
MEASURED 10% Tolerance TOTAL
Core
S.No CABLE ID TYPE FUNCTION LENGTH on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT
(Mtr) Length (mt) LENGTH (mt)
TB3:1 E10 1 E10 X02:1
4c 2.5mm2
TB3:3 E30 2 E30 X02:2 PT METERING
9 D1 E04 33kV BUS PT-1_JB D1CRP Cu/PVC/SWA/PVC 30 3 33.00 3
TB3:5 E50 3 E50 X02:3 CONNECTIONS
CABLE
TB3:7 E70 4 E70 X02:4
DC SUB DB-1 16A MCB:+ve J1/D1 1 J1/D1 X03:1 2c 2.5mm2 DC SUB DB-1 TERMINALS TO BE
20 D1 J01 D1CRP DC SUPPLY 8 0.8 9 2
(BCR-D1) 16A MCB:-ve J2/D1 2 J2/D1 X03:2 Cu/PVC/SWA/PVC VERIFIED AT SITE
DC SUBDB-2 16A MCB:+ve J3/D1 1 J3/D1 X03:5 2c 2.5mm2 DC SUB DB-2 TERMINALS TO BE
21 D1 J02 D1CRP DC SUPPLY 8 0.8 9 2
(BCR-D1) 16A MCB:-ve J4/D1 2 J4/D1 X03:6 Cu/PVC/SWA/PVC VERIFIED AT SITE
Page 2 of 7
ANIMALA PSS_33kV LINE-1 (D1) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
MEASURED 10% Tolerance TOTAL
Core
S.No CABLE ID TYPE FUNCTION LENGTH on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT
(Mtr) Length (mt) LENGTH (mt)
Page 3 of 7
ANIMALA PSS_33kV LINE-1 (D1) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
MEASURED 10% Tolerance TOTAL
Core
S.No CABLE ID TYPE FUNCTION LENGTH on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT
(Mtr) Length (mt) LENGTH (mt)
TB:2 K101 1 M2 X04:58
TB:1 K161 2 M1 X04:59
TB:9 K162 3 M9 X04:60
TB2:5 K163 4 H4A X04:61
10c 2.5mm2
TB1:15 K164 5 K164 X04:62 ISOLATOR
28 D1 K07 D189D D1CRP Cu/PVC/SWA/PVC 33 3.3 37.00 4
TB1:16 K165 6 K165 X04:63 INDICATION
CABLE
TB1:2 K166 7 K166 X04:64
SPARE 8 SPARE
SPARE 9 SPARE
SPARE 10 SPARE
Page 4 of 7
ANIMALA PSS_33kV LINE-1 (D1) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
MEASURED 10% Tolerance TOTAL
Core
S.No CABLE ID TYPE FUNCTION LENGTH on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT
(Mtr) Length (mt) LENGTH (mt)
TB3:2 K101 1 M2 X04:21
TB3:1 K119 2 M1 X04:22
TB3:9 K120 3 M9 X04:23
TB3:17 1K101 4 K1 X04:178
10c 2.5mm2 EARTH SWITCH
TB3:18 1K102 5 K2 X04:179
33 D1 K12 D157D D1CRP Cu/PVC/SWA/PVC INDICATION & 36 3.6 40.00 4
TB3:19 1K103 6 K3 X04:180
CABLE INTERLOCK
TB3:20 1K104 7 K3A X04:181
SPARE 8 SPARE
SPARE 9 SPARE
SPARE 10 SPARE
203 K8 1 K3 X04:208
204 K16 2 K4 X04:209
208 K17 3 K11 X04:210
209 K19 4 K4 X04:211
201 K1 5 J1 X04:214
202 K2 6 J2 X04:215
14c 2.5mm2
253 K3 7 K1 X04:216 TC1 CLOSE &
35 D1 K14 D152 D1CRP Cu/PVC/SWA/PVC 60 6 66.00 5
254 K4 8 K54 X04:217 CONTROL
CABLE
256 K5 9 K55 X04:218
259 K6 10 K52 X04:219
260 K7 11 K54 X04:220
SPARE 12 SPARE
SPARE 13 SPARE
SPARE 14 SPARE
Page 5 of 7
ANIMALA PSS_33kV LINE-1 (D1) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
MEASURED 10% Tolerance TOTAL
Core
S.No CABLE ID TYPE FUNCTION LENGTH on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT
(Mtr) Length (mt) LENGTH (mt)
X04:49 K905 1 K101 X04:230
4c 2.5mm2
X04:50 K907 2 K145 X04:231 DC FAIL/BCPU
37 D1 K16 D1CRP D3CRP Cu/PVC/SWA/PVC 9 0.9 10.00 3
X04:80 K909 3 K113A X04:233 FAIL/BCPU MCB TRIP
CABLE
X04:82 K911 4 K114A X04:235
NOTE
1 D1CT1_R Cable BOQ Lugs BOQ
1) LOOP 2S3 TO S' GLAND
CABLE TYPE Total Length (mts) Total GLANDS Lug Size Total Lugs
TYPE
2 D1CT1_Y 1 10pr 1.0mm2 Shield/Armour CABLE 0 0 1.0 Sq.mm Lug 0
1) LOOP 2S3 TO S' 2 2c 2.5mm2 Cu/PVC/SWA/PVC CABLE 117 12 2.5 Sq.mm Lug 472
3 4c 2.5mm2 Cu/PVC/SWA/PVC CABLE 381 18 4.0 Sq.mm Lug 52
3 D1CT1_B 4 10c 2.5mm2 Cu/PVC/SWA/PVC CABLE 771 32 6.0 Sq.mm Lug 0
1) LOOP 2S3 TO S' 5 14c 2.5mm2 Cu/PVC/SWA/PVC CABLE 132 4 16.0 Sq.mm Lug 0
6 19c 2.5mm2 Cu/PVC/SWA/PVC CABLE 0 0 25.0 Sq.mm Lug 0
4 D1CT1_JB 7 2c 4.0mm2 Cu/PVC/SWA/PVC CABLE 0 0 35.0 Sq.mm Lug 0
1) LOOP TB1:3,6,9,10 AND CONNECT TO EARTH 8 4c 4.0mm2 Cu/PVC/SWA/PVC CABLE 132 4 70.0 Sq.mm Lug 0
2) LOOP TB2:1,4,7,10 AND CONNECT TO EARTH 9 6c 4.0mm2 Cu/PVC/SWA/PVC CABLE 16 6 200.0 Sq.mm Lug 0
10 10c 4.0mm2 Cu/PVC/SWA/PVC CABLE 0 0 400.0 Sq.mm Lug 0
5 33kV BUS PT-1_R 11 4c 6.0mm2 Cu/PVC/SWA/PVC CABLE 0 0
1) END OF PRIMARY WINDING TO BE EARTHED 12 4c 16.0mm2 Al/XLPE/SSA/PVC CABLE 0 0
13 1c 25.0mm2 Cu/PVC/SSA/PVC CABLE 0 0
6 33kV BUS PT-1_Y 14 3.5c 70.0mm2 Al/XLPE/SSA/PVC CABLE 0 0
1) END OF PRIMARY WINDING TO BE EARTHED 15 3.5c 400.0mm2 Al/XLPE/SSA/PVC CABLE 0 0
9 D189A
1) LOOP TB:2,10, TB2:6, TB1:3,14
2) LOOP TB1:9,10
10 D189B
1) LOOP TB:2,10, TB2:6, TB1:3,14
2) LOOP TB1:9,10
11 D189C
1) LOOP TB:2,10, TB2:6, TB1:3,14
2) LOOP TB1:9,10
Page 6 of 7
ANIMALA PSS_33kV LINE-1 (D1) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
MEASURED 10% Tolerance TOTAL
Core
S.No CABLE ID TYPE FUNCTION LENGTH on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT
(Mtr) Length (mt) LENGTH (mt)
12 D189D
1) LOOP TB:2,10, TB2:6, TB1:3,14
2) LOOP TB1:9,10
13 D189E
1) LOOP TB:2,10, TB2:6, TB1:3,14
2) LOOP TB1:9,10
14 D189F
1) LOOP TB:2,10, TB2:6, TB1:3,14
2) LOOP TB1:9,10
15 D157B
1) LOOP TB3:2,10
16 D157D
1) LOOP TB3:2,10
17 D152
1) LOOP 354,356,352,419,411,415,407,405
18 D1CRP
1) X01:2,4,6,8,9 TERMINALS DISCONNECTING LINKS TO
BE KEPT OPEN
2) X01:11,13,15,17,18 TERMINALS DISCONNECTING
LINKS TO BE KEPT OPEN
3) LOOP X04:230,232
19 GENERAL
1) ALL CABLE LENGTHS TO BE VERIFIED AT SITE
Page 7 of 7