GUARANTEED TECHNICAL PARTICULARS FOR 110 KV ISOLATORS

ISOLATORS AND INSULATORS

S.No. DETAILS 110 KV ISOLATORS

GENERAL

1 a) Name of the manufacturer GR POWER SWITCHGEAR LTD

b) Country of Manufacture HYDERABAD - INDIA

c) Manufacturers' type designation "DB' Double Break

d) Standard applicable for isolators and earthing IS 9921 Part I to V


switches.

e) Rated voltage Ur (kV) 110 KV

f) Rated current under site conditions (A) at 50 1250 Amps.


Deg. C ambient.

g) Rated frequency (Hz) 50 Hz.

h) Number of poles Three.

i) Whether all 3 poles are ganged mechanically. Yes, ganged mechanically.

j) Pole to pole spacing 2700 mm.

k) Type of installation Outdoor.

2 Guaranteed ratings

a) Rated short time current of isolator for 3 S 31.5 KA/78.75 KA peak


(KA) and dynamic current (kAp).

b) Opening time of isolator and earth switch (s) 10 to 12 Secs.

c) Closing time of isolator and earth switch (s) 10 to 12 Secs.

d) Temperature rise over 50 Deg. C ambient Within the limits of IS.


temperature corresponding to maximum
continuous current (Deg. C).

3 Dielectric withstand capacity of completely assembled


isolator/isolator and earth switch.

a) One minute dry power frequency withstand


test voltage (kV rms)

i) against ground (KV rms) 230 KV rms.


GUARANTEED TECHNICAL PARTICULARS FOR 110 KV ISOLATORS

ISOLATORS AND INSULATORS

S.No. DETAILS 110 KV ISOLATORS

ii) across isolating distance (KV rms) 265 KV rms.

b) 1.2/50 micro s impulse withstand test voltage.

i) against ground (kVp) 550 KV Peak.

ii) across isolating distance (kVp) 630 KV Peak.

c) 250/2500 micro s switching surge withstand


test voltage (dry & wet)

i) against ground (kVp) Not applicable

ii) across isolating distance (kVp) Not applicable

d) Corona extinction voltage (KV rms) Not applicable

e) Radio interference level at 1.1 Ur/_/3 (in micro Not applicable


volts) at 1.0 MHz

f) Total creepage distance to ground 3075 mm


mm.

4 Operating mechanism

A) For Main Blades

a) Type of motor operating / manually driven Manual operating mechanism with reduction gear
mechanism.

b) Manufacturer's type/designation BOM

c) Rated torque of the mechanism 45 Kg m.

d) Type and rating of motor Not Applicable

B) For Earth Switches

a) Type of motor operating / manually driven Manual operating mechanism


mechanism.

b) Manufacturer's type/designation BOM' Bottom operating mechanism.

c) Rated torque of the mechanism 45 Kg m.

d) Type and rating of motor Not applicable.

4.1 Interlocks

a) Whether mechanical/constructional interlock Yes, mechanical/constructional interlock provided.


between isolator and earth switch provided.
GUARANTEED TECHNICAL PARTICULARS FOR 110 KV ISOLATORS

ISOLATORS AND INSULATORS

S.No. DETAILS 110 KV ISOLATORS

b) Details of electrical interlock enclosed for

i) Isolator Electrical interlock enclosed.

ii) Earth Switch Not Applicable

c) Arrangement provided to prevent electrical or Yes, arrangement provided and interlock


manual operation unless interlock conditions continuously rated.
are satisfied whether interlock coil is
continuously rated.

d) Rated DC control voltage and variation 110 V DC variation +10%/-15%


allowed.

e) Power consumption (W) 20 Watts.

4.2 Controls

a) Rated DC control voltage (V) 110 V DC.

b) Limits of voltage +10% / -15%.

c) Power consumption of control coils (Watts) 20 Watts.

5 Constructional Features

a) Minimum clearance in air

i) Between phases (mm) 1600 mm

ii) Between live parts to earth (mm) 1100 mm

iii) Distance between terminals of same phase 1830 mm


(mm)

b) Whether position of earth switch can be Yes, Earth Switch can interchangeable on either
interchanged at site to either side of pole side.

c) Minimum clearance between live part and 1100 mm


earth switch blade throughout the entire
operational arc of earth switch (mm).

d) Terminal pad details

i) Diameter & length 100 x 12.5 mm

ii) Material of pad Alu. Flat.

e) Insulator data
GUARANTEED TECHNICAL PARTICULARS FOR 110 KV ISOLATORS

ISOLATORS AND INSULATORS

S.No. DETAILS 110 KV ISOLATORS

i) Height 1220 mm

ii) Type Solidcore

iii) No. of insulator stacks/phase Three

iv) No. of insulators/stack One

f) Main contacts

i) Type of contacts Reverse loop/turn & twist

ii) Contact area (cm2) 3.84 cm2

iii) Material of contacts HDE Copper Flat

iv) Contact pressure (kg/cm2) Medium pressure

v) Maximum current density under normal 1.6 A for HDE Cu. Flat.
current carrying capacity (A/cm2) 2.0 A for HDE Cu. Tube.
1.0 A for Alu.
1.25 A for Alu. Tube.

vi) Thickness of silver plating 10 to 15 microns.

g) Number of auxiliary contacts on isolator / pole 4 NO / 4 NC


for owner's use.

h) Number of auxiliary contacts on earth switch 4 NO / 4 NC


pole for owner's use.

i) Auxiliary contacts

i) Rated voltage (V) 110 V DC

ii) Rated continuous current (A) 10 Amps

iii) Rated DC breaking current with 20 ms time 2 Amps.


constant (A).

j) Mounting dimensions of isolators

i) Distance between supports 1220 mm.

ii) Top dimensions of support 200 mm.

k) Height from mounting plane to top of terminal 4600 mm


stud.
GUARANTEED TECHNICAL PARTICULARS FOR 110 KV ISOLATORS

ISOLATORS AND INSULATORS

S.No. DETAILS 110 KV ISOLATORS

l) Whether cable glands required included in the


NOT IN OUR SCOPE OF SUPPLY
scope for inter pole cabling to be done by the
owner.

CONTROL CABINETS:

1 Manufacturers' Name GRPS or its equivalent

2 Indoor/Outdoor application Outdoor.

3 Design ambient air temperature (Deg C) 45 Deg. C.

4 Standard applicable IS 722 & IS 1298.

5 Thickness of sheet steel (mm) and whether cold rolled or 2.64 mm Hot rolled.
hot rolled.

6 Degree of protection provided IP 55

7 Bill of material for all the equipment mounted on control


cabinet giving the following details:

a) Make and type

b) Applicable standard

c) Voltage rating
Will be submitted later
d) Current rating

e) Duty class, if applicable

f) Manufacturer's catalogue No.

g) Total heat load of cabinet (for purpose of


ventilation requirement).

8 Colour of finish paint IS :5

a) Outside 631 of IS 5

b) Inside 631 of IS 5

9 Control wiring

a) Size of conductor

i) for CT circuits Not applicable

ii) for other circuits 2.5 Sq mm


GUARANTEED TECHNICAL PARTICULARS FOR 110 KV ISOLATORS

ISOLATORS AND INSULATORS

S.No. DETAILS 110 KV ISOLATORS

b) Conductor Solid/Stranded Stranded.

c) Number of stranded/conductor 7 Nos.

10 Terminal Blocks

a) Make and type Elmex / Connectwell

b) Current rating

i) Power terminals (A) 35 Amps

ii) Other terminals (A) 25 Amps

11 Space heater rating at 240 V DC Not Applicable

12 Control cabinet drawing showing the following:-

a) Outline dimensions, floor opening,


floor/wall/pedestal fixing arrangements Will be submitted later
weights etc.,

b) Front view, inside view showing the mounting


arrangement of various equipment. Will be submitted later

13 Schematic / wiring diagram of control cabinet enclosed. Will be submitted later

14 Interconnection drawing showing owner's external cable,


connections to the control cabinet enclosed isolators & Will be submitted later
Terminal connectors.

15 Type test report to verify degree of protection enclosed. Will be submitted later

16 Details of terminal rows

i) Whether arranged vertical or horizontal. Vertically

ii) Clearance from adjacent components. 250 mm

iii) Distance between rows 150 mm.

iv) Whether transparent protection cover Yes, provided.


provided.

BUSHING / SUPPORT INSULATORS:

1 Manufacturers' Name SIL or IEC


GUARANTEED TECHNICAL PARTICULARS FOR 110 KV ISOLATORS

ISOLATORS AND INSULATORS

S.No. DETAILS 110 KV ISOLATORS

2 Type Solidcore

3 Applicable standards IEC - 168

4 Height 1220 mm

i) Diameter (Top) 127 mm

ii) Diameter (Bottom) 184 mm

5 Total creepage distance (mm) 3075 mm

6 Rated voltage (kV) 123 kv

7 Power frequency withstand voltage for 1 min. (kV rms) 254/230 kv rms
dry and wet.

8 1.2/50 micro sec. Impulse withstand voltage (kVp) 550 KV Peak

9 250/2500 micro sec. Switching impulse withstand voltage Not applicable.


(kVp) dry and wet.

10 Corona extinction voltage (KV) 105 kv

11 Weight (Kgs) 60 Kgs.

12 Max. allowable span (mm) --

13 Cantilever strength (Kg) 6 KN

14 OGA Drawing enclosed Yes.


TERMINAL CLAMPS AND CONNECTORS:

1 Manufacturers' Name GRPS or its equivalent

2 Applicable standards IS:5561

3 Type Rigid

4 Material of connector

a) Clamp body LM 6 Alu. Alloy

b) Bolts & Nuts MS HDG

c) Spring washers Spring Steel.

5 Rated current 1250 Amps

6 a) Rated terminal load (Kg) --


b) Factor of safety Two
GUARANTEED TECHNICAL PARTICULARS FOR 110 KV ISOLATORS

ISOLATORS AND INSULATORS

S.No. DETAILS 110 KV ISOLATORS

7 Minimum thickness of any part (mm) 10 mm.

8 Weight of clamp complete with hardware 1.0 kg

9 OGA Drawing enclosed Will be submitted later

for GR POWER SWITCHGEAR LTD.,

AUTHORIZED SIGNATORY