You are on page 1of 4

TRANSMISSION AND DISTRIBUTION

Checking earth
electrode impedance
Information from Fluke

Most facilities have earthed electrical systems, so that in the event of a lightning strike or utility overvoltage, current will find a safe path to earth.
To ensure a reliable connection to earth, electrical codes, engineering standards, and local standards often specify a minimum impedance
for the ground electrode. This application note describes the principle methods for testing earth electrodes and connections.

The primary goal of an earthing system is Resistivity increases with decreasing f r e q u e n c y a n d i t s h a r m o n i c s.


to ensure personnel safety and protection temperature This prevents stray currents from
of installations against damage. Two l Can be affected by buried metal interfering with ground impedance
important phenomena are lightning and tanks, pipes, re-bar, etc. measurements
power system faults. These can cause l Separate source and measure leads to
l Varies with depth
circulation of large currents, which might compensate for the long leads used
create hazardous voltages in installation Since resistivity may decrease with depth, in this measurement
structures. one way to reduce earth impedance
l Input filtering designed to pick up the
is to drive an electrode deeper. Using test signal and screen out all others
The grounding and bonding systems an array of rods, a conductive ring or a
connect the earth near the building with grid are common ways of increasing the l Clamp-on ground testers are ver y
the electrical system and building steel. different because they have both a
effective area of an electrode. Multiple
In a lightning strike, the facility will be source transformer and a measurement
rods should be outside of each other ’s
at approximately the same potential. transformer. The clamp-on ground
areas of influence to be most effective
By keeping the potential gradient low, tester uses advanced filtering to
(see Fig. 2).
d a m a g e i s m i n i m i s e d. Fi g. 1 s h o w s recognise the test signal and screen
an earthing system for a commercial The acceptable limits for earth electrode out all others.
building. impedance for different types of installation
The fall-of-potential method
are given in the relevant national standards
Earth electrode impedance – in this case South African National The fall-of-potential method is the traditional
Standards (SANS. method for testing electrode resistance
The impedance from the electrode to the
and is specified in numerous standards.
earth varies depending on two factors: the
How do earth impedance testers work? In it’s basic form, it works well for small
resistivity of the surrounding earth and the electrode systems like one or two earth
structure of the electrode. There are two types of earth impedadance
rods. We will also describe the Tagg slope
testers: Three and four point testers and
The resistivity of earth is complicated, technique which can help draw accurate
clamp-on testers (Fig.3). Both types apply
because it: conclusions about larger systems.
a voltage on the electrode and measure
l Depends on composition of the soil the resulting current. A three or four-pole How it works
(e.g. clay, gravel and sand) tester combines a current source and
voltage measurement in a multimeter- The fall-of-potential method connects to
l Can vary even over small distances the earth at three places. The connections
due to the mix of different materials style package. They use multiple stakes
and/or clamps. are made to:
l D e p e n d s o n m i n e r a l ( e. g . s a l t )
l E/C1 – the earth electrode being
content Earth testers have the following
tested.
l Varies with compression and can vary characteristics:
l S/P2 – A voltage (potential)
with time due to settling l AC test current measurement stake driven into the
l Changes with temperature, l Test frequency that is close to, but earth some distance away from the
freezing (and thus time of year). distinguishable from the power electrode.

Fig. 1: An earthing system combining reinforcing Fig. 2: Earth electrodes have “areas of influence”
steel and a rod electrode. that surround them. Fig. 3: Clamp-on earth tester.

energize - August 2009 - Page 25


ADsa7/05 03.08.2005 18:53 Uhr Seite 1
ADsa7/05 03.08.2005 18:53 Uhr Seite 1
ADsa7/05 03.08.2005 18:53 Uhr Seite 1

TRANSMISSION AND DISTRIBUTION Insulati


ADsa7/05 03.08.2005 18:53 Uhr Seite 1
ADsa7/05 03.08.2005 Enhanceme
18:53 Uhr
ADsa7/05 03.08.2005 18:53 Uhr
The 62% Rule Controll
with
Depth of Distance Distance
electrode from E to from E to
protecti
You may be able to use a shortcut if your
under Test (E) potential
stake (P2)
current stake
(C2) test meets the following criteria: Wild Li
Interventi
2 15 25 l You are testing a simple electrode
(not a large grid or plate) Wild Life Intervention
3 19 30
l You can place the current stake
6 25 40
30 m or more from the electrode
9 31 50

Controlled
under test
Table 1: Approximate distance to auxiliary stakes l The soil is uniform We provide a diverse ra
using the 62% rule (in meters).
and HV cable joints an
Under these conditions place the current
We
We provide
bushings aa diver
and bimetall
provide diver
stake 30 m or more from the electrode
and
piercing HV cable
connectors, jointw
Fig. 4: Schematic for fall-of-potential.
Widest Distance Distance
under test. Place the Bowthorpe EMP
potential stake andat and
HV cableRaychem joint
world-wide bushings
market for
bushings and bim and
the bim
pro
dimension from E to from E to 62% of the distance between the currentUnit A, 59 Roan Cresc
(Diagonal, potential current stake and the electrode extensive
under Lifepiercing
Wildrange
test Intervention
and
connector
of polymeric
piercing connector

Co
PO Box 134, Olifantsfo
diameter or stake (P2) stake (C2) take a measurement.service in overtake
As a check, 130 countries a
straight-line) of climatic conditions
Unit
Unit A, from
A, 5959 Roan
theCa
Roan C
electrode array two or more measurements: one with the
use in distribution
PO Box and 134, transmOlifa
under test (E) potential probe 1 m closer to the electrode
PO Box Enhancemen
TIS supplies 134, Olifa
world leading
products and Insulation
components Tyc
20 30 50 under test, and another 1 m farther away EMP and Raychem
conductors or busbars are a
designed andwildlife.
manufactured
the protection of utilityare
The covers ma t
(see Fig. 6). If you are on the flat portion
porcelain surgeBowth
performance arresters
Tyco a
Elec
25 50 80
of the fall-of-potential curve, thenservice.the in all climatic c
installations
Low residual voltages world- in com
30 70 100 readings should be roughly the sameof and
tion capacity A the for
Designed
variety metal-oxid
of use in distribu
extens
different sh
50 100 170 you can record the first reading asarresters
High-voltage your and
products
breaker components
bushings,
– with bus
resistance.
manufactured
bushings, service
to IEC and
voltage A
regul
70 130 200 seismic forceswith ofthe0.5g to IEE
high energy absorp 6
custom makes these sha
a compact design andclimati
of damage. High-voltage
with aa

C
Table 2: Approximate distance to auxiliary stakes The Tagg slope technique seismic forces
Installation of be
use
can 0.5gmade
to IE
in
insulated switchgear
design
exit
for electrode arrays (in meters). We provide a diverse range of market leading products for underground holes to– the
andcable
with make
a choice ovoft
require
and
and HV cable Large
joints andelectrodes or grounding
the network systemsscreenedproduc
engineer.
this arrester
and reusedfamily the idea
for other m
terminations (conventional and plug-in), and unscr

Controlled
lifetime costs.
bushings and require
bimetallic special
mechanicalconsideration.
connectors. We also If supply
you’ve overheaddesign
• Low-voltage line eq
gapless
plotted
piercing connectors, wedgeresistance
type line clamps 2 and
'.-'$+($***,)
readings forclamps,
substation nine
For • more
High- and medium-vo
across all voltag
information on
different P2 locations and 2 ! TIS• Energy
outdoorsales
&%!,%-'$+
there is no clear Bow
applications
depart
Lowwor
• Compact medium-volBow re
But somewhere in the middle, something Unit A, 59 Roan Crescent, Corporate Park North,
flattening on your graph, Old Pretoria
outdoor
then the Road,
applications
tagg Randjespark Ex
Unit• A,
Rugged
59 Roan wor
arresters
Crescenfor
interesting happens. PO Box 134, Olifantsfontein, 1665. Tel +27(0)11 635 8000 Fax
2 +27(0)11
• tion
635
Protection
'%(+%!,%-'$+ 8100
Randjespark Ext 103, Mfo
systems ca
exte
exte
slope technique (also called the slope
Bowthorpe EMP and Raychem
Tel +27(0)11
2 ,))*+)*'))!$.0
635 8000
High-v serv
serv
F
As we move from the influence of the method) can help establish the earth
Unit A, 59 Roan Crescent,
world-wide market
Randjespark
2 )'++!'&*0*+%*')%! forExtthe
seismi clim
pr
103, Midr
Fig. 5: A plot of measured impedances versus electrodes and into the mass of the earth, impedance. clim
extensive range
for high-voltage
+27(0)11 635 8000 Fax
ofcable
polymeric use +2
position of the potential stake allows us to see the the test current no longer causes significant a sheat
compuse
pro
earth impedance. change in potential. If you plot a series of Fig. 7 shows an example service in over
dataset for which130 countries
insulat prod
there is no obvious flat section.conditions
climatic There can from the des
measurements, moving the potential stake desi
be a number of reasons for a curve like
the ne
use in distribution and transm

Co
away from the electrode under test, and Low
towards the current stake you will notice this: products and componentsLow Ty
tion
a flattening of the curve. An ideal curve designed and manufactured 2 '.tion
H/C2 – A current stake driven into the l For electrode systems that cover large Hig
l
is shown in Fig 5. The flattest part of the 2 ! High
seis
earth a further distance away. areas it may be difficult to place stakes seis
curve is where the earth resistance is read.
far enough away Low residual voltages in com
outdoa co
Fig. 4 shows this schematically and Fig. 5 In reality, the curve never goes entirely flat a co
tion capacity of the metal-oxi 2 '% insu
l You may not be able to place the C1 Bowtho insu
shows the three connections made using
a typical earth tester. Raytech
but reaches a very gentle slope where
changes in resistance are small.
High-voltage arresters2 –,
stake at the center of the electrode
world-w
seismic forces of 0.5g 2to)'+
IEE
withthe
the
ENERGY
l The area you haveatocompact place stakes mayand 2 '
The tester injects an alternating current The extent of the influence of the electrode design extensi
with
for
2 'ha
depends on its depth and its area. Deeper be limited insulated switchgear – make2 !
into the earth between the electrode Raytech Energy, 42 Industry Road, Olifantsfontein 1665 service
2 !
ou
under test (E) and the current stake (C2), electrodes require thatTel.
the011
current
- 316 stake
1628, be Fax 011 - If316 you have resistance the
1680 network
readings at theengineer.
20%, ou
driven farther away (see Table 1). For large climatic
2 '
and measures the voltage drop between Email: dpillay@aberdare.co.za,40% website:
and http://www.raytech.co.za
60% points between E and C2, 2 '
the P2 stake and E. It then uses Ohm's law ground rings, grids or arrays, theandinfluence
Bowthorpe EMP
then you can apply the
Raychem are trademarks.
procedure to the
2 '.-'$+($***,)
use in
2
2 ,
,d
2 )
to calculate the impedance between
of the electrode may extend for hundreds
of meters. Table 2 gives suggested starting
data you’ve already taken. 2 ! Calculate the produc
&%!,%-'$+ R
2 )'
fo
for
P2 and E. To perform the test position slope coefficient (μ) using three resistance
outdoor applicationsdesigne
points for current and potential stake measurements from 220%, 40% and 60%
the C2 stake at some distance from the '%(+%!,%-'$+
placement. of the distance from the electrode under
electrode under test. Then, keeping the 2 ,))*+)*'))!$. R
test to the C2 current stake. Low res
C2 stake fixed, move the P2 stake along The three-wire measurement will deliver 2 )'++!'&*0*+%*')% T
the line between E and C2, measuring good results if you use a short C1 lead, or tion cap E
for high-voltage cable sheaB
the impedance along the way. The tricky
part comes in determining where to drive
if you don’t mind having a fraction of an
ohm of lead resistance in your reading.
Raytech High-vo
seismic
ENERGY
the stakes to get a true reading of the For earth impedance measurements
over 10 Ω, the effect of the resistance Then go to Table 6 and look up the P2/C2 a comp
impedance between the electrode and
the earth. of the C1 lead will be small. But for Raytech very ratio Raytech
Raytech
that corresponds to
Energy, 42 Industry Road, Olifantsfontein 1665μ. This will tell you insulate
precise measurements, especially at where
Tel. 011 - 316 1628,ENERGY to look
ENERGY on your
Fax 011 - 316 1680 graph to ascertain the netw
The current probe generates a voltage low resistances, a fourwire tester allows the earth resistance. website:
Email: dpillay@aberdare.co.za, For the sample data
http://www.raytech.co.z
between itself and the electrode under you add a fourth lead to eliminateBowthorpe the EMPinandFig. 7: are
Raytech Energy, 42 Industry Road, Olifantsfontein 1665
Raytech Energy, 42 Industry Road, Olifantsfontein2 1665
Raychem trademarks.
test. Close to the electrode, the voltage contribution of the C1 lead. By running Tel. 011 - 316 1628, Fax 011 - 316 1680 '.-
Tel. 011 -
͸ǡͺȂ 316ͷǡͺ Fax 011 - 316
1628, 1680
is low and the potential probe is said to a separate potential lead (P1) to the Email: dpillay@aberdare.co.za, 2 ! 
website: http://www.raytech.
Raytech ߤ Email:
 ൬ dpillay@aberdare.co.za,
ൌ ൰  ൌareͲǡ͹ͳ website: http://www.raytech.c
be within the influence of the electrode. electrode under test you can take the ͷǡͺȂ
Bowthorpe
Bowthorpe ͶͶ
EMP and Raychem
EMP and
trademarks.
Raychem are trademarks. outdo
Close to the current probe the voltage is drop along the C1 current lead out of the
almost the full voltage output by the tester. measurement.
ENERGY
If we go to the table, for μ = 0,71 the 2 '%(
2 ,
Raytech
energize - August Energy,
2009 42 26
- Page Industry Road, Olifantsfontein 1665 2 )'+
Tel. 011 - 316 1628, Fax 011 - 316 1680
Email: dpillay@aberdare.co.za, website: http://www.raytech.co.za for hig
TRANSMISSION AND DISTRIBUTION
corresponding P2/C2 percentage is
59,6%. So the approximate earth
impedance would be measured at
(59,6% X 100 m), or at 59,6 m. This is very
close to our 60% point at 60 m, where we
read 6,8 Ω. So it would be safe to say the
earth resistance for the electrode under
test is roughly 6,8 Ω.

The selective method


The selective method is a variation of the
fall-of-potential method, available on
high-end earth testers like the Fluke 1625.
The supply neutral, building steel and earth
electrode are all bonded and earthed. In
a traditional fall-of-potential test you have
Fig. 7: Earth impedance can be found from this
no way of knowing how much current is Fig. 6: Stake positions for the 62% rule. curve by using the Tagg slope technique.
flowing between any particular electrode
and the C2 current stake. Selective testing
uses an integrated, high sensitivity clamp-
on current transformer to measure the method, you are actually testing a loop
including:
test current in the electrode under test.
(Fig. 8). The selective earth tester digitally l Electrode under test
filters the current measurement to minimise l Earth electrode conductor
the effects of stray currents. l The main bonding jumper
Stakeless or clamp-on method l The service neutral
l Utility neutral-to-earth bond
The stakeless or clamp-on method allows
you to measure the impedance of a l Utility earth conductors (between
series loop of ground electrodes. The test poles)
is simple and it may be performed on an l Utility pole earth
electrode that is connected to a working In this method the clamp checks the Fig. 8: Connections for selective ground
electric service. To make the measurement continuity of the interconnections of all of electrode measurement.
the tester uses a special transformer the components above. An abnormally
to generate a voltage on the earth high reading or an open circuit indication
conductor at a unique test frequency. It on the instrument points to a poor
uses a second transformer to distinguish connection between two or more of the
the test frequency and measure the aforementioned critical components.
resulting current through the circuit, which The earth electrode of most facilities is in
is determined by the loop resistance. parallel with numerous distribution earth
Fig. 10 shows the connection of the electrodes.
source and measure clamps of the Saturn
Two-pole method
GEO X. Fig. 9 shows the equivalent test
circuit for the stakeless method. When you The two-pole method uses an auxiliar y Fig. 9: Connections for selective electrode
test a building earth electrode using this e l e c t r o d e s u c h a s a w a t e r p i p e. impedance measurement.

Summary of earth electrode test methods advantages and drawbacks


Advantages Drawbacks
Fall-of-potential Widely accepted You have to disconnect the earth
When you see the characteristic curve you know The stakes may not be easy to drive
you’ve got a good measurement. There may not be space around the earth electrode
to drive the stakes
Selective method Don’t have to disconnect the electrode The stakes may not be easy to drive
Widely accepted There may not be space around the earth electrode
When you see the characteristic curve you know to drive the stakes
you’ve got a good measurement.
Stakeless method Convenient Assumes a low-impedance parallel path
Saves time Possible to get very low readings by mistakenly
No disconnections measuring on a hard-wired loop
No stakes
Two-pole method Convenient Impossible to judge the integrity of the auxiliary
Saves time electrode.
No disconnections Can’t be sure you are outside the area of influence
No stakes

Table 3:

energize - August 2009 - Page 28


TRANSMISSION AND DISTRIBUTION

µ P2/C2 µ P2/C2 µ P2/C2 µ P2/C2 µ P2/C2

% % % % %

0,40 43,3 0,65 60,6 0,90 56,2 1,15 50,7 1,40 43,1

0,41 64,2 0,66 60,4 0,91 56,0 1,16 50,4 1,41 42,7

0,42 64,0 0,67 60,2 0,92 55,8 1,17 50,2 1,42 42,3

0,43 63,9 0,68 60,1 0,93 55,6 1,18 49,9 1,43 41,8

0,44 63,7 0,69 59,9 0,94 55,4 1,19 49,7 1,44 41,4

0,45 63,6 0,70 59,7 0,95 55,2 1,20 49,4 1,45 41,0

0,46 63,5 0,71 59,6 0,96 55,0 1,21 49,1 1,46 40,6

0,47 63,3 0,72 59,4 0,97 54,8 1,22 48,8 1,47 40,1

0,48 63,2 0,73 59,2 0,98 54,6 1,23 48,6 1,48 39,7

0,49 63,0 0,74 59,1 0,99 54,4 1,24 48,3 1,49 39,3

0,50 62,9 0,75 58,9 1,00 54,2 1,25 48,0 1,50 38,9

0,51 62,7 0,76 58,7 1,01 53,9 1,26 47,7 1,51 38,4

0,52 62,6 0,77 58,5 1,02 53,7 1,27 47,4 1,52 37,9

0,53 62,4 0,78 58,4 1,03 53,5 1,28 47,1 1,53 37,4

0,54 62,3 0,79 58,2 1,04 53,3 1,29 46,8 1,54 36,9

0,55 62,1 0,80 58,0 1,05 53,1 1,30 46,5 1,55 36,4

0,56 62,0 0,81 57,9 1,06 52,8 1,31 46,2 1,56 35,8

0,57 61,8 0,82 57,7 1,07 52,6 1,32 45,8 1,57 35,2

0,58 61,7 0,83 57,5 1,08 52,4 1,33 45,5 1,58 34,7

0,59 61,5 0,84 57,3 1,09 52,2 1,34 45,2 1,59 34,1

0,60 61,4 0,85 57,1 1,10 51,9 1,35 44,8

0,61 61,2 0,86 56,9 1,11 51,7 1,36 44,5

0,62 61,0 0,87 56,7 1,12 51,4 1,37 44,1

0,63 60,9 0,88 56,6 1,13 51,2 1,38 43,8

0,64 60,7 0,89 56,4 1,14 50,9 1,39 43,4

Table 5: Table for the Tagg slope techniue (for 2 decimal places).

Fi g. 1 2 s h o w s t h e c o n n e c t i o n s. T h e
tester measures the combined earth
impedance of the electrode under test,
the earth impedance of the auxiliar y
electrode, and the impedance of the
measurement leads. The assumption is
that the earth impedance of the auxiliary
e l e c t r o d e i s v e r y l o w, w h i c h w o u l d
probably be true for metal pipe without
plastic segments or insulated joints. The
effect of the measurement leads may
Fig. 10: Connection for a stakeless measurement. be removed by measuring with the leads
shorted together and subtracting this
reading from the final measurement.

Because of the unknowns involved in this


technique, it is recommended only when
the earthing system and auxiliary electrode
are well known. Fig. 12: Equivalent circuit for
two-point measurement.

ͳ
ܴ௘௤  ൌ   ൌ  ͳൗʹ π Contact Val Verwer, Comtest,
Fig.11: Test current paths in the stakeless method. ͶͲܺ ͳൗʹͲπ Tel 01 254-2200, info@comtest.co.za v

energize - August 2009 - Page 29

You might also like