You are on page 1of 94

User Manual

PV Grid-Connected
Inverter




II
Function Description
Wiring Procedure

 。





5 min



A B C D
TN-C TN-C-S TN-S
Transformer Transformer Transformer
L1 L1 L1
L2 L2 L2
L3 L3 L3
PEN N N
PE PE

L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
Inverter Inverter Inverter

TT IT
Transformer Transformer
L1 L1
L2 L2
L3 L3
N

L1 L2 L3 N PE L1 L2 L3 N PE
Inverter Inverter

SG 110 CX

Code of Product Series


Code of power level
PV grid-connected inverter
1
6

3
4 7

Length Width

Height
× ×

.
DC1 MPPT
(Boost 1)
L1

DC EMI AC AC AC EMI
Filter Relays L2
Filter Filter

MPPT L3
DC9 (Boost 9)
N

DC DC BUS Inverter Circuit


Current Switch DC SPD (DC/AC) AC SPD PE
Monitoring

Function Description


Transformer
PV array Inverter Grid
Rise the to-ground electromotive force
at the negative pole of the PV array







光伏并网逆变器
GRID-CONNECTED PV INVERTER
1
型号 Model SG110CX
序列号 S/N
直流输入DC-Input
最大输入电压 Max. Input Voltage DC 1100 V
最小MPP电压 Min. MPP Voltage DC 200 V
最大MPP电压 Max. MPP Voltage DC 1000 V
最大输入电流 Max. Input Current DC 9*26 A
最大短路电流 Isc PV DC 9*40 A
交流输出AC-Output 2
额定输出电压 Rated Output Voltage 3/N/PE AC 400/230 V
额定输出频率 Rated Output Frequency 50/60 Hz
最大输出电流 Max. Output Current AC 158.8 A
额定输出功率 Rated Output Power 100 kW
最大视在功率 Max.Apparent Power 110 kVA
功率因数范围 Power Factor Range 0.8 Leading...0.8 Lagging

安全等级 Safety Class Ⅰ


过压等级 Overvoltage Category Ⅲ[AC], Ⅱ[DC]
防护等级 Enclosure IP66
工作温度范围 Ambient Temperature -30℃ ... +60℃

阳光电源股份有限公司
SUNGROW POWER SUPPLY CO., LTD. 4
www.sungrowpower.com 中国制造 Made in China
a
Inverter (x1) Mounting-bracket (x1) Screw-in handle (x4)

DC connectors and cord Four-hole sealing block for


communication terminal (x3) M10 fastening screw sets (x4)
end terminals (x18)

b
Screws Allen wrench (x1) Documents c

× × ×




IP66


Max. RH: 100%


Max.:+60°C Min.: -30°C
(non-condensing)

 Confined Space

Made of non-inflammable materials

Max. load bearing capacity ≥ 4


KG times of inverter weight

°
Vertical Backward Horizontal Forward Upside down

°
0~80

10°

≥600mm

≥800mm

≥400mm

≥1000mm

≥450mm

≥800mm ≥800mm ≥800mm ≥400mm

≥500mm


880.0

φ φ




φ

×
×

M4

1.5N.m
BC
D

A E
F

16mm

35N.m
×

M6

4.5N.m

×
×
×
M4

1.5N.m
A B
C

16mm

35N.m

M6

4.5N.m




E
A B C D
A Inverter B C

1 3
4

< ≤


L = E + (2~3)mm

1 2

6~7N.m

 ,

 ℃

 ±






L1 L2 L3

M1 M2 M3

M4

 ≤

65mm

47mm

54mm

Aluminium adapter
terminal

Aluminium cable
When D≥47mm,
remove this seal

Cable outer
diameter D

L = E + (2~3)mm
N

L1
L2
L3
PE E

N
L1
L2
L3
PE
M12

20~30 N.m

Phase cable

M8

7~9 N.m

PE cable

83mm

15~19N.m



DC 1
PV input 1 MPPT1
DC 2

DC 1

PV input 2 MPPT2 Inverter

DC 2
· · ·

· · ·

DC 1

PV input 9 MPPT 9
DC 2

7mm

Positive Crimp Contact

Negative Crimp Contact

 
Positive Insulator Negative Insulator

Crimp Contact Crimp Contact

Cable Gland Cable Gland

ON

OFF

880.0
+

-
+
+
- - +
-

- +
a b c 2
1

L = E + (2~3)mm

Tracking system power cable

N
L1
L2

L3
PE
AC cable
M12

20~30 N.m

Phase cable

M8

7~9 N.m

PE cable

33mm
83mm

6~8N.m
15~19N.m

 (≥ ,


RS485-RJ45 interface RS485 - Dip switch

SW1 SW2

RS485
OFF OFF
RS485 120Ω 120Ω DI2+ DI2- DI2- DI2-
ON ON

RS485 TRACKER LOCAL STOP ALARM


A1 B1 PE A1 B1 PE A2 B2 PE A2 B2 PE DI1+ DI1- DI1- DI1- COM1 NC1 NO1 COM2 NC2 NO2

RS485 - terminal block interface


Inverter Terminal block RJ45

RS485
A1 B1 PE A1 B1PE

RS485 RS485
OUT

OUT OUT

Logger PC

RJ45 RJ45 RJ45

RS485 RS485
RS485 RS485

RS485 RS485

OUT OUT OUT

IN IN

Terminal block Terminal block Terminal block


RS485 RS485 RS485
A1 B1 PE A1 B1 PE A1 B1 PE A1 B1 PE A1 B1 PE A1 B1 PE

OUT IN OUT IN OUT

Inverter 1 Inverter 2~(N-1) Inverter N


OUT
OUT IN OUT IN

Plant monitoring station

Logger
120Ω

SW1 SW1 SW1


OFF OFF OFF
120Ω 120Ω 120Ω
ON ON ON

Inverter 1 Inverter 2~(N-1) Inverter N


OUT
OUT IN OUT IN

Plant monitoring station

Logger


Wiring Procedure


7 mm

a b c 2
1

M2

1 3
2 4 5 6 0.2 N.m

Insert the terminal .


33mm

6~8 N.m

a b c 2
1

Wire sequence:
Pin 1: White-and-orange Pin 1----8
2: Orange
Pin 3: White-and-green Pin
4: Blue
Pin 5: White-and-blue
Pin 6: Green
Pin 7: White-and-brown
Pin 8: Brown
12345678
Pin 3 and Pin 6 are for
communication connection

RS485+ A RS485- B
33mm

6~8 N.m

SW1 SW2
RS485

OFF OFF
120Ω 120Ω DI2+ DI2- DI2- DI2-
RS485

ON ON

RS485 TRACKER LOCAL STOP ALARM


A1 B1 PE A1 B1 PE A2 B2 PE A2 B2 PE DI1+ DI1- DI1- DI1- COM1 NC1 NO1 COM2 NC2 NO2

Emergency stop dry contact Fault output dry contact



逆变器
Inverter interior Inverter interior

Free of fault,
Fault occurs, relay trips.
relay does not trip.
Circuit is connected, and
Circuit is disconnected, and
LED indicator gets on
NC COM NO
LED indicator is off NC COM NO

逆变器
Inverter interior Inverter interior

Free of fault, relay does not Fault occurs, and relay


trip. trips.
Circuit is connected, and LED Circuit is disconnected,
indicator is steady on and LED indicator gets off.
NC COM NO NC COM NO


Inverter interior

DI DI PGND PGND

passive switch

Inverter 1 Inverter 2 Inverter N

DI DI PGND PGND DI DI PGND PGND


... DI DI PGND PGND

Controlled
switch

Inverter 1 Inverter 2 Inverter N

DI DI PGND PGND DI DI PGND PGND


... DI DI PGND PGND

Controlled
switch

A1 A1 B1 B1 A1 A1 B1 B1 A1 A1 B1 B1

IN IN
OUT OUT OUT

Logger
Ethernet port RS485 terminal

PC
Network port
Ensure that the impedance at the input node is less than 600Ω.

4.2~4.5 N.m




iSolarCloud

iSolarCloud Home

Faults and alarms


Running information

Power generation

History record
Events

More Parameter setting System parameter

Password change


Nameplate

QR code
 “ ”,

Set according to local standards


1
2
3
PID recovery

7
Fault Alarm





1

2
Risk of burns and electric shock!

“3.4 ".




M6

2
℃ ℃

℃ ℃










Sungrow Power Supply Co., Ltd.
Add: No.1699 Xiyou Rd.,New & High Technology Industrial Development Zone, 230088,Hefei, P. R. China.
Post Zip: 230088
Web: www.sungrowpower.com Tel: +86 551 6532 7834/6532 7845
E-mail: info@sungrow.cn Fax: +86 551 6532 7856

Specifications are subject to changes without advance notice.