16 Accessories
The following accessories are available for the ADVC:
Ensure that the ADVC is switched IOEX;
off before proceeding with the TTS.
installation of any accessory.
Additional accessories are under development.
Input Output Expander Card The Input Output Expander (IOEX2) card provides optically isolated
(IOEX2) input contacts and voltage free output contacts to allow connection of
an external Remote Terminal Unit (RTU). It is installed in a die cast,
sealed enclosure which is mounted on, and earthed via, a DIN rail in the
customer compartment.
A “mapping” held in the ADVC database controls the function of the
IOEX2. It specifies what database information is “mapped” into the
IOEX2 outputs and which controls are “mapped” into the IOEX2 inputs.
The bottom line of the IOEX Status display page identifies the mapping
loaded:
The standard mapping for inputs and outputs are shown in "" -
page 16-3 and "Outputs - Standard Mapping" - page 16-4.
Some equipment may be supplied with alternative mappings.
Item Description
Switchgear Any
Inputs 8
Outputs 8
16-1
Advanced Controller Operations Manual
IOEX2 Installation
The IOEX2 is mounted on the DIN rail in the Customer enclosure at the
top of the ADVC as shown in the following picture:
The IOEX2 is suspended from the DIN rail by way of two fittings on its
rear surface:
16-2
Accessories
To fit the IOEX2:
Ensure that the ADVC is switched 1 Holding the IOEX2 perpendicular, place the upper hooks of the
off before proceeding with the hanging fittings over the top edge of the DIN rail.
installation of the IOEX2. 2 Push the IOEX2 firmly against the back surface of the Customer
compartment until the lower end of the hanging fittings engage with
the bottom edge of the DIN rail.
3 Push the green/yellow earth terminal firmly on to the DIN rail until it
is engaged at both the top and bottom.
4 Connect the IOEX2 supply (18-40 VDC) and the RS 232 plug from
the controller.
Field Description
Invalid Map “Invalid Map” means there is a problem with the IOEX2
mapping in the database. Contact the manufacturer.
- - - - - - - - - - - - - IOEX STATUS - - - - - - - - - - - S
Inputs 1------8 Local
Outputs 1*--*----8 Unplugged
Standard IOEX Mapping
Input Terminal
Inputs ON
Number Number
Recloser
1 1-2 Trip the switchgear, set lockout and inhibit all close
operations
16-3
Advanced Controller Operations Manual
Input Terminal
Inputs ON
Number Number
Recloser
The recloser “close” input will only function when the Work Tag is off.
Tripping and controlling all other settings is independent of the Work
Tag status.
If the IOEX Trip input is held on while either the IOEX close or
manual close input is activated, the recloser will not close. This is
indicated in the event log by a ‘Close Blocking ON’ and ‘Close
Blocking OFF’ event whenever the IOEX Trip input changes state.
The SEF protection ON functionality operates as discussed in
“Protection Features” on page 9-1. If the earth fault protection or the
SEF availability for the active protection group are turned off then
the SEF protection will NOT turn on.
If both SEF protection ON and OFF inputs are on, the default is SEF
protection ON.
If both Auto Reclose ON and OFF inputs are on, the default is
Auto Reclose ON.
All the above inputs are edge-triggered, so the effect will not take place
if the blocking condition is removed.
a. The IOEX contacts are not guaranteed to change during fast Auto Reclose
sequences but will indicate the final steady state condition within 150ms.
16-4
Accessories
Phase Trip On On
a. The trip Source outputs do not indicate other causes of a trip such as Loss of
Phase.
Power Consumption
If an IOEX2 is fitted to the control cubicle, the battery hold-up time may
be affected.
This is due to the current drawn by the IOEX2. The manufacturer’s
battery hold-up time rating is based on a recloser installation without the
IOEX2 fitted.
16-5