Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 1 of 72

Protocol Database for Automatic Circuit


Reclosers With Advanced Controllers
COPYRIGHT Schneider Electric (Australia) PTY LTD 2009

File Version: $Revision: 213 $

331 Version: 44-14.00

Contents
Appendix A.1 Digital Data
A.1.1. Switchgear and Controller State Flags
A.1.2. Operator/Protection Flags for ACR
A.1.3. Protection Trip Flags ACR
A.1.4. Distributed Automation Flags
A.1.5. Pickup Flags
A.1.6. IOEX Inputs
A.1.8. Protocol IOEX Control Status
Appendix A.2 Analog Data
A.2.1. Line Currents
A.2.2. Voltage Measurements
A.2.3. System Power
A.2.4. SF6 Gas Pressure
A.2.5. Protection State
A.2.6. Protection Sequence and Trip Data
A.2.7. Switchgear Details
A.2.8. Controller Data
A.2.9. Distributed Automation
A.2.10. Daily Data
A.2.11. Supply Outage Measurement
A.2.12. Frequency Measurement
A.2.15. Sequence Components
Appendix A.3 Accumulator Data
Appendix A.5 LBS Points Data
A.5.1. Operator/Detection Flags for LBS
A.5.2. Detection Flags LBS
Appendix A.6 LBS Analog Data
A.6.1. Detection State
A.6.2. Fault Detection Data
Appendix A.7 Protocol-Specific Data
A.7.2. Protocol-Specific Analog status points.
A.7.3. Protocol-Specific Counter status points.
Appendix B.1 Digital Controls

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 2 of 72

Appendix B.2 Analog Controls


Appendix B.3 Protocol IOEX Controls

Appendix A.1Digital Data


Changes to digital Status Points are time stamped internally and available for transmission by
protocols which support transmission of time tags.

A.1.1Switchgear and Controller State Flags


These points show the state of the switchgear and/or the controller.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
For any of the following
conditions:-
This flag indicates the
operator has placed  Trip or Close
the switchgear in an Isolated.
abnormal state such
Abnormal None of the
as "Work Tag  Switchgear
0 Operator specified conditions 41-00.00
Applied". This means mechanically
Settings are true.
it will operate locked open (if
differently to its applicable).
normal mode of
operation.(1)  Work Tag Applied.

For any of the following


conditions:-

 Battery not
normal. This is
made up of
multiple
conditions:
Battery.. OFF,
Over Voltage, Low
Voltage.

 Capacitor charge
"status" is Failure.

 Low Power Mode.

 SF6 Gas Pressure


Low or Invalid (if
applicable)

The controller has  Switchgear data


Maintenance detected one or more not valid (includes No maintenance

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 3 of 72

Required conditions which connection to an required.


require maintenance. invalid switch
(1) type).

 Any vacuum
interrupter contact
life is less than
20%.

 Mechanism Fail.

 Switchgear not
1 41-00.00
connected.

 Firmware
missmatch.

 The PCOM is not


calibrated.

 Power Supply is
"Over Voltage".

Auxiliary Status of controller Auxiliary supply


2 Auxiliary supply fail. 41-00.00
Supply Fail auxiliary supply(1) normal.
The controller is in
either Local or
LOCAL control
Remote control. This
Remote Control ON. ON.
Controller affects the close
3 41-00.00
Mode command and the
LOCAL control OFF. Remote Control
permissions to
OFF.
set/remove work tags
(1)
These are repeats of
Switchgear the mechanism travel Switchgear Tripped Switchgear not
4 41-00.00
Tripped - open switches. When the Tripped
switchgear is
Switchgear disconnected from the Switchgear not
5 control cubicle they Switchgear Closed 41-00.00
Closed Closed
are both cleared.
6 Phase Ai Live 41-00.00
7 Phase Bi Live Shows if phase 41-00.00
8 Phase Ci Live bushings are above or 41-00.00
below the Live Line Phase Live Phase Dead
9 Phase Ax Live Threshold after supply 41-00.00
10 Phase Bx Live timeout.(3)(5) 41-00.00
11 Phase Cx Live 41-00.00
All Source side
Source Any Source side
12 bushings are 41-00.00
Voltage Status bushings are live.
Note that these points dead.
are different to the All load side
13 41-00.00
Load Voltage Load/Source Any load side bushings bushings are

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 4 of 72

Status Live/Dead events in are live. (5) dead.


the controller event Current of 2.5A or more Current of less than
Load Current record.
14 is flowing in at least one 2.5A is flowing in 41-00.00
On
phase. all three phases.
A Phase, Earth/Ground
One of the protection No protection
Protection or SEF/SGF Protection
15 elements has picked elements are 41-00.00
Pickup Element is in the picked
up. picked up.
up state.
The direction of
Power Flow Source I to Load
16 positive power flow as Source X to Load I. 41-00.00
Direction X.
defined by user.(4)
Indicates the
switchgear is
mechanically locked
Switchgear not
20 Locked in position. Not Switchgear Locked. 41-00.00
Locked.
supported on the N-
Series where it will
always be zero.
Indicates the
controller has
successfully retrieved
the data from the Switchgear
Switchgear Switchgear Memory
21 switchgear memory. Memory Data 41-00.00
Data Invalid Data Not Valid
When invalid the Valid
switchgear attributes
and gas pressure are
zeroed.
Shows the connection
state between the
switchgear and the
controller. When
connected the
Switchgear Switch disconnected Switch connected
22 switchgear Trip, Close 41-00.00
Connection from control cubicle. to control cubicle.
and Locked
indications are valid.
When disconnected
switchgear data will
be forced Invalid.
All vacuum
Indicates the wear of Any vacuum interrupter
Contact Life interrupters have
23 the contacts in the contact life is less than 41-00.00
Low contact life >=
vacuum interrupters 20%.
20%.

This point will only be  SF6 Gas


set when the Pressure
switchgear is Normal.
SF6 Gas connected,  SF6 Gas
Gas Pressure Low or
24 Pressure Low- switchgear data is Pressure Not 41-00.00
Invalid.
or-Invalid valid, switchgear type Known.
has SF6 and the gas  Switchgear
pressure is Low or Does Not
Invalid. Have SF6
Gas.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 5 of 72

Close Isolate Switch Close Isolate


25 Close Isolate Shows the state of the OFF (i.e. Close is Switch ON (i.e. 41-00.00
trip and close isolate disabled). Close is enabled.)
switches on the
operator control Trip Isolate Switch
Trip Isolate Switch OFF
26 Trip Isolate panel ON(i.e. Trip is 41-00.00
(i.e. Trip is disabled).
enabled).
Shows the state of the
Work (Hot Line) Tag
Work/Hot Line Work (Hot Line) Tag Work (Hot Line)
27 setting. No Closing 41-00.00
Tag Applied Tag Removed
may be performed
with this flag set.
Battery supply not
normal.

This includes :-
Note : Also part of
Battery Supply Battery supply
28 "Maintenance 41-00.00
Fail  Battery Off. Normal.
Required".
 Battery Overvolt.
 Battery Low Volts.

The Trip/Close
Capacitor Capacitor Charge Capacitor Charge
29 Capacitors have failed 41-00.00
Charge Failure Failed. OK.
to charge.
The switchgear has
Mechanism
30 failed to Trip or Close Mechanism Failure. Mechanism OK. 41-00.00
Fail
electrically
The Dummy Circuit
Breaker is an internal
point used for SCADA
system testing. It can
Dummy Circuit
be Tripped or Closed.
31 Breaker DCB Closed. DCB Not Closed. 41-00.00
The value of this point
Closed
is non-volatile, ie. Is
retained through
power-downs and
restarts.
Directional blocking is
The directional
enabled and Vo is
blocking facility
sustained (after Directional blocking
SEF/SGF High includes detection of
balancing) above the is not enabled or
32 Residual high residual voltage 41-00.00
Min SEF/SGF Vo Vo is below the
Voltage Alarm (Vo) above the
threshold for the High threshold.
SEF/SGF threshold
Vo Alarm time or
setting.(2)
longer.
Supply Supply Outage
Supply Outage
33 Outage Measurement is 41-00.00
Measurement is ON.
Measurement OFF.
Status of cubicle door.
34 Door Open Door open. Door closed. 41-00.00

Switch Function is Automatic Function is Load

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 6 of 72

35 Function Circuit Recloser Break Switch 41-00.00


Auxiliary Status of controller Auxiliary supply has Auxiliary supply
36 Supply Fail auxiliary supply failed for more than 120 restored for more 41-00.00
Delayed (delayed). seconds. than 20 seconds.
The Dummy Circuit
Breaker is an internal
point used for SCADA
system testing. It can
Dummy Circuit
be Tripped or Closed.
37 Breaker DCB Tripped. DCB Not Tripped. 41-00.00
The value of this point
Tripped
is non-volatile, ie. Is
retained through
power-downs and
restarts.
Status of a battery
test. This is the result
of a large load applied
The battery has failed a
Battery Test for 10 seconds, and
38 battery test and The battery is ok. 41-00.00
Fail then removed for 10
requires replacement.
seconds and
comparing the three
resulting voltages
Battery Test in The battery test is in The battery test is
39 41-00.00
Progress progress. NOT in progress.
No controller
settings have been
changed.
Settings The settings have been
40 Cleared by binary 41-00.00
Changed changed by a user.
output "Reset Fault
Flags" or "Clear
Settings
Changed".
There are no Non
A non critical alert is
Normal Alert At least 1 normal alert is Critical Alerts
41 active on the 44-00.00
Active active on the controller present on the
controller.
Controller.
There are no
Critical Alert A critical alert is active At least 1 critical alert is Critical Alerts
42 44-00.00
Active on the controller. active on the controller present on the
Controller.
Normal state,
Cleared on next
Not suitable for poll Set when a Trip
49 Trip Request internal scan after 43-06.11
oriented protocols. Request is issued.
Set. Point cleared
after 1 second.
1- This item indicates the status of the switchgear. It is recommended that it is always sent to a
SCADA system and displayed. It indicates in summary form the information which an operator can
use to determine if the switchgear is working correctly, if maintenance is required and if the local
operator has left the equipment in normal operating mode.
2- This data item is only available in configurations which support the Directional Blocking feature and
will always be '0' otherwise.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 7 of 72

3- The phase designation A, B, C is determined by the user, refer to Switchgear Details section,
Phase Designation in the Switchgear Technical Manual.
4- The power flow direction (source/load designation) is determined by the user. See Binary Output
"Power Flow Direction" for control.
5- If no X side CVTs present then value will always be zero.

A.1.2Operator/Protection Flags for ACR


These flags show the status of the operator controls and the state of some of the protection settings,
refer to the Protection State Section. They are equivalent to the indications available on the Operator
Control Panel on the controller.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
Earth/Ground
Earth/Ground Protection Earth/Ground
0 Protection 41-00.00
ON. Protection OFF.
Enabled
SEF/SGF
SEF/SGF protection
1 Protection SEF/SGF protection ON. 41-00.00
OFF.
Enabled
2 Auto Reclose Auto Reclose ON. Auto Reclose OFF. 41-00.00
Cold Load Pickup is in
Auto.This means the cold
load function is Cold Load pickup is
Cold Load functioning and may, or OFF. This means the
3 41-00.00
Auto may not, be affecting the cold load function is
threshold multiplier. This completely disabled.
is indicated by the Cold
Load Active flag.
Cold load is NOT Idle. Cold Load is Idle or is
This means the threshold turned OFF. This
Cold Load See Protection multiplier is being raised means the threshold
4 41-00.00
Active State section. by the cold load pickup multiplier will not be
function in order to raise affected by the cold
cold load. load function.
High Current
High Current Lockout
5 Lockout High Current Lockout ON. 41-00.00
OFF.
Enabled
Either Loss Of Phase
Loss of Phase Loss of Phase Trip Protection is OFF or
6 (1) 41-00.00
Protection ENABLED. Loss Of Phase Alarm
ENABLED.
Sequence Sequence Control
7 Sequence Control ON. 41-00.00
Control OFF.
Live Load Live Load Blocking
8 Live Load Blocking ON. 41-00.00
Blocking OFF.
Protection turned
Protection
9 Protection ON. OFF. No protection 41-00.00
ON/OFF
trips will occur.
Automatic
Protection Automatic Protection Automatic Protection

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 8 of 72

Group Group Selection is ON. Group Selection is


10 41-00.00
Selection OFF.
The Under/Over
The Under/Over
Normal Freq Frequency protection
11 Frequency protection has 41-00.00
Close On/Off has "Normal Freq
"Normal Freq Close" ON.
Close" OFF.
Dead Lockout Setting is Dead Lockout Setting
12 Dead Lockout 41-00.00
ON. is OFF.
Loss Of Loss Of Phase / Loop Loss Of Phase / Loop
13 41-00.00
Phase / Loop Linked. Unlinked.
The Under/Over The Under/Over
Under Frequency protection Frequency protection
14 41-00.00
Frequency Trip "Under Frequency Trip" "Under Frequency
feature is enabled. Trip" is disabled.
The Under/Over The Under/Over
Over Frequency protection Frequency protection
15 41-00.00
Frequency Trip "Over Frequency Trip" "Over Frequency
feature is enabled. Trip" is disabled.
Protection Protection group A is Protection group A is
16 (2) 41-00.00
Group A Active active. not active.
Protection Protection group B is Protection group B is
17 (2) 41-00.00
Group B Active active. not active.
Protection
Protection group C is Protection group C is
18 Group C (2) 41-00.00
active. not active.
Active
Protection
Protection group D is Protection group D is
19 Group D (2) 41-00.00
active. not active.
Active
Protection Protection group E is Protection group E is
20 (2) 41-00.00
Group E Active active. not active.
Protection Protection group F is Protection group F is
21 (2) 41-00.00
Group F Active active. not active.
Protection
Protection group G is Protection group G is
22 Group G (2) 41-00.00
active. not active.
Active
Protection
Protection group H is Protection group H is
23 Group H (2) 41-00.00
active. not active.
Active
Protection Protection group I is Protection group I is
24 (2) 41-00.00
Group I Active active. not active.
Protection Protection group J is Protection group J is
25 (2) 41-00.00
Group J Active active. not active.
Either Loss Of Phase
Loss of Phase Alarm is Alarm is DISABLED,
Loss of Phase
26 (1) ENABLED (ie no trip will or Loss Of Phase 41-00.00
Alarm
occur). Protection
ENABLED.
Directional Protection
27 Directional Protection is is not enabled. Only 41-00.00
Directional enabled. Separate one protection group
Protection protection groups exist for exists, pickup and

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 9 of 72

Enabled each direction, pickup and tripping is non-


tripping is directional. directional.
Cold Load (reverse)
Cold load (reverse) is
is Idle or is turned
NOT Idle. This means the
OFF. This means the
Cold Load threshold multiplier is
28 threshold multiplier 41-02.43
Reverse Active being raised by the cold
will not be affected by
load pickup function in
the cold load
order to raise cold load.
function.
Cold load is at the Cold Load has not
Cold Load
29 maximum time and reached the 41-02.50
Maximum
multiplier. maximum time.
Cold Load Cold load(Reverse) is at Cold Load(Reverse)
30 Reverse the maximum time and has not reached the 41-02.50
Maximum multiplier. maximum time.
Reverse Cold Load
Pickup is in Auto.This Reverse Cold Load
means the cold load pickup is OFF or
function is functioning and directional protection
Cold Load
31 may, or may not, be is DISABLED. This 41-02.50
Reverse Auto
affecting the threshold means the cold load
multiplier. This is indicated function is completely
by the Cold Load Reverse disabled.
Active flag.
Auto Reclose in the
Auto Reclose in the
Forward Auto FORWARD
32 (3) FORWARD protection 41-02.85
Reclose protection direction is
direction is ON.
OFF.
'High Current
Reverse High 'High Current Lockout' in
Lockout' in the
33 Current (3) the REVERSE protection 41-02.85
REVERSE protection
Lockout direction is ON.
direction is OFF.
Sequence Control in
Reverse Sequence Control in the
the REVERSE
34 Sequence (3) REVERSE protection 41-02.85
protection direction is
Control direction is ON.
OFF.
Auto Reclose in the Auto Reclose in the
Reverse Auto
35 (3) REVERSE protection REVERSE protection 41-02.85
Reclose
direction is ON. direction is OFF.
The status of the
Under/Over
Normal Normal Voltage Close is Normal Voltage
36 Voltage Normal 42-00.00
Voltage Close ON Close is OFF
Voltage Close
Setting
The status of the
Under Voltage Under Voltage Trip is
37 Under Voltage Under Voltage Trip is ON 42-00.00
Trip OFF
Trip setting
The status of the
Over Voltage Over Voltage Trip is
38 Over Voltage Over Voltage Trip is ON 42-00.00
Trip OFF
Trip setting

39 Sag Monitoring The status of the Sag Monitoring is ON 42-00.00


Sag Monitoring Sag Monitoring is

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 10 of 72

Setting OFF
The status of the
Swell Swell Monitoring is
40 Swell Monitoring Swell Monitoring is ON 42-00.00
Monitoring OFF
Setting
Earth/Ground
Earth/Ground The status of the Protection Blcoking is
Earth/Ground Protection
41 Protection Earth/Ground On. No Earth/Ground 44-0.47
blocking is Off
Block Protection Block Protection will
operate.
NPS Protection
NPS The status of the
NPS Protection blocking is Blcoking is On. No
42 Protection NPS Protection 44-0.47
Off NPS Protection will
Block Block
operate.
1- Loss of Phase Protection is either in Trip ENABLED, Alarm ENABLED or OFF.
2- Only one protection group is active at any one time unless Directional Protection is ON then only
two protection groups are active. eg Protection Groups C and D active (C is the forward protection
group and D the reverse).
3- Only valid when 'Directional Protection' is Active.

A.1.3Protection Trip Flags ACR


This group of points indicates what happened in the most recent protection sequence. For example the
recloser may have tripped, closed, tripped again and locked out. Or it may have tripped, closed and
stayed closed because the fault was cleared.

In both cases the flags below are set to show what caused of the trips and whether the lockout state
has been reached or not.

A set of flags is available for each trip in a protection sequence.

Analog data is available which shows the fault currents during the sequence and how many trips
occurred. Refer A.2.6

Note: A sequence starts when there is a protection trip or a sequence advance.

Most of these flags are cleared by a protocol command, a switchgear trip/close by the operator, or
when a new protection sequence starts.

This data is volatile, i.e. it is zeroed on controller software reset.

If there is more than one protocol running simultaneously in the controller this data is replicated
between the protocols so that each master station can clear its data independently from the others.

Version
Point Name Description Set = '1' Clear = '0'
Introduced

This shows that a


protection
Sequence in sequence has Start of sequence
0 41-00.00
Progress started and not ie. a protection trip End of sequence.
yet completed. or sequence Either by lockout or
Note that an advance has sequence reset

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 11 of 72

operator trip occurred. timeout.


does not cause a
"Sequence in
Progress".
This shows that
the protection
sequence is over
and the other
flags are set.
Can be used to
drive an operator
alarm through End of sequence.
Protection the SCADA Either by lockout or
1 41-00.00
Data Valid system to warn sequence reset
that a protection timeout.
sequence has
occurred. Note
that an operator
trip alone does
not cause a
"Protection Data All flags are cleared
Valid" . by:
Phase
Phase Overcurrent  "Reset fault
2 Overcurrent 41-00.00
Protection Trip 1 flags and
Trip 1
currents"
Phase control.
Phase Overcurrent
3 Overcurrent Any operator 41-00.00
Protection Trip 2 
Trip 2 close action.
Phase  Start of a new
Phase Overcurrent
4 Overcurrent sequence. 41-00.00
Protection Trip 3
Trip 3  Controller
Phase software reset
Phase Overcurrent
5 Overcurrent (data is 41-00.00
Protection Trip 4
Trip 4 volatile).
Earth/Ground Earth/Ground  Protection
6 Overcurrent Overcurrent turned OFF. 41-00.00
Trip 1 Protection Trip 1
Earth/Ground Earth/Ground
7 Overcurrent Overcurrent 41-00.00
Trip 2 Protection Trip 2
Earth/Ground Earth/Ground
8 Overcurrent Overcurrent 41-00.00
Trip 3 Protection Trip 3
Earth/Ground Earth/Ground
9 Overcurrent Overcurrent 41-00.00
Trip 4 Protection Trip 4
SEF/SGF Sensitive
10 Overcurrent Earth/Ground Fault 41-00.00
Trip 1 Protection Trip 1
SEF/SGF Sensitive
11 Overcurrent Earth/Ground Fault 41-00.00
Trip 2 Protection Trip 2

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 12 of 72

SEF/SGF Sensitive
12 Overcurrent Earth/Ground Fault 41-00.00
Trip 3 Protection Trip 3
SEF/SGF Sensitive
13 Overcurrent Earth/Ground Fault 41-00.00
Trip 4 Protection Trip 4
Sequence Sequence Advance
14 41-00.00
Advance 1 1
Sequence Sequence Advance
15 41-00.00
Advance 2 2
Sequence Sequence Advance
16 41-00.00
Advance 3 3
17 Reserved Always 0 41-00.00
Only one flag
Single Shot
provided
Single Shot Protection was
18 because a single 41-00.00
Protection active at the time of
shot trip forces
the trip.
lockout.
Protection Flags
are cleared by one
of the following
Only one flag actions:-
provided Trip was caused by
Loss Of Phase
19 because Loss Of Loss of Phase "Reset Fault 41-00.00
Trip 
Phase protection Protection. Flags and
forces lockout. Currents"
control.
 Operator
Close.
 At the time of
Phase A was lost at the next trip
Loss Of Phase the flags are
20 (1) time of Loss Of 41-00.00
Phase A Lost 'refreshed'.
Phase trip.
Old flags are
cleared and
the cause of
the 'most
Phase B was lost at recent'
Loss Of Phase
21 (1) time of Loss Of protection 41-00.00
Phase B Lost
Phase trip. operation set.
 Protection
turned OFF.
 Controller
Phase C was lost at Software
Loss Of Phase reset (data is
22 (1) time of Loss Of 41-00.00
Phase C Lost volatile).
Phase trip.

The High Current


Only one flag
Lockout forced the
High Current because High
23 controller to lockout 41-00.00
Lockout Current Lockout
during the most
forces lockout.
recent protection

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 13 of 72

sequence.
Indicates the
controller is in
lockout. Cleared by:
Therefore no
auto-reclosing  Any close
will take place. action.
 "Reset Fault
Controller is in Flags and
24 Lockout If the switchgear 41-00.00
lockout. Currents"
is closed this flag
will be clear. control.
When this flag is
clear it indicates
the protection
sequence
cleared the fault.
A combination of an
One flag only
OCPM Operator
because operator Cleared by any
25 Operator Trip Trip OR an IOEX 41-00.00
trip forces close action.
Operator Trip OR a
lockout.
Protocol Trip.
Protection Flags
Set if the most are cleared by one
recent protection The most recent of the following
Protection operation was protection operation actions:-
26 Flag - Phase caused by a was caused by a 41-00.00
Overcurrent Phase Phase Overcurrent  "Reset Fault
Overcurrent Protection Trip Flags and
Protection Trip. Currents"
control.
 Operator
Set if the most
The most recent Close.
recent protection
Protection protection operation  At the time of
operation was
Flag - was caused by an the next trip
27 caused by an 41-00.00
Earth/Ground Earth/Ground the flags are
Earth/Ground
Overcurrent Overcurrent 'refreshed'.
Overcurrent
Protection Trip. Old flags are
Protection.
cleared and
the cause of
Set if the most the 'most
The most recent recent'
recent protection
Protection protection operation protection
operation was
Flag - was caused by an operation set.
28 caused by an 41-00.00
SEF/SGF SEF/SGF  Protection
SEF/SGF
Overcurrent Overcurrent turned OFF.
Overcurrent
Protection Trip.
Protection Trip.

Cleared by:

29  Any Operator 41-00.00


Close or
The most recent trip Operator Trip.
OCP Operator was caused by a This includes

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 14 of 72

Trip local or remote remote control


operator panel trip. commands.
 Start of a new
sequence.

Cleared by:
The most recent trip
IOEX Operator was caused by an  Any Operator 41-00.00
30
Trip IOEX Operator Trip Close or
input Operator Trip.
This includes
remote control
The most recent trip commands.
IOEX was caused by an  Start of a new
31 sequence. 41-00.00
Protection Trip IOEX Protection
Input

The most recent trip Cleared by:


was caused by a
33 Protocol Trip  Any Operator
41-00.00
remote protocol or
WSOS trip request. Close or
Operator Trip.
The most recent trip This includes
was caused by a remote control
Loop Automation, commands.
Automation
34 Generator Control,  Start of a new 41-00.00
Trip - A
or an Auto sequence.
Changeover Trip
request.

Set if the most Protection Flags


recent protection are cleared by one
operation was of the following
due to Under actions:-
Frequency.
Under "Reset fault
Protection operation 
Frequency The source flags and
35 caused by Under 41-00.00
Protection frequency has currents"
Frequency.
Flag fallen below the control.
Under Frequency  Any Operator
threshold for the Close.
Trip Delay count  At the time of
and a Trip has the next trip
occurred. the flags are
'refreshed'.
Old flags are
Set if most recent cleared and
protection the cause of
36 operation was the 'most 41-00.00
due to Over recent'
Frequency. protection
Over Protection operation operation set.
Frequency The source caused by Over  Start of a new

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 15 of 72

Protection frequency has Frequency. sequence.


Flag risen above the The time
Over Frequency stamp reflects
threshold for the this.
Trip Delay count  Protection
and a Trip has turned OFF
occurred.

Phase A Phase A
41 Overcurrent Overcurrent 41-00.00
Trip 1 Protection Trip 1
Phase A Phase A
42 Overcurrent Overcurrent 41-00.00
Trip 2 Protection Trip 2
Phase A Phase A
43 Overcurrent Overcurrent 41-00.00
Trip 3 Protection Trip 3
Phase A Phase A
44 Overcurrent Overcurrent 41-00.00
Trip 4 Protection Trip 4
Phase B Phase B
45 Overcurrent Overcurrent 41-00.00
Trip 1 Protection Trip 1
Phase B Phase B Cleared by:
46 Overcurrent Overcurrent 41-00.00
 "Reset Fault
Trip 2 Protection Trip 2
flags and
Phase B Phase B
Currents"
47 Overcurrent Overcurrent 41-00.00
control.
Trip 3 Protection Trip 3
 Any Operator
Phase B Phase B Close. This
48 Overcurrent Overcurrent includes 41-00.00
Trip 4 Protection Trip 4 remote control
Phase C Phase C commands.
49 Overcurrent Overcurrent  Start of a new 41-00.00
Trip 1 Protection Trip 1 sequence.
Phase C Phase C
50 Overcurrent Overcurrent 41-00.00
Trip 2 Protection Trip 2
Phase C Phase C
51 Overcurrent Overcurrent 41-00.00
Trip 3 Protection Trip 3
Phase C Phase C
52 Overcurrent Overcurrent 41-00.00
Trip 4 Protection Trip 4
Peak Fault Current
Instantaneous for trip was above
53 41-00.00
Trip Flag 1 the Instantaneous
Multiplier setting.

Instantaneous Peak Fault Current


54 for trip was above 41-00.00
Trip Flag 2
the Instantaneous

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 16 of 72

Multiplier setting.
Peak Fault Current
Instantaneous for trip was above
55 41-00.00
Trip Flag 3 the Instantaneous
Multiplier setting.
Peak Fault Current
Instantaneous for trip was above
56 41-00.00
Trip Flag 4 the Instantaneous
Multiplier setting.
Protection Flags
The most recent trip are cleared by one
Most Recent
was caused by an A of the following
57 Trip Phase A 41-00.00
Phase Overcurrent actions:-
Overcurrent
Protection Trip.
 "Reset Fault
Flags and
Currents"
The most recent trip control.
Most Recent
was caused by a B  Operator
58 Trip Phase B 41-00.00
Phase Overcurrent Close.
Overcurrent
Protection Trip  At the time of
the next trip
the flags are
'refreshed'.
The most recent trip Old flags are
Most Recent
was caused by a C cleared and 41-00.00
59 Trip Phase C
Phase Overcurrent the cause of
Overcurrent
Protection Trip the 'most
recent'
protection
operation set.
The peak current  Protection
for the most recent turned OFF.
Instantaneous Controller
trip was greater 
60 Most Recent Software 41-00.00
than the
Trip Reset (data is
Instantaneous
setting. volatile).

Cleared by:
Set if a lockout  "Reset Fault
Dead Lockout caused by the Flags and
61 41-00.00
Trip Flag 'Dead Lockout'
Currents"
Feature occurred. control.
 Operator
Close.
 Controller
Software
Trip while Work Tag Reset(data is
62 Work Tag Trip or Hot Line Tag volatile). 41-00.00
applied.  Protection
turned OFF.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 17 of 72

Trip Flags are


cleared by one of
The most recent the following
Most Recent Trip was caused by actions:-
65 41-00.00
Trip Phase a Phase
overcurrent fault  "Reset Fault
Flags and
Currents"
control.
 Operator
Close.
The most recent trip  At the time of
Most Recent
was caused by an the next trip
66 Trip 41-00.00
Earth/Ground the flags are
Earth/Ground
overcurrent fault 'refreshed'.
Old flags are
cleared and
the cause of
the 'most
recent'
The most recent protection
Most Recent Trip was caused by operation set. 41-00.00
67
Trip SEF/SGF a SEF/SGF  Protection
overcurrent fault turned OFF.

Cleared by one of
the following
actions:

 'Reset Flags
Indicates the and Currents'
most recent Most recent close control.
Operator close was caused by local or  Controller
68 41-00.00
Close caused by a local remote panel close Software
or remote panel request. Reset (data is
close request. volatile).
 At the time of
the next
Close.

Cleared by one of
the following
actions:
Most recent close
69 IOEX Close caused by an IOEX  'Reset Flags 41-00.00
Indicates the close input. and Currents'
most recent control.
close was  Controller
caused by an Software
IOEX close Reset (data is

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 18 of 72

input. volatile).
 At the time of
the next
Close.

Cleared by one of
the following
actions:

 'Reset Flags
Indicates the and Currents'
most recent Most recent close control.
close was caused by a  Controller
70 Protocol Close 41-00.00
caused by a protocol close Software
protocol close request. Reset (data is
request. volatile).
 At the time of
the next
Close.

Cleared by one of
the following
Indicates the actions
most recent
close was  'Reset Flags
caused by a and Currents'
Most recent close
Distributed control.
caused by a
Automation Automation  Controller
71 Distributed 41-00.00
Close Close request (ie Software
Automation Close
Loop Reset (data is
request.
Automation, Auto volatile).
Changeover, or  At the time of
Generator the next
Control). Close.

Cleared by one of
Indicates the the following
most recent actions
Most recent close
close was
caused by a Normal
caused by a  'Reset Flags
Voltage Close
Normal Normal Voltage and Currents'
72 request. (NOTE that 41-00.00
Voltage Close Close request. control.
this feature does
(NOTE This  Controller
not exist at the
feature does not Software
moment).
exist at the Reset (data is
moment). volatile).
 At the time of
the next
Close.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 19 of 72

Cleared by one of
the following
actions:

 'Reset Flags
Indiciates the
and Currents'
most recent
Most recent close control.
Normal close was
caused by Normal  Controller
73 Frequency caused by a 41-00.00
Frequency Close Software
Close Normal
request. Reset (data is
Frequency Close
volatile).
request
 At the time of
the next
Close.

Set if any of the


following caused
the most recent
close:
Cleared by one of
the following
 CCEM actions:
external
button on N-
 'Reset Flags
Series.
and Currents'
The most recent  Mechanical
control.
close caused by action. The
 Controller
74 External Close an action switchgear 41-00.00
Software
external to the detected as
Reset (data is
Controller. closed without
volatile).
a close
 At the time of
reques.
the next
 Electrical
Close.
action (only
available on
the Advanced
controller).

Cleared by one of
the following
actions:
Set if the most
recent close  'Reset Flags
Live Load
request was and Currents'
75 Block 41-00.00
blocked due to a control.
Occurred
Live Load  Controller
condition. Software
Reset (data is
volatile).
 Protection
OFF.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 20 of 72

 At the time of
the next
Close.

Protection Flags
are cleared by one
of the following
actions:-

 "Reset Fault
Flags and
Currents"
control.
 Operator
Indicates if the Close.
most recent The most recent  At the time of
Protection protection protection operation the next
76 Flag - NPS operation was was caused by an protection trip 41-00.00
Overcurrent caused by an NPS Overcurrent the flags are
NPS Overcurrent Protection Trip. 'refreshed'.
Protection Trip. Old flags are
cleared and
the cause of
the 'most
recent'
protection
operation set.
 Protection
turned OFF.

Most Recent Trip


Flags are cleared
by one of the
following actions:-

 "Reset Fault
Flags and
Currents"
control.
The most recent trip  Operator
Most Recent was caused by a Close.
77 41-00.00
Trip NPS NPS overcurrent  Protection
fault. turned OFF.
 Start of a new
sequence.
 At the time of
the next trip
the flags are
'refreshed'.
Old flags are
cleared and
the cause of

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 21 of 72

the 'most
recent' trip
set.
 Controller
reset

Protection Flags
NPS are cleared by one
NPS Overcurrent
78 Overcurrent of the following 41-00.00
Protection Trip 1
Trip 1 actions:-

 "Reset Fault
NPS Flags and
NPS Overcurrent
79 Overcurrent Currents" 41-00.00
Protection Trip 2
Trip 2 control.
 Operator
NPS Close.
NPS Overcurrent  Protection
80 Overcurrent 41-00.00
Protection Trip 3 turned OFF.
Trip 3
 Start of a new
sequence.
NPS  Controller
NPS Overcurrent reset
81 Overcurrent 41-00.00
Protection Trip 4
Trip 4

Protection Flags
are cleared by one
of the following
actions:-

 "Reset Fault
Flags and
Most recent trip Currents"
Most Recent
82 caused by an IOEX control. 41-00.00
Trip External
Protection Input  Operator
Close.
 Protection
turned OFF.
 Start of a new
sequence.

Protection Flags
are cleared by one
of the following
actions:-
83 41-00.00
 "Reset Fault
The most recent trip Flags and
was caused by a Currents"
Loop Automation, control.
Automation Generator Control,  Operator

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 22 of 72

Trip - B or an Auto Close.


changeover Trip  At the time of
request. the next trip
the flags are
'refreshed' at
this time old
flags are
cleared and
the cause of
the 'most
recent'
protection
operation set.
One flag only The most recent trip Protection
Mechanical 
84 because this trip was caused by a turned OFF. 41-00.00
Trip
forces lockout Mechanical Trip.  Start of a new
sequence.

This flags
whether the most
Most Recent The most recent trip
recent trip was
Trip Phase was caused by a
85 caused by a 41-00.00
Overcurrent - Phase Overcurrent
Phase These flags are
Close Reset Fault.
Overcurrent cleared by one of
Fault. the following
This flags actions:
Most Recent whether the most
The most recent trip
Trip recent trip was  "Reset Fault
was caused by an
86 Earth/Ground caused by an Flags and 41-00.00
Earth/Ground
Overcurrent - Earth/Ground Currents"
Overcurrent Fault.
Close Reset Overcurrent control.
Fault.  Any Close
This flags action.
whether the most  Protection
Most Recent The most recent trip turned OFF.
recent trip was
Trip SEF/SGF was caused by an Controller
87 caused by an  41-00.00
Overcurrent - SEF/SGF software reset
SEF/SGF
Close Reset Overcurrent Fault. (data is
Overcurrent
Fault. volatile).
This flags
Most Recent whether the most The most recent trip
Trip NPS recent trip was was caused by an
88 41-00.00
Overcurrent - caused by an NPS Overcurrent
Close Reset NPS Overcurrent Fault.
Fault.
Reverse
Reverse Phase
Phase
89 Overcurrent 41-00.00
Overcurrent
Protection Trip 1
Trip 1

Reverse Reverse Phase


90 Phase Overcurrent 41-00.00
Overcurrent Protection Trip 2

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 23 of 72

Trip 2
Reverse
Reverse Phase
Phase
91 Overcurrent 41-00.00
Overcurrent
Protection Trip 3
Trip 3
Reverse
Reverse Phase
Phase
92 Overcurrent 41-00.00
Overcurrent
Protection Trip 4
Trip 4
Reverse Reverse
Earth/Ground Earth/Ground
93 41-00.00
Overcurrent Overcurrent
Trip 1 Protection Trip 1
Reverse Reverse
Earth/Ground Earth/Ground All flags are cleared
94 by: 41-00.00
Overcurrent Overcurrent
Trip 2 Protection Trip 2
Reverse Reverse  "Reset fault
Earth/Ground Earth/Ground flags and
95 currents" 41-00.00
Overcurrent Overcurrent
Trip 3 Protection Trip 3 control.
 Any operator
Reverse Reverse close action.
Earth/Ground Earth/Ground Start of a new 41-00.00
96 
Overcurrent Overcurrent sequence.
Trip 4 Protection Trip 4  Controller
Reverse software reset
Reverse Sensitive
SEF/SGF (data is
97 Earth/Ground Fault 41-00.00
Overcurrent volatile).
Protection Trip 1
Trip 1  Protection
Reverse turned OFF.
Reverse Sensitive
SEF/SGF
98 Earth/Ground Fault 41-00.00
Overcurrent
Protection Trip 2
Trip 2
Reverse
Reverse Sensitive
SEF/SGF
99 Earth/Ground Fault 41-00.00
Overcurrent
Protection Trip 3
Trip 3
Reverse
Reverse Sensitive
SEF/SGF
100 Earth/Ground Fault 41-00.00
Overcurrent
Protection Trip 4
Trip 4
Only one flag
Single Shot
Reverse provided
Protection was
101 Single Shot because a single 41-00.00
active at the time of
Protection shot trip forces
the reverse trip.
lockout.
Cleared by:

102 The High Current  Any close 41-00.00


Only one flag Lockout forced the action.
Reverse High because High controller to lockout  "Reset Fault
Current Current Lockout during the most Flags and

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 24 of 72

Lockout forces lockout. recent reverse Currents"


protection control.
sequence.

Set if the most Protection Flags


The most recent are cleared by one
recent protection
Reverse protection operation of the following
operation was
Protection was caused by a actions:-
103 caused by a 41-00.00
Flag - Phase Reverse Phase
Reverse Phase
Overcurrent Overcurrent  "Reset Fault
Overcurrent
Protection Trip Flags and
Protection Trip.
Currents"
Set if the most control.
The most recent  Operator
recent protection
Reverse protection operation Close.
operation was
Protection was caused by a  At the time of
caused by a
104 Flag - Reverse the next trip 41-00.00
Reverse
Earth/Ground Earth/Ground the flags are
Earth/Ground
Overcurrent Overcurrent 'refreshed'.
Overcurrent
Protection Trip. Old flags are
Protection.
cleared and
the cause of
Set if the most the 'most
recent protection The most recent recent'
Reverse
operation was protection operation protection
Protection
caused by a was caused by a operation set. 41-00.00
105 Flag -
Reverse Reverse SEF/SGF Protection
SEF/SGF 
SEF/SGF Overcurrent turned OFF.
Overcurrent
Overcurrent Protection Trip.
Protection Trip.
Reverse
Reverse Phase A
Phase A
106 Overcurrent 41-00.00
Overcurrent
Protection Trip 1
Trip 1
Reverse
Reverse Phase A
Phase A
107 Overcurrent 41-00.00
Overcurrent
Protection Trip 2
Trip 2
Reverse
Reverse Phase A
Phase A
108 Overcurrent 41-00.00
Overcurrent
Protection Trip 3
Trip 3
Reverse
Reverse Phase A
Phase A
109 Overcurrent 41-00.00
Overcurrent
Protection Trip 4
Trip 4
Reverse
Reverse Phase B
Phase B
110 Overcurrent 41-00.00
Overcurrent
Protection Trip 1
Trip 1
Reverse
111 Phase B Reverse Phase B 41-00.00
Overcurrent Overcurrent

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 25 of 72

Trip 2 Protection Trip 2


Reverse
Reverse Phase B
Phase B
112 Overcurrent 41-00.00
Overcurrent
Protection Trip 3
Trip 3
Reverse
Reverse Phase B
Phase B
113 Overcurrent 41-00.00
Overcurrent
Protection Trip 4
Trip 4
Reverse
Reverse Phase C
Phase C
114 Overcurrent 41-00.00
Overcurrent
Protection Trip 1
Trip 1
Reverse
Reverse Phase C
Phase C
115 Overcurrent Cleared by: 41-00.00
Overcurrent
Protection Trip 2
Trip 2
 "Reset Fault
Reverse
Reverse Phase C flags and
Phase C
116 Overcurrent Currents" 41-00.00
Overcurrent
Protection Trip 3 control.
Trip 3
 Any Operator
Reverse Close or
Reverse Phase C
Phase C Operator Trip. 41-00.00
117 Overcurrent
Overcurrent This includes
Protection Trip 4
Trip 4 remote control
Peak Fault Current commands.
Reverse for reverse trip was  Start of a new
118 Instantaneous above the sequence. 41-00.00
Trip Flag 1 Instantaneous
Multiplier setting.
Peak Fault Current
Reverse for reverse trip was
119 Instantaneous above the 41-00.00
Trip Flag 2 Instantaneous
Multiplier setting.
Peak Fault Current
Reverse for reverse trip was
120 Instantaneous above the 41-00.00
Trip Flag 3 Instantaneous
Multiplier setting.
Peak Fault Current
Reverse for reverse trip was
121 Instantaneous above the 41-00.00
Trip Flag 4 Instantaneous
Multiplier setting.
Protection Flags
The most recent
Most Recent are cleared by one
reverse trip was of the following
Reverse Trip
122 caused by an A 41-00.00
Phase A actions:-
Phase Overcurrent
Overcurrent
Protection Trip.
 "Reset Fault
Flags and

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 26 of 72

Currents"
The most recent control.
Most Recent
reverse trip was Operator
Reverse Trip 
123 caused by a B Close. 41-00.00
Phase B
Phase Overcurrent At the time of
Overcurrent 
Protection Trip the next trip
the flags are
'refreshed'.
The most recent Old flags are
Most Recent
reverse trip was cleared and
Reverse Trip
124 caused by a C the cause of 41-00.00
Phase C
Phase Overcurrent the 'most
Overcurrent
Protection Trip recent'
protection
operation set.
 Protection
The peak current
turned OFF.
for the most recent
Instantaneous  Controller
reverse trip was
125 Most Recent Software 41-00.00
greater than the
Reverse Trip Reset (data is
Instantaneous
volatile).
setting.

Trip Flags are


cleared by one of
The most recent the following
Reverse Most
Reverse Trip was actions:-
128 Recent Trip 41-00.00
caused by a Phase
Phase
overcurrent fault  "Reset Fault
Flags and
Currents"
control.
 Operator
The most recent Close.
Reverse Most Reverse Trip was  At the time of
129 Recent Trip caused by an the next trip 41-00.00
Earth/Ground Earth/Ground the flags are
overcurrent fault 'refreshed'.
Old flags are
cleared and
the cause of
the 'most
The most recent recent'
Reverse Most Reverse Trip was protection
130 Recent Trip caused by a operation set. 41-00.00
SEF/SGF SEF/SGF  Protection
overcurrent fault turned OFF.

Protection Flags
are cleared by one
of the following
actions:-

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 27 of 72

 "Reset Fault
Flags and
Currents"
control.
 Operator
Close.
 At the time of
the next
Indicates if the
The most recent protection trip
most recent
Reverse protection operation the flags are
protection
Protection was caused by a 'refreshed'.
131 operation was 41-00.00
Flag - NPS reverse NPS Old flags are
caused by an
Overcurrent Overcurrent cleared and
NPS Overcurrent
Protection Trip. the cause of
Protection Trip.
the 'most
recent'
protection
operation set.
 Protection
turned OFF.

most recent Trip


Flags are cleared
by one of the
following actions:-

 "Reset Fault
Flags and
Currents"
control.
 Operator
Close.
 Protection
turned OFF.
The most recent
Most Recent  Start of a new
Reverse Trip was
132 Reverse Trip sequence. 41-00.00
caused by aNPS
NPS  At the time of
overcurrent fault.
the next trip
the flags are
'refreshed'.
Old flags are
cleared and
the cause of
the 'most
recent' trip
set.
 Controller
reset

Protection Flags
133 Reverse NPS Reverse NPS are cleared by one 41-00.00
Overcurrent Overcurrent of the following

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 28 of 72

Trip 1 Protection Trip 1 actions:-

Reverse NPS Reverse NPS  "Reset Fault


134 Overcurrent Overcurrent Flags and 41-00.00
Trip 2 Protection Trip 2 Currents"
control.
 Operator
Reverse NPS Reverse NPS Close.
135 Overcurrent Overcurrent  Protection 41-00.00
Trip 3 Protection Trip 3 turned OFF.
 Start of a new
sequence.
Reverse NPS Reverse NPS  Controller
136 Overcurrent Overcurrent reset 41-00.00
Trip 4 Protection Trip 4

This flags
Most Recent whether the most
The most recent
Reverse Trip recent reverse
reverse trip was
137 Phase trip was caused 41-00.00
caused by a Phase
Overcurrent - by a Phase
Overcurrent Fault.
Close Reset Overcurrent These flags are
Fault. cleared by one of
This flags the following
whether the most actions:
Most Recent The most recent
recent reverse
Reverse Trip reverse trip was
trip was caused  "Reset Fault 41-00.00
138 Earth/Ground caused by an
by an Flags and
Overcurrent - Earth/Ground
Earth/Ground Currents"
Close Reset Overcurrent Fault.
Overcurrent control.
Fault.  Any Close
This flags action.
Most Recent whether the most The most recent  Protection
Reverse Trip recent reverse reverse trip was turned OFF.
139 SEF/SGF trip was caused caused by an  Controller 41-00.00
Overcurrent - by an SEF/SGF SEF/SGF software reset
Close Reset Overcurrent Overcurrent Fault. (data is
Fault. volatile).
This flags
Most Recent whether the most
The most recent
Reverse Trip recent reverse
reverse trip was
140 NPS trip was caused 41-00.00
caused by an NPS
Overcurrent - by an NPS
Overcurrent Fault.
Close Reset Overcurrent
Fault.

These flags are


cleared by one of
the following
actions:

Indicates that the  "Reset Fault


most recent Most recent close Flags and
Directional close was caused by a Currents"

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 29 of 72

Protection caused by a directional control.


Auto Restore directional protection auto  Any Close
protection auto restore. action.
restore.  Controller
141 software reset 41-00.00
(data is
volatile).

Cleared by either:

Rev Sequence Reverse Sequence  "Reset fault


142 41-04.03
Advance 1 Advance 1 flags and
currents"
control.
Indicates a
 Any operator
sequence
close action.
advance has
Rev Sequence Reverse Sequence  Start of a new
143 taken place for 41-04.03
Advance 2 Advance 2 sequence.
protection in the
 Controller
reverse
software reset
direction.
(data is
volatile).
Rev Sequence Reverse Sequence  Protection
144 turned OFF. 41-04.03
Advance 3 Advance 3

Indicates
Under Voltage whether an
An Under Voltage
145 Trip Protection Under Voltage 42-00.00
Trip has occurred.
Trip Trip has
occurred.
Indicates Cleared by:
Over Voltage
whether an Over An Over Voltage
146 Trip Protection 42-00.00
Voltage Trip has Trip has occurred.  "Reset Fault
Trip
occurred. flags and
Set if the number Currents"
of Trips followed control.
by a Close due to  Any Operator
Excess Under Under Voltage Excess Under Close or
147 Voltage Protection has Voltage Sequecnes Operator Trip. 42-00.00
Sequences exceeded the have occurred This includes
allowed number remote control
in the time commands.
allocated  Start of a new
Set if the time sequence.
allocated for a
Voltage Voltage has failed
close after a
148 Recovery to recover in the 42-00.00
Voltage
Timeout allocated time
protection trip
has expired.
Set if the number
of Trips followed

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 30 of 72

by a Close due to
Over Voltage
Excess Over Protection has Excess Over
149 Voltage exceeded the Voltage Sequecnes 42-00.00
Sequences allowed number have occurred
in the time
allocated
Active
150 Protection 42-00.00
Group A
Active
151 Protection Cleared by one of 42-00.00
Group B the following
actions
Active
152 Protection 42-00.00
Group C  'Reset Flags
and Currents'
Active protocol
153 Protection command. 42-00.00
Group D  Any operator
Active close
154 Protection The active The active 42-00.00
(including
Group E protection group protection group for
remote
for the most the most recent
Active commands).
recent protection protection
155 Protection  Start of a new 42-00.00
sequence. sequence.
Group F sequence.
Active The time
156 Protection stamp reflects 42-00.00
Group G this.
 Controller
Active Software
157 Protection Reset (data is 42-00.00
Group H volatile).
Active
158 Protection 42-00.00
Group I
Active
159 Protection 42-00.00
Group J
A Phase
A Phase
160 Overcurrent 44-04.25
Overcurrent Fault
Fault
B Phase
B Phase
161 Overcurrent 44-04.25
Overcurrent Fault
Fault
C Phase
C Phase
162 Overcurrent 44-04.25
Overcurrent Fault
Fault

This point is a
combination (OR)
between Phase
Overcurrent Phase
Phase Protection Trip 1, Cleared by Overcurrent 44-

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 31 of 72

Overcurrent Phase Overcurrent  Operator trip. Protection 14.00


Trip Protection Trip 2,  Any close. Trip
Phase Overcurrent  Reset Flags'
163
Protection Trip 3, Protocol
Phase Overcurrent Command.
Protection Trip 4.
This point is a
These flags show combination (OR)
which elements between
were picked up Earth/Ground
at the time of the Overcurrent
most recent Protection Trip 1,
Earth/Ground
Earth/Ground fault. Earth/Ground
Overcurrent 44-
164 Overcurrent Overcurrent
Protection 14.00
Trip Protection Trip 2,
Trip
Earth/Ground
Overcurrent
Protection Trip 3,
Earth/Ground
Overcurrent
Protection Trip 4.
This point is a
combination
(OR) between
Earth/Ground
Overcurrent
Protection Trip 1,
Earth/Ground
SEF/SGF Sensitive
Overcurrent
165 Overcurrent Earth/Ground Fault 44-14.00
Protection Trip 2,
Trip Protection Trip
Earth/Ground
Overcurrent
Protection Trip 3,
Earth/Ground
Overcurrent
Protection Trip
4.
1- Note: The phase designation A, B, C is determined by the user, refer to the Switchgear Details
section and the Switchgear Technical Manual.

A.1.4Distributed Automation Flags


These flags show the status of the operator controls for the Loop Automation and Auto-Changeover
options. Refer to the Distributed Automation section. They are equivalent to the messages displayed
on the controller's Operator Control Panel. These flags are only valid when the Loop Automation or
Auto-Changeover option is enabled for the current configuration and are always '0' otherwise.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
Loop Loop Automation is
0 Loop Automation is OFF. 41-00.00
Automation On ON.

Loop

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 32 of 72

Automation
1 Auto Restore Auto Restore is ON. Auto Restore is OFF. 41-00.00
On
The Tie Recloser will only
Loop The Tie Recloser is restore supply to its Load
Automation Tie configured to restore side or the Recloser Type
2 41-00.00
Restore supply in both is not set to 'Tie'.
Direction directions.
(1)
Loop
Automation Recloser Type is set Recloser Type is not set
3 41-00.00
Recloser Type to 'Feeder'. to 'Feeder'.
Feeder
Loop
Automation Recloser Type is set Recloser Type is not set
4 41-00.00
Recloser Type to 'MidPoint'. to 'MidPoint'.
MidPoint
Loop
Automation Recloser Type is set Recloser Type is not set
5 41-00.00
Recloser Type to 'Tie'. to 'Tie'.
Tie
Normal state, Cleared on
Loop Not suitable for Set when Loop
next internal scan after
8 Automation Trip poll oriented Automation issues a 41-00.00
Set. Point cleared after 1
Request protocols. Trip Request.
second.
Normal state, Cleared on
Loop Not suitable for Set when Loop
next internal scan after
9 Automation poll oriented Automation issues a 41-00.00
Set. Point cleared after 1
Close Request protocols. Close Request.
second.
1- Notes

1.The power flow direction (source/load designation) is determined by the user, refer to Recloser
and Controller State Flags section, Power Flow Direction for status, Power Flow Direction for
control.

A.1.5Pickup Flags
These flags show the pickup and reset of individual protection elements.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
A-Phase
0 Overcurrent (1) Pickup. Pickup Reset. 41-00.00
Pickup
B-Phase
1 Overcurrent (1) Pickup. Pickup Reset. 41-00.00
Pickup
C-Phase
2 Overcurrent (1) Pickup. Pickup Reset. 41-00.00
Pickup
Earth/Ground

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 33 of 72

Overcurrent
3 Pickup. Pickup Reset. 41-00.00
Pickup
SEF/SGF
4 Overcurrent Pickup. Pickup Reset. 41-00.00
Pickup
Under
5 Frequency Pickup. Pickup Reset. 41-00.00
Pickup
Over Frequency
6 Pickup. Pickup Reset. 41-00.00
Pickup
Phase A Current has
Phase A Pickup
11 exceeded its threshold 41-00.00
Latched Cleared by
setting.
Phase B Current has
Phase B Pickup  "Reset fault
12 exceeded its threshold 41-00.00
Latched flags and
setting.
currents"
Phase C Current has
Phase C Pickup control.
13 exceeded its threshold 41-00.00
Latched  Next pickup
setting.
detected and
Earth/Ground Current this pickup
Earth/Ground
14 has exceeded its has cleared. 41-00.00
Pickup Latched
threshold setting.  Protection
SEF/SGF Current has turned OFF.
exceeded its SEF/SGF
SEF/SGF
15 threshold setting but 41-00.00
Pickup Latched
not the Earth/Ground
threshold setting.
Cleared by
Measured frequency
Under  "Reset fault
has fallen below the
16 Frequency flags and 41-00.00
low frequency
Pickup latched currents"
threshold.
control.
 Next pickup
detected and
this pickup
Measured frequency has cleared.
Over Frequency has risen above the Protection
17  41-00.00
Pickup Latched high frequency turned OFF.
threshold.

Phase A voltage has


fallen below the 'Phase
Loss of Phase Lost' setting for longer
18 A indication than the Loss Of 41-00.00
latched Phase time setting (but
not if all three phases Cleared by
are lost in this time).
 "Reset fault
Phase B voltage has flags and
19 fallen below the 'Phase currents" 41-00.00
Loss of Phase Lost' setting for longer control.
B indication than the Loss Of  Next pickup

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 34 of 72

latched Phase time setting (but detected and


not if all three phases this pickup
are lost in this time). has cleared.
Phase C voltage has  Protection
fallen below the 'Phase turned OFF.
Loss of Phase Lost' setting for longer
20 C indication than the Loss Of 41-00.00
latched Phase time setting (but
not if all three phases
are lost in this time).
NPS NPS Current has
21 Overcurrent exceeded the NPS Pickup Reset. 41-00.00
Pickup threshold setting.
Cleared by

 "Reset fault
flags and
currents"
control.
NPS Current has
NPS Pickup  Next pickup
22 exceeded the NPS 41-00.00
Latched detected and
threshold setting.
this pickup
has cleared.
 Protection
turned OFF.

This flags whether a


Phase Overcurrent One or more trips were
Accumulated
Trip occured. This caused by Phase
23 Phase All fault flags are 41-00.00
flag can be set at the Overcurrent
Overcurrent Trip cleared by one of
same time as other protection.
accumulated flags. the following
actions:
This flags whether an
Earth/Ground One or more trips were
Accumulated  "Reset Fault
Overcurrent Trip caused by
Earth/Ground Flags and
24 occured. This flag can Earth/Ground 41-00.00
Overcurrent Currents"
be set at the same Overcurrent
Trip. control.
time as other protection.
accumulated flags.  Any operator
close action.
This flags whether an  Controller
SEF/SGF Overcurrent One or more trips were software
Accumulated
Trip occurred. This caused by Sensitive reset (data is 41-00.00
25 SEF/SGF
flag can be set at the Earth/Ground fault volatile).
Overcurrent Trip
same time as other protection.  Start of a
accumulated flags. new
This flags whether a sequence.
Sequence Advance
Accumulated
ocurred. This flag can One or more sequence
26 Sequence 41-00.00
be set at the same advances occurred.
Advance.
time as other
accumulated flags.
The fault flag is

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 35 of 72

cleared by one of
the following
actions:

 "Reset Fault
Flags and
This flags that a NPS
A NPS fault has been Currents"
27 NPS Alarm fault has been picked 41-00.00
picked up. control.
up.
 Controller
software
reset (data is
volatile).

All fault flags are


cleared by one of
the following
actions:

 "Reset Fault
Flags and
This flags whether an Currents"
Accumulated NPS Overcurrent Trip One or more trips were control.
NPS occured. This flag can caused by NPS  Any operator
28 41-00.00
Overcurrent be set at the same Overcurrent close action.
Trip. time as other protection.  Controller
accumulated flags. software
reset (data is
volatile).
 Start of a
new
sequence.

A phase pickup on any


Any Phase Whether any phase phase has been
All phase pickups
29 Overcurrent has detected detected. 41-00.00
have been reset.
Pickup overcurrent.
(2)
The flag is cleared
by one of the
following actions:

 "Reset Fault
This flags that a Loss
Flags and
Of Phase condition A Loss Of Phase
Loss Of Phase Currents"
30 has been detected condition has been 41-00.00
Alarm control.
but Loss Of Phase is detected.
 Controller
in the Alarm mode.
software
reset (data is
volatile).

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 36 of 72

Reverse A-
Reverse Pickup
31 Phase (1) Reverse Pickup. 41-00.00
Reset.
Overcurrent
Reverse B-
Reverse Pickup
32 Phase (1) Reverse Pickup. 41-00.00
Reset.
Overcurrent
Reverse C-
Reverse Pickup
33 Phase (1) Reverse Pickup. 41-00.00
Reset.
Overcurrent
Reverse
Earth/Ground Reverse Pickup
34 Reverse Pickup. 41-00.00
Overcurrent Reset.
Pickup
Reverse
SEF/SGF Reverse Pickup
35 Reverse Pickup. 41-00.00
Overcurrent Reset.
Pickup
Reverse Phase Reverse Phase A
36 A Pickup Current has exceeded 41-00.00
Latched its threshold setting. Cleared by
Reverse Phase Reverse Phase B
 "Reset fault
37 B Pickup Current has exceeded 41-00.00
Latched its threshold setting. flags and
currents"
Reverse Phase Reverse Phase C
control.
38 C Pickup Current has exceeded 41-00.00
 Next pickup
Latched its threshold setting.
detected and
Reverse Earth/Ground Current this pickup
39 Earth/Ground has exceeded its has cleared. 41-00.00
Pickup Latched threshold setting.  Protection
SEF/SGF Current has turned OFF.
Reverse exceeded its SEF/SGF
40 SEF/SGF threshold setting but 41-00.00
Pickup Latched not the Earth/Ground
threshold setting.
Reverse NPS Reverse NPS Current
41 Overcurrent has exceeded the NPS Pickup Reset. 41-00.00
Pickup threshold setting.
Cleared by

 "Reset fault
flags and
currents"
control.
Reverse NPS Current
Reverse NPS  Next pickup
42 has exceeded the NPS 41-00.00
Pickup Latched detected and
threshold setting.
this pickup
has cleared.
 Protection
turned OFF.

This flags whether a

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 37 of 72

Reverse Phase
Reverse Overcurrent Trip One or more trips were All fault flags are
Accumulated occured. This flag can caused by Reverse cleared by one of
43 the following 41-00.00
Phase be set at the same Phase Overcurrent
Overcurrent Trip time as other protection. actions:
accumulated flags.
 "Reset Fault
This flags whether a
Flags and
Reverse
Reverse One or more trips were Currents"
Earth/Ground
Accumulated caused by Reverse control.
Overcurrent Trip
44 Earth/Ground Earth/Ground  Any operator 41-00.00
occured. This flag can
Overcurrent Overcurrent close action.
be set at the same
Trip. protection.  Controller
time as other
software
accumulated flags.
reset (data is
This flags whether a volatile).
Reverse SEF/SGF Start of a
Accumulated One or more trips were 
Overcurrent Trip new
Reverse caused by a Reverse
45 occurred. This flag sequence. 41-00.00
SEF/SGF Sensitive Earth/Ground
can be set at the
Overcurrent Trip fault protection.
same time as other
accumulated flags.
The fault flag is
cleared by one of
the following
actions:

 "Reset Fault
This flags that a Flags and
Reverse NPS A reverse NPS fault
46 reverse NPS fault has Currents" 41-00.00
Alarm has been picked up.
been picked up. control.
 Controller
software
reset (data is
volatile).

All fault flags are


cleared by one of
the following
actions:
This flags whether a
 "Reset Fault
reverse NPS
Accumulated One or more trips were Flags and
Overcurrent Trip
Reverse NPS caused by a reverse Currents"
47 occured. This flag can 41-00.00
Overcurrent NPS Overcurrent control.
be set at the same
Trip. protection.  Any operator
time as other
close action.
accumulated flags.
 Controller
software
reset (data is
volatile).
 Start of a
new

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 38 of 72

sequence.

Any Phase
Whether any phase A phase reverse All phase reverse
Reverse
48 has detected reverse pickup on any phase pickups have been 41-00.00
Overcurrent
overcurrent. has been detected. reset.
Pickup
The measured
'Source' Voltage has
Under Voltage
49 fallen below the Pickup Reset 42-00.00
Pickup
Under Voltage trip
threshold
The measured
Over Voltage 'Source' Voltage has
50 Pickup Reset 42-00.00
Pickup risen above the Over
Voltage trip threshold
Cleared by
The measured
'Source' Voltage has  "Reset fault
Under Voltage flags and
51 fallen below the Pickup 42-00.00
Pickup Latched currents"
Under Voltage trip
threshold control.
 Next pickup
detected and
this pickup
The measured has cleared.
Over Voltage 'Source' Voltage has  Protection
52 Pickup 42-00.00
Pickup Latched risen above the Over turned OFF.
Voltage trip threshold

1- Note: The phase designation A, B, C is determined by the user, refer to switchgear details section
and the Switchgear Technical Manual.
2- If directional protection is ENABLED then this point only refers to the forward direction.

A.1.6IOEX Inputs
These flags reflect the raw states of the IOEX inputs after a 30ms debounce. These flags will be clear if
the associated IOEX card is not connected.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
IOEX Input Input Not
0 41-00.00
Input 1 Asserted Asserted
IOEX Input Input Not
1 41-00.00
Input 2 Asserted Asserted
IOEX Returned State changes after 30ms Input Input Not
2 41-00.00
Input 3 debounce. Asserted Asserted
IOEX Input Input Not
3 41-00.00
Input 4 Asserted Asserted
IOEX Input Input Not
4 41-00.00
Input 5 Asserted Asserted

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 39 of 72

IOEX Input Input Not


5 41-00.00
Input 6 Asserted Asserted
IOEX Input Input Not
6 41-00.00
Input 7 Asserted Asserted
IOEX Input Input Not
7 41-00.00
Input 8 Asserted Asserted

A.1.8Protocol IOEX Control Status


Indicate the status of "Digital Controls:Protocol IOEX Controls" points.

"Protocol IOEX Control Status" points can be selected to stimulate IOEX outputs with the IOEX
configuratioon tool.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
Protocol
IOEX
0 41-00.00
Control 1
State
Protocol
IOEX
1 41-00.00
Control 2
State
Protocol
IOEX
2 41-00.00
Control 3
State
Protocol
IOEX
3 41-00.00
Control 4 Virtual RTU points that are
State Protocol IOEX Protocol IOEX
set/cleared directly by there
Control 'x' Control 'x' NOT
Protocol respective "Digital Control:Protocol
asserted. asserted.
IOEX IOEX Controls" point.
4 41-00.00
Control 5
State
Protocol
IOEX
5 41-00.00
Control 6
State
Protocol
IOEX
6 41-00.00
Control 7
State
Protocol
IOEX
7 41-00.00
Control 8
State

Appendix A.2Analog Data

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 40 of 72

A.2.1Line Currents
Note: These relate to the user designated phases rather than the physical bushings.

Version
Point Name Description Min Max Unit(s) Resolution Deadband
Introduced
0 A-Phase Current The line current 0 16000 Amps 0.1 10 41-00.00
1 B-Phase Current flowing through 0 16000 Amps 0.1 10 41-00.00
2 C-Phase Current each phase. (1) 0 16000 Amps 0.1 10 41-00.00
The vector
summation of the
Earth/Ground
3 line currents flowing 0 16000 Amps 0.1 5 41-00.00
Current
through the 3
phases.
A-Phase Load
Current Prior to
5 0 16000 Amps 0.1 10 41-00.00
most recent
Pickup The line current
flowing through
B-Phase Load
each phase just
Current Prior to
6 prior to the first 0 16000 Amps 0.1 10 41-00.00
most recent
pickup of the most
Pickup
recent sequence
C-Phase Load occurring. (1)
Current Prior to
7 0 16000 Amps 0.1 10 41-00.00
most recent
Pickup
A-Phase
8 Maximum 0 16000 Amps 0.1 10 41-02.35
Demand The maximum line
B-Phase current detected on
9 Maximum each phase since 0 16000 Amps 0.1 10 41-02.35
Demand the last maximum
C-Phase demand reset
10 Maximum 0 16000 Amps 0.1 10 41-02.35
Demand
Day of A-Phase
11 Maximum 0 366 Days 1 1 41-02.35
Demand The Day of the year
of the maximum line
Day of B-Phase
current detected on
12 Maximum 0 366 Days 1 1 41-02.35
each phase since
Demand
the last maximum
Day of C-Phase demand reset
13 Maximum 0 366 Days 1 1 41-02.35
Demand
Minute of A-
14 Phase Maximum 0 1439 Mins 1 1 41-02.35
Demand The minute of the
Minute of B- day of the maximum
15 Phase Maximum line current detected 0 1439 Mins 1 1 41-02.35
Demand on each phase since
the last maximum

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 41 of 72

Minute of C- demand reset


16 Phase Maximum 0 1439 Mins 1 1 41-02.35
Demand
Second of A-
17 Phase Maximum The Second of the 0 59 Seconds 1 1 41-02.35
Demand minute of the
Second of B- maximum line
18 Phase Maximum current detected on 0 59 Seconds 1 1 41-02.35
Demand each phase since
Second of C- the last maximum
19 Phase Maximum demand reset 0 59 Seconds 1 1 41-02.35
Demand
The average of the
Instantaneous 3
line currents flowing
20 Phase Current 0 16000 Amps 0.1 10 42-00.60
through the 3
Average
phases. (1)
1- Note: The phase designation A, B, C is determined by the user, refer to Switchgear Details section
and the Switchgear Technical Manual.

A.2.2Voltage Measurements
Both Phase/(Earth/Ground) and Phase/Phase voltages are available (three phase switchgear only).
Usually the utility requires only one of these to be sent to the SCADA system.

Voltages are provided for all terminals with voltage measurement. The number of terminals with
voltage measurement varies depending on the model of switchgear, refer to the equipment manual.
The phase designation is assigned by the user. Refer to Switchgear Details section. The table below
distinguishes between the I and X sides of the switchgear, some models refer to the 1 and 2 sides (eg.
A1, A2).

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Phase to
Ai Phase to Earth/Ground voltage
0 Earth/Ground for Phase A on the I 0 30000 Volts 1 100 41-00.00
Volts side of the switchgear
measured.
Phase to
Bi Phase to Earth/Ground voltage
1 Earth/Ground for Phase B on the I 0 30000 Volts 1 100 41-00.00
Volts side of the switchgear
measured.
Phase to
Ci Phase to Earth/Ground voltage
2 Earth/Ground for Phase C on the I 0 30000 Volts 1 100 41-00.00
Volts side of the switchgear
measured.

Ax Phase to Phase to
3 Earth/Ground Earth/Ground voltage 0 30000 Volts 1 100 41-00.00
Volts for Phase A on the X
side of the switchgear

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 42 of 72

measured.
Phase to
Bx Phase to Earth/Ground voltage
4 Earth/Ground for Phase B on the X 0 30000 Volts 1 100 41-00.00
Volts side of the switchgear
measured.
Phase to
Cx Phase to Earth/Ground voltage
5 Earth/Ground for Phase C on the X 0 30000 Volts 1 100 41-00.00
Volts side of the switchgear
measured.
Phase A to Phase B
ABi Phase to
6 voltage on the I side 0 38000 Volts 1 100 41-00.00
Phase
of the switchgear.
Phase B to Phase C
BCi Phase to
7 voltage on the I side 0 38000 Volts 1 100 41-00.00
Phase
of the switchgear
Phase C to Phase A
CAi Phase to
8 voltage on the I side 0 38000 Volts 1 100 41-00.00
Phase
of the switchgear
Phase A to Phase B
ABx Phase to
9 voltage on the X side 0 38000 Volts 1 100 41-00.00
Phase
of the switchgear. (1)
Phase B to Phase C
BCx Phase to
10 voltage on the X side 0 38000 Volts 1 100 41-00.00
Phase
of the switchgear. (1)
Phase C to Phase A
CAx Phase to
11 voltage on the X side 0 38000 Volts 1 100 41-00.00
Phase
of the switchgear. (1)
Phase to
I Side Voltages -
Earth/Ground voltage
Phase to
averave of 3 phases
12 Earth/Ground - 0 30000 Volts 1 100 41-00.00
on the I side of the
Average of 3
switchgear
phases
measured.
I Side Voltages -
Phase to Phase A
Phase to Phase -
13 voltage on the X side 0 38000 Volts 1 100 42-00.60
Average of 3
of the switchgear. (1)
phases
1- If no Xside CVTs present then value will always be zero.

A.2.3System Power

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Total Real Power
flowing through the
switchgear. This can be
a signed quantity which

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 43 of 72

indicates direction of
power flow, or an
unsigned quantity
which is always
Real
positive regardless of -
0 Power - 1900000 kW 1 250 41-00.00
the direction of the 1900000
P
power flow. This is
determined by the
controller
configuration.
Apparent
1 Power - Apparent power. 0 1900000 kVA 1 250 41-00.00
S
Total Reactive Power
flowing through the
switchgear.

This is a signed
quantity if the operator
Reactive setting "Power
-
2 Power - Measurement" is set to 1900000 kVAR 1 250 41-00.00
1900000
Q "Signed"

The sign is negated if


"Power Measurement"
is set to "Signed" AND
"Power Direction" is set
to "Source x -> Load i".
Power factor. This is
calculated from the
Real and Apparent
Power power.
3 0 1 N/A 0.01 0.01 41-00.00
Factor
See Technical Manual
for accuracy
specification.
Real Power flowing
through the A phase.
This can be a signed
quantity which
indicates direction of
A Phase power flow, or an
Real unsigned quantity -
4 1900000 kW 1 250 41-00.00
Power - which is always 1900000
P positive regardless of
the direction of the
power flow. This is
determined by the
controller
configuration.

Apparent Power
A Phase flowing through the A
Apparent phase. This is an -

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 44 of 72

Power - unsigned quantity 1900000


S which is always
5 1900000 kVA 1 250 41-00.00
positive irrespective of
direction of power flow.
Reactive Power flowing
through the A phase.
A Phase
This is an unsigned
Reactive
6 quantity which is 0 1900000 kVAR 1 250 41-00.00
Power -
always positive
Q
irrespective of direction
of power flow.
A Phase Power factor.
This is calculated from
the Real and Apparent
A Phase
power.
7 Power 0 1 N/A 0.01 0.01 41-00.00
Factor
See Technical Manual
for accuracy
specification.
Real Power flowing
through the B phase.
This can be a signed
quantity which
indicates direction of
B Phase power flow, or an
Real unsigned quantity -
8 1900000 kW 1 250 41-00.00
Power - which is always 1900000
P positive regardless of
the direction of the
power flow. This is
determined by the
controller
configuration.
Apparent Power
flowing through the B
B Phase
phase. This is an
Apparent -
9 unsigned quantity 1900000 kVA 1 250 41-00.00
Power - 1900000
which is always
S
positive irrespective of
direction of power flow.
Total Reactive Power
flowing through the
B Phase
switchgear. This is an
Reactive
10 unsigned quantity 0 1900000 kVAR 1 250 41-00.00
Power -
which is always
Q
positive irrespective of
direction of power flow.
B Phase Power factor.
B Phase This is calculated from
11 Power the Real and Apparent 0 1 N/A 0.01 0.01 41-00.00
Factor power.

See Technical Manual

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 45 of 72

for accuracy
specification.
Real Power flowing
through the C phase.
This can be a signed
quantity which
indicates direction of
C Phase power flow, or an
Real unsigned quantity -
12 1900000 kW 1 250 41-00.00
Power - which is always 1900000
P positive regardless of
the direction of the
power flow. This is
determined by the
controller
configuration.
Apparent Power
flowing through the C
C Phase
phase. This is an
Apparent -
13 unsigned quantity 1900000 kVA 1 250 41-00.00
Power - 1900000
which is always
S
positive irrespective of
direction of power flow.
Reactive Power flowing
through the C phase.
C Phase
This is an unsigned
Reactive
14 quantity which is 0 1900000 kVAR 1 250 41-00.00
Power -
always positive
Q
irrespective of direction
of power flow.
C Phase Power factor.
This is calculated from
the Real and Apparent
C Phase
power.
15 Power 0 1 N/A 0.01 0.01 41-00.00
Factor
See Technical Manual
for accuracy
specification.

A.2.4SF6 Gas Pressure


Not all models of switchgear have gas pressure measurement.

Point 0 and 1 are the same measurement, just in different units. Normally only one is sent back to the
SCADA system.

The pressure is zeroed if switchgear data is invalid. Refer to Recloser and Controller State Flags
section.

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
0 Gas Pressure SI - 300 kPa 1 5 41-00.00

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 46 of 72

100
SF6 gas
Gas Pressure pressure.
1 -14 44 PSI 0.1 1 41-00.00
Imperial

A.2.5Protection State
Refer also to Operator/Protection flags for switchgear

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Value is zero when Cold Load
is Idle or OFF. When Cold
Load is not idle this shows the
Operational Cold Load Time,
0 Cold Load 0 480 Mins 1 1 41-00.00
i.e. the current time being used
to calculate the Operational
Cold Load Threshold
Multiplier.
0 = Protection Group A
Protection
1 Group in 1 = Protection Group B 0 9 N/A 1 1 41-00.00
service.
n = Other Protection Group
0 = NPS Protection OFF
NPS
2 protection 1 = NPS Protection ON 0 2 N/A 1 1 41-00.00
status
2 = NPS Protection Alarm only
Value is zero when Cold Load
is Idle or OFF. When Cold
Load is not idle this shows the
Reverse Operational Cold Load Time,
3 0 480 Mins 1 1 41-02.43
Cold Load i.e. the current time being used
to calculate the Operational
Cold Load Threshold
Multiplier.
0 = Loss of phase OFF
Loss of
4 phase 1 = Loss of phase ON 0 2 N/A 1 1 44-04.20
status
2 = Loss of phase Alarm only

A.2.6Protection Sequence and Trip Data


These analog points record data about a protection sequence including maximum trip currents. They
are derived from the trip current events, as recorded in the event log and give the current for each
phase and any other enabled protecion element currents greater than the "Zero Amps Indicated"
threshold.

Other data recorded includes the number of trips in the protection sequence and the Protection Group
(s) that were active at the start of the protection sequence.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 47 of 72

Protection Sequence and Trip Data is cleared to zero by the following actions :-

 "Reset fault flags and currents" control.


 Any Operator Close or Trip action.
 Start of a new sequence.

When new values are stored, the event time stamp is the time of the end of the sequence to 10ms
resolution.

Similarly when the values are cleared the event is time tagged to 10ms resolution. Thus the time
stamps correspond to the digital time stamps in Appendix A.1.3.

This data is volatile, and are zeroed on controller software reset.

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
A-Phase
0 A Phase current at trip. 0 16000 Amps 1 1 41-00.00
Current Trip-1
A-Phase Written on a Protection
1 Trip after a pickup has 0 16000 Amps 1 1 41-00.00
Current Trip-2
occurred. Four values are
A-Phase provided: one for each
2 0 16000 Amps 1 1 41-00.00
Current Trip-3 possible trip in the
A-Phase sequence.(1)
3 0 16000 Amps 1 1 41-00.00
Current Trip-4
B-Phase
4 B Phase current at trip. 0 16000 Amps 1 1 41-00.00
Current Trip-1
B-Phase Written on a Protection
5 Trip after a pickup has 0 16000 Amps 1 1 41-00.00
Current Trip-2
occurred. Four values are
B-Phase provided: one for each
6 0 16000 Amps 1 1 41-00.00
Current Trip-3 possible trip in the
B-Phase sequence.(1)
7 0 16000 Amps 1 1 41-00.00
Current Trip-4
C-Phase
8 C Phase current at trip. 0 16000 Amps 1 1 41-00.00
Current Trip-1
C-Phase Written on a Protection
9 Trip after a pickup has 0 16000 Amps 1 1 41-00.00
Current Trip-2
occurred. Four values are
C-Phase provided: one for each
10 0 16000 Amps 1 1 41-00.00
Current Trip-3 possible trip in the
C-Phase sequence.(1)
11 0 16000 Amps 1 1 41-00.00
Current Trip-4
Earth/Ground Earth/Ground current at
12 0 16000 Amps 1 1 41-00.00
Current Trip 1 trip. Written on a
Earth/Ground Protection Trip after a
13 pickup has occurred. This 0 16000 Amps 1 1 41-00.00
Current Trip 2
includes SEF/SGF Fault
Earth/Ground currents. Four values are
14 0 16000 Amps 1 1 41-00.00
Current Trip 3 provided: one for each
Earth/Ground possible trip in the
15 0 16000 Amps 1 1 41-00.00
Current Trip 4 sequence.(2)

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 48 of 72

Active
The protection group that
16 Protection 0 9 N/A 1 1 41-00.00
is being used at present.
Group
The number of trips or
sequence advances that
occurred in the protection
sequence. This number
Trips In will be less than the full
17 0 4 Trips 1 1 41-00.00
Sequence programmed sequence if
the fault was cleared, or if
the sequence was
terminated by high
current lockout.
A-Phase The Current recorded for
18 Current most A Phase at the time of the 0 16000 Amps 1 1 41-00.00
recent trip most recent trip.(1)
B-Phase The Current recorded for
19 Current most B Phase at the time of the 0 16000 Amps 1 1 41-00.00
recent trip most recent trip.(1)
C-Phase The Current recorded for
20 Current most C Phase at the time of 0 16000 Amps 1 1 41-00.00
recent trip the most recent trip.(1)
The Current recorded for
Earth/Ground Earth/Ground at the time
21 Current most the most recent trip. This 0 16000 Amps 1 1 41-00.00
recent trip includes SEF/SGF Fault
currents.(2)
NPS Current
22 0 16000 Amps 1 1 41-00.00
Trip 1 NPS Trip Current. Written
NPS Current on a Protection Trip after
23 0 16000 Amps 1 1 41-00.00
Trip 2 a pickup has occurred.
NPS Current Four values are provided:
24 one for each possible trip 0 16000 Amps 1 1 41-00.00
Trip 3
NPS Current in the sequence.(2)
25 0 16000 Amps 1 1 41-00.00
Trip 4
NPS Current The NPS Current
26 most recent recorded at the time of 0 16000 Amps 1 1 41-00.00
trip the most recent trip.(2)
The maximum current
value that was logged for
Maximum A-
phase A during the most
27 Phase Fault 0 16000 Amps 1 1 41-00.00
recent sequence if phase
Current
A picked up. Not reset by
a Trip.(1)
The maximum current
value that was logged for
Maximum B-
phase B during the most
28 Phase Fault 0 16000 Amps 1 1 41-00.00
recent sequence if phase
Current
B picked up. Not reset by
a Trip.(1)
The maximum current
value that was logged for

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 49 of 72

phase C during the most


Maximum C-
recent sequence if phase
29 Phase Fault 0 16000 Amps 1 1 41-00.00
C picked up. Not reset by
Current
a Trip.(1)
The maximum current
value that was logged for
Maximum Earth/Ground during the
30 Earth/Ground most recent sequence if 0 16000 Amps 1 1 41-00.00
Fault Current phase Earth/Ground
picked up. Not reset by a
Trip.
The maximum current
value that was logged for
Maximum
NPS during the most
31 NPS Fault 0 16000 Amps 1 1 41-00.00
recent sequence if NPS
Current
picked up. Not reset by a
Trip.
Active
The reverse directional
Reverse
32 protection group that is 0 9 N/A 1 1 41-00.00
Protection
active.(3)
Group
The number of forward
trips or sequence
advances that occurred in
the protection sequence.
This number will be less
Fwd Trips In
33 than the full programmed 0 4 Trips 1 1 41-04.03
Sequence
sequence if the fault was
cleared, or if the
sequence was terminated
by another protection
element.(3)
The number of reverse
trips or sequence
advances that occurred in
the protection sequence.
This number will be less
Rev Trips In
34 than the full programmed 0 4 Trips 1 1 41-04.03
Sequence
sequence if the fault was
cleared, or if the
sequence was terminated
by another protection
element.(3)
1- Note: The phase designation A, B, C is determined by the user, refer to Switchgear Details section
and the Switchgear Technical Manual.
2- Note: Only valid when the respective protection element is 'Enabled' (Earth/Ground, NPS etc) and
the element current was greater than the "Zero Amps Indicated" threshold during the pickup.
3- Note: Only valid when Directional Protection is ENABLED.

A.2.7Switchgear Details
This is switchgear configuration data held in the switchgear memory or Controller.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 50 of 72

Version
Point Name Description Min Max Unit(s) Resolution Deadband
Introduced
The serial
number of the
Switch
switchgear.
0 Serial 0 2147483647 N/A 1 1 41-00.00
Requires full 32
Number
bits for this to
work.
I Contact
1 The percentage 0 100 % 0.01 1 41-00.00
Life
of vacuum
II Contact
2 interrupter life 0 100 % 0.01 1 41-00.00
Life
remaining for
III Contact each phase.
3 0 100 % 0.01 1 41-00.00
Life
The count of the
Operations number of closes
4 0 65535 Operations 1 1 41-00.00
Counter performed by the
switchgear.
The low 4
decimal digits of
Switch
the serial
Serial
6 number of the 0 9999 N/A 1 1 41-00.00
Number [0-
switchgear.
9999]
Requires 16 bits
for this to work.
The high decimal
Switch digits of the
Serial serial number of
7 0 65535 N/A 1 1 41-00.00
Number the switchgear.
[10000+] Requires 16 bits
for this to work.

A.2.8Controller Data

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Battery The controller battery
0 0 32 Volts 0.01 1 41-00.00
Voltage voltage.
ADVC
The Controller serial
2 Serial 0 2147483647 N/A 1 1 41-00.00
number.
Number
The code version is a
six-digit number that
Code has the form yy-xx.xx
3 0 100000000 N/A 1 1 41-00.00
Version with the dash and
point formatting
removed.
Battery Status
0=Battery Overvolts,

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 51 of 72

1=Battery Normal,
Battery
4 2=Battery Low Volts, 0 3 N/A 1 1 41-00.00
Status
3=Battery Off.
The code version is a
four-digit number that
has the form xx.xx
Code
with the point
5 Version 0 65535 N/A 1 1 41-00.00
formatting removed.
[Minor.Cut]
Combines with high 16
bits in the form yy-
xx.xx.
The code version is a
two-digit number that
Code
has the form yy.
6 Version 0 65535 N/A 1 1 41-00.00
Combines with low 16
[Major-]
bits in the form yy-
xx.xx.

A.2.9Distributed Automation
Refer also to Distributed Automation Flags.

This point is only valid when the loop automation option is enabled for the current configuration and is
otherwise always repeated as zero.

Version
Point Name Description Min Max Unit(s) Resolution Deadband
Introduced
This is the Loop
Automation timeout value
LA while counting down prior
0 Remaining to a Trip or Close action 0 1800 Seconds 1 10 41-00.00
Time occurring. When no action
is pending the value is
zero.

A.2.10Daily Data
Daily data is updated at midnight, but only when collected over a full 24-hour period.

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
This is the maximum
Maximum current average of all
0 Average phases for the previous full 0 16000 Amps 0.1 1 41-00.00
Current day ending at midnight
(2sec filter window).

Time of This is the end time of the


Maximum maximum average demand
2 current of all relevant 0 1439 Mins 1 1 41-00.00
Average
Current phases for the previous full
day ending at midnight. The

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 52 of 72

time is in minutes since


midnight.
This is the maximum
Maximum
average demand current of
Average
3 all relevant phases for the 0 16000 Amps 1 10 41-00.00
Demand
previous full day ending at
Current
midnight.
The average demand
Average period in force at the time
4 Demand the "Maximum Average 1 1440 Mins 1 1 41-00.00
Period Demand Current" was
recorded.

A.2.11Supply Outage Measurement

Version
Point Name Description Min Max Unit(s)
Introduced
Source The number of supply outages on the
0 0 2147483647 N/A 41-00.00
Outages source terminals.(1)(2)
Source
The total duration of supply outages on
1 Outages 0 2147483647 Seconds 41-00.00
the source terminals, in seconds.(1)(2)
Duration
Load The number of supply outages on the
2 0 2147483647 N/A 41-00.00
Outages load terminals.(1)(2)
Load
The total duration of supply outages on
3 Outages 0 2147483647 Seconds 41-00.00
the load terminals, in seconds.(1)(2)
Duration
The count of the number of voltage
Sags recorded since the last reset. A
4 Sag Count 0 2147483647 N/A 42-00.00
reset is done from the OCP or WSOS
only!
The count of the number of voltage
Swells recorded since the last reset. A
5 Swell Count 0 2147483647 N/A 42-00.00
reset is done from the OCP or WSOS
only!
The accumulated time of all Sags since
Sag
6 the last reset. A reset is done from the 0 2147483647 Seconds 42-00.00
Duration
OCP or WSOS only.
The accumulated time of all Swells
Swell
7 since the last reset. A reset is done from 0 2147483647 Seconds 42-00.00
Duration
the OCP or WSOS only.
1- Power flow direction (source/load designation) is determined by the user. Refer to Recloser and
Controller State Flags section, Power Flow Direction for status and section B, Power Flow Direction
for control.
2- Data active only when Power Quality option Supply Outage Measurement is Available and ON.

A.2.12Frequency Measurement

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 53 of 72

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
The measured Frequency.
0 Frequency Returns a value of 0 for 0 65 Hz 0.1 1 41-00.00
unavailable

A.2.15Sequence Components
Zero, Positive and Negative Phase Sequence currents and voltages, valid when controller is
configured "Sequence Componets Available.

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
ZPS The zero phase sequence
0 0 16000 Amps 0.1 10 41-00.00
Current current.
PPS The positive phase
1 0 16000 Amps 0.1 10 41-00.00
Current sequence current.
NPS The negative phase
2 0 16000 Amps 0.1 10 41-00.00
Current sequence current.
ZPS The zero phase sequence
3 0 30000 Volts 1 10 41-00.00
Voltage voltage.
PPS The positive phase
4 0 30000 Volts 1 10 41-00.00
Voltage sequence voltage.
NPS The negative phase
5 0 30000 Volts 1 10 41-00.00
Voltage sequence voltager.

Appendix A.3Accumulator Data


Unit Version
Point Name Description Min Max
(s) Introduced
The accumulated kWH at the most recent
freeze and reset operation. This could be
signed or unsigned depending on controller
configuration.This data is volatile, and is
KWH
0 zeroed on controller software reset. If more 0 2147483647 KWH 41-00.00
Cumulative
than one protocol is running simultaneously in
the controller, this data is replicated between
the protocols so each master station can clear
its data independently from the others.
The accumulated kWH in the forward
direction (ie Source to Load) at the most
recent freeze and reset operation. This data is
KWH volatile, and is zeroed on controller software
1 Cumulative reset. If more than one protocol is running 0 2147483647 KWH 41-00.00
Forward simultaneously in the controller, this data is
replicated between the protocols so each
master station can clear its data
independently from the others.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 54 of 72

The accumulated kWH in the reverse


direction (ie Load to Source) at the most
recent freeze and reset operation. This data is
KWH volatile, and is zeroed on controller software
2 Cumulative reset. If more than one protocol is running 0 2147483647 KWH 41-00.00
Reverse simultaneously in the controller, this data is
replicated between the protocols so each
master station can clear its data
independently from the others.

Appendix A.5LBS Points Data


A.5.1Operator/Detection Flags for LBS
These flags show the status of the operator controls and the state of some of the protection, refer to
the Detection State section. They are equivalent to the indications available on the Operator Control
Panel on the controller. These flags are undefined on an ACR, see Operator/Protection Flags for ACR
for the equivalent ACR flags.

It may seem strange that points that do similar things on an ACR and LBS have been mapped twice.
However, experience has shown that the small differences in behaviour of the points have caused
much confusion both in the code and scada system in previous products. The cost to both the
customer and supplier is more than to maintain the points separately.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
Detection
0 Detection ON Detection OFF 43-00.12
Enabled
Earth/Ground
Earth/Ground Detection
1 Detection Earth/Ground Detection ON 43-00.12
OFF
Enabled
SEF/SGF
SEF/SGF Detection
2 Detection SEF/SGF Detection ON 43-00.12
OFF
Enabled
Sectionaliser Sectionaliser OFF
3 Sectionaliser Auto 43-00.12
Auto (Load Break Switch)
Cold load pickup is in Auto.
Cold Load pickup is
This means that the cold OFF.
load function is functioning
4 Cold Load Auto and may, or may not, be 43-00.12
This means that the
affecting the threshold
cold load function is
multiplier. This is indicated
completely disabled.
by the Cold Load not Idle
flag below.
Cold load is NOT Idle.
Cold Load is Idle or OFF.
Cold Load see also This means that the
5 43-00.12
Active A.2.5 This means the threshold threshold multiplier is
multiplier is not being being raised by the
affected by the cold load cold load pickup

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 55 of 72

function. function in order to pick


up cold load.
Live Load Live Load Blocking
6 Live Load Blocking ON 43-00.12
Blocking OFF
Automatic
Automatic Detection
Detection Automatic Detection Group
7 Group Selection is 43-00.12
Group Selection is ON
OFF
Selection.
Detection Detection group A is
8 Detection group A is active 43-00.12
Group A Active not active
Detection Detection group B is
9 Detection group B is active 43-00.12
Group B Active not active
Detection Detection group C is
10 Detection group C is active 43-00.12
Group C Active not active
Detection Detection group D is
11 Detection group D is active 43-00.12
Group D Active not active
Detection Detection group E is
12 Detection group E is active 43-00.12
Group E Active not active
Detection Detection group F is
13 Detection group F is active 43-00.12
Group F Active not active
Detection Detection group G is
14 Detection group G is active 43-00.12
Group G Active not active
Detection Detection group H is
15 Detection group H is active 43-00.12
Group H Active not active
Detection Detection group I is not
16 Detection group I is active 43-00.12
Group I Active active
Detection Detection group J is not
17 Detection group J is active 43-00.12
Group J Active active
Cold Load has not
Cold load is at the maximum
20 Cold Load Max reached the maximum 43-00.31
time and multiplier.
time.

A.5.2Detection Flags LBS


This group of points indicates what happened in the most recent fault detection. Unlike the ACR, these
flags don't attempt to reconstruct a fault sequence. The flags are not cumulative, they are cleared as
each new fault is detected. For example, if there is an earth fault followed by a phase fault, the earth
fault flag will be cleared when the phase fault flag is set.

In addition analogue data is available which shows the fault currents refer to Protection Sequence and
Trip Data Section A.2.6.

Most of these flags are cleared either by protocol command or when the switchgear is tripped/closed
by the operator or when a new fault is detected.

This data is volatile, i.e. it is zeroed on controller software reset.

If more than one protocol is running simultaneously in the controller, this data is replicated between the
protocols so that each master station can clear its data independently from the others.

This table is not valid for ACR, see 1 for ACR equivalent.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 56 of 72

Version
Point Name Description Set = '1' Clear = '0'
Introduced
This shows that a
Start of sequence. A
protection SectionaliserTrip
Sequence in detection trip or
0 sequence has 43-00.12
Progress sequence advance has
started and not yet Sequence Reset
occurred.
completed.
A Phase
A Phase Overcurrent
1 Overcurrent 43-00.12
Fault
Fault
B Phase Cleared by
B Phase Overcurrent
2 Overcurrent 43-00.12
Fault
Fault These flags show  Operator trip.
C Phase which elements  Any close.
C Phase Overcurrent
3 Overcurrent were picked up at  Reset Flags' 43-00.12
Fault
Fault the time of the Protocol
Earth/Ground most recent fault. Command.
Earth/Ground
4 Overcurrent 43-00.12
Overcurrent Fault
Fault
SEF/SGF
SEF/SGF Overcurrent
5 Overcurrent 43-00.12
Fault
Fault
Cleared by

 Operator trip.
 Any close.
 Sequence
Supply
6 Supply Interrupt. Supply Interrupt Reset. 43-00.12
Interrupt
 'Reset Flags'
Protocol
Command.

Cleared by

 Operator trip.
 Any close.
Sectionaliser
7 Sectionaliser Trip. Sectionaliser Trip  'Reset Flags' 43-00.12
Trip
Protocol
Command.

The most recent trip was


caused by any a
combination of an OCPM Cleared by any close
8 Operator Trip 43-00.12
Operator Trip OR an action.
IOEX Operator Trip OR a
Protocol Trip.
The most recent Cleared by one of
Operator close was caused Set if the most recent the following actions 43-00.12
15
Close by a local or close caused by local or
remote panel close remote panel close  'Reset Flags

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 57 of 72

request request and Currents'


protocol
The most recent
Set if the most recent command.
close was caused
16 IOEX Close close was caused by an  Controller 43-00.12
by an IOEX close
IOEX close input. Software Reset
input.
(data is
volatile).
The most recent
Set if the most recent  At the time of
close caused by a
17 Protocol Close close caused by a the next Close. 43-00.12
protocol close
protocol close request.
request.
Set if any of the following
caused the most recent Cleared by one of
close the following actions

 CCEM external  'Reset Flags


button on N-Series. and Currents'
 Mechanical action. protocol
The most recent
The switchgear command.
close caused by an
19 External Close detected as closed  Controller 43-00.12
action external to
without a close Software Reset
the Controller
request. (data is
 Electrical action volatile).
(only available on  At the time of
the Advanced the next Close.
controller).

Cleared by one of
the following actions

 'Reset Flags
and Currents'
protocol
Set if the most recent
Live Load command
close request was
20 Block  Controller 43-00.12
blocked due to a Live
Occurred Software Reset
Load condition
(data is
volatile)
 At the time of
the next Close

A Phase OC
Overcurrent Fault on
22 Fault Non- 43-00.12
Phase A
Latching
B Phase OC
Overcurrent Fault on Cleared by
23 Fault Non- 43-00.12
Phase B
Latching
 Operator trip.
C Phase OC
Overcurrent Fault on  Any close.
24 Fault Non- 43-00.12
Phase C  Reset Flags'
Latching
Protocol
Earth/Ground These flags show Command.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 58 of 72

OC Fault Non- which elements Overcurrent Fault on  Fault current


25 43-00.12
Latching have a fault. Earth/Ground going below
SEF/SGF OC the pickup
Overcurrent Fault on threshold for
26 Fault Non- 43-00.12
SEF/SGF the fault reset
Latching
time.
Phase OC
Overcurrent Fault on A,
27 Fault Non- 43-00.12
B or C Phase
Latching
NPS Fault Overcurrent Fault on
28 43-00.22
Non-Latching NPS
Cleared by

These flags show  Operator trip.


NPS which elements  Any close.
29 Overcurrent were picked up at NPS Overcurrent Fault  Reset Flags' 43-00.22
Fault the time of the Protocol
most recent fault. Command.

The fault flag is


cleared by one of the
following actions:

 "Reset Fault
Flags and
This flags that a
A NPS fault has been Currents"
30 NPS Alarm NPS fault has 43-00.31
picked up. control.
been picked up.
 Controller
software reset
(data is
volatile).

This point is a The most recent trip was


combination (OR) caused by any a
between Operator combination of Operator
Combined Cleared by any close
31 Trip, OCPM Trip OR an OCPM 44-14.00
Operator Trip action.
Operator Trip, Operator Trip OR an
IOEX Operator IOEX Operator Trip OR a
Trip, Protocol Trip. Protocol Trip.
1- The phase designation A, B, C is determined by the user, refer to Switchgear Details section and
the Switchgear Technical Manual.
2- Supply Reset is a LBS feature that is not currently available. It allows the fault flags to be reset
when normal current is restored.

Appendix A.6LBS Analog Data


It may seem strange that points that do similar things on an ACR and LBS have been mapped twice.
However, experience has shown that the small differences in behaviour of the points have caused
much confusion both in the code and scada system in previous products. The cost to both the
customer and supplier is more than to maintain the points separately.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 59 of 72

A.6.1Detection State
Refer also to Operator/Protection Flags for LBS section.

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Value is zero when Cold Load
is Idle or OFF. When Cold
Load is not idle this shows the
0 Cold Load operational cold load time, i.e. 0 480 Mins 1 1 43-00.00
the current time being used to
calculate the operational cold
load threshold multiplier.
Detection
0 = Detection Group A 1 =
Group
1 Detection Group B n = Other 0 9 N/A 1 1 43-00.00
currently
Detection Group
selected
0 = NPS Detection OFF
NPS
2 detection 1 = NPS Detection ON 0 2 N/A 1 1 43-00.31
status
2 = NPS Detection Alarm only

A.6.2Fault Detection Data


These analogue points record data about detected faults, including maximum fault currents. These are
derived from the Max Current events, which are recorded in the event log and record the current for
each phase and for earth/ground.

For any one fault more than one fault current can be set. For example a Phase/Phase fault might set
an A-Phase current and a B-Phase current.

Other data recorded includes the supply interrupt count and the Detection Group that was active at the
start of the fault detection sequence.

Fault Detection Data is cleared to zero by the following actions: -

 "Reset Fault Current" remote control command defined below.


 Any Operator Close or Trip action.
 New fault detected.

The time stamps correspond to the digital time stamps in Detection Flags LBS section.

This data is volatile, and are zeroed on controller software reset.

If more than one protocol is running simultaneously in the controller, this data is replicated between the
protocols so that each master station can clear its data independently from the others.

Point Name Description Min Max Resolution Deadband


Unit Version

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 60 of 72

(s) Introduced
The number of the
Active
Detection Group which
0 Detection 0 9 N/A 1 1 43-00.00
was active at the start
Group
of the sequence.
Supply Interrupt The number of Supply
1 0 10 N/A 1 1 43-00.00
Count Interrupts Counted.
Written on a Max
Most Recent -
2 Current event for A 0 16000 Amps 1 1 43-00.00
A-Phase Fault
Phase(1)
Written on a Max
Most Recent -
3 Current event for B 0 16000 Amps 1 1 43-00.00
B-Phase Fault
Phase(1)
Written on a Max
Most Recent -
4 Current event for C 0 16000 Amps 1 1 43-00.00
C-Phase Fault
Phase(1)
Earth/Ground Fault
Most Recent Current - Written on an
5 Earth/Ground E-Max event. This 0 16000 Amps 1 1 43-00.00
Fault includes SEF/SGF
Fault currents.
NPS Fault Current -
Most Recent
6 Written on an E-Max 0 16000 Amps 1 1 43-00.22
NPS Fault
event.
1- The phase designation A, B, C is determined by the user, refer to Switchgear Details section and
the Switchgear Technical Manual.

Appendix A.7Protocol-Specific Data


Points in these sub-appendices apply to specific protocol handlers.

A.7.2Protocol-Specific Analog status points.


These analog points are specific to protocols. They will not function if the concerned protocol is not
running.

Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Transmitted frame
0 DNP3 TX Count 0 32768 N/A 1 1 41-00.00
count.
Received frame
1 DNP3 RX Count 0 32768 N/A 1 1 41-00.00
count.
DNP3 RX Length Received message
2 0 32768 N/A 1 1 41-00.00
Error length error.
DNP3 RX CRC Received message
3 0 32768 N/A 1 1 41-00.00
Error CRC error.
DNP3 Master The DNP Master
4 0 65519 N/A 1 1 41-00.00
Address station address.
DNP3 Controller The DNP address

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 61 of 72

5 Address of the controller. 0 65519 N/A 1 1 41-00.00


DNP3 RX Error Received message
6 0 32768 N/A 1 1 41-00.00
Count error count.
MITS Transmitted
7 MITS TX Count 0 4095 N/A 1 1 42-00.18
frame count.
MITS Received
8 MITS RX Count 0 4095 N/A 1 1 42-00.18
frame count.
MITS Received
MITS RX CRC
9 message CRC 0 4095 N/A 1 1 42-00.18
Error
error.
IEC 101/104 TX Transmitted frame
10 0 32768 N/A 1 1 42-00.00
Count count.
IEC 101/104 RX Received frame
11 0 32768 N/A 1 1 42-00.00
Count count.
IEC 101/104 RX Received message
12 0 32768 N/A 1 1 42-00.00
CRC Error CRC error.
IEC 101/104 RX Received message
13 0 32768 N/A 1 1 42-00.00
SYNC Error CRC error.
IEC 101/104 RX
Received message
14 Frame Time Out 0 32768 N/A 1 1 42-00.00
CRC error.
Error
MODBUS TX Transmitted frame
15 0 99999 N/A 1 1 44-14.00
Count count.
MODBUS RX Received frame
16 0 99999 N/A 1 1 44-14.00
Count count.
MODBUS RX Received message
17 0 99999 N/A 1 1 44-14.00
Length Error length error.
MODBUS RX Received message
18 0 99999 N/A 1 1 44-14.00
CRC Error CRC error.

A.7.3Protocol-Specific Counter status points.


These analog points are specific to protocols. They will not function if the concerned protocol is not
running.

Unit Version
Point Name Description Min Max
(s) Introduced
Accumulated KWH.
DNP3 KWH
0 0 2147483647 KWH 41-00.00
Cumulative Counter can be read, frozen,
frozen read, and reset.
Accumulated KWH in the forward
direction (ie Source to Load).
DNP3 KWH
1 0 2147483647 KWH 41-00.00
Cumulative Forward
Counter can be read, frozen,
frozen read, and reset.
Accumulated KWH in the reverse
DNP3 KWH direction (ie Load to Source).
2 0 2147483647 KWH 41-00.00
Cumulative Reverse
Counter can be read, frozen,

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 62 of 72

frozen read, and reset.

Appendix B.1Digital Controls


These controls provide:-

 The same controls which an operator can use on the first system status screen of the Operator
Control Panel of the controller
 Additional controls specific to the protocol such as "reset fault flags and currents".

Changes to protection are made by selecting a different active Protection Group in the same way an
operator makes changes.

Changes to a selection of protection features are provided for operational purposes. Changes to the
main configuration parameters of the protection are not permitted over the protocol. This is done either
at the control panel itself or by using the WSOS program that is specifically designed for the task.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
Applies Work Tag.
Removes Work
Work tag can only Tag. Rejected if:
be applied locally if
controller is in local Work tag can only
Applies/Removes mode, or remotely if be removed locally
0 Work Tag 41-00.00
the Work Tag controller is in if controller is in
remote mode. Work local mode, or
tag is rejected if remotely if
controller is closed controller is in
and it is not able to remote mode.
trip.
Earth/Ground
Protection /
Detection OFF and
Earth/Ground SEF/SGF
Protection / Protection /
Detection ON. Detection OFF.
Turn Earth/Ground Rejected if: Rejected if:
Earth/Ground Fault
Fault Protection /
1 Protection / 41-00.00
Detection ON or
Detection  Single phase  Earth/ground
OFF.
measurement. fault OFF is
not allowed.
 Single phase
measurement.

SEF/SGF
Protection /
Detection ON and
Earth/Ground

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 63 of 72

Protection /
Detection ON.
Rejected if:
Turn Sensitive
SEF/SGF Earth/Ground SEF/SGF
 SEF/SGF is
2 Protection / Protection / Protection / 41-00.00
not available.
Detection Detection ON or Detection OFF.
 Single phase
OFF.
measurement.

Auto Reclose ON.


Rejected if:
Turn auto reclose
3 Auto Reclose function ON or Auto Reclose OFF. 41-00.00
 Switch is LBS.
OFF.

Close. Rejected if:

 Close or Trip
coil is isolated.
 Controller
mode is
opposite to Trip. Rejected if:
location of
requester (i.e.  Trip coil is

local/remote). isolated.
 SF6 Gas  Switchgear

Pressure Low Data Invalid.


(if applicable)  ACR AND
AND Gas Low SF6 gas
Inhibit is ON. pressure is
 Work Tag is low (if
applied. applicable)
 Switchgear AND Gas Low
Operate the
Data Invalid. Inhibit is ON.
4 ACR / LBS Control recloser / load break 41-00.00
 Mechanically  LBS AND SF6
switch
interlocked (if gas pressure
applicable). is low (if
 Live load applicable).
blocking ON  Mechanically
AND any load interlocked.
side terminal  Trip capacitor
live. is charging or
 Trip and/or failed.
Close  Hit and Run
capacitors are ON.
charging or
failed.
 Generator
Control has
close blocking
ON.
 Hit and Run
ON.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 64 of 72

Resets all Fault


Currents to zero
This command and clears all
Reset Fault Flags clears all protocol protection trip or
5 No action 41-00.00
and Currents fault flags and fault detection fault
currents. status flags and
Settings Changed
flag.
Turn ALL
Protection /
Detection OFF.
Rejected if:
Enable or disable all
Protection / Enable Protection /
6 protection /  Protection / 41-00.00
Detection Control Detection
detection functions. Detection
OFF is not
allowed.

Changes the
Source / Load
Power Flow
7 designation for the Source X, Load I Source I, Load X 41-00.00
Direction
recloser. See Note
(1).
Sets the operational
cold load time to
either zero or to the Sets Cold Load
maximum Time to its Sets cold load time
configured value maximum value. to zero. This means
(including the This means the the Threshold
reverse protection Cold Load Multiplier will not be
group if configured). Threshold Current affected by the Cold
This affects the will be set to its Load function.
Operational Cold maximum value. Rejected if:
Load Threshold Rejected if:
Multiplier. Rejected
11 Cold Load Idle/Max  Cold load 41-00.00
if Cold Load is
 Cold load support is
configured to OFF in
support is OFF.
the currently active
OFF.  Cold load is
protection group.
 Cold load is below the
After a new time is
above the IDLE
set, the Cold Load
IDLE threshold.
function will
threshold.
immediately start to
increment or
decrement the value
depending on the
load current.

12 High Current 41-00.00


Controls the High Lockout ON.
High Current Current Lockout Rejected if: High Current

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 65 of 72

Lockout Function.  Switch is LBS. Lockout OFF.

Loss of Phase
Loss of Phase
Protection OFF.
Protection ON.
Rejected if:
Rejected if:
 Switch is LBS.
 Switch is LBS.
 Single phase
Loss of Phase Depricated from  Single phase
13 measurement. 41-00.00
Protection 44.04.20 measurement.
 Loss Of
 Loss Of Phase
Phase and
and Loop Auto
Loop Auto
linked.
linked.

Sequence Control
ON. Rejected if:
Sequence Control
14 Sequence Control 41-00.00
 Switch is LBS. OFF.

Live Load Blocking Live Load Blocking


15 Live Load Blocking 41-00.00
ON. OFF.
Freezes the kWH
Cumulative
kWH Cumulative
accumulator value
Accumulator
16 Freeze/Reset kWH ready for No Action 41-00.00
freeze/reset
transmission and
operation.
resets the running
count back to zero.
Operate the Dummy
17 DCB Control Close. Trip. 41-00.00
Circuit Breaker.
Automatic
Protection/Detection
Group Selection
ON. Rejected if:
Controls Automatic Automatic
APGS / ADGS
18 Protection/Detection Protection Group 41-00.00
Control  APGS/ADGS
Group Selection. Selection OFF.
ON is Not
Allowed.

Loop Automation
ON. Rejected if:

 Loop
automation
capability "Not
Available".
 Trip coil
isolated.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 66 of 72

 Close coil
isolated.
 Mechanism
fail.
 Switchgear
Data Invalid.
 Battery Not
Normal.
 Capacitor
charge Not
OK.
 SF6 Gas
Pressure Low
(if applicable)
Loop Automation Controls Loop Loop Automation
19 AND Low Gas 41-00.00
Control Automation. OFF.
Interlock is
ON.
 Tripped AND
(Midpoint OR
Feeder).
 Closed AND
TIE.
 No CVTs on
both sides
AND (TIE OR
Auto Restore
ON).

Supply Outage
Supply Outages Supply Outage
20 Measurement 41-00.00
Control Measurement ON.
OFF.
Resets all Supply
Outage accumulator
Supply Outages
21 values for the No action 41-00.00
Reset
controller, this is not
protocol specific.
Turn Normal Turn Normal
Frequency Close Frequency Close
ON. Rejected if: OFF. Rejected if:
Normal Frequency
22 41-00.00
Close
 Switch is LBS.  Switch is LBS.

Turn Sectionalising
ON. Rejected if:
Turns Sectionalising Turn Sectionalising
23 Sectionaliser Auto  Switch is 41-00.00
ON and OFF. OFF.
ACR.

Turn Dead Lockout


ON. Rejected if:

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 67 of 72

 Switch is LBS.
 No X side
voltage
measurement
Turns Dead Lockout possible and Turn Dead Lockout
24 Dead Lockout power flow 41-00.00
ON and OFF. OFF.
direction is X
to I side.

Make Loss Of
Phase / Loop
Linked. Rejected if:
Links and unlinks
Make Loss Of
Loss Of Phase / the Loss Of Phase
25  Switch is LBS. Phase / Loop 41-00.00
Loop and Loop Auto ON
 Single phase Unlinked.
setting.
measurement.

Under Frequency Under Frequency


Protection Trip ON. Protection Trip
Enables or disables Rejected if : OFF. Rejected if :
Under Frequency
26 Under frequency 41-00.00
Trip Control
Protection Trip.  LBS.  LBS.

Over Frequency Over Frequency


Protection Trip ON. Protection Trip
Enables or disables Rejected if: OFF. Rejected if:
Over Frequency
27 Over Frequency 41-00.00
Trip Control
Protection Trip  LBS.  LBS.

Activates Group A
Activates Group A
as
Protection/Detection as
28 protection/detection No action 41-00.00
Group A Active protection/detection
group. Refer Note
group.
2.
Activates Group B
Activates Group B
as
Protection/Detection as
29 protection/detection No action 41-00.00
Group B Active protection/detection
group. Refer Note
group.
2.
Activates Group C
Activates Group C
as
Protection/Detection as
30 protection/detection No action 41-00.00
Group C Active protection/detection
group. Refer Note
group.
2.

Activates Group D Activates Group D


Protection/Detection as as
31 No action 41-00.00
Group D Active protection/detection protection/detection
group. Refer Note group.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 68 of 72

2.
Activates Group E
Activates Group E
as
Protection/Detection as
32 protection/detection No action 41-00.00
Group E Active protection/detection
group. Refer Note
group.
2.
Activates Group F
Activates Group F
as
Protection/Detection as
33 protection/detection No action 41-00.00
Group F Active protection/detection
group. Refer Note
group.
2.
Activates Group G
Activates Group G
as
Protection/Detection as
34 protection/detection No action 41-00.00
Group G Active protection/detection
group. Refer Note
group.
2.
Activates Group H
Activates Group H
as
Protection/Detection as
35 protection/detection No action 41-00.00
Group H Active protection/detection
group. Refer Note
group.
2.
Activates Group I as
Activates Group I as
Protection/Detection protection/detection
36 protection/detection No action 41-00.00
Group I Active group. Refer Note
group.
2.
Activates Group J
Activates Group J
as
Protection/Detection as
37 protection/detection No action 41-00.00
Group J Active protection/detection
group. Refer Note
group.
2.
Freezes the kWH
kWH Cumulative Cumulative Forward
Forward accumulator value
Freeze/Reset kWH
55 Accumulator ready for No action 41-00.00
Accum Fwd
freeze/reset transmission and
operation. resets the running
count back to zero.
Freezes the kWH
kWH Cumulative Cumulative Reverse
Reverse accumulator value
Freeze/Reset kWH
56 Accumulator ready for No action 41-00.00
Accum Rev
freeze/reset transmission and
operation. resets the running
count back to zero.

Start battery test.


Rejected if:
Start/Stop Battery
60  No auxiliary No action 41-00.00
Test
supply.
 No battery
supply.
 In pickup or

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 69 of 72

protection
sequence
 Within 15mins
of previous
test

Clear 'Settings
Clear 'Settings
61 Changed' status No action 41-00.00
Changed'
flag.
Set the Maximum Set the Maximum
Demand Indicator Demand Indicator
Reset Maximum
74 values to the values to the No action 41-02.35
Demand Indicators
present phase present phase
values values
Sets the operational
cold load (reverse) Sets Cold Load
time to either zero or (reverse) Time to its Sets cold load
to the maximum (reverse) time to
maximum value.
configured value. zero. This means
This means the
This affects the the Threshold
Cold Load
reverse Operational Threshold Current Multiplier will not be
Cold Load affected by the Cold
will be set to its
Threshold Multiplier. maximum value. Load function.
Rejected if Cold Rejected if:
Rejected if:
Cold Load Reverse Load is configured
75 41-02.43
Idle/Max to OFF in the  Cold load
 Cold load
currently active support is
support is
protection group. OFF.
OFF.
After a new time is  Cold load time
 Cold load time
set, the Cold Load is below the
is above the
function will IDLE
IDLE
immediately start to threshold.
threshold.
increment or
decrement the value
depending on the
load current.
Sets the operational
cold load time to
either zero or to the
maximum
configured value. Sets Cold Load
This affects the Time to its
Operational Cold maximum value. Sets cold load time
Load Threshold This means the to zero. This means
76 Cold Load Off/Max Multiplier. Rejected Cold Load the Threshold 41-02.50
if Cold Load is Threshold Current Multiplier will not be
configured to OFF in will be set to its affected by the Cold
the currently active maximum value. Load function.
protection group. Rejected if: Rejected if:
After a new time is
set, the Cold Load  Cold load  Cold load
function will support is support is
immediately start to OFF. OFF.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 70 of 72

increment or
decrement the value
depending on the
load current.
Sets the operational
cold load (reverse)
time to either zero or
to the maximum Sets Cold Load
Sets cold load time
configured value. (reverse) Time to its
(reverse) to zero.
This affects the maximum value.
This means the
Operational Cold This means the
Threshold Multiplier
Load Threshold Cold Load
will not be affected
Multiplier. Rejected Threshold Current by the Cold Load
if Cold Load is will be set to its
Cold Load Reverse function. Rejected
77 configured to OFF in maximum value. if: 41-02.50
Off/Max
the currently active Rejected if:
protection group.
 Cold load
After a new time is  Cold load
support is
set, the Cold Load support is
OFF.
function will OFF.
immediately start to
increment or
decrement the value
depending on the
load current.
Controls the Normal
Normal Voltage Turns Normal Turns Normal
78 Voltage Close 42-00.00
Close Voltage Close ON Voltage Close OFF
setting.
Turns Under Turns Under
Controls the Under
79 Under Voltage Trip Voltage Tripping Voltage Tripping 42-00.00
Voltage Trip setting.
ON OFF
Controls the Over Turns Over Voltage Turns Over Voltage
80 Over Voltage Trip 42-00.00
Voltage Trip setting. Tripping ON Tripping OFF
Controls the Sag Turn Sag monitoring Turn Sag
81 Sag Monitoring 42-00.00
Monitoring setting. ON monitoring OFF
Controls the Swell Turn Swell Turn Swell
82 Swell Monitoring 42-00.00
Monitoring setting. monitoring ON monitoring OFF
Performs a reset of
Reset Sag/Swell Resets the Sag and
the Sag and Swell
83 Counters and Swell counters and No action 42-00.00
counters and total
Durations durations
duration
If the controller is If the controller is If the controller is
operating as an operating as an operating as an
ACR then turn Auto ACR then turn Auto ACR then turn Auto
Reclose function ON Reclose ON. Reclose OFF.
Auto Reclose or or OFF. If the
86 44-04.02
Sectionaliser Auto controller is If the controller is If the controller is
operating as a LBS operating as a LBS operating as a LBS
then turn then turn then turn
Sectionaliser Auto Sectionaliser Auto Sectionaliser Auto
ON or OFF. ON. OFF.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 71 of 72

Appendix B.2Analog Controls

Unit Version
Point Name Description Min Max Resolution
(s) Introduced
Protection / Detection
1 0 9 N/A 1 41-00.00
Group
0 = NPS Protection /
Detection OFF

NPS Protection / 1 = NPS Protection /


2 0 2 N/A 1 41-00.00
Detection Control Detection ON

2 = NPS Protection /
Detection Alarm only
0 = Loss of phase OFF

1 = Loss of phase ON
4 Loss of Phase Control 0 2 N/A 1 44-04.20
2 = Loss of phase Alarm
only

Appendix B.3Protocol IOEX Controls


These controls provide virtual RTU output terminals.

They can be accessed by any point configuration tool eg. Protocols, IOEX.

Version
Point Name Description Set = '1' Clear = '0'
Introduced
Protocol Sets or clears a Clears a
Sets a configurable
42 IOEX Control configurable access configurable access 41-00.00
access point.
1 point. Note 1. point.
Protocol Sets or clears a Clears a
Sets a configurable
43 IOEX Control configurable access configurable access 41-00.00
access point.
2 point. Note 1. point.
Protocol Sets or clears a Clears a
Sets a configurable
44 IOEX Control configurable access configurable access 41-00.00
access point.
3 point. Note 1. point.
Protocol Sets or clears a Clears a
Sets a configurable
45 IOEX Control configurable access configurable access 41-00.00
access point.
4 point. Note 1. point.
Protocol Sets or clears a Clears a
Sets a configurable
46 IOEX Control configurable access configurable access 41-00.00
access point.
5 point. Note 1. point.
Protocol Sets or clears a Clears a
Sets a configurable
47 IOEX Control configurable access configurable access 41-00.00
access point.
6 point. Note 1. point.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010


Protocol Database for Automatic Circuit Reclosers With Advanced Controllers Page 72 of 72

Protocol Sets or clears a Clears a


Sets a configurable
48 IOEX Control configurable access configurable access 41-00.00
access point.
7 point. Note 1. point.
Protocol Sets or clears a Clears a
Sets a configurable
49 IOEX Control configurable access configurable access 41-00.00
access point.
8 point. Note 1. point.

file://C:\Program Files\WSOS\DNPADVC\ADVC-PTCL-331.html 23/03/2010