AC80B HIGH-PERFORMANCE VC INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
49
AC80B HIGH-PERFORMANCE VC INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
● Electromagnetic disturb in
● resume load and save.
E.EEP Memory fault memory period.
● Seek support from factory.
● EEPROM damage.
50
AC80B HIGH-PERFORMANCE VC INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
yes
Clear short circuit Whether there is short circuit between outout terminal U/V/W and the motor
no
yes
Short the cable or Cable between output terminal U/V/W and motor
add outout reactor is too long that leakage current cause inverter protection
no
yes
Clear disturbance Is there serious electromagnetic disturbance?
no
yes
While disconnect output wire and run,whether there is system fault alarm
no
no
yes
Connect load and
Three phase outout voltage balance is ok or not?
operate as follows
yes
yes
Reduce load or
Whether overload or not?
enhance power
no no no
no yes
Display E.SC Display E.SC Display E.SC while Display E.SC while
while start while stop constant speed machine stop
yes
yes
yes no
yes
no
Torque enhance value Whether acceleration Whether deceleration Whether load
is suitable or not time is too short time is too short change suddently
no yes yes
yes
no
Torque enhance ACC time can be Dec time can be Reduce load change
valuecan be prolonged or not
reduced or not prolonged or not or enhance power
51
AC80B HIGH-PERFORMANCE VC INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
yes
Whether short circuit between output terminal
Clear short circuit
U/V/W and motor or earth circuit
no no no
yes
Reduce load or
Whether load is too large
enhance power
no
no
Whether torque
Can be reduced? enhance value is too no no
yes yes
yes
yes
Set longer acceleration Whether set longer Reduce load change
time or not? decelerationtime or improve power
yes
Prolong setting time
no
no
52
AC80B HIGH-PERFORMANCE VC INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
no
Reduce power voltage
Fower votage in fixed range or not
into fixed range
no no no
yes
Stop motor and restart. Whether it stops while restart the motor
Or DC braking,then
start(F1.00:1). Or speed
no no no
track start(F1.00:2)
Whether act while load suddently changes to"0"
no no no
no
Whether DC circuit voltage of main loop is above protection value while act
Maybe inverter fault or
misact.Plese seek for yes yes yes
no yes
technic support
Whether act while yes
suddently stop ACC Can prolong DCC time or not
yes no
no
yes
ACC time can be
prolong or not prolong
no
yes
Reduce Load intertia can be reduced or not
no no no
53
AC80B HIGH-PERFORMANCE VC INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
yes
Restart after reset Whether power off,including instant power off
no no
no no
Modify power supply
no
system as required Whether power voltage is in fixed range as required
yes yes
yes
Is there any big load start or stop under the same power supply
no no
no
Adjust FA.10 setting votage between DC circuit P+ and N- in
main loop is over FA.10 setting or not
yes yes
no
Change fan Whether cooling fan works normally
yes
Maybe temperature ditection no
circuit fault.please seek for Whether temperature display(C-12)is
technic support the same as the actual temperature
yes
yes
Reduce load and Whether load and carried frequency
carried frequency F0.17 setting are too high
no
yes
Clear the air-logged channel Whether air cooling channels are air-logged
no
Adjust the temperature to no
the fixed range as required Whether the temperature is within the fixed range as required
yes
54
AC80B HIGH-PERFORMANCE VC INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
Over load
yes
no
Whether electric thermal relay overload
Correct setting value
relay setting FA.20 is suiable
yes
Reduce load or yes
improve capacity Whether load too high
no no
Restart after motor stop or yes
change start mode F1.00 Whether the motor stops while restart
to 1/2
no no
yes
Prolong ACC/DCC time Whether ACC/DCC time is too short
no no no
Change torque improving
Whether torque improving or V/F curve setting is suitable
or V/F curve setting
yes yes
No display
Inverter keyboard
LED no display
yes
55
AC80B HIGH-PERFORMANCE VC INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
Motor heat
motor heat
no yes
Adjust torque imporoving Whether torque improving and V/ Whether motor continuously
value and V/F characteristic F characteristic are suitable or not run at low speed
no
yes
yes
Reduce load or
improve capacity Whether load is too large Use special motor for inverter
no
yes
Whether output terminals U/V/W output
voltage /current three phase balance well Maybe motor fault
no
yes no
Work after solving Whether keyboard Have input command
fault and reset displays fault information signal or not
yes
no
no
It works after checking
Have input frequency It works after checking the
the cause and solving
signal or not cause and slving the problem
the problem
yes
yes It works after correct the
Whether upper frequency limit F0.11 or given frequency
upper frequency or given
is lower than the start frequency F1.01setting frequency
yes
no
Is there voltage output on output terminal U/V/W Maybe inverter fault .Please
and three phase balance ok or not? find technic support
yes
yes
no
Whether load Whether wiring is
is too large Correct connect
correct or not
yes
no
no
Motor fault Whether torque improving Improve torque
value is suitable improving value
yes
56