CTER Current Sensor Current sensor error or circuit Send the inverter back
detecting error malfunctions for repairing
5-1
Chapter 5 Troubleshooting and maintenance
5-2
Chapter 5 Troubleshooting and maintenance
5-3
Chapter 5 Troubleshooting and maintenance
1. The inverter will ramp stop and then flash E.S., when input
External external emergency stop signal via the multifunctional input
E.S. emergency stop terminal (refer to descriptions of 5-00~5-06).
2. Please wiring the terminal before to set 5-00~5-06=29.
The inverter stops immediately and then flashes b.b., when external
b.b. External base
base block is input through the multifunctional input terminal (refer
block
to descriptions of 5-00~5-06).
5-4
Chapter 5 Troubleshooting and maintenance
5-5
Chapter 5 Troubleshooting and maintenance
Are wiring for output terminals T1, T2, and T3 ‧Wiring must match U, V, and W
correct? terminals of the motor.
Motor runs
inversely
Are wiring for forward and reverse signals ‧Check wiring are correct if necessary.
correct?
Are wiring for analog frequency inputs correct? ‧Check wiring are correct if necessary.
The motor
speed can ‧Check the operation mode of the
Is the setting of operation mode correct?
not be operator.
regulated.
Is the load too heavy? ‧Reduce the load.
5-6
Chapter 5 Troubleshooting and maintenance
Is fault fully NO
understood?
YES
Any
Symptoms other than burn NO symptoms of burn YES Check burnt and damaged
out, damage, or fuse meltdown in parts
the inverter?
out and damage?
YES
Abnormal NO
signal? Is the main circuit NO Replace DM
DM intact?
YES
5-7
Chapter 5 Troubleshooting and maintenance
Perform parameter
initializations
YES
YES
Are there NO
voltage outputs in output Replace the control board
terminals U, V and W
YES
Connect the motor to run Is the control NO
board working well after
replacement
YES
NO
Are output
current of each phase
even?
YES
NO
‧
The inverter faults
Perform detailed check
The inverter is OK
5-8
Chapter 5 Troubleshooting and maintenance
YES
YES
Any abnormal NO
Is the current detector
indications?
OK?
YES
Input operation command Replace control board Replace the current controller
YES
Are there NO
voltage output at U,V and W output Replace control board
terminals?
YES
Is the inverter
NO
Connect the motor to run working well after
replacement
NO
YES
The inverter’s output is OK
NO
‧
The inverter faults
Perform detailed check
5-9
Chapter 5 Troubleshooting and maintenance
NO
Apply the power
NO
Input operation command
YES
Are there NO
voltage output at T1,T2,T3 Replace the control board
output terminals?
Is the inverter NO
YES working well after
Connect the motor to run replacement
YES
YES
Any abnormal value?
NO
YES
The inverter’s output is OK
NO
‧
The inverter faults
Perform detailed check
5-10
Chapter 5 Troubleshooting and maintenance
YES Is MCCB
applied?
NO
Can MCCB be NO
applied? Short circuited wiring
Is LED 101lit? NO
7300CV fault
YES
5-11
Chapter 5 Troubleshooting and maintenance
NO
NO
Bad connection between YES Correct the bad connection
7300CV and the motor
NO
5-12
Chapter 5 Troubleshooting and maintenance
5-13
Chapter 5 Troubleshooting and maintenance
L1(L) T1(V)
Power source Hookup of insulation test
L2 T-VERTER T2(V) Motor
L3(N) T3(V)
Ground terminal
Ground terminal
5-14