Motor connected in delta and not in star. Rectify connection Mains voltage deviates by more than ± 5% from the nominal voltage of the motor. A Drive motor is running higher voltage is especially unfavorable for Provide for the correct mains hot (> 80°C, can be highly polarized motors since their no-load voltage detected by current rating is already near to the full measurement only) load current rating when voltage is normal. Provide for unobstructed Amount of cooling air insufficient and/or entrance and exit of cooling cooling pipes clogged up air
Cooling air is pre-heated Provide for fresh air
Overload at normal mains voltage, current Install a more powerful drive
too high, r.p.m. too low unit (measure power)
Nominal operational mode (S1 to S8 VDE
Drive motor is running 0530.1.66) exceeded. If the motor is Set rating according to the hot (> 80°C, can be running hot due to too frequent switching, operating conditions. It would detected by the use of a more powerful motor is be the best to consult a measurement only) insufficient as the same failure would specialist appear. Supply cable has defective contact Rectify defective contact (temporary single-phasing!)
Fuse melted Replace fuse
Fuse melted Replace fuse
Motor does not start running Check and adjust motor Motor protection activated protection for correct adjustment Bilfinger Water Technologies GmbH, Global Business Unit Water Treatment Motor failures Version: 11 February 2014 Page 2 / 2
Fault Cause Measure
Motor contactor does not switch, control Check control of motor fault contactor and rectify fault Motor is designed for delta connection, but Rectify connection Motor does not run or is connected in star only starts slowly Voltage or frequency deviate strongly from Provide better mains the target value at least when switched on conditions If delta current not too high, connect direct on line; Motor does not start Torque is insufficient for star connection otherwise use more powerful when connected in star, motor or special design after but starts when consultation connected in delta Contact fault at star/delta switch Rectify fault
Motor humming and Windings defective
Motor must be repaired by a has high power specialist consumption Rotor is fouling windings
Short circuit in the cable Rectify short circuit
Fuses are melting or motor protection Fault to be rectified by skilled Short circuit in the motor releases immediately electrician
Cables wrongly clamped Rectify connection
Wrong rotational Interchange two mains supply
Motor connected wrongly direction cables
2 Coil damages
Fault Cause Measure
One phase in the delta connection lacking, Motor must be rewound, One phase out insufficient motor protection repair motor protection One phase in the star connection lacking, Motor must be rewound, Two phases out insufficient motor protection repair motor protection Overload, blockage, excessive switching, Motor must be rewound, Three phases out at insufficient motor protection, incorrect repair motor protection, rectify same time connection connection, check drive unit Internal short circuit Mechanical damage in windings or other (several windings Motor must be rewound fault in insulation melted in one groove