Diff Harmonic Restraint:

Test Module
Name: OMICRON Diff Harmonic Version: 4.00
Restraint
Test Start: 04-Feb-2019 15:58:23 Test End: 04-Feb-2019 16:00:57
User Name: Manager:
Company:

Test Results for Testphase R-N at Reference Side Primary for 2. Harmonic
Ixf/Idiff Ixf/Idiff Angle Check
Idiff Dev (rel) Dev.(abs) State Result
Nominal Actual (Ixf,Idiff) Test
0.50 I/In 15.000 % 14.90 % -120.0 ° -0.68 % -0.1025 Tested Passed
0.80 I/In 15.000 % 14.93 % -120.0 ° -0.49 % -0.0732 Tested Passed
1.10 I/In 15.000 % 14.93 % -120.0 ° -0.49 % -0.0732 Tested Passed
1.40 I/In 15.000 % 14.93 % -120.0 ° -0.49 % -0.0732 Tested Passed
1.70 I/In 15.000 % 14.94 % -120.0 ° -0.42 % -0.0635 Tested Passed
2.00 I/In 15.000 % 14.98 % -120.0 ° -0.16 % -0.0244 Tested Passed
2.30 I/In 15.000 % 14.92 % -120.0 ° -0.55 % -0.0830 Tested Passed
2.60 I/In 15.000 % n/a -120.0 ° n/a n/a Tested Failed
2.90 I/In 15.000 % n/a -120.0 ° n/a n/a Tested Failed

State:
9 out of 9 points tested.
7 points passed.
2 points failed.

General Assessment: Test failed