Installation Manual
Pnnted in Austna.
lnstallat1on Manual - manual gasflare FAI 3 lnstallat,on Manual - manual gasflare FAI 4
2. SAFETY
1. GENERAL The Bilgeri EnvironTec GmbH gas tiares are designed and constructed taking into conslderation the
highest safety requirements, and upon carefully choosing other matching standards to follow, as well
1.1 To the operating personnel as other technical specifications. It meets the current state of technology and guarantees the highest
measure of safety. However, in operating conditions this safety can only be achieved if all necessary
This operating ma nuai informs about the safety, assembly, function, ope ration and maintenance of the measures are followed. It is subject to the due diligence of the operator to plan and execute these
gas tiare. If properly following the instruction, a long, trouble free and safe operation is guaranteed. measures and to contrai its execution.
See Annex The gas tiares of type FA! are conceptualized for burning of explosive gases of the Group IIA
temperature class Tl (methane with C02 biogas plants or water treatment plants).
1.4 To understand this manual better • From the customer sicle it must be made sure that unintentional operation in and explosive
atmosphere is safely prevented. See operator Ex-protection zone plan.
Conventions • The operation of the manual gasflare must be carried out under the supervision of the operating
staffs! When uncontrolled tlame extinction (eg by a gust of wind), butterfly valve must be closed
f1iM:Hfüi
This danger symbol refers to an imminent threatening, serious, danger, which leads with certainty to
immediately in order to prevent the further gas flow. Ther starting procedure must be
performed again.
If automatic option is chosen, the gasflare is monitored automatically and the procedure
-
serious injuries or even to death, if the danger is not avolded. discribed above is not applicable.
The burning of explosive gas/air mixtures in the gas tiare in not permitted!
Cross-references
Cross references are presented in italics.
Installation Manual - manual gasflare FAI 7 Installation Manual - manual gasflare FAI 8
2.2 Improper use 2.4 Waming, mandatory and information signs on the device
If not usmg as lnstructed (improper use), for example: The following signs can be found on the gas flare (OIN 4844):
• if the gas flare, including contrai cabinet are not ready for operation, or were mod1fied
• by unauthorized access ta the sw1tch cabinet and wmng Fire, open light and smoking is prohibited !
• hot parts
Warning hot surface
• explosion
• electrocut1on
Only trained and mstructed personnel is allowed ta operate the gas flare. The completJOn of the
instruction should be documented in writing.
The minimum age of operating personnel 1s 18 years. • Make sure that all parts are completely cooled off.
Make sure that the operating personnel 1s instructed on ail applicable questions conceming work safety Rre Hazard!
and environmental protection, and that they understand and follow the operating manual, particularly
the safety instructions contained therein. The safety distance ta prevent damage by lire impact on buildings and surfaces of stationary traffic
should be 5 m •provided not otherwise stated in relevant local fire protection provisions.
Please follow ail warning and information labels attached ta the gas flare. Also ensure that such signs
are not removed and always remain legible. (See above). • the Sm surrounding area around the gas nare must be kept free of any growth (bushes, trees).
Within this safety distance, fire, open light, smoking and storing of flammable or ignitable
Defects ta the gas flare must be removed immediately. The manufacturer must be notilied immediately materials is prohibited.
in the event of malfunction. Do not make any changes or reconstruction yourself.
In justilied exceptional cases these distances may be reduced, if other measures for avoiding fire impact
When exchanging defective components, use only original components with the same electrical and are ensured for the surrounding area.
mechanical data. Otherwise, this will not maintain safety and function.
2.6 Due diligence of operator
Ali safety equipment, fasteners and electrical connections and lines must be checked regularly for proper
condition.
As the operatar, you must especially make sure that
Unrestricted access ta the gas flare by people or animais must be prevented with suitable means (e.g.
safety fence). • the gas tiare is only used as instructed.
• The gas nare is only operated when functioning properly, and especially that the function of the
safety equipment is checked regularly. If there is damage or destruction, or a riskfree operation
of the gas tiare cannot be guaranteed for other reasons, then the system must immediately be
6i5Htifüi taken out of operation and may under no circumstance be put back into operation.
Danger of electrlc shockl • The necessary persona! protective equipment is available and is used by the operating,
maintenarice and repair personnel.
Electrical work is may only be performed by qualified electrical engineers. An electrical engineer is
someone, who based on professional education, knowledge and experiences, as well as knowledge of • The instruction manual is always in legible condition and available completely at the operating
the relevant regulations of the assigned work, is able ta recognize potential dangers and take appropriate location.
safety measures.
• Only adequately qualified and authorized personnel may operate, maintain and repair the
• When working on starter electrodes, it is mandatary ta operate the emergency shut-off switch, system. The personnel is regularly instructed in all questions coriceming work safety and
or safely interrupt the power supply. Please also stop the gas supply by closing the manual tlap. environmental protection, understands the operating manual and especially the safety
• Before working in the switch cabinet, rnake sure ta shut-off the power supply, and secure it instructions contained therein.
from unintentionally switching back on, and attach the respective waning sign. Ali safety and waming signs attached ta the gas tiare are not removed and remain legible.
EnvironTec GmbH will not assume any responsibility for damages or operating malfunctionsthat have
been created by improper use or gross negligence.
Installation Manual - manual gasflare FAI 11 lnstallatKJn Manual - manual gasflare FAI 12
• Poor monitoring of parts that are subject to wear or agrng 3.2 Structure
• Improperly completed reparrs The gas tiare can be obtarned rn varrous srzes. See 7.2 Gas llare by mode! sae.
IMMMI
The descnptions and rnstructJons rn th1s operatrng and maintenance manual refer to the standard
designs. Therefore, not ail details and condrtrons have been mentioned. If missing informatron, please
contact Env1ronTec GmbH immediately.
For details about our warranty please refer trJ our general terms and conditions, or your agreement
documentation.
Installation Manual - manual gasflare FAI 13 Installation Manual - manual gasflare FAI 14
To start the flare, first the butterfly valve must be opened and the ON button must be pressed
lmmediately after. Pressing the on button will sparc the flare and the flare starts buming. After the flare
starts buming, stop pressing on the ON button.
To stop the flare, close the butterlfy valve.
The start/stop command is issued by an external signal (e.g. gas storage fill level). The
monitoring/autornatic functions described for the hand operation will take place as described above.
By default one (or more) diffusion burner heads are used. There 1s a mixture of fuel and oxidant (air)
The manual vavle ls used for manually opening and closing the gas supply lines for repairs or when in the combustion chamber. The mtxing is essentially completed by diffusion and leads to the formation
taking out of operation as an additional shut-off valve. lt is equipped with a hand lever and an opening of a diffusion flame.
regulator. Below the burner head, there is a air dise to regulate the air flow.
The burner heads are replaceable and are manufactured from temperature resistant stainless steel.
Ignition electrodes
The combustion gas is ignited directly above the burner head by means of two high voltage ignition
Fig. 5: OveraH v.av of the /lare base, pPhg and axnbustbn chamber electrodes. An electric arc is generated between the ignition electrodes, which under normal
circumstances will immediately Ignited the gas mixture.
The entire gas flare is manufactured from stainless steel. The base and frame, as well as no gaswetted
parts are from matenal 1.4301,the entIre gas piping and the combustion chamber of material 1.4571. Control / swltch cabinet (option)
Anchoring
Fig. 8: Swi/d1 cabinet· view of the door wlth lghts and SWitches
The power supply needed is 230 V, 50 Hz. The respective operating conditions of the gas flare are
displayed by means of pilot lights on the switch cabinet.
The flare contrai can be directly incorporated in the control/visualization of the respective operating
plant (biogas plant, digester gas, or similar). The following signais are planned for this purpose:
Generally, biogas is 100% humidity saturating. To prevent iœ format10n or freezing of the valves, an
electrical support heater with thermostat may be used, and the fitt1ngs can be insulated additionally.
For this purpose the valves and applicable piping sections are covered by a heating cable. The
temperature contrai occurs via a thermostat in a manner that the fittings are always kept at > O °C.
The heated system parts are then also insulated.
In the standard production the gas flare is equipped with a grounding connection to a gas flare base.
From the customer side, the connection must be completed according to the local or national
regulations.
Installation Manual - manual gasflare FAI 19 Installation Manual - manual gasflare FAI 20
The gas flare ,s t,ed down fiat on palettes. Small parts or valves > DN 150 are packed on the pallet • Gas flare FA! 150
separately.
• Gas flare FA! 300
The items are packaged tn a manner that the gas flare can be accommodated and transported on site
ustng a fork lift. • Gas flare FA! 500
• Open pipe ends or valves must be protected from water penetrattng, or small animais, by 5.2 Accessories
means of protect,ve flaps intended for this purpose.
See 3.5 Gas nare, add-on equipment and options.
Installation Manual - manual gasflare FAI 21 Installation Manual - manual gasflare FAI 22
6.1 Identification plate gas tiare FAI 7.1 Gas tiare general information
Gas primary pressure (mbar) 12,S - 20
Das Typenschild der Gasfackel is placed on the gas flare.
Heating value (kWh/ Nm 3 ) = flow rate x 6,5
Medium* Biogas (65% CH4, 34% C02, 1% H25)
*The percentages listed are assumed biogas compositions common for biogas or digester gas plants.
The information about the type specifications can be found in the prospectus sheet "Biogas Flare FA!".
7.3 Accessories
Descrintion Data Comrnents
Switch cabinet Stainless steel
Display for flare status LCD 2-lines In the switch cabinet door
Installation Manual - manual gasflare FAI 23
f•i3@.fü;• Pii34ihfüi
Danger of persona! injury, property and environmental damage!
Danger of persona! lnjury, property and envlronmental damage!
Electrical and gas pressure engineering connect1on conditions must coincide with the information in
Please follow the safety instructions in Chapter 2. Safety. Chapter ''fechrncal Data".
The electrlcal connection may only be completed by instructed and qualified spec1alized engineering
comparnes.
To reduce the probability of electrical corrosion, the entire electrical installation of the system should
Danger of explosion!
be designed in a network configuration TN-C-5 or TN-5.
The gas flare is not permitted to be used in Ex zones.
For operating the gas tiare a wiring provlded by the customer is necessary.
• When positioning the gas tiare, please observe the ex zone plan of the biogas or digester
system!
Potential equallzation
Requirements
The customer s1de (operator) must ensure potential equalizat1on
• The gas tiare may only be setup outside.
• No w1res (power etc.) may be run in the v1cinity of the bumer head or above it.
• Fire protection distances to buildings, areas of stat10nary traffic and bushes and trees must be
maintained. For this purpose see the warning signs in Chapter 2.
• The manual shut-off tlap must always be easily accessible without using any aids.
• To avoid risks of mechanical damage (e.g. with start-up), the traffic areas should be a safe
distance away from the gas tiare.
• The structure of the foundation (Static) for the gas tiare may only be implemented according
to the respective foundation drawings. F,g. 12: Groundilg aJf1l1ec/ion a the gas ffare
• When preparing the installation make sure that possible concrete fixtures (lines, etc.) are not The standard release of the gas tiare is equipped with a labelled grounding connection.
damaged.
lightenlng protection
• Unload flare from truck / container, remove transport locks, place crane hook.
• Place a strap or steel cable and fasten it to the flare as showed in Figure 13.
1
Knmhoken ,
cranehaol< • Verticalty set gas flare on concrete foundation.
!AVORSICHT!
Danger of persona! lnjury and property damage!
There is risk of inJury and damage to the gas flare, because of bpping before the gas flare is correctty
attached to the concrete foundabon, and is secured with guy ropes.
• Unhook crane hook only after fixing the anchor of the lift belt.
Settings
Electrode distances
• Drill hole
• Insert anchor
• Set anchor
• Set torque
Air supply
• Check the function of the condensate drain cock, and empty condensate. See also 11.5
f•iM=Hfüi
Danger of persona! lnjury, property and envlronmental damage!
• Inspection and mamtenance work.
P/ease lbllow the salèty instructions in Chapter 2. Salèty.
• Ali fastenlng parts used for the installation of the gas flare at the place of utilization must be
checked, and if necessary tightened. Please observe the tightening torque of the respective
fastenlng element. See 11.4 Torques. The flare body must be firmly anchored and tightened 9,1 Initial start up
using three steel ropes.
Before putting the gas flare ,nto operation the first time,
• Make sure that ail safety equipment such as protective covers, emergency switch/button
(formerly emergency shut-off), main switch etc. are available, correctly installed, and are • make sure you are well familiar with it:
functioning.
• the equipment and operating elements, see under operation
• Check the gas flare for visible damage and immediately remove the defects noted. The gas • the measures in case of an emergency.
flare may only be operated if in perfect condition!
• Make sure that ail control activities have been completed before initial start up. See 8.3. Alter
• Check the marked protective area to make sure that it ts free of installation and before initial start up.
• people or vehicles and • Complete the check list. See 12.2 Check list for initial start up .
• no objects (e.g. curtains, flags, birds' nests, etc) could blow or walk from the buildings or • Document the first inspection of the gas seal and initial start up. See 12.J Proof of repair work
building parts into the protective area. and /eak tests.
• Remove ail objects and other materials not needed for operation from the work area.
• Check and make sure that the electrical connection was made according to the valid provisions.
The cable feed through must be tightly screwed in and water tight.
• Make sure that ail components for ensurlng the potential equalization are correctly attached as
specified in DIN or the EC guidelines, and were checked by the electrical engineer.
• Check and make sure that the gas connection was made according to the valid provisions.
• Make sure that an adequate quality of gas is available. The quantity, quality and pressure is
prevalent for proper operation.
IMM@i
The minimum gas quantity required to start up the gas flare can be obtained from the technical data
of the gas flare according to data table 7.2 or the "project specific data sheet" in the Annex.
9.2 Start-up 9.3 Operation
Only alter you are convmced that the gas flare 1s ready for operation, can you put the gas flare mto Standard:
operation .
Alter the flare started when pressing the ignition button ON, the button can be released. The flare wlll
• Before connect1ng the supply voltage, check that... burn as long there is gas. If closing the butterfly valve, the tiare will stop burning.
• Turn the power supply on, i.e. turn on fuse. If necessary unlock emergency stop switch
(previously emergency button).
• Check if...
the message from the tlame indicator is 1n queue (check by using a lighter).
o the function of the malfunction confirmation button
o the function of the interfaces.
Fig. 21: Gis' tiare FA/, switd1 cabinet
Conduct a test operatton:
• Set the selector switch to MANUAL The automat,c valve shoulcl open and alter about two
seconds ignition will start. VALVE OPEN lights up (optional). Swilth cabinet Iock 5 Sigoal lamp error or reset button
• If the flare burns and the contrai light is on OPERATION, then one can assume that the 2 Mode selector switch 6 Display
confirmatton ON of the gas flap works properly and the tiare systems works. OPERATION only 3 SiÇ11ill lamp motor valve apen 7 Eme<gency stop switch (prl!VIOUSly
lights up tf the tlame monitoring detects a flame. Alter a few seconds the ignition stops 4 SiÇ11i!l lamp operatlon emergency button)
(optional).
• Slowly close the manual flap unttl no more gas escapes. As soon as the tlame is ext1nguished, Ignition process
the automattc flap must close immediately and alter a few seconds the tiare makes aoother
attempt at start1ng. This will s1mulate oon-combustible or too httle gas. First, the pneumattc or electncally operated gas flap is opened. At the same time the ignition
transformer is activated, a ignition spark (electric arc) is generated above the tiare burner and the
(If the flare malfunctions then ail possible faults must be examtned and removed. See 10.2 contmuous combustion of the gas is imbated.
Troubleshoottng).
• Turn the gas tiare to AUTOMATIC to contrai operation externally (optional). Here, the tlame is contmuously monitored by a UV flame sensor. If a flame is detected, the ignitton is
shut off alter a t1me delay of 10 seconds.
If oo flame is detected over an ignition pertod of about 10 seconds, the ignition will stop and the
automattc value wtll close momentarily.
If based on poor gas quality the tlame stalls, the tlame will attempt to ignite. If alter five starting
attempts a burning flame is still oot detected, the flare will switch to malfunction.
If a flame is detected even though the flap 1s not opened, then the flare will switch to malfunction.
Installation Manual - manual gasflare FAI 33
Pressure control (optional, only with automatlc) 9.4 Taking out of operation
Via two pressure switches the turn-on and shut-off point for the nare is defined. Here the turn-on Signal
for the Hare is generated by the pressure switch, and the ignition process runs automatically as If the gas flare must be taken out of operation because or for example greater maintenance work, then
described above. The pressure contrai functions via the contrai, if the selection switch is turned to only trained qualified employees who have read the operating manual and have the respective
AUTOMATIC. authorization can complete this work.
In this switch position, the ignition of the gas nare occurs the same way as in AUTOMATIC OPERATION. • Engage the emergency stop switch
As a result, dunng start-up drive the gas can be manually burned off.
• Interrupt power supply (turn off fuse) and secure fram restarting.
Operating mode OFF (optional)
• Close butterfly valve
In the OFF position of the switch attached to the switch cabinet, the burn off and ignition is not possible.
Air regulation:
To contrai the combustion air supply, there is one airregulating dise placed below the burner.
An adjustment of the airregulating dise is necessary if the flame burns unstable. That means:
• If the name is strang and blows out based on the high name speed, or burns far above the
combustion chamber, then the airregulating dise must be closed.
• If the flame burns far below, directly on the burner, and if the combustion is instable, then
more air is needed and the airregulating dise must be opened.
• Press the Emergency Stop switch to interrupt the supply voltage. The emergency stop switch
catches and with a slight turn can be deactivated again.
Wintermode
IMM%i
Communication
The flare contrai is designed to be directly incorporated in the control and visualization of the respective
operating system (only if automatic option is choosen).
Installation Manual - manual gasflare FAI 35
Troubleshooting table
10.MALFUNCTIONS AND REMOVAL MALFUNCTIONS
Malfunctlon
f iM=Hfüi
1
Power supply 1s
General malfunctlons
Fuse was triggered Check flare on site
Power cable is defect Loosen emergency off switch, check
Danger of persona! injury, property and environmental damage! interrupted or ready
Emergency stop switch was fuse
message 1s not seen
pressed Check power supply
Please fbl/ow the safety instructions m C/iapter 2. Safety. Contact manufacturer and follows
SPS is defect
test instructions,
Malfunction contrai Switch is not in "Automatic" mode
10.1 Behaviour in case of malfunctions Check fiare
Tighten flange connection, replace
Loose fiange, defect seals, seals, check valves.
• In case of malfunction of the electrical system or contrai units always contact EnvironTec System is no longer
mechanical load Oleck, if mechanical forces are
GmbH or the blogas plant manufacturer. technically sealed
Other exterior effects working (e.g. by setting
the terrain severe weather etc.1
You can reach us on business day from 8 am to 5 pm at +43 (0) 55 78 7 70 05 (outside of these hours
leave a message on voicemail , fax or email). See contact information on page
Ramefault
Not enough gas, poor gas quality.
2 of this document.
Gas feed is interrupted Test gas
UV sen50r is dirty or defective, Check gas supply
• in case of fire, 1mmediately contact the lire department, Tel: 112!
Flame monitoring (UV wiring error Clean UV sen50r, check flame
sen50r, fiame detector) Defect high voltage line to the ig- monitoring
For malfunctions that last more than 24 hours, suitable measures must be mitiated such as reducing
the feed quantities, 50 that the gas product10n is reduced, and it 1s no longer necessary to use the gas does not detect a fiame nition electrodes or corroded Check ignition
alter ignition process plug. Ignition electrodes - check
fiare m contmuous operation.
Distance between the electrodes distances and if necessary correct
(between 0.5 and 0.8 cm) Check ignition transformer
Ali spare parts (except for valves) can be obtained withm one day by couner service. See 11.7
Ianition transformer is defective
Spare parts.
After fifth successful Very poor gas quality
Test gas.
ignition process, the Gas pressure is tel0 high or too
Check gas supply
•MM@I fiame stalls and burns low
for less than 30 seconds Fame monitorioo is defect
Even though the flap is
Check fiame monitoring
Please inform us at any time about your system malfunct1ons. We depend on the expenences you make Flame monitoring is defective, Check fiame monitoring
closed, the fiame is
with the system, 50 that we can always make improvements. fiap does not close Check wmng
detected
Electrodes or cable or plug are
No ignition Check ignition
defective
10.2 Troubleshooting
A maJQrity of the malfunctions that occur can usually be attributed to a small error in the system of
your system. Stay cairn and think about the situation. Sorne malfunctions can easily be localized and Fault acknowledgement (only if automatic option 1s choosen)
removed if thinking about the problem logically.
A malfunction is identified when the indicator light on the tiare cabinet is lit and displays the message
For this purpose use the following list of malfunction messages. "Malfunction".
For malfunctions that cannot easily be removed, please contact EnvironTec GmbH, or the manufacturer With the acknowledgment key on the switch cabinet (longer than 2 s), or the remote acknowledgement
of the system in which the gas fiare is installed. key (see communication), the occurring disturbance can be reset at any time.
Installat1011 Manual - manual gasflare FAI 38
• Interrupt power supply (turn off fuse) and secure from restarting.
• Lock all work areas of the system, and make sure that no animais, chiklren or unauthorized
people are in the work area .
11.2Record
The inspection and maintenance work, as well as sealing checks completed must be
documented without fail. See 12.3 Proof of repa1r work and leak tests.
Installationsanleitung - manuelle Gasfackel FAI 39 Installat10nsanleitung - manuelle Gasfackel FAI 40
Infonnat10n in Nm
To hold screws by tightemng us1ng the specified tension, they may only be tightened up to the maximum
permitted t19htening torque. If exceeding the tlghtemng torque, the screw may stretch out and the
tension force is lost.
Screw MS MlO M12 M16
Quallty A2/A4-70
drv u = 0.14 17.7 34.8 59.9 148
Lubricated* u = 0.10 13 28 45 105
Quallty 8.8 zinc plated drv u = 0.14 25.4 49.5 85. 2 211
When opening the condensate water discharge drain, gas may escape
• Before opening the discharge drain, set the selection switch to FLARE OFF
The discharge drain is located at the lowest pomt of the flare piping.
f•iMiHfüi
Danger of surge
See also 11.5 Inspection and mamœnanœ work - Before working on the electnœl equipment
• Check Electrode distance according to informatfon in the illustration above. If necessary reset.
• Remove sensor
To order spare parts for the gas flare, please contact us directly.
Please ta speed up the ordering process, take note of the information of the flare's identification plate
(e.g. The identification plate, senal number, year made).
•MIMI
We recommend keeping a spare part package on hand ta allow immediate repairs.
Fl{l. 25: Test plate an the switr:h cabnet See contact information on page 2 of this document
• Every 3 years check the switch cabinet and inspect ail electronic and electrical components.
Ooerator
Address
Zio / Citv
Phone
Device / Serial Number FAI/50/ 15/ 500-05-08 /Giraud
*Depending on the scope and risk potential of the technical system, a detailed assessment
method may be necessary for the initial start-up.
Responsible for the Responsible for the Responsible for the start up:
assembly: electrical installation:
12.3Annexes