You are on page 1of 16

1331

Performance of two cast-in-place box culverts


under high embankments
Olajide Samuel Oshati, Arun J. Valsangkar, and Allison B. Schriver

Abstract: Two cast-in-place reinforced concrete box culverts (Longs Creek and McBean Brook culverts) with similar
geometry were instrumented to monitor earth pressures. The Longs Creek structure is a 7.30 m wide by 4.53 m high
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14

double-cell box under 14.10 m of fill, constructed using the positive projection installation (PPI) method. The McBean
Brook structure is a 6.75 m wide by 4.65 m high double-cell box culvert under 25.10 m of fill, constructed using the
induced trench installation (ITI) method. Earth pressures were monitored as the fill height above the culvert was increased
for both structures. Data from the McBean Brook culvert at a fill height of 14.40 m are compared with the data from the
Longs Creek culvert. The similar geometries of these two prototype culverts provide a unique opportunity to compare their
performance based on the two different installation methods. For a comparable height of soil cover, measured vertical earth
pressures on the roofs were 0.94 and 0.56 times the overburden pressures for the Longs Creek (PPI) and the McBean
Brook (ITI) culverts, respectively. The average measured lateral earth pressure was 0.32 times the overburden pressure at
the Longs Creek culvert (PPI), and 0.46 times the overburden pressure at the McBean Brook culvert (ITI). Data from the
McBean Brook culvert pertaining to base contact pressure are also presented, but could not be compared directly with the
Longs Creek culvert, as base pressures were not measured. Measured pressures at the base of the McBean Brook culvert
show the presence of drag forces developed on the sidewalls of box culverts. Results from centrifuge model testing are
also presented and compared with the field-measured pressures.
Key words: induced trench, earth pressure, box culvert, soil arching, centrifuge testing, high embankments.
For personal use only.

Résumé : Deux ponceaux rectangulaires coulés sur place et renforcés (ponceaux Longs Creek et McBean Brook), qui ont
une géométrie similaire, ont été instrumentés afin de mesurer les pressions des terres. La structure Longs Creek est un
ponceau rectangulaire à double cellule de 7,30 m de largeur par 4,53 m de hauteur, placé sous 14,10 m de remblai,
et construit à l’aide de la méthode d’installation par projection positive (IPP). La structure McBean est un ponceau
rectangulaire à double cellule de 6,75 m de largeur par 4,65 m de hauteur, placé sous 25,10 m de remblai, construit avec la
méthode d’installation de tranchée induite (ITI). Les pressions des terres sont suivies depuis que la hauteur du remblai sur
le ponceau a été augmentée pour les deux structures. Les données du ponceau McBean Brook à une hauteur de remblai de
14,40 m sont comparées aux données du ponceau Longs Creek. La géométrie similaire de ces deux prototypes de ponceaux
offre une opportunité unique de comparer les performances selon les différentes méthodes d’installation. Pour une hauteur
de remblai comparable, les pressions des terres verticales mesurées sur les toits étaient de 0,94 et 0,56 fois les pressions
des terres pour le ponceau Longs Creek (IPP) et le ponceau McBean Brook (ITI), respectivement. La pression des terres
latérale moyenne était de 0,32 fois la pression des terres au ponceau Longs Creek (IPP), et 0,46 fois la pression des terres
au ponceau McBean Brook (ITI). Les données du ponceau McBean Brook en lien avec la pression de contact à la base
sont aussi présentées mais n’ont pas pu être comparées directement avec le ponceau Longs Creek, puisque les pressions à
la base n’y ont pas été mesurées. Les pressions mesurées à la base du ponceau McBean Brook démontrent la présence de
forces de traînée développées sur les murs de côté des ponceaux rectangulaires. Des résultats obtenus à partir d’essais en
centrifuge sont aussi présentés et comparés aux mesures de pression sur le terrain.
Mots-clés : tranchée induite, pression des terres, ponceau rectangulaire, effet d’arche, essai en centrifuge, digues
élevées.
[Traduit par la Rédaction]

Introduction cant earth loads on the underground structures. Rigid culverts,


either circular or box, have been a common design choice for
Modern highway construction and development sometimes high embankment fills. The use of precast or cast-in-place box
requires construction of high embankments (fill height above culverts under embankments has increased over the years,
the culvert top, H ⱖ 10 m) over underground rigid and flexible owing to its structural competence and ease of construction. In
structures. The high embankment fills usually impose signifi- designing these underground box structures, several factors are
Received 9 February 2012. Accepted 22 August 2012. Published at www.nrcresearchpress.com/cgj on 19 November 2012.
O.S. Oshati, A.J. Valsangkar, and A.B. Schriver. Department of Civil Engineering, University of New Brunswick, Head Hall, 17
Dineen Drive, P.O. Box 4400, Fredericton, NB E3B 5A3, Canada.
Corresponding author: Olajide Samuel Oshati (e-mail: s1q47@unb.ca).

Can. Geotech. J. 49: 1331–1346 (2012) doi:10.1139/t2012-094 Published by NRC Research Press
1332 Can. Geotech. J. Vol. 49, 2012

considered: the site condition, fill height, rigidity of the cul- [1] WE ⫽ FeγsBcH
vert, material properties, bedding, available time, cost, and
hydraulic and structural requirements. where WE is the total unfactored earth load,
When high embankment fills are required over rigid culverts,
most jurisdictions favour two main installation methods: the Fe ⫽ 1 ⫹ 0.20 H/Bc
positive projection installation (PPI) and the induced trench in-
[2] Fe ⱕ 1.15 for compacted fill on culvert sides
stallation (ITI) methods. In the ITI method, a zone of compress-
ible material (hay, sawdust, peat, shredded rubber tires, etc.) is Fe ⱕ 1.40 for uncompacted fill on culvert sides
placed above the culvert. The concept behind the ITI method is to
reduce the vertical earth pressure, not only by the inclusion of Fe is the soil–structure interaction factor, ␥s is the unit weight
lower density fill material (compressible layer), but also mainly of the fill soil, Bc is the outside width of the culvert, and H is
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14

from inducing positive arching (i.e., column of soil directly above the fill height above the culvert roof. The term Fe represents
the culvert settles more relative to the adjacent soil) from differ- indirectly the negative arching factor to account for positive
ential settling initiated by the compressible fill material. In ITIs, projecting installation. The proposed equations for Fe are
earth load from the column of soil directly above the culvert is semi-empirical in nature. Equation [2] implies that the factor
partially supported by the shear forces developed on the soil Fe increases linearly with ratio H/Bc, but reaches a limiting
interface with adjacent soil columns, thereby resulting in some of value of 1.15 at an H/Bc ratio of 0.75 for compacted fill and 1.4
the load being redistributed to the adjacent fill. On the other hand, at an H/Bc ratio of 2 for an uncompacted fill. The combined
the PPI does not include a compressible zone within the embank- term (␥s, Bc, H) in eq. [1] represents the weight of the soil
ment and there is no load reduction on the culvert roof. Instead, prism above the culvert, per unit length of the culvert.
negative soil arching is experienced when using the PPI method, AASHTO (2010) provides no guidelines as to the method or
where the column of soil directly above the culvert settles less procedure for determining the earth load exerted on box cul-
relative to the adjacent soil. In the PPI, the earth load from the verts installed under an induced trench embankment. How-
adjacent soil columns is supported by shear forces developed on ever, AASHTO (2010) recognizes the ITI method as one of the
the soil interface with the middle soil column, thereby causing acceptable methods of installation and suggests the use of
some of the load to be redistributed to the middle soil column. accepted tests methods, soil–structure interaction analyses or
For personal use only.

Recent publications (Katona and Vittes 1982; Kang et al. previous experience to determine the load.
2008; McAffee and Valsangkar 2008; McGuigan and The purpose of the current study is to compare earth pres-
Valsangkar 2010; Oshati et al. 2012) have indicated the pres- sure data from two instrumented field installations of similar
ence of drag forces developed on sidewalls of box culverts. box culverts constructed using the PPI and ITI methods. The
study presents earth pressures measured on the roof and one
These drag forces develop due to the shear forces generated
side of the culvert for both field installations, along with the
from differential settling between the soil column and the
base contact pressures measured for the ITI. Centrifuge model
sidewalls of the culvert. As a result, the base pressure is
test results for the PPI and the ITI are also presented. The
greater than the vertical pressure on the roof plus the pressure
effect of the H/Bc ratio for the different field installations
exerted by the dead load (DL) of the culvert. reported in literature is compared with the AASHTO recom-
The University of New Brunswick (UNB) and the New mended soil–structure interaction factor (Fe).
Brunswick Department of Transportation (NBDOT) have been
studying the soil–structure interaction of rigid circular and box Box culvert research
culverts using physical testing, numerical modelling, and field
instrumentation and monitoring for over 10 years. However, General background
most of the previous studies undertaken at UNB pertain to Research related to earth loads on underground structures
precast circular pipes installed under high embankments con- has been ongoing for decades. The pioneering contributions to
structed using the ITI method. Recently, Oshati et al. (2012) earth load on buried structures and installation methods can be
published results from the field instrumentation of an induced attributed to Marston (Marston and Anderson 1913; Marston
trench double-cell rectangular box culvert, providing field- et al. 1917; Marston 1930). Early contributions from Schlick
(1920, 1932, 1952) and Spangler (Spangler 1933, 1950, 1958;
based evidence of increased base pressure. This paper focuses
Spangler and Handy 1973) also paved the way to understand-
on field instrumentation and monitoring of two similar cast-
ing the mechanism behind load transfer in buried structures.
in-place double-cell rectangular box culverts approximately
The majority of the research done on box culverts has focussed
45 km apart: Longs Creek and McBean Brook culverts. The on the PPI method with limited research on the ITI construc-
Longs Creek box culvert was constructed and installed using tion. Figure 1 shows a simplified arching mechanism of a
the PPI method, while the McBean Brook culvert was con- positive projection embankment installation (negative arching)
structed and installed using the ITI method. and an induced trench installation (positive arching).
The latest edition of the American Association of State
Highway and Transportation Officials (AASHTO) AASHTO Previous field instrumentation and monitoring
LRFD bridge design specifications (AASHTO 2010) provides Penman et al. (1975) reported on a summary of work done
equations for calculating the unfactored earth load acting on by Binger in 1948 as part of works done on the 1942 Panama
box culverts for embankment and trench installation. Equa- Canal third locks project on a 2.70 m wide by 3.30 m high
tions [1] and [2] present the AASHTO (2010) equation for (Bc/Hc ⫽ 0.82) reinforced concrete culvert. The culvert was
determining the unfactored load on top of box culverts in an installed under 15 m of compacted sandstone fill embankment.
embankment installation (PPI). The pressure measuring gauges installed on the roof of the

Published by NRC Research Press


Oshati et al. 1333

Fig. 1. Simplified arching mechanism of a PPI and an ITI.


Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14
For personal use only.

culvert were protected by a 0.60 m layer of hand-compacted from the study showed that both magnitude and distribution of
clay. Pressure measured on the roof of the culvert at the centre pressure seemed to be strongly influenced by compaction. Earth
of the rockfill embankment was 415 kPa at the end of con- pressure measured under a permanent soil cover of 2.59 m,
struction, which corresponded to 180% of the overburden 80 days after completion of the embankment at the top was
pressure (230 kPa) estimated from the field density tests. approximately 72 kPa on an average, corresponding to 144% of
Katona and Vittes (1982) reported the measured earth pres- the overburden pressure. The approximate average coefficient of
sure data from an instrumented 1.22 m by 1.22 m (Bc/Hc ⫽ 1) measured lateral earth pressure on the sidewalls was 0.57.
box culvert constructed by the Kentucky Department of Trans- Vaslestad et al. (1993) instrumented and monitored three
portation. The culvert was founded on a dense granular bed prototype culverts, one of which was a 2.0 m wide by 2.25 m
within bedrock. Eight Carlson earth pressure cells were in- high box culvert (Bc/Hc ⫽ 0.78). The study represents one of
stalled around the buried culvert. A total of 23 m of silt (MH, the few field studies on box culverts installed using the ITI
as classified according to ASTM 2006) embankment fill was method. Expanded polystyrene was used as the compressible
placed above the culvert roof. The reported earth pressure layer. The study focused mainly on the vertical earth pressure
measured on the roof and average base pressures were approx- exerted on the box culvert roof, and the long-term behaviour of
imately 148% and 161% of the overburden pressure, respec- induced trench installed culverts. Earth pressure on the top
tively. The approximate average measured lateral pressures slab was measured using hydraulic pressure cells and was
were 35% and 18% of the overburden pressure on the right and compared with the overburden pressure. The lateral earth
left side of the culvert, respectively. Katona and Vittes (1982) pressures and base contact pressures were not measured in the
reported the presence of shear traction on sidewalls, which study. Upon completion of the embankment at a fill height of
produce significant downward force that must be accounted 10.80 m, the measured earth pressure on the roof was 63% of
for with respect to increased pressure on the bottom slab. the overburden pressure. The 3 year research showed no
Tadros et al. (1989) instrumented and tested a cast-in-place significant increase in vertical earth pressure on the culvert
reinforced double-cell concrete box culvert. The 30.50 m long, after construction.
3.66 m by 3.66 m (Bc/Hc ⫽ 1) culvert was instrumented to Yang et al. (1999) instrumented two sections of a 7.0 m
measure soil pressure, strains, deflections, and settlements wide by 3.9 m high double-cell box culvert (Bc/Hc ⫽ 1.79), to
around the culvert. The sidefill was compacted as the embank- measure earth pressure distribution on the roof and sidewall.
ment was raised; after reaching a permanent fill height of Geokon model 4810 vibrating wire hydraulic type soil pres-
2.59 m above the roof of the culvert, an additional 1.07 m sure cells were used. The culvert was founded on 600 mm of
surcharge was placed for a total soil cover of 3.66 m. The earth well-graded crushed gravel. Two sections were instrumented:
pressures were monitored using 28 vibrating wire earth pressure section A was buried under 19 m of fill and section B under
cells, mounted in steel boxes. The earth pressure measurements 11.7 m of fill. Data collected over 600 days showed that with
were supplemented with six vibrating wire piezometers and 40 H/Bc ⬍ 0.5, soil–structure interaction coefficient (Fe) ranged
vibrating wire strain gauges to measure hydrostatic boundary from 0.73 to 1.85 and with H/Bc ⬎ 0.5, the soil–structure
water pressure, moments, and thrusts. Soil pressure measured interaction coefficient ranged from 0.8 to 2.0. The recorded

Published by NRC Research Press


1334 Can. Geotech. J. Vol. 49, 2012

weighted average vertical pressures were about 30% and 20% 42% and 52% of the overburden pressure at the roof and sides
greater than the AASHTO (1996) recommended pressures for of the culvert, respectively.
H/Bc ⬍ 0.5 and H/Bc ⬎ 0.5, respectively. The largest lateral
pressure was measured at the base of the wall. Results from the Previous model tests and numerical analysis
study suggest that the pressures calculated using equations Dasgupta and Sengupta (1991) studied the behaviour of
given in AASHTO (1996) did not match field observations. reinforced box culverts, using a large-scale model box culvert
Bennett et al. (2005) instrumented two sections of a 3.0 m backfilled with sand. Deflection, pressure, and strain were mea-
wide by 2.4 m high cast-in-place double-cell reinforced con- sured on the 1200 mm by 1200 mm (Bc/Hc ⫽ 1) box culvert
crete box culvert (Bc/Hc ⫽ 1.25). Vibrating wire pressure cells founded on sand. The culvert was installed under 2.40 m of sand
were used to determine the earth pressures on the roof. Strain embankment fill. Twelve deflecting diaphragm pressure cells
gauges mounted on the wall and roof were used to determine were placed around the culvert for pressure measurement pur-
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14

the axial force in the wall and bending moment in the roof, poses. The measured pressures showed a linear relationship with
which was then used to obtain the pressure on the roof as the the fill height at the top and bottom of the culvert. The rate of
fill height increased. Soil–structure interaction factors were pressure increase measured for the top slab was greater than the
also predicted using results from the pressure cells and strain bottom slab; after 2 m of fill the rate of change of pressure on the
gauges. Findings from the pressure cells that had good corre- wall decreased. Nonuniform pressure distribution was observed
lations with the strain gauges in the wall and roof suggest that at the top and bottom slab with the higher pressures at the stiffer
soil–structure interaction factor did not change with the em- end walls. The pressure distribution on the walls displayed a
bankment height, with an observed mean of 1.51. Bennett parabolic distribution with the maximum value at about 0.3 times
et al. (2005) also observed that the pressure on the roof of a the height of the wall from the base of the culvert. The total
culvert installed using the PPI method was significantly vertical pressure measured in the study was the same on both the
greater than the soil overburden pressure on the culvert. top slab and the bottom raft, and was greater than the weight of
Sun et al. (2011) monitored earth pressures around an soil directly on the slab.
induced trench cast-in-place box culvert using geofoam as the Bourque (2002) used the UNB geotechnical centrifuge to
compressible fill. The culvert was 3.35 m wide and 3.73 m measure vertical and horizontal soil pressures acting on twin
high (Bc/Hc ⫽ 0.90), founded on an unyielding bed, with fill induced trench box culverts. Bourque (2002) also performed
For personal use only.

height of approximately 15.90 m above the culvert roof. Sun parametric studies using numerical modelling to address the
et al. (2011) monitored three sections: the first section had a effect of culvert spacing, width of the compressible layer,
0.61 m thick geofoam with a width of 3.35 m (Bc), the second culvert geometry, and backfill type. Bourque (2002) observed
section had 0.61 m thick geofoam with a width of 4.88 m that the horizontal pressure for the induced trench was higher
(1.5Bc), and the third section was used as the control without than vertical pressure for both single and twin culvert installation.
a geofoam compressible layer. Instrumentation consisted of However, Bourque’s study did not address base pressures and
three strain gauges, 12 pressure cells, and two inverted settle- also only investigated a model culvert of ratio Bc/Hc ⫽ 1. Results
ment plates. The upper half of the embankment consisted of from Bourque’s study were later incorporated into a detailed
limestone rock mixed with red residual clay and the lower half study by McGuigan and Valsangkar (2011) where the issue of
was compacted red residual clay. On the culvert roof, for increased base pressure was addressed.
sections with geofoam width 1.5Bc and 1Bc, Sun et al. (2011) MacLeod (2003) investigated earth pressures around in-
measured an average pressure of 8.9% and 11.2%, respec- duced trench conduits using centrifuge testing and numerical
tively, of the pressures measured at the section without geo- modelling, and compared the results with prototype results
foam. Average measured pressure on the sidewall was 13.6% reported in the literature. MacLeod (2003) also investigated
of the pressure measured on the culvert roof at the section the effect of variables such as conduit shape (circular and box),
without geofoam. Sun et al. (2011) reported that measured backfill material, compressible zone width, compressible zone
lateral pressures at the section with a geofoam width of 1Bc thickness, compressible zone stiffness, and compressible zone
were similar to the vertical pressure, but 41.37 kPa larger than location on the performance of induced trench conduits. Re-
the vertical pressure at the section with a geofoam width of sults from the centrifuge tests performed by MacLeod (2003)
1.5Bc. On the basis of the projected linear relationship between were incorporated in a later study by McGuigan and Valsangkar
geofoam and the logarithm of time, Sun et al. (2011) con- (2010).
cluded that the earth pressure on box culverts will remain McAffee (2005) used centrifuge tests to simulate different
stable for the design life using the ITI method. However, base H/Bc ratios of field prototype structures installed using the ITI
contact pressure was not measured in the 5 year study. method, for both single and twin box culverts, and compared
Oshati et al. (2012) published results of earth pressure the centrifuge test results with the PPI method. Results from
measurements around an induced trench constructed rectangu- McAffee’s study confirmed significant reduction in vertical
lar box culvert. The instrumented culvert was 6.75 m wide and pressure on the roof and increased lateral pressures on the
4.65 m high (Bc/Hc ⫽ 1.54), under 25 m of embankment fill. sidewalls for each condition studied. McAffee (2005) ob-
Base pressures measured across two instrumented sections of served that the compressibility, width, and height of the com-
the culvert showed an increase of 25% from the measured pressible layer were important factors for load reduction in
pressure on the roof plus dead weight pressure of the culvert. underground conduits. McAffee (2005) also conducted tests
The increased base pressure was attributed to downward drag that considered different compressible zone configurations.
forces developed on the sidewalls of box culverts installed The study, however, did not investigate base contact pressures
using the ITI method. Average earth pressures reported were and only considered square-shaped culverts.

Published by NRC Research Press


Oshati et al. 1335

Fig. 2. Longs Creek culvert instrumentation locations (data from Take and Valsangkar 1999).
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14

Li and Qubain (2004) used the finite element method (FEM) Fig. 3. Longs Creek culvert with lateral earth measuring contact
to model a concrete box culvert to evaluate the effects of cell installed.
foundation yielding on design load. Yielding, partially yield-
ing, and unyielding foundations were analysed and compared
For personal use only.

with classical and conventional methods. Plane strain FEM


was used to analyse a 3.35 m wide by 3.81 m high (Bc/Hc ⫽
0.88) precast concrete box culvert under 11.58 m of embank-
ment fill. A two-dimensional FEM program SIGMA/W was
used. Li and Qubain (2004) reported that the vertical earth
pressure measured from the unyielding foundation was 1.30
times the nominal earth load on average, while for the yielding
foundation, measured vertical earth pressure was approxi-
mately equal to the nominal earth load. Li and Qubain (2004)
observed that the partially yielding foundations showed simi-
lar pressure distribution to the unyielding foundation. Li and
Qubain (2004) also observed that with yielding foundations,
resulting moment in the middle section of the top slab is
significantly reduced and end moments consequently were
increased slightly. The reported average lateral pressure for the
unyielding foundation was 0.27 times the nominal vertical
pressure, and 0.41 times the nominal vertical earth pressure Table 1. Nuclear density results around Longs Creek box culvert.
for the yielding foundation. Li and Qubain (2004) reported that
earth pressure predictions based on AASHTO (1998) could Average Average unit Standard No. of
underestimate the magnitude of soil pressure for unyielding density (kg/m3) weight (kN/m3) deviation (kN/m3) observations
foundations due to the lack of consideration of the site con- 2180.42 21.38 0.18 12
dition in the specified upper limit. In conclusion, Li and 2151.42 21.1 0.44 12
Qubain (2004) suggest that the conventional design proposed 2142.5 21.01 0.6 20
by AASHTO (1998) may still be conservative with the as-
sumption of uniform pressure distribution for unyielding
foundations.
Kim and Yoo (2005) used finite element modelling to culvert and concluded that the ITI method could reduce
analyse different geometric configurations and backfill mate- the soil–structure interaction factor. The study focused on the
rial properties for a concrete box culvert installed using the ITI beneficial load reduction that can be achieved from the ITI
method. The study reported that the preferred width of the method, and did not address lateral earth pressure or base contact
compressible layer should not exceed 1.5Bc and that the ratio pressure. Kim and Yoo (2005) also only examined square-
of the thickness of the compressible layer to the height of the shaped culverts.
culvert should not be greater than 1.5. Kim and Yoo (2005) Kang et al. (2008) reported on the results from numerical
observed that the maximum load reduction rate is achieved analysis of a box culvert under high fill, and highlighted the
when the compressible layer is placed directly on top of the effects of frictional forces developed on sidewalls of box culverts

Published by NRC Research Press


1336 Can. Geotech. J. Vol. 49, 2012

Fig. 4. Transverse section through McBean Brook induced trench culvert (all dimensions in metres; from Oshati et al. 2012).
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14
For personal use only.

on the base contact pressure. Kang et al. (2008) proposed a ometry for twin positive projecting and induced trench box
preferred compressible zone geometry, formulas for earth load culverts. McGuigan and Valsangkar (2011) observed that twin
reduction rate for the proposed compressible zone geometry, culverts installed using the PPI method gave lower pressures
and a PPI soil–structure interaction factor accounting for than single culverts. A single compressible zone spanning both
downward drag forces developed on the sidewalls of the box culverts was proposed for culverts spaced at 0.5Bc and 1Bc,
culvert. Kang et al. (2008) also found that the AASHTO while for a spacing of 1.5Bc, two individual compressible
(2004) design equation used for calculating earth loads for zones of 1.2Bc width were found to give optimum earth
embankment installation could be unconservative. pressures. Earth pressures on the roof of twin induced trench
McGuigan and Valsangkar (2010) presented the results of culvert were observed to be higher than the corresponding
parametric studies on a single box culvert using centrifuge pressures on the roof of single culverts. Lower lateral pres-
tests and numerical modelling to evaluate the pressures acting sures were observed for twin culverts compared to single
on the top, sides, and base of a box culvert. McGuigan and culverts and lower base pressures were observed for twin
Valsangkar (2010) also recommend practical optimal pre- culverts with 0.5Bc spacing than for single culverts. McGuigan
ferred compressible zone geometry, along with physical evi- and Valsangkar (2011) concluded that lower pressures corre-
dence for the increased base pressure caused by downward spond to the smallest spacing (0.5Bc).
drag forces developed on the sidewalls of box culverts. Results
of the study compared ITI with PPI and investigated the effect Field construction and instrumentation
of the compressible zone stiffness on earth pressures exerted
on the culvert. In their study, McGuigan and Valsangkar The two sites selected for this study are approximately
(2010) observed that with a preferred compressible zone width 45 km apart: the Longs Creek double-cell rectangular box
of 1.2Bc and a thickness of 0.5Hc, a 78% reduction in vertical culvert (Bc/Hc ⫽ 1.61) was installed under 14.10 m of fill in a
pressure on the roof was achieved for an unyielding founda- positive projection embankment while the McBean Brook
tion when compared with the PPI and a 47% reduction in base double-cell rectangular box culvert (Bc/Hc ⫽ 1.45) was in-
contact pressure compared with PPI. The yielding foundation stalled under 25.10 m of fill in an induced trench embankment.
on the other hand achieved a 78% and 35% reduction in The two sites were selected for their similarities in culvert size,
average roof and base pressures, respectively, compared with shape, site condition, Bc/Hc ratio, and construction materials
the PPI. In agreement with McAffee (2005), McGuigan and used. The comparison was based on measured data at approx-
Valsangkar (2010) observed that compressible zone stiffness imately 14.10 m of fill above the roof of both culverts, which
plays an important role in the load reduction achieved on the gives a comparable H/Bc ratio. The section titled “McBean
roof and base of culverts. However, the study by McGuigan Brook culvert⬙ provides details on the typical dimensions for
and Valsangkar (2010) was limited to a fill height of 12 m and the two cast-in-place reinforced rectangular boxes.
a ratio Bc/Hc ⫽ 1.
In 2011, McGuigan and Valsangkar (2011) used centrifuge Longs Creek culvert
testing and numerical modelling to evaluate culvert spacing The Longs Creek culvert is a 193.50 m long cast-in-place
(clear distance between culverts) and compressible zone ge- double-cell reinforced rectangular concrete box with a height of

Published by NRC Research Press


Oshati et al. 1337

Fig. 5. (a) McBean Brook culvert dimensions and instrument location (from Oshati et al. 2012); (b) typical dimensions of Longs Creek
concrete box culvert (all dimensions in metres).
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14
For personal use only.

4.53 m and a base width of 7.70 m installed under 14.10 m of fill. (Take and Valsangkar 1999). Nine pressure cells were placed
The culvert was part of the re-alignment of the Trans-Canada within the soil mass with sand bedding to measure vertical
Highway passing through New Brunswick, Canada. Construction earth pressure and four pressure cells were mounted on the
was done in two time periods, the first period running from July wall to measure lateral earth pressures. Settlement plates were
to October 1997 and the second from May to August 1998. The located close to each pressure cell.
Longs Creek culvert was designed and constructed as a positive The vertical earth pressure measuring cells were positioned
projecting culvert. The Longs Creek culvert instrumentation con- to enable comparison of the measured pressures around the
sists of 13 pneumatic-type contact pressure cells (Petur Model relatively stiff concrete culvert with the measured pressure
TP-100P), nine settlement plates, one pneumatic piezometer, and within the fill (Fig. 2). The locations of lateral earth pressure
two standpipes to check the accuracy of the piezometer data measuring cells are shown in Fig. 3. A nuclear density gauge

Published by NRC Research Press


1338 Can. Geotech. J. Vol. 49, 2012

Fig. 6. Centrifuge model set-up (all dimensions in millimetres; from Oshati et al. 2012). EPS, expanded polystyrene.
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14
For personal use only.

was used to observe the field density of the backfill material materials. Due to significant variation in gradation of borrow
(Table 1). Field-corrected standard Proctor dry density mea- A material, the angle of internal friction is assumed to be 30°
surements on eight fill materials used around the site averaged with an effective cohesion of 0 (McGuigan and Valsangkar
2085 kg/m3. The culvert was backfilled with Class “A” back- 2011). Construction work at the McBean Brook was com-
fill as shown in Fig. 2, and the rest of the embankment was pleted in two phases. Phase 1 started in January 2010 and
built with Borrow “A” material. The specifications of these ended in October 2010 with an approximate fill height of 4 m
materials are presented in the next subsection. The groundwa- above the roof of the culvert. Phase 2 of the construction
ter table was below the base of the culvert during the moni- commenced in April 2011 and was completed in July 2011,
toring period. when an embankment fill height of 25.10 m above the culvert
roof was reached. The groundwater table was below the base
McBean Brook culvert of the culvert (elevation of 52.9 m) for most of the initial
The McBean Brook culvert is a cast-in-place reinforced
monitoring period, but was 0.60 m above the base slab (ele-
double-cell rectangular box buried under 25.10 m of fill. The
vation of 54.6 m) as the water was diverted through the culvert
construction of this culvert was part of an upgrade of the new
before the embankment was raised to the final height.
route 8 Nashwaak–Marysville bypass in New Brunswick,
To measure earth pressures around the culvert, a total of
Canada. The 142 m long culvert has a base width of 7.35 m
and height of 4.65 m. The existing ground was excavated to a 32 Geokon vibrating wire earth pressure cells (model 4800;
depth of 2900 mm; the culvert was then founded on a 500 mm Geokon Inc., Lebanon, New Hampshire) were used. The pressure
thick class A backfill compacted to 95% standard Proctor cells are made with de-aired hydraulic oil stored in circular
maximum dry density. The sides and top of the McBean Brook stainless steel plates with a diameter of 230 mm, thickness of
culvert were also backfilled with class A fill compacted to 95% 6 mm, and an aspect ratio of 38.3. Figure 5 shows the locations
standard Proctor maximum dry density up to a height of of the pressure cells around the prototype culvert. Two differ-
500 mm above the roof of the culvert. Class A backfill is a ent sections, A and B, 8 m apart along the length of the culvert
well-graded granular material with not more than 10% re- were selected for redundancy in earth pressure measurements.
tained on a 100 mm sieve and not more than 10% passing a Both sections were under the full embankment height and each
75 ␮m sieve. Earlier testing done at the UNB gave an angle of section had 16 pressure cells installed around the culvert. A
internal friction of 40° and an effective cohesion of 0 total of 10 pressure cells were installed at the base and roof of
(McGuigan and Valsangkar 2011). A 2500 mm thick by each section of the culvert to measure the base contact and
8000 mm wide compressible fill layer was placed above the roof vertical earth pressures. To measure lateral pressures a
culvert, on top of the class A backfill. The compressible layer total of six pressure cells were installed on the sides in a
was then backfilled with borrow A material to a final height of staggered fashion; for each section, the north and south sides
25.10 m above the roof of the culvert (Fig. 4). Borrow A had three pressure cells each.
material is any soil or rock particles with no more than 25% Prior to field installation, 17 pressure cells were ran-
passing a 75 ␮m sieve and contains no organic or deleterious domly selected from each pressure range and calibrated in

Published by NRC Research Press


Oshati et al. 1339

Fig. 7. Average vertical earth pressure measured: (a) transducer A (b) transducer B (adapted from Oshati et al. 2012).
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14
For personal use only.

the laboratory. The cells were not calibrated to their maximum pressures over 60% of the combined culvert width for both the
capacity as the maximum pressure applied was just over 400 kPa, top and base orientation, and for the sides the average pressure
which is approximately one-fifth of the cell with the highest over 44% of the culvert height.
capacity used. However, the calibration proved that the cells were The transducers were calibrated prior to centrifuge testing.
working within the maximum range of pressures expected at the The calibration was done for the top and side transducers using
top, sides, and base of the culvert. For the purpose of this study, a rigid foundation and rigid side support, with the rigid foun-
earth pressure readings at a fill height of 14.40 m are used for dation thickness equal to the height of culvert (Hc). The
comparison with the Longs Creek culvert. overburden pressure for the top (␥H) and at mid-height on the
side (␥Hs) were determined, where ␥ is the unit weight of
Centrifuge testing the fill, H is equal to the fill height above the culvert top, and
All centrifuge model tests were done using a 1.6 m radius, Hs is the fill height from mid-height of the culvert side to the
geotechnical centrifuge with the ability to accelerate a 100 kg top of the fill. McGuigan and Valsangkar (2010) recom-
payload at 200 times earth’s gravitational force. To model the mended a separate calibration for transducers located at the
field prototype geometries, a scaled aluminum model culvert base of model culverts due to less localized arching around
76 mm by 52.4 mm by 195 mm in length was used. The model these transducers. Therefore, separate calibration was com-
culvert housed two pressure transducers that were used to pleted for transducers located at the culvert base. Rigid sup-
measure earth pressures. The transducers used were KYOWA ports were used on the sides of the culvert calibrating the
BEC-A-500 kPa soil pressure cells, with a capacity of 500 kPa transducers at the base of the culvert. For all calibrations the
and a high stiffness to reduce localized soil arching around the centrifuge was gradually ramped up to 50 times earth’s grav-
cell. The pressure-measuring face of the transducers have a itational field (50g). All calibrations were done in the box to
diameter of 23 mm. In total, the two transducers measure account for all boundary effects. The theoretical overburden

Published by NRC Research Press


1340 Can. Geotech. J. Vol. 49, 2012

Fig. 8. Average lateral earth pressure measured: (a) transducer A (b) transducer B (adapted from Oshati et al. 2012).
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14
For personal use only.

pressure was calculated based on the fill height, density of the McAffee and Valsangkar 2008; McGuigan 2010) and was
sand, and gravity level. Upon calibration several tests were found to produce uniform backfill beds. A constant drop height
done for both the PPI and the ITI, both constructed on a of sand was maintained throughout the sample preparation to
yielding foundation. Vertical, lateral, and base pressures were maintain a relatively constant density. After each test, the
measured for both conditions. General setup for the centrifuge density of the sand used was determined, providing an average
configuration is shown in Fig. 6. density of 1541 kg/m3. The strong box used in this study has
Silica sand was used as backfill and the yielding base layer. internal dimensions of 265 mm in width, 195 mm in length,
Expanded polystyrene (EPS) was used as the compressible fill and 495 mm in depth. Figures 7 through 9 show the average
material. The H/Hc ratio for all tests was maintained at 5.38, pressures measured in centrifuge tests on the roof, sides, and
with an H/Bc ratio of 3.71, where Bc is the outside width of the base of the culvert for each installation method. The figures
culvert. A gravitational acceleration of 50g represents approx- present the centrifuge test results as a plot of the prototype fill
imately 14.10 m of fill on a culvert with a Bc/Hc ratio of 1.45. height against measured pressure as recorded during testing.
The manual air pluviation method as described by Ueno Figure 7 presents the data pertaining to the vertical earth
(1998) was used to prepare models. This technique has been pressures measured on the roof of the model culvert. It is seen
used by other researchers in the past (e.g., Bourque 2002; from this figure that the vertical earth pressures on the roof are

Published by NRC Research Press


Oshati et al. 1341

Fig. 9. Average base contact pressure measured: (a) transducer A (b) transducer B (adapted from Oshati et al. 2012).
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14
For personal use only.

significantly reduced in ITI culverts when compared with PPI from the DL of culvert (Fig. 9) for PPI model culverts dem-
culverts. The negative arching in the case of PPI results in the onstrates that the pressures at the base are increased due to
vertical pressure on the roof being 1.12 to 1.23 times the drag loads mobilized on the sidewalls. Similar observations
overburden pressure. In comparison, the earth pressures on can also be made for the model ITI culverts.
the roof for the ITI model culvert recorded 0.21 to 0.24 times
the overburden pressure due to positive arching. The data Comparison of field and centrifuge data
presented in Fig. 7 also demonstrate that load cells A and B results
were giving consistent readings. Measured lateral earth pres-
sures in the centrifuge model tests are presented in Fig. 8. The Earth pressure data from two similar geometry culverts are
data indicate that the lateral earth pressures exerted on the compared for performance under high fill embankments. The
sidewalls for ITI model culverts are higher than those for two culverts were installed using two different installation
the model PPI culverts. Similar findings have been already methods (ITI and PPI). Field-measured pressures are presented
reported by Bourque (2002), MacLeod (2003), McAffee and and compared with model culvert pressures. The comparisons
Valsangkar (2008), and McGuigan and Valsangkar (2010). were done at similar fill heights above the roof of the culverts.
The data pertaining to the base contact pressures from the The earth pressure measured on the roof of the Longs
centrifuge model testing are presented in Fig. 9. The measured Creek culvert was 0.94 times the theoretical overburden earth
values are compared with the overburden vertical pressure on pressure. For the McBean Brook culvert, 0.56 times the the-
the roof plus the pressures resulting from the DL of the culvert. oretical overburden earth pressure was measured on the roof of
Comparison of vertical pressures on the roof of 1.12 to 1.23 the culvert. The average pressure measured on the roof of a
times the overburden (Fig. 7) plus DL with those at the base of positive projecting culvert in the centrifuge model culvert was
1.56 to 1.77 times the overburden pressure plus the pressure 1.17 times the overburden pressure, which agrees closely with

Published by NRC Research Press


1342 Can. Geotech. J. Vol. 49, 2012

Fig. 10. Comparison of average vertical earth pressures across culvert roofs.
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14

the AASHTO (2010) embankment installation (PPI) unfac- embankment was approximately equal to the overburden pres-
For personal use only.

tored earth pressure equation for culverts installed with com- sure of the embankment.
pacted sidefills. The measured vertical earth pressure on the The average measured lateral earth pressure was 0.34 times
roof of the Longs Creek culvert presented in Fig. 10 is from a the measured overburden earth pressure adjacent to the side-
single pressure cell (PC-20540) located on the roof. The pres- wall and 0.32 times the calculated overburden earth pressure at
sure cell (PC-20540) was positioned on a less stiff portion of the Longs Creek (PPI) site. The difference between the mea-
the roof. The earth pressure measured over the roof of the rigid sured and calculated earth pressures is negligible as there was
box culvert is not uniform and the earth pressures measured on neither positive nor negative arching occurring at the Long
the stiffer wall section tend to be higher than earth pressures Creek site. The average measured lateral earth pressure at the
measured in a relatively less stiff section (Li and Qubain 2004; McBean Brook site was 0.82 times the measured earth pres-
Dasgupta and Sengupta 1991; Katona and Vittes 1982; Oshati sure on the roof and 0.46 times the calculated earth pressure on
et al. 2012). In addition to the issue of location of the pressure the roof. This significant difference in estimated lateral earth
cell in a less stiff section of the roof, the earth pressures on the pressures is anticipated as the measured vertical earth pres-
roof were also influenced by the yielding foundation at the Longs sures are significantly reduced due to positive arching, thereby
Creek site. The effect of a yielding foundation on the earth resulting in a higher percentage when measured lateral pres-
pressures is further discussed in the following paragraph. For sures are expressed as a ratio of measured vertical pressures.
each analysis, fill unit weight of 21kN/m3 and a fill height of Average measured lateral earth pressures from centrifuge test-
approximately 14.10 m were used. ing were 0.34 times the calculated overburden earth pressure
Figure 10 shows the results of the vertical earth pressures for the PPI and 0.52 times the calculated overburden earth
measured on the roof of the McBean Brook culvert (ITI), pressure for the ITI. Lateral earth pressures measured on the
Longs Creek culvert (PPI), computed AASHTO (2010) culvert sidewalls for the McBean and Longs Creek culverts are
recommended design pressure for PPI, and centrifuge- presented in Fig. 11. The plot shows the earth pressures
measured vertical earth pressures for a PPI. It should be noted measured on the side from the top of the culvert downwards.
that AASHTO (2010) equations are applicable to PPI culverts, The average centrifuge measured pressure for PPI agrees
but the data from ITI culvert are also presented in this figure closely with the average pressure measured by the four lateral
for comparison. The validity of earth pressure measure- earth measuring cells at the Longs Creek culvert site. The
ments on the roof of the Longs Creek culvert (PPI) was lateral earth pressures measured on the two north sections at
confirmed with settlements measured within a similar hor- the McBean Brook culvert site show that the lateral earth
izontal plane in the embankment, and evidence of the pressures increase linearly with depth. For the Longs Creek
absence of differential settlement between the soil column culvert, the maximum and minimum coefficients of lateral
above the culvert and adjacent soil columns was observed earth pressure were 0.46 and 0.25, respectively. The estimated
(Take and Valsangkar 1999; Valsangkar 2000). Valsangkar coefficient of at-rest earth pressure based on the angle of
(2000) attributed the absence of negative arching to a rela- internal friction of 40° for class A material is 0.35. The lateral
tively yielding foundation underneath the Longs Creek cul- earth pressure distribution for the Longs Creek culvert wall
vert. Therefore, the vertical earth pressure on the roof of the was approximately parabolic, similar to the findings by
Longs Creek culvert installed within a positive projection Dasgupta and Sengupta (1991). Average lateral earth pressure at

Published by NRC Research Press


Oshati et al. 1343

Fig. 11. Comparison of lateral earth pressures.


Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14

Fig. 12. Comparison of base contact pressure.


For personal use only.

the McBean Brook culvert over two instrumented sections was Base contact pressure was not monitored at the Longs Creek
140 kPa, which corresponds to a 49% increase from the average culvert site. The results presented in Fig. 12 are from the mea-
measured lateral earth pressures at the Longs Creek (PPI) culvert sured base pressures at the McBean Brook culvert, the Longs
site. This percentage increase is also close to the results from the Creek culvert measured vertical earth pressure on the roof plus
centrifuge models tested, where ITI models registered a 50% approximated DL pressure of the culvert, the AASHTO (2010)
increase in lateral earth pressure when compared with PPI. The unfactored vertical load plus approximated culvert DL pres-
observation of increased lateral earth pressures for ITI culverts in sure, and the centrifuge measured base pressures for a model
relation to PPI culverts is consistent with earlier research done at Longs Creek culvert installation. The McBean Brook culvert
UNB. The positive arching in the case of ITI culverts reduces measured average base pressure (221.2 kPa) was 0.66 times
vertical earth pressures on the roof, but also results in additional the calculated overburden (fill only) plus the DL pressure of
lateral stresses on the sidewalls that translates into drag forces the culvert and 0.72 times the measured roof pressure plus the
acting downwards on the sidewalls. DL pressure at the Longs Creek (PPI) site. These results were

Published by NRC Research Press


1344 Can. Geotech. J. Vol. 49, 2012

Table 2. Calculated Fe on Longs Creek culvert roof. Table 3. Calculated Fe on the roof of two instrumented sections of
McBean Brook culvert.
Measured
H (m) pressure (kPa) H/Bc Fe Section A – Measured
1.75 32 0.24 0.87 H (m) pressure (kPa) H/Bc Fe
2.95 57 0.4 0.92 0.18 6.83 0.03 1.83
3.47 81 0.47 1.11 0.4 6.83 0.06 0.81
3.57 79 0.49 1.05 1 26.13 0.15 1.24
4.42 94 0.6 1.01 3 62.94 0.44 1
5.38 116 0.74 1.03 3.3 55.45 0.49 0.8
7.7 161 1 1 3.8 73 0.56 0.91
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14

8.72 178 1.19 0.97 4 96.5 0.59 1.15


12.85 258 1.76 0.96 6.29 123.97 0.93 0.94
12.85 266 1.76 0.99 8.52 141.54 1.26 0.79
13.89 271 1.9 0.93 10.43 153.2 1.54 0.7
14.15 279 1.94 0.94 12.13 162.3 1.8 0.64
12.96 165.99 1.92 0.61
14.43 172.54 2.14 0.57
18.03 184.14 2.67 0.49
18.66 198.77 2.76 0.51
compared with AASHTO (2010) predicted pressures for the
18.81 199.44 2.79 0.5
same scenario. Based on the reasonable agreement between
19.78 204.88 2.93 0.49
the vertical and lateral earth pressures measured by the cen-
21.61 215.66 3.2 0.48
trifuge with the actual measured pressures for the Longs Creek
23.56 228.15 3.36 0.46
culvert, the centrifuge base pressure result is assumed to be
25.08 235.33 3.71 0.45
close to the average expected pressure at the site. Both the
25.08 230.83 3.71 0.44
compacted and uncompacted sidefill for AASHTO (2010)
For personal use only.

25.08 226.07 3.71 0.43


predictions were lower than the centrifuge average measured
pressure, suggesting the need to account for downward drag Section B – Measured
forces developed on the sidewalls of box culverts. H (m) pressure (kPa) H/Bc Fe
Under the conditions examined, the McBean Brook culvert
0.18 6.92 0.03 1.85
ITI instrumentation appears to record significantly lower earth
0.4 6.92 0.06 0.82
pressures on the roof for a fill height of 14 m compared with
1 29.33 0.15 1.4
the Longs Creek culvert PPI. The significant increase in lateral
3 65.14 0.44 1.03
earth pressure exhibited with depth at the McBean Brook ITI
3.3 47.95 0.49 0.69
was not observed at the Longs Creek PPI. The average base
3.8 61.64 0.56 0.77
contact pressure measured beneath the McBean Brook culvert
4 97.54 0.59 1.16
was 221 kPa, which shows a 10% increase from the measured
6.29 123.17 0.93 0.93
earth pressure on the roof plus the culvert DL pressure, indi-
8.52 144.56 1.26 0.81
cating the presence of downward drag forces on the sidewalls.
10.43 155.9 1.54 0.71
Though the base contact pressure was not measured for the
12.13 162.82 1.8 0.64
Longs Creek positive projecting rectangular box culvert, cen-
12.96 164.31 1.92 0.6
trifuge testing data for base contact pressure showed that the
14.43 168.46 2.14 0.56
base pressure is in excess of the pressure on the roof of the
18.03 179.05 2.67 0.47
culvert plus the DL pressure. Similar observations of increased
18.66 184.77 2.76 0.47
base pressure have been reported in literature (Katona and
18.81 183.51 2.79 0.46
Vittes 1982; Kang et al. 2008; Oshati et al. 2012). Centrifuge
19.78 185.72 2.93 0.45
results show an increase ranging from 0%– 4% and 16%–31%
21.61 192.56 3.2 0.42
in base contact pressure from the overburden pressure plus the
22.68 199.54 3.36 0.42
dead weight for the PPI and ITI configurations, respectively.
25.08 203.07 3.71 0.39
Results from the centrifuge testing in the current study suggest
25.08 200.83 3.71 0.38
the need for field instrumentation of box culverts (Bc ⬎ Hc)
25.08 201.1 3.71 0.38
under high fills installed using PPI to measure base contact
pressure.
Results from field measurements of earth pressures show
that earth pressure on box culverts is influenced by the H/Bc mately 0.60 is reached. For ITI culverts, the factor Fe will be
ratio along with compaction effort. Measured pressures from less than one due to positive arching. From Table 3 it is noted
the Longs Creek culvert and the McBean Brook culvert as that factor Fe did not reach a minimum limiting value at the
presented in Tables 2 and 3 show that the soil–structure McBean Brook site. More field data are needed to arrive at an
interaction factor (Fe) either reduces or reaches a constant appropriate equation for Fe as a function of the H/Bc ratio.
value as the H/Bc ratio increases. For PPI culverts, the value of Figure 13 shows the variation of Fe with different H/Bc
Fe increases or stays constant until an H/Bc ratio of approxi- ratios for PPI culverts and comparison with the AASHTO

Published by NRC Research Press


Oshati et al. 1345

Fig. 13. Variation of Fe with H/Bc..


Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14
For personal use only.

(2010) values. This figure includes the data from the present forces along sidewalls of box culverts, which subsequently
research as well as the data reported in the literature. It can be increases the base contact pressure. Results from this study
noted from this figure that AASHTO (2010) predicted values show that centrifuge testing can also be used for prelimi-
could be unconservative and therefore these equations should nary evaluation of culverts installed under high fill embank-
be used with caution. The available data for PPI culverts show ment, and that the ITI method provides substantial cost
that factor Fe reaches a limiting value for the H/Bc ratio of savings from the reduction of earth pressures on the roof
about 5. and base of box culverts.
Conclusion
Acknowledgement
A relatively yielding foundation can significantly reduce
vertical earth pressure on culverts, as was the case for the Financial support for this research was provided by New
Longs Creek culvert (PPI). Average vertical earth pressure on Brunswick Department of Transportation (NBDOT) Canada.
the roof of the McBean Brook culvert (ITI) at a fill height of
approximately 14.4 m was 170 kPa, which corresponds to a References
39% reduction in vertical earth pressure (270 kPa) measured at AASHTO. 1996. AASHTO LRFD Bridge Design Specifications.1st
the Longs Creek culvert (PPI). Average lateral earth pressure ed. American Association of State Highway and Transportation
(139.6 kPa) measured at the McBean Brook culvert (ITI) Officials, Washington, D.C.
compared with the average measured pressure (93.7 kPa) at AASHTO. 1998. AASHTO LRFD bridge design specifications. 2nd
the Longs Creek culvert (PPI) showed an increase of 49%.
ed. American Association of State Highway and Transportation
Base contact pressures measured at the McBean Brook culvert
Officials, Washington, D.C.
(ITI) indicate that downward drag forces are developed on the
AASHTO. 2004. AASHTO LRFD bridge design specifications. 3rd
sidewalls of box culverts. Centrifuge testing results confirmed
ed. American Association of State Highway and Transportation
the presence of increased base pressure from the overburden
pressure plus the DL pressure of box culverts. Officials, Washington, D.C.
The results from this study suggest that the soil–structure AASHTO. 2010. AASHTO LRFD bridge design specifications. 5th
interaction factor (Fe) reduces as the ratio H/Bc increases, but ed. American Association of State Highway and Transportation
the relationship is dependent on the rate of settlement, which Officials, Washington, D.C.
can be influenced by several construction factors (compaction, ASTM. 2006. Standard practice for classification of soils for engi-
bedding, installation method). Findings from the present study neering purposes (Unified Soil Classification System). ASTM
suggest that the AASHTO (2010) unfactored vertical earth standard D2487. American Society for Testing and Materials,
load equations for embankment installations (PPI) appears West Conshohocken, Pa.
to be a reasonable estimate for yielding foundations, pro- Bennett, R.M., Wood, S.M., Drumm, E.C., and Rainwater, N.R.
vided necessary accommodations for an uneven pressure 2005. Vertical loads on concrete box culverts under high embank-
distribution on the roof are considered. There is a need to ments. Journal of Bridge Engineering, 10(6): 643– 649. doi:
recognise and account for the presence of downward drag 10.1061/(ASCE)1084-0702(2005)10:6(643).

Published by NRC Research Press


1346 Can. Geotech. J. Vol. 49, 2012

Bourque, S. 2002. Centrifuge and numerical modeling of induced Oshati, O.S., Valsangkar, A.J., and Schriver, A.B. 2012. Earth pres-
trench twin conduits. M.Sc.E. thesis, Department of Civil Engi- sures exerted on an induced trench cast-in-place double-cell rect-
neering, University of New Brunswick, Fredericton, N.B. angular box culvert. Canadian Geotechnical Journal, 49(11):
Dasgupta, A., and Sengupta, B. 1991. Large-scale model test on 1267–1284. doi:10.1139/T2012-093.
square box culvert backfilled with sand. Journal of Geotechnical Penman, A.D.M., Charles, J.A., Nash, J.K.T.L., and Humphreys, J.D.
Engineering, 117(1): 156 –161. doi:10.1061/(ASCE)0733-9410 1975. Performance of culverts under Winscar Dam. Géotechnique,
(1991)117:1(156). 25(4): 713–730. doi:10.1680/geot.1975.25.4.713.
Kang, J., Parker, F., Kang, Y.J., and Yoo, C.H. 2008. Effects of Schlick, W.J. 1920. Supporting strength of drain tile and sewer pipe
frictional forces acting on sidewalls of buried box culverts. Inter- under different pipe-laying conditions. Iowa Engineering Experi-
national Journal for Numerical and Analytical Methods in Geo- ment Station, Iowa State College, Ames, Iowa. Bulletin 57.
mechanics, 32(3): 289 –306. doi:10.1002/nag.628. Schlick, W.J. 1932. Loads on pipes in wide ditches. Iowa Engineering
Can. Geotech. J. Downloaded from www.nrcresearchpress.com by Texas A&M University on 11/14/14

Katona, M.G., and Vittes, P.D. 1982. Soil structure analysis and Experiment Station, Iowa State College, Ames, Iowa. Bulletin 108.
evaluation of buried box-culvert designs. Transportation Research Schlick, W.J. 1952. Loads on negative projecting conduits. Highway
Record, 878: 1–7. Research Board, Proceedings of the Annual Meeting (American
Kim, K., and Yoo, C.H. 2005. Design loading on deeply buried box Association of University Teachers of Insurance). No. 31, pp.
culverts. Journal of Geotechnical and Geoenvironmental Engineering, 308 –319.
131(1): 20–27. doi:10.1061/(ASCE)1090-0241(2005)131:1(20). Spangler, M.G. 1933. The supporting strength of rigid pipe culverts.
Li, J., and Qubain, B.S. 2004. Soil pressure distribution on culverts Iowa Engineering Experiment Station, Iowa State College, Ames,
with various foundation yielding conditions. In Proceedings of the Iowa. Bulletin 112.
17th ASCE Engineering Mechanics Conference, Newark, Del., Spangler, M.G. 1950. Field measurements of the settlement ratios of
13–16 June 2004. University of Delaware, Newark, Del. various highway culverts. Iowa Engineering Experiment Station,
MacLeod, T. 2003. Earth pressures on induced trench conduits. Iowa State College, Ames, Iowa. Bulletin 170.
M.Sc.E. thesis, Department of Civil Engineering, University of Spangler, M.G. 1958. A practical application of the imperfect ditch
New Brunswick, Fredericton, N.B. method of construction. Highway Research Board, Proceedings of
Marston, A. 1930. The theory of external loads on closed conduits in the Annual Meeting. No. 37, pp. 271–277.
the light of the latest experiments. Iowa Engineering Experiment Spangler, M.G., and Handy, R.L. 1973. Soil engineering. 3rd ed.
For personal use only.

Station, Iowa State College, Ames, Iowa. Bulletin 96. Intext Press Inc., New York.
Marston, A., and Anderson, A.O. 1913. The theory of loads on pipes Sun, L., Hopkins, T., and Beckham, T. 2011. Long-term monitoring
in ditches and tests of cement and clay drain tile and sewer pipe. of culvert load reduction using an imperfect ditch backfilled with
Iowa Engineering Experiment Station, Iowa State College, Ames, geofoam. Transportation Research Record, 2212(1): 56 – 64. doi:
Iowa. Bulletin 31. 10.3141/2212-06.
Marston, A., Schlick, W.J., and Clemmer, H.F. 1917. The supporting Tadros, M.K., Benak, J.V., Abdel-Karim, A.M., and Bexten, K.A.
strength of sewer pipe in ditches and methods of testing sewer pipe 1989. Field testing of a concrete box culvert. Transportation Re-
in laboratories to determine their ordinary supporting strength. search Record, 1231: 49 –55.
Iowa Engineering Experiment Station, Iowa State College, Ames, Take, A., and Valsangkar, A.J. 1999. Longs Creek concrete box
Iowa. Bulletin 47. culvert preliminary report. Department of Civil Engineering, Uni-
McAffee, R.P. 2005. Soil-structure interaction in rigid culverts in- versity of New Brunswick, Fredericton, N.B. Report issued to
stalled in induced trenches. Ph.D. dissertation, Department of Civil NBDOT August 1998.
Engineering, University of New Brunswick, Fredericton, N.B. Ueno, K. 1998. Methods for preparation of sand samples. In Pro-
McAffee, R.P., and Valsangkar, A.J. 2008. Field performance, cen- ceedings of the International Conference Centrifuge ‘98, Tokyo,
trifuge testing, and numerical modelling of an induced trench Japan, 23–25 September 1998. Edited by T. Kimura, O. Kusakabe,
installation. Canadian Geotechnical Journal, 45(1): 85–101. doi: and J. Takemura, A.A. Balkema, Rotterdam, the Netherlands.
10.1139/T07-086. Vol. 2, pp. 1047–1055.
McGuigan, B.L. 2010. Earth pressures and loads on induced trench Valsangkar, A.J. 2000. Earth pressures on Longs Creek box culverts.
culverts. Ph.D. dissertation, Department of Civil Engineering, Uni- Department of Civil Engineering, University of New Brunswick,
versity of New Brunswick, Fredericton, N.B. Fredericton, N.B. Report issued to NBDOT August 2000.
McGuigan, B.L., and Valsangkar, A.J. 2010. Centrifuge testing and Vaslestad, J., Johansen, T.H., and Holm, W. 1993. Load reduction on
numerical analysis of box culverts installed in induced trenches. rigid culverts beneath high fills: long-term behavior. Transporta-
Canadian Geotechnical Journal, 47(2): 147–163. doi:10.1139/ tion Research Record, 1415: 58 – 68.
T09-085. Yang., M.Z., Drumm, E.C., Bennett, R.M., Mauldon, M. 1999. Mea-
McGuigan, B.L., and Valsangkar, A.J. 2011. Earth pressures on twin surement of earth pressures on concrete box culverts under high-
positive projecting and induced trench box culverts under high way embankments. In Field Instrumentation for Soil and Rock.
embankments. Canadian Geotechnical Journal, 48(2): 173–185. ASTM Special Technical Publication 1358. American Society for
doi:10.1139/T10-058. Testing and Materials, West Conshohocken, Pa. pp. 87–100.

Published by NRC Research Press

You might also like