Acid Dew point calculation for CFB Boilers

Parameters Value Units


SO2 in flue gas #REF! ppm
Air preheater flue gas pressure -200 mmWC (g)
745.3 mmHg (a)
Moisture in flue gas #REF! % vol
#REF!
Partial pressure of H2O #REF! mmHg(a)
Natural log of f #REF!
SO2 to SO3 conversion #REF! %
#REF!
SO2 in volume percent #REF! %
Partial pressure of SO3 #REF! mmHg(a)
Natural log of j #REF!

Dew Point of Acid Vapors - Sulfurous acid Equation: 1000/T dp=2.276-0.0294 ln(PH2O)-.0858 ln(PSO3)+0.0062
ln(PH2O)ln(PSO3)
Formula as metioned above #REF!
#REF! oK

#REF! oC

150~160 oC
Remarks
Use value in ppm not of mg/NM3

Convert to mmHG (abs) from mmWC


Reference value 10%, based on Lab results
convert to fraction

Assued value Constant 2%


convert to fraction
ppm to % conversion
Mol wt of SO2 & SO3

6-0.0294 ln(PH2O)-.0858 ln(PSO3)+0.0062

Display value on DCS near TT-1020-05. Compare


value with TT-1020-05A/B

If calculated value is higher than operating


value of TT-1020-05A/B, then generate alarm
with description "Operating temperature lower
than Acid dew point temperature"