You are on page 1of 2

GAVR-12A

Universal 7 Amp 1/2 Wave Self Excited


Dip-Switch Programmalbe Automatic
Voltage Regulator
Features
l < 1% Regulation
l 220/440 VAC Programmable Input
l Rugged Compact Design
l With Under Frequency Protection
l Soft Start Voltage Ramping
l EMI Suppression
l Built-in Hihg Capacity 10Amp Fuse
Specifications
SensingInput Voltage 180~260VAC,1phase2wire VoltageBuild-up Residualvolts at AVR teminal>5VAC
Power Input Voltage 180~260VAC,1phase2wire External Volts Adjustment 7%with 1K 1watt trimmer
Output Voltage Max.90VDC@240VACinput Sotf Start Ramp Time 2sec.
Current Continuous 4A Unit Power Dissipation Max.8Watt
Intermittent 7A for 10SEE. EMI Suppression Internal Electromagnetic Interference Filtering
Resistance Min.12 Max.100 Thermal.Drift 0.03%per chage in AVR ambient
Under Frequency Protection 60Hz system presets knee point at 55Hz
(Factory Settings) 50Hz system presets knee point at 45Hz
Volts Regulation < 1%(with 4%engine governing)

Environment
Vibration 3G@100~2K Hz Relative Humidity < 95%
Operating Temperatuer -40~65 Storage Temperature -40~85

Mechanical Specifications

AVR Controls
R2 R1 T F- F+ N VolTS Voltage A djustment
FUSE

STAB Stability Adjustment


U/F To Set the U/F*Knee Point
121
110

*U/F:Under Frequency Protection


Physical Specifications
LOW SPFEED
Dimensions 121.0(L)92.0(W)60.0(H)mm
LED

5
VOLT STAB U/F 80
92
121

92
80
110

LOW SPEED
FUSE LED

F+
U/F
F
STAB
T

R2 VOLT

R1

N
N
S
S 220VAC
380VAC
R GEN
R GEN
T
T
FIELD
FIELD

N T F F+
N T F F+
GAVR 12A
GAVR 12A
R1 R2
R1 R2

EXT
VR
1K

POWER 120
F IELD
100
50Hz 60Hz
80
N T F F+
60
GAVR 12A
40
3-12V
20 / 5W

R1 R2

20
EXT
VR
1K 0 10 20 30 40 50 60