Instruction Manual: LX70/700 D/A Conversion Module
Instruction Manual: LX70/700 D/A Conversion Module
3
Safety Instructions
Please read this manual and the related documentation thoroughly and familiarize
yourself with product information, safety instructions and other directions before
installing, operating, performing inspection and preventive maintenance.
Please be aware that the instructions are marked with either a warning symbol or
attention symbol.
4
Overview
Hardware Features
LX700 D/A Module (8, 4 CH) LX70 D/A Module (4, 2 CH)
Voltage output: LX-AO8V, AO4V Voltage output: LX70-AO4V, AO2V
Current output: LX-AO8C, AO4C Current output: LX70-AO4C, AO2C
Inverter
Read data with the advanced instruction, READ
LX Motor speed
controller
Thermometer
5
D/A Conversion Modules for LX700 PLC System
LX-AO8V (8CH, voltage output) LX-AO4V (4CH, voltage output)
Input terminal
(CH.0 to CH.7)
Set the output voltage
range with the DIP switch
on the bottom of the
module.
Unused terminal
(No connection)
Unused terminal
(No connection)
I0 I0
C0 Input terminal C0
I1 (CH.0 to CH.7) I1
C1 Set the output current C1
I2 range with the DIP switch I2
C2 on the bottom of the C2
I3 module. I3
C3 C3
I4
C4
I5 Unused terminal
C5 (No connection)
I6
C6
I7
C7 A.GND: Analog ground
F.G: Frame ground
Unused terminal
(No connection)
6
D/A Conversion Modules for LX70 PLC System
LX70-AO4V (4CH, voltage output) LX70-A02V (2CH, voltage output)
7
LISTED
General Specifications UL 62Y6
C ®
US IND. CONT. EQ.
Item Specifications
Operating 30 to 85 % RH (Non-condensing)
Humidity
Storage 30 to 85 % RH (Non-condensing)
8
Voltage Output Module Specifications
PLC Series LX700 LX70
Number of output
8 Channels 4 Channels 4 Channels 2 Channels
channels
Allowable output
5 K Ω or more
load resistance
• Between output channel and internal circuit: DC/DC converter and
Isolation method photocoupler isolation
• Between output channels: Non-insulation
• I/O contact type, 8CH: 128 points output, 4CH: 64 points output, 2CH: 32
Number of I/O points points output
• Shared memory type: 16 points
5 V 420 mA 5 V 380 mA 5 V 350 mA 5 V 340 mA
Internal current or less or less or less or less
consumption (5 V)(b) (80 mA/CH (80 mA/CH (80 mA/CH (80 mA/ CH
at D/A output) at D/A output) at D/A output) at D/A output)
External connection LX700: 20-pin removable terminal
LX70: 20-pin terminal block (M3.0)
method block (M3.5)
(a) You can select an I/O range and maximum resolution that suits your purpose using the
dip switch on the bottom of the module. The conversion speed and conversion data
stability will differ depending on the resolution you select. See "Output Range Selection".
(b) It is recommended not to use more than eight (8) voltage output D/A modules on a
backplane. (You can still mount more than eight (8) voltage output D/A modules on a
backplane, but operating all of them at the same time may encounter the limitation of
total current consumption.)
9
Current Output Module Specifications
PLC series LX700 LX70
Allowable output
5 KΩ or more
load resistance
Between output channel and internal circuit: DC/DC converter and
Isolation method photocoupler isolation
Between output channels: No insulation
I/O contact type, 8CH: 128 points output, 4CH: 64 points output, 2CH: 32
Number of I/O points points output
Shared memory type: 16 points
5 V 1000 mA 5 V 680 mA 5 V 650 mA 5 V 500 mA
Internal current or less or less or less or less
consumption (5 V)(b) (20 mA/CH (20 mA/CH (20 mA/CH (20 mA/CH
at D/A output) at D/A output) at D/A output) at D/A output)
External connection LX700: 20-pin removable terminal
LX70: 20-pin terminal block (M3.0)
method block (M3.5)
(a) You can select an I/O range and maximum resolution that suits your purpose using the
dip switch on the bottom of the module. The conversion speed and conversion data
stability will differ depending on the resolution you select. See "Output Range Selection"
on page 11.
(b) It is recommended not to use more than five (8) current output D/A modules on a
backplane. (You can still mount more than five (5) current output D/A modules on a
backplane, but operating all of them at the same time may encounter the limitation of
total current consumption.)
10
Operating Procedure
Procedure Operation
1. Select conversion data input method
Conversion with SW8.
Conversion data data I/O OFF: I/O contact type
I/O method setting method ON: Shared memory type
(SW8 setting) setting 2. SW8 is only recognized on power-on, so
(SW8) input method cannot be changed during
PLC operation.
11
Dip Switch Settings
SW1 to SW3: Output Range Setting
For Voltage Output Modules (LX-AO8V/AO4V, LX70-AO4V/AO2V)
SW1 SW2 SW3 Output range and conversion data Remarks
OFF OFF OFF ±10 V: -10,000 to 10,000
ON OFF OFF ±5 V: -10,000 to 10,000
OFF ON OFF 0 to 10 V: 0 to 10,000
ON ON OFF 0 to 5 V: 0 to 10,000
OFF OFF ON ±10 V: -16,383 to 16,383
ON OFF ON ±5 V: -16,383 to 16,383
OFF ON ON 0 to 10 V: 0 to 16,383
ON ON ON 0 to 5 V: 0 to 16,383
12
Installation
Installation Dimensions
LX700 PLC System Dimensions (mm)
B
TR OUT
TR OUT
TR OUT
TR OUT
TR OUT
DC IN
DC IN
DC IN
CPU
LX
115.5 118.5
unit (mm)
111.0 Dimensions
Slot Type
A B
3-slot type 205.0 184.0
5-slot type 276.0 254.0
8-slot type 381.0 360.0
10-slot type 452.0 430.0
12-slot type 522.0 501.0
5.0 * 4
27.5
81.0
unit (mm)
Slot Type P L
3-slot type 205.0 153.8
5-slot type 276.0 224.2
8-slot type 381.0 329.8
7.0
22.5 L
10-slot type 452.0 400.2
12-slot type 522.0 470.6
P
13
LX700 CPU, D/A Conversion Module Dimensions (mm)
D/A
D/A
CPU
RUN RUN
ERROR ERROR
115.5
35.0 104.0
LX
A
105.0
30.0
38.0
C
4 - M5
14
unit (mm)
Slot Types Catalog Number Dimensions (A) Dimensions (B) Dimensions (C)
2-slot type LX70-BASE02 157.2 128.6 114.6
3-slot type LX70-BASE03 192.4 163.8 149.8
5-slot type LX70-BASE05 262.8 234.2 220.2
6-slot type LX70-BASE06 298.0 269.4 255.4
8-slot type LX70-BASE08 368.4 339.8 325.8
10-slot type LX70-BASE10 438.8 410.2 396.2
12-slot type LX70-BASE12 508.6 480.6 466.6
D/A
105.0
RS232C
35.0
15
Installing a D/A Conversion Module on a PLC System:
1. Wire analog I/O cables to the terminal block.
2. Turn on the power connected to the D/A conversion module.
3. Turn on the main PLC power.
ATTENTION
D/A Conversion Module Installation Precautions
• Avoid installing a D/A conversion module next to output module
or power supply modules.
• Install a D/A conversion module as near as possible to the right
edge of the backplane.
16
Mounting/Dismounting Module
Mounting Dismounting
1. Insert the module by inserting the 1. Unfasten the screw that holds the
tab into the groove first and pushing module in place using a
the module against the backplane. screwdriver.
2. Push the top of the module toward 3. Hold on pressing the locking button
the backplane until it is clamped in on the top edge of the module, and
place. pull the module from the backplane
Locking button
screwdriver
17
Wiring
Wiring Precautions
What Is A.GND of the D/A Conversion Module?
A.GND A.GND
• On an analog circuit, the digital part and external signal part are isolated with a
photocoupler, and the power supply is isolated with a DC/DC converter.
• Usually the A.GND terminal is used to maintain a stable potential by connecting
it to a FG terminal or a high impedance condenser. However, in many cases,
noises from F.G terminal still may cause D/A module to measure wrong values.
To address this problem, our D/A module provides external FG and G.AND
terminals, allowing for a connection fitting to each application.
• In addition, our D/A module maintains high impedance at +, - terminal and
A.GND terminal.
18
Wiring Diagrams
Voltage Output D/A Conversion Module Wiring Diagram:
LX-AO8V/AO4V, LX70-AO4V/AO2V
FG
19