You are on page 1of 14

Article

Advances in Structural Engineering


2017, Vol. 20(12) 1793–1806
Seismic performance of emulative Ó The Author(s) 2017
Reprints and permissions:
precast concrete beam–column sagepub.co.uk/journalsPermissions.nav
DOI: 10.1177/1369433217693633

connections with alternative journals.sagepub.com/home/ase

reinforcing details

Hung-Jen Lee1, Hsi-Ching Chen2 and Jia-Hao Syu3

Abstract
This article presents an experimental investigation on alternative reinforcing details for the bottom bars of precast concrete beams at
cast-in-place beam–column joints to achieve the behaviour as for monolithic reinforced concrete beam–column connections. To
relieve steel congestion and fabrication difficulties, it is proposed to use headed bars for the bottom bars that are protruded from pre-
cast beams and anchored in the middle of the beam–column joint. In total, six interior beam–column connection specimens were
tested under reversed cyclic loading. The primary test variables were the transverse beams and the anchorage of the bottom beam
bars in the joint. Hysteretic behaviour, including strength degradation, stiffness degradation and energy dissipation, was evaluated in
accordance with the acceptance criteria for special moment-resisting frames. Test results demonstrated that emulative precast con-
crete specimens with bottom beam bars anchored in the joint middle can perform as well as monolithic beam–column connections
with continuous beam bars passing through the joint. On the basis of the experimental results, design recommendations are drawn
for these types of emulative precast beam–column connections.

Keywords
anchorage, beam–column joint, headed reinforcement, precast concrete, seismic testing

Introduction reductions in site formwork and labour, increased con-


struction speed and high-quality control. The primary
Because of their advantages in time and cost savings, drawback of this arrangement is the steel congestion in
precast concrete building structures are becoming more the cast-in-place joint, where the protruded bottom
and more common around the world. For earthquake- bars from each precast beam element need to be stag-
resistant concrete frames, several alternative solutions gered well in the joint core to prevent them from con-
have been developed for moment-resisting connections flicting with each other, as shown in Figure 2.
between precast beam and column components to This article proposes alternative reinforcing details
achieve the behaviour as for monolithic reinforced for the bottom beam bars to relieve the steel congestion
concrete structures (Chen et al., 2012; Choi et al., in the cast-in-place connections for special moment
2013; Guan et al., 2016; Ha et al., 2014; Im et al., 2013; frames. As shown in Figure 1(b), the bottom beam bars
Pampanin, 2005; Park, 2002; Watanabe, 2007; Xue of the precast beam elements are terminated by anchor
and Zhang, 2014). Figure 1(a) illustrates one of the tra- plates or heads with anchorage lengths not exceeding
ditional arrangements for emulative precast concrete
moment frames that is used in New Zealand, Japan
1
and Taiwan. The semi-precast beam elements are Department of Civil and Construction Engineering, National Yunlin
University of Science and Technology, Yunlin, Taiwan
placed on the edges of the column top, followed by 2
Graduate School of Engineering Science and Technology, National
reinforcement fabrication and concrete casting in the Yunlin University of Science and Technology, Yunlin, Taiwan
cast-in-place joint, beam tops and slabs. Afterwards, 3
Lee Ming Construction Co., Ltd, Taichung, Taiwan
the upper precast column element is connected by
longitudinal column bars that protrude into mortar- Corresponding author:
Hung-Jen Lee, Department of Civil and Construction Engineering,
grouted coupling sleeves within the column to form an National Yunlin University of Science and Technology, Douliu 64002,
emulating monolithic reinforced concrete frame. This Yunlin, Taiwan.
typical arrangement has many advantages such as Email: leehj@yuntech.edu.tw
1794 Advances in Structural Engineering 20(12)

Figure 1. Precast concrete beam–column connections emulating monolithic reinforced concrete frames: (a) conventional hooked
bars and (b) alternative headed bars.

experimentally studied by Japanese researchers in


1990s (Castro et al., 1991; Matsudo et al., 1992; Satoh
et al., 1996). The experimental results showed that
emulative cast-in-place connection performance could
be achieved for anchoring bottom beam bars in the
joint middle with additional confinement reinforce-
ment in the joint. These reinforcing details can avoid
steel congestion of the bottom beam bars from two
opposite faces of the joint, but it can also result in
another congestion problem related to joint transverse
reinforcement in the joint core. To date, it is well
accepted that the use of headed bars in place of hooked
bars is a viable solution to steel congestion in beam–
column connections and presents no significant design
Figure 2. Staggered hooked bars in an interior beam–column
problems (Kang et al., 2009; Wallace et al., 1998).
connection.
Chen et al. (2012) tested four beam–column connec-
tions using lap splices of headed bars protruding from
one-half of the column depth. Heads allow the bars to beam bottom ends that extended to the far side of the
be developed in a shorter length than required for stan- confined core, while the top beam reinforcement was
dard hooks (Thompson et al., 2006). Heads also liber- continuously extended through the joint. The research-
ate the space occupied by the bent-up hook extensions ers observed satisfactory and comparable performance
in the joint. The use of headed bars that terminate in between the emulative and monolithic concrete speci-
the middle of the joint, rather than hooked bars that mens subjected to reversed cyclic loading up to an
extended to the far side of the joint core, can relieve the inter-storey drift ratio of 3% or 5%.
steel congestion and construction difficulties in the More recently, Chiu et al. (2016) tested seven inte-
cast-in-place connection. However, headed bars with a rior and five exterior monolithic reinforced concrete
shorter anchorage length may also increase the poten- beam–column connections to investigate the seismic
tial for concrete breakout failure, which should be pre- anchorage behaviour of headed bars with varying
cluded by providing adequate reinforcement in the anchorage lengths and bar spacing. In the tested inte-
joint. rior beam–column connections, the top beam bars
To avoid steel congestion of the bottom beam bars, were continuously extended through the joint, while
the termination of the bottom bars of precast beams the bottom beam bars were lap-splice or non-overlap
with bent-up hooks in the middle of the joint was anchored by heads in the joint. For a joint with low
Lee et al. 1795

shear demand, the test results showed that the seismic ACI 374.1-05 (ACI Committee 374, 2005). Therefore,
anchorage performance of the bottom beam bars an experimental programme is conducted to verify the
(either lap-spliced or non-overlapped in the joint) is as proposed anchorage details for the bottom beam bars
good as that of the top beam bars passing through the of precast beams. Different from prior research works,
joint. However,
pffiffiffiffi for a joint with a design shear stress the anchorage performance of headed bottom bars was
about 1:25 fc0 MPa, bottom beam bars with non- evaluated with a varied bottom-to-top reinforcement
overlap anchoring have inferior performance than area ratio and a high shear stress acting on the joint.
those that are lap-splice anchored in the joint.
Therefore, Chiu et al. (2016) preferred to use lap-splice
anchorage for bottom beam bars in joints with high Experimental investigation
design shear stresses. Notably, the specimens tested by Six large-scale reinforced concrete interior beam–
Chiu et al. (2016) had an equal area of top and bottom column connection specimens, as shown in Figure 3,
reinforcements. In common design practice, the bot- were constructed and tested at YunTech in Taiwan to
tom reinforcement area As, bot could be less than the investigate the use of alternative reinforcing details for
top reinforcement area As, top at the joint face for a spe- ductile connections of precast beams and columns.
cial moment frame beam. For such case, a less critical The experimental programme was designed using a
0
and relatively lower flexural tension from the bottom concrete compressive strength fc of 55 MPa and yield
beam bars would be anchored in the joint. strengths of 420 and 490 MPa, respectively, for longi-
This article proposes that the bottom beam bars be tudinal and transverse reinforcements. The primary
non-overlap anchored by heads in the middle of the test variables were the ratio of the bottom-to-top beam
joint, as shown in Figure 1(b). This allows for more reinforcement area (As, bot =As, top ), the anchorage of the
freedom of design, proportion, erection and fabrica- bottom beam bars in the joint and the presence of
tion in precast concrete elements. According to ACI transverse beams. The specimens were designed as part
318-14 Section 18.9.2.3, precast concrete frames with of a special moment frame in high seismic zones and
alternative details that do not satisfy the prescriptive followed the requirements of ACI 550.1R-09 (ACI
requirements shall be proven by experiments satisfying Committee 550, 2009) and ACI 318-14 (ACI
the acceptance criteria for moment frames defined by Committee 318, 2014), except for the joint shear stress

D13 D13 D13


hoops hoops hoops
@100 @100 @150

8-D25 12-D25 12-D25 12-D25


top

4-D25
bottom

8-D25
top

6-D25
bottom

Figure 3. Test matrix and reinforcing details of beam–column joint specimens.


1796 Advances in Structural Engineering 20(12)

Table 1. Material properties and connection parameters.

Parameter Specimen
A1 A2 A3 B1 B2 B3
0
Concrete fc (MPa) 56.8 61.9 49.2 55.6 51.2 53.2
Longitudinal beam b3h 400 mm 3 500 mm 400 mm 3 500 mm
As, top 8-D25 (SD420a) 6-D25 (SD420a)
As, bot 4-D25 (SD420a) 6-D25 (SD420a)
Mpr + 484 kN m, 2787 kN m + 631 kN m, 2631 kN m
Av 4-D13 at 100 mm (SD490b)
Transverse beam b3h NA NA 400 mm 3 500 mm NA NA 400 mm 3 500 mm
Column b3h 500 mm 3 500 mm
Ast 12-D25 (SD420a)
Ash 4-D13 at 100 mm (SD490b)
Joint s (mm) 100 100 150 100 100 150
Ash =sbc 0.0112 0.0112 0.0075 0.0112 0.0112 0.0075
Ash, ratio c 1.10 1.01 1.69 1.12 1.22 1.56
0
fc : compressive strength of concrete cylinders at testing date; b: section width; h: section overall depth; As, top : area of top beam reinforcement; As, bot :
area of bottom beam reinforcement; Ast : total area of longitudinal reinforcement; Ash : total cross-sectional area of transverse reinforcement; Av : area
of shear reinforcement; s: spacing of transverse reinforcement; bc : column core dimension measured to the outside edges of the transverse
reinforcement composing area Ash ; Mpr : probable flexural strength of the beam calculated using a bar stress of 1:25fy for positive and negative
bending moments; NA: not available.
a
SD420 D25 reinforcement; bar area = 507 mm2; measured yield strength fy = 470 MPa.
b
SD490 D13 reinforcement; bar area = 127 mm2; measured yield strength fy = 498 MPa.
c
The provided amount of transverse reinforcement divided by the amount of transverse reinforcement required by ACI 318-14; the required amount
for specimens A3 and B3 is one-half of that for other specimens because of confinement from transverse beams.

and the anchorage details of the bottom bars that were force in equilibrium with the probable beam moments
investigated in this test programme. Mpr at the joint faces, which were determined using a
bar stress of 1:25fy , for positive and negative bending
moments, respectively; Lb is the unit beam length
Connection design (4.5 m for tested specimens); Lc is the unit column
Figure 3 and Table 1 show the element dimensions, length (3 m for tested specimens) or the equivalent
reinforcing details, material properties, and test para- storey height; and hc is the column depth of 500 mm.
meters for the test specimens. Three specimens, desig- For the test specimens listed in Table 1, the value of Vu
nated as Group A, used eight and four D25 reinforcing is computed to be 2720 kN using equation (1).
bars for the longitudinal reinforcement in the beam top All test specimens had a square column section of
and bottom, respectively, resulting in an unequal rein- 500 mm 3 500 mm detailed with 12 D25 Grade 420
forcement ratio in the beam section. The other three (specified fy = 420 MPa) longitudinal reinforcing bars
specimens, designated as Group B, used six D25 rein- and D13 Grade 490 (specified fy = 490 MPa) trans-
forcing bars symmetrically for the top or bottom beam verse hoops and ties at a spacing of 100 mm. The
reinforcement, resulting in a reinforcement ratio of Grade 490 reinforcement was used to reduce the
As, bot =As, top = 1:0. The total amount of beam longitu- amount of transverse reinforcement for confinement
dinal reinforcement is 12 D25 reinforcing bars, and of 55-MPa concrete column. According to the ACI
thus, the design shear force of the joint (Vu ), which is 318 and ACI 352R-02 requirements for joints in spe-
estimated by the method recommended by ACI 352R- cial moment frames, the primary connection design
02 (ACI-ASCE Committee 352, 2002), is almost the parameters are computed as follows.
same for each test specimen
 
Vu = 1:25fy As, top + As, bot  Vcol ð1Þ Column-to-beam flexural strength ratio. To produce yield-
  ing in the beams rather than in the columns, the col-
+ 
Mpr + Mpr Lb umns shall be stronger than the beams framing into a
Vcol = ð2Þ joint of a special moment frame and satisfy
ðLb  hc Þ Lc
P
where As, bot is the area of bottom beam bars; As, top is Mnc
Mr = P ø 1:2 ð3Þ
the area of top beam bars; fy is the specified yield Mnb
strength of reinforcement; Vcol is the column shear
Lee et al. 1797

P P
where Mnb and Mnc are the sum of the nominal transverse beams are anchored by heads to shorten the
flexural strengths of the beams and columns, respec- development length and promote the confinement
tively, calculated at the joint faces. The nominal flex- effect.
ural strength of the column is 670 kN m under an Using the design concrete strength of 55 MPa, the
0
axial compression of 0:05Ag fc for the test specimens. joint shear demand-to-capacity ratio is equal to 1.18
According to ACI 374.1-05, it is conservative not to for the test joints without transverse beams but equal
apply axial load, which will be generally less than the to 0.88 for the test joints with transverse beams. In
balanced load and increase the flexural strength in the other words, the design joint shear stress in specimens
columns. However, zero axial load is unrealistic and A1, A2, B1 and B2 is 18% higher than the permissible
may be too conservative for bond performance of value; thus, these joint specimens are expected to
beam bars in the joint. Therefore, a least column axial achieve beam yielding followed by joint shear failure
0
of 0:05A at a limited inter-storey drift ratio. However, speci-
P g fc was conservatively used in this programme.
The Mnb are 1047 and 1041 kN m for beams in mens A3 and B3 have a design joint shear stress below
Group A and B specimens, respectively. Thus, the the permissible value and are expected to develop
moment strength ratio Mr is 1.28 or 1.29 for the test beam hinging until joint shear failure occurs at a rela-
connections in Group A or Group B, respectively. tively large drift ratio.
Yielding of the flexural reinforcement should occur in
the beams first.
Provided-to-required transverse reinforcement ratio in the
joint. To maintain the integrity of the joint concrete
Joint shear demand-to-capacity ratio. To avoid premature and to reduce the degradation of the joint shear capac-
shear failure of joints, the demand of joint shear force ity, transverse reinforcement required in the column
(Vu , equation (1)) shall not exceed the nominal shear ends shall be extended through the joint, unless a joint
capacity of the joint (Vn ) times the strength reduction is considered to be effectively confined by beams on all
factor f of 0.85 four sides where the required amount of transverse
reinforcement shall be permitted to be reduced by one-
qffiffiffiffi
half, as given in Section 18.8.3 of ACI 318-14
Vu ł fVn = fg fc0 Aj ð4Þ
pffiffiffi0ffi   0 0
Ash Ag f f
pffiffiffi0ffi g fc ispffiffiffithe
where ffi nominalpffiffiffiffishear stress
pffiffiffiffi of ø 0:3  1 c and 0:09 c ð6Þ
1:67 fc MPa (20 fc0 psi) or 1:25 fc0 MPa (15 fc0 psi) sbc Ach fyt fyt
for an interior joint with or without transverse beams, where Ash is the total cross-sectional area of the trans-
respectively, and Aj is the effective cross-sectional area verse reinforcement, including crossties, within spacing
of the joint. Definitions of Aj can be found in ACI 318 s and perpendicular to dimension bc , which is the
and ACI 352R-02. This article uses the one adopted in cross-sectional dimension of the column core without
ACI 318-14, which is equal to the gross area of the col- concrete cover; Ag and Ach are the gross area and the
umn for the test specimens shown in Figure 3. core area of the column, respectively; and fyt is the
The strength reduction factor f is omitted for specified yield strength of the transverse reinforcement.
experimental studies and then the joint shear demand- Kim and LaFave (2007) identified that an ‘Ash ratio’
to-capacity ratio is (provided amount of joint transverse reinforcement
divided by the amount required by equation (6)) could
Vu Vu vu
= pffiffiffi0ffi = pffiffiffi0ffi ð5Þ be a key influencing parameter for the shear behaviour
Vn g f c Aj g fc of beam–column joints. All the connections in this test
programme were well confined by transverse reinforce-
where vu is the design shear stress of the joint and
ment and had ‘Ash ratio’ exceeding 1.0, as shown in
equal to 10.9 MPa (Aj = 500 3 500 mm2 and
Table 1.
Vu = 2720 kN from equation (1)) for all test
specimens.
Notably, the specified nominal shear strengths of Anchorage in beam–column joint. For Grade 420 straight
specimens A1, A2, B1 and
pffiffiffiffiB2 (joint without transverse beam bars passing through the joint, ACI 318 and ACI
beams) is equal to 1:25 fc0 MPa but that of specimens 352R-02 require a minimum column depth of 20 bar
A3 pandffiffiffiffi B3 (joint with transverse beams) is diameters (20db ) for joints of special moment frames.
1:67 fc0 MPa. Due to set-up limitation, each trans- All test connections shown in Figure 3 used Grade 420
verse beam stub only had a length of 150 mm, which is 25-mm-diameter longitudinal reinforcing bars and a
less than one overall beam depth, and may not be column depth of 500 mm, which is approximate to
effective for confinement. Therefore, all the bars in the 20db . For headed deformed bars anchored in the joints
1798 Advances in Structural Engineering 20(12)

of special moment frames, ACI 318 gives a minimum relatively severe. Kang et al. (2009) extensively
development length, measured from the beam–column reviewed studies on the use of headed bars and con-
interface to the bearing face of the head, as follows cluded that the minimum clear spacing between headed
bars can be reduced to 2db in beam–column joints con-
0:19fy fined by transverse reinforcement. Thereafter, Kang
‘dt, 318 = the greatest of pffiffiffi0ffi db , 8db , 150 mm ð7Þ
fc et al. (2012) tested two exterior beam–column joints
with closely spaced headed bars and concluded that
with limitations of (a) specified fy not exceeding the clear bar spacing of approximately 2db or the use
420 MPa, (b) bar size not exceeding 36 mm, (c) of two bar layers may be reasonably permitted for
normal-weight concrete, (d) each head has a net bear- headed bars anchored in the exterior beam–column
ing area exceeding four times the nominal cross- joints subjected to earthquake-type loading. Similar
sectional area of the bar, (e) minimum clear cover of conclusions are also drawn by Chiu et al. (2016).
2db for each bar and (f) minimum clear spacing of 3db Therefore, this experimental programme decided to
between parallel bars. use a minimum clear spacing of 2db between beam bars
The recommendations of development length for anchored in the joints.
headed bars given by ACI 352R-02 are somewhat dif- Figure 4 shows the stress–strain relations obtained
ferent. For joints of special moment frames, critical from the tensile tests of Grade 420 D25 bare and
sections for the development of beam bars should be headed bars. The 65-mm-diameter steel head was
taken at the outside edge of the confined core, and the attached to a reinforcing bar end by a friction–welding
minimum development length for headed bars is connection, which obstructed some of the bearing face
of the head; thus, the net bearing area of the head was
0:15fy only about 4.3 times the nominal cross-sectional area
‘dt, 352 = the greatest of pffiffiffi0ffi db , 8db , 150 mm ð8Þ
fc of the bar. As shown in Figure 4, the bar-to-head con-
nections are strong enough to break the bar in tensile
and bar heads should be located in the confined core tests resulting in stress–strain behaviour identical to
within 50 mm from the back of the confined core that of bare bars.
(ACI-ASCE Committee 352, 2002).
Substituting bar fy of 420 MPa and design concrete
0
strength fc of 55 MPa into equations (7) and (8) result- Test method and load protocol
ing in minimum development lengths of 10.8db and Figure 5 shows the test set-up and reinforcing details
8.5db, respectively. The latter should add a cover thick- in this experimental programme. The bottom column
ness of 25 mm (1db) for comparison with test speci- was hinged to the strong floor with a one-dimensional
mens shown in Figure 3. The provided development rocking steel base. The beams were laterally braced to
length of the headed bars is only 9db, measured from restrain out-of-plane deformation and linked to the
the bearing face of the head to the column face. strong floor using roller supports at the right and left
Furthermore, all test specimens were detailed with ends. At the beginning of each test, a constant axial
0
longitudinal beam bars at a clear spacing of 2db load of 0:05Ag fc was applied to the column top by a
between bars. Obviously, the anchorage conditions of hydraulic jack and pretension steel rods. The upper
the bottom beam bars used in this test programme are column was horizontally connected to the reaction wall

Figure 4. Stress–strain curves obtained from bar tensile tests (200-mm gauge length).
Lee et al. 1799

Figure 5. Overview of typical test set-up and details of cross section.

by one displacement-controlled actuator to apply cyc- followed by joint shear failure (‘BJ’ failure) at a drift
lic loading in a quasi-static manner. The test set-up ratio of 4% or 6%, due to the difference in joint shear
was arranged to eliminate the P-delta effect and simu- demand-to-capacity ratios. All beam longitudinal rein-
late a 3/4-scale beam–column joint specimen with a forcements developed the bar yield strength and under-
column height (storey height) of 3 m and a beam span went inelastic load reversals without bond or
of 4.5 m (the distance between the roller-supported anchorage failure in the joint. The measured and
inflection points). observed responses are summarized and discussed in
A typical displacement-controlled loading protocol the following subsections.
consisting of three reversed cycles at gradually
increased drift ratios (0.50%, 0.75%, 1.0%, 1.5%, 2%,
3%, 4%, 6% and 8%) was used in this study. The tar- Global response
get displacement at the loading point of the upper col- Figure 6 shows the cyclic lateral load–displacement
umn was computed by multiplying the target drift curves for all test specimens, where the drift ratio is
ratio to the simulated storey height of 3000 mm. The equal to the lateral displacement (d) at the loading
axial load and lateral force at the upper column were point divided by the simulated storey height of
monitored by load cells. Several displacement transdu- 3000 mm (Figure 5). The lateral load Q is also normal-
cers were attached to the test specimen to measure the ized to the ideal yield load (Qy = 430 kN) in balance
global lateral drifts and local deformations (joint shear with the sum of the nominal flexural strengths of the
deformation and beam end rotation). Numerous strain beams calculated at the joint faces using the measured
gauges were pre-attached to reinforcements at key material properties (Table 1). Figure 6 also illustrates
locations to record the strain histories. In general, the the displacement ductility ratio m = d=dy in the posi-
loading protocol and test procedure in this experimen- tive and negative directions for each test specimen,
tal programme are consistent with respect to ACI where the idealized yield displacement dy was equal to
374.1-05 (ACI Committee 374, 2005). The presented Qy divided by a secant stiffness obtained at the mea-
test results herein continued up to 6% or 8% drift sured displacement corresponding to 0.75Qy in the first
ratio for the observation of failure modes. However, cycle of 1.5% drift. The definition of dy value can be
the performance of test specimens should be evaluated found in ACI 374.2R-13 (ACI Committee 374, 2013).
prior to the limiting drift ratio of 4% because the 6% Typically detailed specimens A1 and B1, with con-
or 8% drift may be too large for a well-designed spe- tinuous beam bars passing through the joint, devel-
cial moment frame. oped yielding of beam bars in 1.5% drift cycles and
attained maximum lateral resistance (Qm ) at 3% drift
ratio, as shown in Figure 6, followed by strength and
Experimental results and discussion stiffness degradation due to shear cracks and damage
The experimental results showed that each test connec- in the joint. The maximum experimental shear stresses
tion was capable of developing yielding in beams acting on the joint, back calculated using Qm and
1800 Advances in Structural Engineering 20(12)

Drift Ratio (%) Drift Ratio (%) Drift Ratio (%)


-8 -6 -4 -2 0 2 4 6 8 -8 -6 -4 -2 0 2 4 6 8 -8 -6 -4 -2 0 2 4 6 8
1.5
600
A1 μ= 1 2 3 4 A2 μ= 1 2 3 4 A3 μ= 1 2 3 4 5
Lateral Load, Q(kN)

400 1.0

200 0.5

Q/Qy
0 0.0

- 200 - 0.5

- 400 - 1.0
- 600 4 3 2 1 =μ 4 3 2 1 =μ 5 4 3 2 1 =μ - 1.5
600
B1 μ= 1 2 3 4 B2 μ= 1 2 3 4 B3 μ= 1 2 3 4 5
1.0
Lateral Load, Q(kN)

400

200 0.5

Q/Qy
0 0.0

- 200 - 0.5

- 400 - 1.0
- 600 4 3 2 1 =μ 4 3 2 1 =μ 5 4 3 2 1 =μ - 1.5
- 240 - 120 0 120 240 - 120 0 120 - 240 - 120 0 120 240
Displacement, δ (mm) Displacement, δ (mm) Displacement, δ (mm)
Figure 6. Lateral load–displacement responses for test specimens.

measured material properties, for specimens A1 and a larger drift ratio of 6%, and then completed the 8%
B1 were 11% and 9%, respectively,
pffiffiffiffi higher than the drift cycles for failure observation. The Qm-back-calcu-
nominal strength of 1:25 fc0 MPa specified by ACI lated experimental shear stresses in the joints of
318-14 for interior joint without transverse beams. Specimens A3 and B3 p are
ffiffiffiffi 13% and 16% less than the
Measured shear deformations on the joints of nominal value of 1:67 fc0 MPa specified by ACI 318-
Specimen A1 and B1 exhibited inelastic hysteresis in 14. Due to the presence of the transverse beams, the
4% drift cycles followed by joint shear failure. Neither joint damage in Specimens A3 and B3 was not as
Specimen A1 nor B1 showed any bond failure along severe as cruciform Specimens A2 and B2.
the straight beam bars in the joint during testing, and
thus, the development length of 20db is concluded to
be adequate for the test specimens. Crack observations
As shown in Figures 6 and 7, the hysteresis and Figure 8 compares the crack patterns observed at the
envelope curves of Specimen A2 with alternative rein- 3% drift ratio. In addition to the primary shear cracks
forcing details for the anchorage of the bottom beam that propagated diagonally in the joints, secondary
bars are almost identical to those of Specimen A1; cracks also initiated along the bottom beam bars
however, those of Specimen B2 are somewhat inferior anchored by heads in the joint, especially in Specimen
to those of Specimen B1. Although the global B2. Increasing the number of bottom beam bars that
responses of the four cruciform beam–column connec- terminate in the middle of the joint by heads seems to
tions were very similar during testing, a little more increase the potential for concrete breakout. As
strength degradation can be observed in Specimen B2. addressed in the commentary of Section 25.4.4.2 in
This can be attributed to the numbers of bottom beam ACI 318-14, breakout failure can be precluded in
bars anchored in the middle of the joint. However, joints by either keeping the anchorage length from
Specimens A3 and B3 with transverse beams obviously exceeding 0.66d, where d is the effective depth of the
perform better than the other four cruciform speci- beam section, or by providing adequate transverse
mens (Figure 6). Both specimens developed beam hin- reinforcement to enable a strut-and-tie mechanism.
ging, attained their maximum lateral resistance (Qm ) at The provided anchorage length of the headed bars in
Lee et al. 1801

Figure 7. Comparison of envelope curves for test specimens: (a) Group A specimens and (b) Group B specimens.

Figure 8. Crack patterns observed at 3% drift ratio.

the joints of the test specimens is only about 0.5d, and drift ratios for the four cruciform specimens. All beam
thus, the role of the transverse reinforcement becomes bar strains measured at the beam–column faces (loca-
crucial. Figure 9 illustrates a strut-and-tie model, tion at 6250 mm) went above the ideal yield strain of
where the flexure tension that developed in the bottom 2155 me (obtain from Figure 4) at the 2% drift ratio
beam bars was anchored by heads and resisted by fan- indicating the development of beam yielding. For spe-
shaped struts and transverse reinforcement. The cimens A1 and B1, a clear strain gradient per distance
anchorage performance of the bottom beam bars and along the straight beam bar passing through the joint
the force-transferring behaviour of the transverse rein- can be observed in Figure 10. This indicated that the
forcement can be monitored by strain gauge readings. bond resistance in the joint had not been completely
destroyed till the 3% drift ratio. It is concluded that
the development length of 20db is adequate for the
Local response straight beam bars used in the test specimens. For spe-
The strains of reinforcing bars were measured using cimens A2 and B2 with alternative reinforcing details,
electrical resistance strain gauges attached to some the beam bar strains measured at the beam–column
reinforcing bars at selected locations. Figure 10 shows faces (location at 6250 mm) and in the joint core
the strain profiles along the bottom beam bars at peak (location at 6100 mm) exceeded the bar yield strain at
1802 Advances in Structural Engineering 20(12)

and B2 were effectively anchored by heads with a short


anchorage length and a clear spacing of 2db in the
beam–column joints. Notably, the joints were well
detailed with transverse reinforcement.
Figure 11 compares the profiles of tie bar strains
measured at one top column crosstie (Gauge 11) above
the top beam bars, three inner joint crossties (Gauges
12–14) between the top and bottom beam bars and
another bottom column crosstie (Gauge 15) below the
bottom beam bars for the cruciform test specimens.
Each gauge was attached to the centre of the crosstie
parallel to the beam bars. Figure 11 shows that the tie
bar strains measured in the joint (Gauges 12–14)
remained elastic in the 1.5% drift cycles but went
beyond the yield strain of 2500 me at the 2% drift
ratios for all test specimens. Notably, the tie bar strains
measured in the top and bottom column (Gauges 11
Figure 9. Strut-and-tie modelling for Specimen A2 with and 15) remained elastic over the entire loading history
headed bars anchored in the joint middle.
in Specimens A1 and B1 with continuous bottom beam
bars. In contrast, the tie bar strains measured below
the 2% drift ratios indicating almost the entire bar ten- the discontinuous bottom beam bars in Specimens A2
sile force was transferred to the end anchorage. It is and B2 (Gauge 15) went beyond the yield strain of
evident that the bottom beam bars in specimens A2 2500 me after the 2% drift cycles. Besides, the tie bar

Figure 10. Profiles of strain developed along bottom beam bars for test specimens.
Lee et al. 1803

Figure 11. Profiles of tie bar strain along the column height.

strain of Gauge 14 in Specimen B2 was relatively larger


than that of Gauge 14 in Specimen B1 for each drift
level. These phenomena can be explained using
Figure 9, where the tensile force of the bottom beam
bars was transferred to the transverse reinforcement in
the joint and the bottom column.
For the anchorage of the bottom beam bars by
heads in the middle of the joint, yielding of the column
transverse reinforcement is not preferred because it
may affect the column confinement. Therefore, it is
recommended to provide one more set of joint trans-
verse reinforcements below the bottom beam bars Figure 12. Breakout failure precluded in joint by providing
anchored in the joint, as shown in Figure 12. To pre- adequate transverse reinforcement to tie the potential failure
clude breakout failure, this article recommends that surface.
the total amount of joint and column transverse rein-
forcements covered by the fan-shaped struts should be
capable of resisting the total tensile force to be devel- headed bars in the confined core, which is based on a
oped in the bottom beam bars, as given below breakout prism angle of approximately 35° (ACI 318-
X 14 Chapter 17).
Ash fyt ø As, bot fy ð9Þ For Specimens A2 and B2, the effective embedded
P depth of the headed beam bars in the confined column
where Ash is the amount of effective transverse rein- core was about 8db (200 mm), and thus, all three sets
forcement in the joint and bottom column, parallel to of joint transverse reinforcements and the upper two
the bottom beam bars and within the critical edge dis- sets of transverse reinforcements in the bottom column
tance of 1.5 times the effective embedded depth of the were effective to tie the assumed breakout prism.
1804 Advances in Structural Engineering 20(12)

Table 2. Test results for comparison with acceptance criteria of ACI 374.1-05.

Parameters Specimen
A1 A2 A3 B1 B2 B3

Initial stiffness for first Positive 12.26 11.48 12.14 12.49 12.15 12.90
cycle of 0.5% drift (kN/ Negative 11.83 11.86 11.89 12.64 12.03 12.26
mm)
Percentage degradation in Positive 22.5% 18.8% 10.6% 18.6% 24.9% 10.6%
lateral resistance from Negative 16.2% 10.7% 2.8% 14.7% 20.8% 5.1%
first to third cycle of 4%
drift
Ratio of secant stiffnessa Positive 0.13 0.15 0.19 0.15 0.11 0.16
around zero drift to initial Negative 0.12 0.13 0.17 0.11 0.10 0.14
stiffness
Relative energy ED/EPP 0.25 0.24 0.25 0.25 0.24 0.23
dissipation ratiob
a
The secant stiffness around zero drift ratio was obtained for positive and negative loading directions between drift ratios of 20.4% and + 0.4% in
the third compete cycle of 4% drift ratio.
b
The relative energy dissipation ratio was the energy dissipated in the third complete cycle of 4% drift ratio divided by the idealized elastoplastic
energy of that cycle.

Using equation (9) with a measured yield strength of 3. Energy dissipation in the third cycle of limiting
fyt = 498 MPa and fy = 470 MPa, the total tie force drift ratio shall not be less than 12.5% of the
provided by five sets of transverse reinforcements is idealized elastoplastic energy of that drift ratio.
33% higher than the yield force of the four D25 bars
in the beam bottom of Specimen A2 but 12% less than In this experimental programme, a limiting drift
that of the six D25 bars in the beam bottom of ratio of 4% is conservatively considered due to the lack
Specimen B2. Therefore, with respect to Specimen A2, of 3.5% drift cycles. Accordingly, Table 2 compares
Specimen B2 exhibited relatively severe damage the hysteresis performance of the third cycle of the 4%
(Figure 8) and strength degradation (Figure 7). drift ratio for the test specimens. All test specimens sat-
isfied the acceptance criteria at a 4% drift ratio except
that the strength degradation in the positive loading
Evaluation of seismic testing performance direction of Specimen B2 was close to 25% and, there-
fore, not ideal. This is attributed to the numbers of
Precast frame systems with alternative details that do
bottom beam bars in excess of the amount of effective
not satisfy the prescriptive requirements of chapter 18
transverse reinforcement in Specimen B2. On the con-
in ACI 318-14 may be used for seismic design if satis-
trary, Specimen A2 with alternate reinforcing details
factory performance can be demonstrated by experi-
performed as well as and perhaps even better than the
ments of the as-built design. ACI 374.1-05 defines a
benchmark Specimen A1 with continuous bottom bars
protocol for the design, analysis and laboratory testing
because of fewer bottom beam bars anchored in the
of such frames. The proposed alternative reinforcing
joint. To conclude, the amount of effective transverse
details for the emulative precast beam–column connec-
reinforcement should be proportioned to the pull-out
tions were designed and tested in this study according
of the headed bars from the joint. Based on the obser-
to ACI 374.1-05. For acceptance, the test results of the
vation of the strain profiles of Figure 11, it is recom-
third complete cycle to a limiting drift ratio not less
mended to provide more transverse reinforcement
than 3.5% should satisfy the following three criteria:
adjacent to the bottom beam bars anchored in the joint
by heads.
1. Strength degradation shall not exceed 25% of Finally, as compared in Table 2, the performance of
the maximum peak strength in the same load- Specimens A3 and B3 with transverse beams is better
ing direction. than that of the other cruciform specimens. Obviously,
2. Secant stiffness between drift ratios of 21/10 the presence of the transverse beams did enhance the
and + 1/10 of the limiting drift ratio shall not joint integrity even though the joint transverse reinfor-
be less than 5% of the initial stiffness obtained cement was also reduced. The transverse beams with
from the first cycle. discontinuous bottom beam bars framing to the joint
Lee et al. 1805

may not be considered effective for confining the joint. Conclusion


This experimental programme is limited to emulative
The experimental results presented in this work demon-
precast beam–column connections under unidirectional
strated that emulative precast beam–column connec-
load reversals. It may be more crucial for such connec-
tions with bottom beam bars anchored in the joint
tions under bidirectional load reversals. This should be
middle can perform as well as monolithic beam–
verified in future experimental studies.
column connections with straight beam bars passing
through the joint. Based on the experimental results, it
Design recommendations is concluded that the bottom beam bars protruding
from precast beam units could be anchored in the joint
To ease the difficulty of the erection and fabrication of middle by heads with limitations of a least net bearing
precast beams at cast-in-place beam–column connec- area of 4Ab for each head, a minimum clear spacing of
tions, it is a viable option to terminate the protruded 2db between bars, a code-conforming anchorage length
bottom bars of precast beams in the middle of the joint and adequate transverse reinforcement.
with adequate anchorage and confinement. On the From the experimental observations, the potential
basis of the experimental results and observations, the for concrete breakout failure increased for the closely
confinement and anchorage of the bottom beam bars spaced headed bars that were used in the test speci-
in the joint is considered to be adequate if following mens. To preclude breakout failure, adequate trans-
conditions are satisfied: verse reinforcement should be provided and distributed
uniformly within the critical edge distance of 1.5 times
1. Joint and column transverse reinforcements the effective embedded depth of the headed bars in the
should conform to Section 18.7.5 of ACI 318- confined core. The amount of transverse reinforcement
14. could be proportioned by establishing load paths in
2. The development length of the headed accordance with strut-and-tie modelling principles.
deformed bars should be in accordance with Finally, with proper design and details, anchorage of
Section 25.4.4 of ACI 318-14, except that a bottom beam bars in the middle of the joint can be a
minimum clear spacing of 2db between bars viable option to relieve the steel congestion in the cast-
could be used in the confined joint. in-place connections for special moment-resisting
3. Breakout failure of the headed bars should be frames.
precluded by providing adequate transverse
reinforcement to enable a fan-shaped strut-and-
tie mechanism, where the amount of transverse Declaration of Conflicting Interests
reinforcement within the critical edge distance The author(s) declared no potential conflicts of interest with
(1.5 times the effective embedded depth of the respect to the research, authorship and/or publication of this
headed bars in the confined core) should be article.
proportional to the tensile force of the bottom
beam bars. Funding
The author(s) disclosed receipt of the following financial sup-
For the test specimens, the clear spacing between port for the research, authorship and/or publication of this
beam bars was only 2db, and the provided development article: This study was supported by the National Science
length of the headed bars was a little shorter than the Council (renamed to Ministry of Science and Technology
required length given by ACI 318-14 or ACI 352R-02. since 2014) in Taiwan.
Such headed bars did perform well in a well-confined
beam–column joint but may not perform as well under References
other conditions. The test results show that the ancho-
rage requirements of ACI 318-14 are conservative for a ACI-ASCE Committee 352 (2002) 352R-02: Recommenda-
tions for Design of Beam-Column Connections in Mono-
well-confined beam–column joint. In addition, it is
lithic Reinforced Concrete Structures. Farmington Hills,
unnecessary and not recommended to anchor top beam MI: American Concrete Institute, p. 38.
bars in the middle of beam–column joints, unless the ACI Committee 318 (2014) 318-14: Building Code Require-
top beam bars cannot be extended through the joint. ments for Structural Concrete and Commentary. Farming-
As shown in Figures 1 and 2, straight and continuous ton Hills, MI: American Concrete Institute, p. 520.
top beam bars are preferred in cast-in-place joints and ACI Committee 374 (2005) 374.1-05: Acceptance Criteria for
beam tops. Moment Frames Based on Structural Testing and
1806 Advances in Structural Engineering 20(12)

Commentary. Farmington Hills, MI: American Concrete Kang THK, Shin M, Mitra N, et al. (2009) Seismic design of
Institute, p. 9. reinforced concrete beam-column joints with headed bars.
ACI Committee 374 (2013) 374.2R-13: Guide for Testing ACI Structural Journal 106(6): 868–877.
Reinforced Concrete Structural Elements under Slowly Kim J and LaFave JM (2007) Key influence parameters for
Applied Simulated Seismic Loads. Farmington Hills, MI: the joint shear behaviour of reinforced concrete (RC)
American Concrete Institute, p. 18. beam–column connections. Engineering Structures 29(10):
ACI Committee 550 (2009) 550.1R-09: Guide to Emulating 2523–2539.
Cast-in-Place Detailing for Seismic Design of Precast Con- Matsudo M, Mikame A, Sasaki H, et al. (1992) Experimen-
crete Structures. Farmington Hills, MI: American Con- tal study on anchorage system of bottom bars in precast
crete Institute. beams. In: Summaries of technical papers of annual
Castro JJ, Yamaguchi T and Imai H (1991) Seismic behavior meeting architectural institute of Japan. Structures II,
of half precast beam-column joints. Proceedings of the pp. 837–838. Hokuriku, 27–29 August, Architectural
Japan Concrete Institute 13(2): 1069–1074. Institute of Japan.
Chen SC, Yan WM and Gao J (2012) Experimental investi- Pampanin S (2005) Emerging solutions for high seismic per-
gation on the seismic performance of large-scale interior formance of precast/prestressed concrete buildings. Jour-
beam-column joints with composite slab. Advances in nal of Advanced Concrete Technology 3(2): 207–223.
Structural Engineering 15(7): 1227–1237. Park R (2002) Seismic design and construction of precast con-
Chiu CK, Chi KN and Lin KC (2016) Experimental investi- crete buildings in New Zealand. PCI Journal 47(5): 60–75.
gation on the seismic anchorage behavior of headed bars Satoh Y, Mikame A, Hayashi K, et al. (1996) Experimental
based on full-size specimens of exterior and interior study on bent bar anchorage in precast R/C beam-column
beam–column joints. Advances in Structural Engineering joint: part III outline of experimental tests. In: Summaries
19(5): 777–794. of technical papers of annual meeting architectural institute
Choi HK, Choi YC and Choi CS (2013) Development and of Japan. C-2, structures IV: reinforced concrete structures
testing of precast concrete beam-to-column connections. prestressed concrete structures masonry wall structures,
Engineering Structures 56: 1820–1835. pp. 689–690. Kinki, 14–16 September, Architectural Insti-
Guan DZ, Guo ZX, Xiao QD, et al. (2016) Experimental tute of Japan.
study of a new beam-to-column connection for precast Thompson MK, Jirsa JO and Breen JE (2006) Behavior and
concrete frames under reversal cyclic loading. Advances in capacity of headed reinforcement. ACI Structural Journal
Structural Engineering 19(3): 529–545. 103(4): 522–530.
Ha SS, Kim SH, Lee MS, et al. (2014) Performance evalua- Wallace JW, McConnell SW, Gupta P, et al. (1998) Use of
tion of semi precast concrete beam-column connections headed reinforcement in beam-column joints subjected to
with U-shaped strands. Advances in Structural Engineer- earthquake loads. ACI Structural Journal 95(5): 590–606.
ing 17(11): 1585–1600. Watanabe F (2007) Design of precast concrete buildings emu-
Im HJ, Park HG and Eom TS (2013) Cyclic loading test for lating monolithic construction. In: Proceedings of the ninth
reinforced-concrete-emulated beam-column connection of Japan-Korea-Taiwan joint seminar on earthquake engineer-
precast concrete moment frame. ACI Structural Journal ing for building structures (SEEBUS 2007), National
110(1): 115–125. Chiao Tung University, Hsinchu, Taiwan, 26–27 October,
Kang THK, Kim W and Shin M (2012) Cyclic testing for pp. 83–92.
seismic design guide of beam-column joints with closely Xue WC and Zhang B (2014) Seismic behavior of hybrid
spaced headed bars. Journal of Earthquake Engineering concrete beam-column connections with composite beams
16(2): 211–230. and cast-in-place columns. ACI Structural Journal 111(3):
617–627.

You might also like