You are on page 1of 92

NX Series(NX700/NX70/NX7)

PLC with Advanced Performance in Compact Size


Advanced Performance in Compact Size, OEMax PLC Series

NX Series, a new family of OEMax PLC, is designed to international


standards so that it can be used globally in a wide variety of markets.

Even diverse requirements of customers can be configured efficiently. NX


PLC can be used for a new facility or system or to dramatically upgrade an
existing one. All of the NX7, NX70, NX700 Series have a full lineup of
diverse modules so that many control system configurations, from
miniature to large size, are possible.

Contents
■ Characteristics of NX Series 3
■ System of PLC Type 4
■ Network Configuration Chart 6
■ Basic Configuration of NX700 10
■ Basic Configuration of NX70 22
■ Special Modules of NX700/NX70 35
Analog Module 36
Special Module 40
Communication and Network Module 48
Field bus 64
■ Configuration Chart of NX7 67
■ Program Device and Software 72
■ External Dimension 79
■ Product Catalog 84

2 I OEMax NX Series
NX Series
NX700 / NX70 / NX7 Series

NX700 Series with Advanced and Integrated Functions


NX700 Series is a new family with dramatically improved functionality, designed for convenience and efficiency in order
to meet and cope with next generation control devices.
-Control Points: Local 1600 points (2048~8192 points including REMOTE))
-Diverse CPU Line-up: CPU700P, CPU700, CPU 750A/B/C/D, etc.
-Memory Capacity: 16K ~ 120K
-Computing Speed: 0.03us ~ 0.4 us
-Internal Points: 2048 ~8192 points
-Data Memory: 2048 ~ 10,240 words

NX70 Series with Expanded Reliability and Extended Configuration


NX70 Series has a similar functions to NX700 but in a more compact size. It is designed to be noise immune and
durable for operation in noisy and hard environments. This results in maximum reliability for customers. New products
are available such as communications modules and high performance specialty modules to accommodate diverse
system configurations.
- Control Points: External I/O 384 points
- Type of Bases: 2,3,5,6,8,10,12 Slot
- Memory Capacity: 9.6K ~ 32K Words
- Computing Speed: 0.2 us ~ 0.4 us
- Internal Points: 2048 ~ 8192 points
- Data Memory: 2048 ~ 6000 Words

NX7 Series with Compact Size and Diverse Functions


NX7 Series is a new product which enables economical system configurations with compact size and integrated special
functions.
- Control Points: External I/O 28~104 point
- Memory Capacity: 9K Words, Communication Port: RS232C/485 dual use 2 Ports.
- Special Functions: Built-in Functions such as: High Speed Counter, Pulse Output, Pulse Catch, PID, Clock Function,
Backup Memory, etc.

OEMAX NX Series I 3
Structure of OEMax Types The OEMax PLC lineup which ranges in size from the
applications. Because of it’s programming (NX-Series,
customers an opportunity to choose the ideal product

Large Scale Control Network Module & Function


�EtherNet (TCP/IP, UDP/IP)
Countermeasure �MW- LINK
NX70
to CIM
�W- LINK
�REMOTE I/O (4 ea, 32 stations)
�DeviceNet (64 node)

Medium Scale Control


Network Diversification CPU70
�384 points
�0.5us
�16k Step
�Comment
NX7 Series Memory

NX7-48
CPU70p1
�Single Unit Type with 48points
�384 points
�Communication 2 port
�0.2us
�9k STEP (Expandable)
Alternative Relay �9.6K words

Sequence
Small Scale Control NX7-28
�Single Unit Type with 28points
�Communication 2 port
�9k STEP (Expandable)

NX7 PLC Single Unit Type NX70 PLC


�Single Unit Block Type Micro-PLC (Compact Size)
�8 Basic Types (4 types with 28 points, 4 types with 48 points)
2 Extension I/O modules (2 Types with 28 points)
�Extendable up to maximum 104 points
�Communication Function: 2 Port(RS232C/ RS485)
�High speed counter and Pulse Output function
�User Software: WinGPC S/W

4 I OEMax NX Series
small NX7 to the medium-size NX700 is scalable in order to be applicable to a wide range of
NX-plus Series), module, and network diversity and compatibility, OEMax PLC provides
for their application.
NX700 Series

Series

CPU750
�384 points
�0.35us
�32K Step
CPU750A CPU750B CPU750C CPU750D
�Comment Memory �2,048 points �2,048 points �8,192 points �8,192 points
�PID Auto Tuning, etc. (Remote inclusive) (Remote inclusive) (Remote inclusive) (Remote inclusive)
�0.35us �0.35us �0.03us(30ns) �0.03us(30ns)
�16K Step �32K Step �60K Step �120K Step
�PID Auto Tuning, etc. �Comment Memory �Comment Memory �Comment Memory
CPU70p2 �PID Auto Tuning, etc. �PID Auto Tuning, etc.
�384 points
�0.2us
�20K words

CPU700 CPU700p
�1,6 ,600 points �2,048 points(Remote inclusive)
�0.4us �0.2us
�16K Step �20K words
�Comment Memory �2Port

Building Block Type NX700 PLC Building Block Type


�Modular small sized PLC (small size) �Modular Medium sized PLC
�CPU Module 4 Types(High Performance: CPU750, �6 Types of CPU Modules
CPU70p2 Standard: CPU70, CPU70p1) -High Performance: CPU750C, CPU750D,
�Backplane: 2, 3, 5, 6, 8, 10, 12 slots -Standard : CPU750A, CPU750B,
�Diverse I/O Modules: High speed Counter (4CH), Pulse -Economical: CPU700, CPU700p)
Output(4CH), Communication Unit(CCU, SCU), �Compatible with Basic/ Expanded Backplane
Network(MW-Link), etc. �Backplane 3, 5, 8, 10, 12 slots
�Maximum 384 points Digital I/O Control �PID Auto Tuning(NX-CPU750), I/O(13 types),
�Medium size PLC functions despite small size Special Modules, etc. (30 types)
�Local maximum 1600 points (Remote I/O - 8,192 points)

OEMAX NX Series I 5
OEMax PLC Network Configuration Diagram A variety of OEMax PLC network options
low-cost serial networks to Ethernet for

A variety of OEMax PLC network options are


EtherNet
available to meet a wide variety of requirements

Large Scale Information Control Network


EtherNet EtherNet

and environments, ranging from small low-cost


serial networks to Ethernet for large scale control Network System, Each Type of
Facility Devices, Building
systems. Management Systems,etc

Specifics of OEMax PLC Network


�OEMax PLC Network enables to configure setting up of
diverse link systems to the environments. Multi Wire-Link Network

�Enables simultaneous executions of Computer Link


and PLC Link so as to collect data from the Computer Multi Drop
or transmit to PLC without disconnection of wiring with
Twist Pair Cable
communication between PLCs.

�Enables to receive or transmit data by the Computer


from PLC so that process time for execution of NX700 Series NX700 Series
MW-Link MW-Link
Computer can be utilized effectively.

�Enables the Remote Programming from PLC or


Medium Scale Control Network

Computer so as to edit or monitor programmings from


other PLCs NX70 Series
Wire-Link Network MW-Link Unit

�Enables mutual information exchanges from the


respective Link Network Systems as well as
communication interface regardless of OEMax PLC Multi Drop
wiring with
types. Twist Pair Cable

�Each Link Unit itself has Self Diagnosis Function(RAS)


NX700 Series Remote I/O Main Station
so that there is no need of monitoring devices for Links MW-Link Unit
and thus economical.

W-Link Master Unit

Multi Drop
Small Scale Network

wiring with
Twist Pair Cable
Remote I/O System

NX700 Series NX70 Series

SLAVE Unit
SLAVE Unit

6 I OEMax NX Series
are available to meet a wide variety of requirements and environments, ranging from small
large scale control systems.
EtherNet Network
EtherNet Corresponds to TCP/IP and UDP/IP, and widely communicable with
computers and the like on the Network (LAN) through interface with 10BASE5
(for N700a), 100BASE-TX, 10BASE-T, 10BASE5 (for NX700) LAN.
★ Corresponding PLC: N700a PLC, N700H PLC, NX700(CPU750) PLC
■ Have functions like Computer Link, Data Transmission, Remote Programming
between other PLCs interfaced with EtherNet Network and computers
NX700 Series Transmission Speed: 100M bit/s(NX700), 10M bit/s(N700a)
EtherNet Unit Maximum No. of NODEs: 100Node/ Segment, Transmission Method: Base Band
No. of Communication Connections: Maximum 8 Connections, Maximum
Distance between Nodes: 2500m~205m

Multi W-Link Network


Large capacity PLC Network System with Twisted-Pair Cable and
economical decentralized (distributed) control system can be
established. (MW-Link Unit)
★ Corresponding PLC: NX700 PLC (CPU750), NX70 PLC (CPU750)
■ Q’y of Data transmissible at a time is 1,020 words and PLC Link
function is 32 stations simultaneously (In addition, L, Ld capacity can
be widely increased)
NX700 Series NX700 Series
■ Distance of transmission can be extended up to 1,200m by speed alteration
MW-Link MW-Link
Transmission Speed: 0.5MBps, 800m Number of Stations: 32 stations/ 1 layer
Layer: 2 Layers Transmission Line: Twisted-Pair Cable

W-Link Network
NX70 Series PLC Network with Twisted-Pair Cable, economical decentralized
MW-Link Unit
control can be established.
★ Corresponding PLC: Supports NX700, NX70 Series (Excluding NX-
CPU700, NX70-CPU70, NX70-CPU70p1)
■ With Multi-Drop wiring of Twisted-Pair Cable, easily established and
high speed-long distance transmission can be achieved.
Transmission Speed: 0.5MBps, 800m Number of Stations: 32 stations/ 1 layer
Layer: 2 layers Transmission Line: Twisted-Pair Cable
NX70 Series NX70 Series

W-Link Unit W-Link Unit Remote I/O System


System for controlling I/O and the like located at long distances and
NX700 Series dispersed areas.
★ Corresponding PLC : Supports Master with NX700 type (excluding NX-CPU700)
MW-Link Unit
Supports Slave with NX700, NX70 type
DeviceNet Network
Transmission Line: Twisted-Pair Cable (700m), 2 line cable (400m)
Number of Stations:32 stations(Slave unit) /Master unit, 4 Master/ CPU unit

DeviceNet Network
Scanner Card for
Computer (PC) As a DeviceNet product which is a Open Network, Device Level
DeviceNet Master Card for
PLC Scanner Card (ISA, PCI, PCMCIA) function is standardized with the Open Architecture and mutually
(Master)
(for NX700)
interfaced with the products that has adopted DeviceNet Profile so as
to enable transmitting and /receiving data.
★ Scanner(Master): N700 PLC, NX700 PLC, Computer Cards (PCI, ISA..)
DeviceNet NX70 Series
(Slave) ■ Slip Type, Micro size (104 x 43 x 52mm)
■ Able to interface between different types of DeviceNet products
Transmission Speed: 0.5MBps No. of Nodes: 64 nodes/ Network
Terminal Type Terminal Type Connector Type
(38 pin) (20 pin) (37 pin) NETWORK Protocol: I/O Slave messaging( Group 2 only)
Robot
DeviceNet(Slave) Inverter ODVA Approval: Granted Standard Test of DeviceNet Conformance

OEMax NX Series I 7
High Tech CPU (WinFPST adopted)
■CPU750A *Refer to the attached

■CPU750B

■CPU750C

NX700 Series
■CPU750D

General Purpose CPU (WinFPST adopted)


■CPU700

General Purpose Plus CPU (WinGPC adopted)


■CPU700P

OEMax NX Series I 9
Basic Configuration of NX700
Basic Configuration and Control I/O Point �Basic configuration and Control I/O Point remain unchanged regardless of CPU Type.
(CPU Type : CPU750A, CPU750B, CPU750C, CPU750D, CPU700, CPU700p)

� 3 Module Type (NX-BASE03) � 5 Module Type (NX-BASE05)

48 points: when configured with 16 points I/O 80 points: when configured with 16 points I/O
192 points: when configured with 64 points I/O 320 points: when configured with 64 points I/O

�8 Module Type (NX-BASE08) �10 Module Type (NX-BASE10)

128 points: when configured with 16 points I/O 160 points: when configured with 16 points I/O
512 points: when configured with 64 points I/O 640 points: when configured with 64 points I/O

�12 Module Type (NX-BASE12)

192 points: when configured with 16 points I/O


768 points: when configured with 64 points I/O

■ Building Block Method with Flexible Unit Combination


�NX700 PLC has 5 types of motherboard and various kinds of I/O units can be freely mounted. (5 types of Motherboard: 3, 5, 8, 10, 12 Module Type)
�I/O Module, Power Source Module, Special Module, and Motherboard are common regardless of CPU type. (6 types of CPU: CPU750A, CPU750B, CPU750C, CPU750D .CPU700, CPU700p)

■ Display of Slot Numbers


Display of slot numbers on the motherboard indicates the number of mountable I/O units and special modules. (ex. 5 slot typed NX-BASE05
motherboard can mount up to 5 I/O units and special modules.)

■ If used as an additional Motherboard


(N. B.)
1)Electricity source unit is required at the additional
Motherboard.
2)CPU unit is disallowed to use at the additional motherboard.
3)One more slot can be used at the additional motherboard
than the motherboard of CPU. (I/O and special module can
Added Cable be mounted at the place of CPU side slot)

■ Basic and additional motherboards can be used reciprocally without distinction.


■ Only one motherboard is allowed to add.

N. B. Units not allowed to use at the added motherboard


CPU unit, CCU unit, CCU+ unit, Remote Slave unit, MW-Link unit, EtherNet unit, DeviceNet Master unit

10 I OEMax NX Series
Caution Commands and programming tools for CPU700p is different from those of CPU750 series
System Configuration
■ Configuration of units that can be mounted
CPU Unit Special Unit I/O unit Peripheral Device
�NX-CPU750A �A/D, D/A, RTD, TC �16 point type �Computer Software
16k Step, 0.35μ
s
�CCU, SCU unit �32 point type - WinFPST S/W(for CPU750, CPU700)
Communication port 2port
�Positioning (1, 2, 3, 4 axis) �64 point type - WinGPC S/W(for CPU700p)
�NX-CPU750B (Open Collector & LineDrive) �Computer Interface Cable
32k Step, 0.35μ
s �High Speed Counter (1/ 2CH) - NX-CBLCPU02,05
Comment Memory �High Performance High
Communication Port 2port
Speed Counter (4CH)
�NX-CPU750C �Pulse Output unit (4CH)
60k Step, 0.03μ
s �Remote I/O SYSTEM
Comment Memory �MW-LINK SYSTEM
Communication Port 2port �EtherNet SYSTEM
�NX-CPU750D �DeviceNet SYSTEM Motherboard
120k Step, 0.03μ
s
Comment Memory �3 slot type
Communication Port 2port �5 slot type
�8slot type
�NX-CPU700
16k Step, 0.4μ
sμs �10slot type
Comment Memory �12 slot type
Communication Port 1port
※ Combined use for Basic/
�NX-CPU700p Additional setup
20k Step, 0.2μ
s
Communication Port 2port
Use WinGPC S/W ※ Display of slot numbers indicates the
number of I/O and special units mounted
Electricity Source (Power) unit ※ CPU module is not necessary when
motherboard is used for extension
�NX-POWER (AC110/220V) purpose and thus one more slot can be
5V 4A, 24V 0.5A used additionally
�NX-PWR220 (AC 220V) 5V 6A
�NX-PWRDC (DC 24V) 5V 5A

■ Restrictions according to the types of units ○ : Usable △ : Usable according to Version × : Unusable

Basic Unit Special Unit Network Unit


Motherboard (3, 5, 8, 10, 12 Module)

Electricity Source (Power supply) Unit

Input Unit

Output Unit

A/D, D/A, RTD, TC Unit

(Open Collector & LineDrive)


Positioning Unit(1,2,3,4 axis)

High Speed Counter Unit (1, 2CH)

Counter Unit (4CH)


High Performance High Speed

Pulse I/O Unit (4CH)

SCU Unit (2CH)

CCU Unit (1CH)

CCU+ Unit (1CH)

(MASTER / SLAVE Unit) *1


REMOTE I/O SYSTEM

Type of Units
(W, W2-Mode)
MW-Link Unit

EtherNet Unit

DeviceNet Master Unit

Computer Software
Mountable
*1
*1

*1

modules
*1

according to CPU Units


Advanced
�NX-CPU750C � NX-CPU750D ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○ ○ ○ ○
Performance CPU
Advanced WinFPST
CPU �NX-CPU750A �NX-CPU750B ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○ ○ ○ ○ S/W

�NX-CPU700 ○ ○ ○ ○ ○ × ○ × × ○ ○ × × × × ○
Prototype
CPU �NX-CPU700p (Plus Type) ○ ○ ○ ○ ○ △ ○ △ △ ○ × ○ △ △ × ○ WinGPC
Note) NX-CPU700p type supports some special functions above OS version 2.0.

※1. Restrictions on mounting Link-system units


Kinds of Unit In case of CPU750A, CPU750B units In case of CPU750C, CPU750D units In case of CPU700 unit In case of CPU700p unit
Can be used up to 5 units including CCU Only 1 unit can be used Unable to use
CCU unit Can be used up to 3 units unit, but only up to 2 ea for PLC link function
(PLC link function is only up Can be used
MW-Link unit (W-mode) Can be used up to 8 units including CCU
to 2 units)
MW-Link unit (W2-mode) unit, but only up to 2 ea for PLC link function
Unable to use Unable to use
EtherNet unit Can be used up to 3 units Can be used up to 8 units
Remote Master unit Master Function: 4 units/ 1 CPU, 32 Slave units/ 1 Master Master 1 unit
CCU+ unit Unable to use Can be used

OEMax NX Series I 11
High Performance CPU Unit (CPU750)
High speed medium-large scaled PLC with Maximum Processing Speed 0.03us(30ns), Capacity of Program 16k~120k,
Sharing same Commands with N700_series and PID Auto Tuning Function and two communication ports mounted. In
addition, large scaled PLC function is compressed into compact size for easy use.

Memory unit
(NX-MEM750A)
�16k STEP(Extended Memory)
�Comment Memory
COM Port Communication Cable
�EPROM Socket TOOL Port
NX-CPU750A NX-CPU750B (Applicable only to CPU750A) NX-CBLCPU02
�16k STEP �32k STEP NX-CBLCPU05
�0.35us �0.35us
�Clock Function �Clock Function C-Language
�Comment Memory BASIC
WinFPST S/W
NX-CPU750C NX-CPU750D
�60k STEP �120k STEP T/P
�0.03us (30ns) �0.03us (30ns)
�Clock Function �Clock Function
�Comment Memory �Comment Memory Computer Computer

■ Characteristics
1. Super high-speed operation speed and sufficient data memory 5. Program edit(insert, delete, correct) function during RUN
CPU TYPE NX700 PLC NX700 PLC NX700 PLC
Item (CPU750A, B) (CPU750C, D) (CPU700) 6. PID Auto tuning function
Operation Command Sequence command 0.35μs 0.03μs 0.4μs Parameter set-up can be done by using command of F355(PID),
(per 1 command) Application command 0.93μs� 0.06μs� Tens of μs� which is an application command
Program capacity 16k,32k step 60k,120kstep 16k step
I/P relay(X) 2,048points 8,192points 2,048points 7. Clock(RTC : Real Time Clock) function basically mounted
O/P relay(Y) 2,048points 8,192points 2,048points Progress of work is programmable by hours and dates with the
Internal relay(R) 4,048points 14,192points 1,568points embedded clock.
Data Capacity

Data register(DT) 6,000words 10,240words 2,048words


File register(FL) 30,717words 32,765words 22,525words 8. RS232C 2 ports mounted on CPU unit
Link relay(L) 1,024points 10,240points 1,024points ∙Interface to programming tool(WinFRST S/W) with TOOL port
Link register(Ld) 128words 8,448words 128words ∙Communication with Touch Panel or computer with COM port
Timer/ Counter(T/C) 1,024points 3,072points 256points
Pulse relay(P) 1,024points 1,024points N/ A 9. COM port supports up to 115kbps
Index register 14words 14words 2words
Program downloading/uploading process can be executed speedily
by drastically improving the communication speed.
2. Scan time 1ms. (when preparing 20,000 Steps)
Time for 1 scan was significantly reduced by adopting parallel system of 10. Corresponds to High speed EtherNet unit, which is an Open Network
operation process and communication process. (when using ∙Enables 100BASE-TX and 10BASE-T (conversion is executed
CPU750C, CPU750D modules) automatically) ; Use UTP cable
∙10BASE5 ; Use Transceiver cable
3. Program memory 120k step (CPU750D) ∙Data transmission speed : 100M bit/s (in case of 100BASE-TX)
∙CPU750A module: 16K STEP(when using extended memory, 32k) ∙Corresponds to TCP/IP and UDP/IP에, able to communicate 8
∙CPU750B module: 32k STEP connections per one unit
∙CPU750C module: 60k STEP
∙CPU750D module: 120k STEP 11. Comment function that enables annotations on the Ladder program
∙There is a separate RAM for Comments so that comments can be
4. Function required in large scaled PLC type was mounted. attached on each interface during programming. Accordingly,
∙1ms(0.001 sec.) unit Timer mounted. conveniently usable when reviewing the Ladder Program or printing.
∙Floating-Point Operation function (trigonometrical function, ∙NX-CPU750D : Basically embedded
numerical index, algebra, square root) ∙NX-CPU750C : Basically embedded
∙Index register added (14 words, IO.ID) ∙NX-CPU750B : Basically embedded
∙PID command mounted ∙NX-CPU750A : Separate Memory unit required.

12 I OEMax NX Series
■ Performance Specification
CPU Type NX-CPU750C
Items NX-CPU750A NX-CPU750B NX-CPU750D
항목
Programming Method/Control Method Relay Symbol Method/ Cyclic Operation Method
Control I/O Point 1,600 point (2,048 points when using REMOTE) 1,600points(8,192points when using REMOTE)
Program Memory Basic 16k step (32k steps when extended) Basic 32k step 750C Basic:60k step 750D:Basic 120k
Operation Speed Sq. command 0.35μs/ 1 command ~ 0.03μs/ 1 command ~
(Rep. Value) Appl. command 0.93μs/ 1 command ~ 0.06μs/ 1 command ~
Command Basic command 95 types 95 types
Type Appl. command 428 types 434 types
External I/P(X) 2,048 points (X0�X127F) 8,192p (X0�X511F)
External O/P(Y) 2,048 points (Y0�Y127F) (Usable as internal relay) 8,192p (Y0�Y511F)
Internal Relay(R) 4,048 points (R0�R252F) 14,192p (R0�R886F)
Interface Data(bit)

Link Relay(L) 2,048 points (L0�L127F) (Usable as internal relay) 10,240p (L0�L639F)
Special Internal Relay (R) 176 points (R9000�R910F)
Memory for Operation

1,024 points(points changeable) 3,072points(points changeable)


Timer/ Counter(T/ C) 1) Timer: 1000 points (T0~T999), 4 types of timers(0.001 Sec. & 3 types) 1) Timer:3000 points (T0�T2999)
2) Counter:24points (C1000~C1023) 2) Counter: 72points (C3000�C3071)
Pulse Relay(P) 1,024 points (P0�P63F)
Data Register(DT) 6,000 words(DT0�DT5999) 10,240words (DT0�DT10239)
Data Memory(Word)

File Register(FL) 14.333 words(30717words with extended memory) 30.717words (FL0~FL30716) 32.765words (FL0�FL32764) x 3bank
Link Register(Ld) 256 words (Ld0�Ld255) (Usable as Data Register) 8,448words (Ld0�Ld8447)
Timer/Counter Set Value Area(SV) 1,024 words (SV0�SV1,023) 3,072words (SV0�SV3,071)
Timer/Counter Exp. Value Area(EV) 1,024 words (EV0�EV1,023) 3,072words (EV0�EV3,071)
Index Register (I0~ID) 14 words (I0�ID) 14words (I0�ID) x 16bank
Error Report Relay(E) N/A 2,048points (E0�E2047)
MCR point 256point
No. of Labels (JMP + LOOP No.) Total 256points
Differential Point Unlimited points
Supplementary Timer (Using F137 Command) Unlimited points (Subtractive 0.01 sec. Timer, 0.01 sec.~ 327.67 sec.)
No. of Step Ladder 1,000 process
No. of Subroutine 100 Subroutine
No. of Interrupt Program 1 program (Timed Interrupt: Time interval range 0.5ms ~ 1.5s .)
Comment Memory Usable(but extended memory is required) Basically embedded (12words x 2,730ea)
Clock Function(Calendar Timer) Basically embedded(year, month, day, hour, min., sec., week)
Shift Register Max. 253points
Self Diagnosis Watchdog Timer, Memory error detection, I/O error detection, Battery error detection, Program grammar check, etc.
Link Function PLC Link, Computer Link, Remote Programming, Data Transmission, Modem Function
PID Auto Tuning PID Auto Tuning Function, Using F355(PID) command
Other Functions User Memory(EPROM & EEPROM execution Function), Programming I/P during RUN, Forced I/O, TEST RUN, Constant Scan function
Memory Backup Approx.10,000 hours, Time saving when using extended memory Approx. 8,000 hours Approx. 3,500 hours

■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited

OEMax NX Series I 13
General Purpose CPU Unit(CPU700)
Processing speed 0.4us, programming capacity 16k Step, basic unit of NX700 PLC usable, convenient functions like
program editing during RUN are available. In addition, Comment Memory is basically embedded for easy use.

EPROM Socket Comm. Cable


(NX-ROM700) NX-CBLCPU02
NX-CBLCPU05

WinFPST S/W
CPU Unit(NX-CPU700)
�16k STEP Basic Memory
�Comment Memory

■ Characteristics
1. High speed processing and large capacity memory 6. Supports the Handy-Loader that BACKs-Up Programs, etc.
Operation speed is 0.4μsec /1command(basic command), NX-CPU700 module can be interfaced with Handy-
equivalent to that of medium sized PLC and program capacity can Loader(CPL5119) that has memory back-up function. This
be extended up to 15,871 STEP. I/O control point can be used up to product(CPL5119) has not only the handy type programming tool
1,600 points maximum. function but also has back-up memory embedded to store ladder
program and data so as to store the program(approx. for 3 days).
2. Forced I/O & Time Chart Monitoring function Accordingly, down loading and up loading of PLC program for this
Forced input and output on PROGRAM MODE(against Y,R,L) and and that facility can be done with this loader only for convenient use.
on RUN MODE(against X,Y,R, L,T,C) can be done. In addition, the
function of control execution status of 16 points at the same time like 7. Add of diverse Command words
time chart of the logic analyzer is provided so as to be used very SET, RST, Data Transfer Instruction(F70~F78), Compressed shift
conveniently when PLC monitoring and debugging. instruction(F98, F99), supplementary timer instruction(F137, STMR)
are added so as to enable more command words to be used.
3. Program Edit Function during RUN
Programs can be corrected, deleted and inserted during RUN without 8. Comment Memory that can attach comments on the Ladder
interruption. (also available on Ladder Symbol mode) Program is basically embedded
RAM 16K Word(12 letters x 2730 ea) is basically embedded to enable
4. Password Function to attach comments on each interface when preparing programs.
This function sets up Password to protect the User Program, that Because that the contents of comment on interfaces and the like are
does not allow access to the program of PLC by anyone except for recorded inside the CPU module, it is convenient to investigate the
the person concerned so as to prevent the trouble of program in contents of instrumentations and the like after several years.
advance and enhance reliability of the system.
9. EPROM Function(User Memory) is optional
5. 100 % compatibility with the existing N-Series PLC EPROM Socket is optional and the user of EPROM can directly
Compatibility of Commands with the existing N-Series PLC purchase and input the Ladder Program. Accordingly, PLC program
can be driven with EPROM.
(EPROM Socket: NX-ROM700, EPROM IC : 27C256-12
equivalent, 2 ea required)

14 I OEMax NX Series
■ Performance Specification
Item Specification
Control Method Cyclic operation method
Operation Speed 0.4㎲/ 1 Command
Program Capacity Max. 15,871 step(16K Step)
Max. I/O Processing Point 1,600 points
Command Basic Command 45 types
Type Application Command 195 types
External I/P (X) 2,048 points (X0~X127F)
External O/P (Y) 2,048 points (Y0~Y127F)
Interface Data(bit)

Internal Relay (R) 1,568 points (R0~R97F)


Link Relay (L) 1,028 points x 2 (L0~L127F)
Special Relay (R)
Memory for Operation

176 points (R9000~R910F)

Timer. Counter (T/C) Total 256 points ① Timer(0.01 sec. Timer, 0.1 sec Timer, 1 sec. Timer), T0~T199
(points changeable) ② Counter(Pre-set type 1 ~ 32,767Counter) , C200~C255
Data Register (DT) 2,048 words (DT0~DT2047)
Data Memory(word)

Link Register (Ld) 128 words x 2 (Ld0~Ld255)


File Register (FL) Max. 22,525 words(FL0~FL22524)
Special Register (DT) 256 words(DT9000~DT9255)
Timer/Counter Set Value Area (SV) 256 words(SV0~SV255)
Timer/Counter Exp. Value Area (EV) 256 words(EV0~EV255)
Index Register (IX, IY) 2 words (IX, IY)
Master Control (MC, MCR) 64 points
Label (JMP, LOOP) 256 points each
Differentials Unlimited
Supplementary Timer (Using F137 command) Points Unlimited (Subtractive 0.01 sec. Timer, 0.01 sec. ~ 327.67 sec.)
Step Ladder 1,000
SUB ROUTINE 100
Interrupt Program 25 ea
Sampling Trace Max. 4,000 ea (1,000 samples) (16 interfaces + 3 words / sample)
Comment Memory Basically embedded, 12 letters x 2,730
① Watchdog Timer ② Memory Error detection ③ I/O error detection
Self Diagnosis ④ Battery error detection ⑤ Program grammar check, etc.
LINK Function ① PLC Link ② Computer Link ③Data Trans. ④REMOTE programming
① EPROM drive function ② Program editing during RUN ③TEST drive
Other Functions
④Forced I/O ⑤Interrupt processing
Memory BACK-UP Lithium Battery Operation Hours: 8,000 Hr
No. of control loops: Max. 32 LOOP, RUN Mode: Forward RUN, Reverse RUN
PID Function
Sampling Time: 0.1~120.0sec., Control Algorithm: PI-D .I-PD (Please refer to the PID Manual for more details.)

■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited

OEMax NX Series I 15
General Purpose CPU Unit(CPU700P) Plus Family Caution Commands and programming tools for CPU700p
is different from those of CPU750 series

Processing Speed 0.2us/1 command, Program capacity 20k words, CPU Unit for plus that can use the basic
unit of NX700 PLC.(Uses WinGPC S/W.)

Comm. Cable
NX-CBLCPU02
NX-CBLCPU05
CPU Unit
(NX-CPU700p)
Computer
WinGPC S/W MMI S/W
T/P, etc.

■ Characteristics
NX-CPU700p is a medium-small sized PLC product intended to provide diverse special modules such as function for high speed processing
of the user program, analog and network module in order to respond suitably to the control environments.
�Control Point 100~1000 point high speed processing for optimal control in the medium scaled control environment
<Basic Command: 0.2us>, productivity improvement intended by embedding the PID function, etc.
�High-speed, large capacity data exchange by direct interface with TOUCH PANNEL is enabled by embedding Da2 channel communication
port and the basic special modules of NX700 can be used.(CCU+ unit, SCU unit, Analog unit, high-speed counter(1CH, 2CH) unit)
�By adopting the diverse I/O modules and detachable terminal block, maintenance/repair and design can be done easily.
Note) High performance special modules(HSC4, Pulse4, Posi 1~4, MW-Link) can be used at above CPU OS Version2.0.

1. Correction of program during RUN 6. Diverse I/O and basic special module support
Correction of program can be done during CPU operation DC24V I/P(16/32/64 points), AC110V I/P, AC220V I/P, Relay
without stopping the system. O/P, TR O/P(16points/32/64points),SSR O/P, A/D, D/A, RTD,
TC, High Speed Counter (1CH, 2CH), CCU+(Comm. leased),
2. PID Processor Embedded SCU(Data Processing Device) can be used.
PID control Logic of 8 loop is embedded so that application of
analog control environment such as temperature/RUN control is 7. Diverse Peripheral Device
exceedingly easy. Equipped with a leased graphic software(WinGPC S/W) for CPU
control, CPU status check and forced I/O, I/O monitoring and
3. Clock(RTC : Real Time Clock) function embedded program download/upload can be done conveniently.
Work process is programmable by hour and day with the
embedded clock. 8. Diverse Communication Function
By providing 2 high speed communication ports, computer link
4. Sufficient program capacity/ back-up function and peripheral devices link without separate module became not
Able to program up to max. 20K words and programs can be only easier but also COM2 port supports user-defined
stored forever by providing ROM Pack module with FLASH communications mode so that bar code reader, Inverter and
back-up method adopted. servo can be linked and controlled by communication.(Binary
communication available)
5. Self Diagnosis Function
Convenient for system error and mal-function detection with the
self diagnosis function.

16 I OEMax NX Series
■ Performance Specification
CPU Type NX-CPU700p
Control Method Program storing, repetitive operation method
External I/O 1,600 points (2,048 points when Remote I/O is used)
Basic Command 28 kinds
Command
Appl. Command 150 kinds
Processing Basic Command 0.2us/step
Speed Appl. Command 0.4~tens of us/step
Program Capacity 20K words
I/O Interface (R) R0.0 ~ R127.15 (2048 points, 128 words)
Link Interface (L) L0.0 ~ L63.15 (1024 points, 64 words)
Internal Interface(M) M0.0 ~ M127.15 (2048 points, 128 words) However, M0.0~ M63.15 can be used as Link Interface
Electrostatic maintenance Interface (K) K0.0 ~ K127.15 (2048 points, 128 words)
Capacity of Special Interface (F F0.0 ~ F15.15 (256 points)
Data Memory
Timer/ Counter 256 channel (timer+counter), set value: 0 ~65535
�Timer: 0.01sec.: CH000 ~ CH063 (64 Ch.), 0.1sec.: CH064 ~ CH255 (192Ch.)
Interface(TC or TIM) �Counter: CH000 ~ CH255 (256 Ch.)

Data Register (W) W0000 ~ W2047, W3072 ~ W5119 (4096 words)


Special Reg.(W,SR) W2560(=SR000)~W3071(=SR511) (512 words)
Clock Function (RTC) year, month, day, hour, minute, second, week
Port 1 Port 1 : RS232C/ RS485 Dual use, 9600/ 19200/ 38400 bps

Communication Port 2 : User Memory(EPROM & EEPROM Drive Function), Program I/P during RUN, Forced I/O, TEST RUN,
Port 2
Function Constant Scan Function

FLASH ROM Backup Approx. 8,000 hours

■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited

OEMax NX Series I 17
Power(Electricity Source)Unit

■ Photo of the Product ■ Performance Specification


Product No. NX-POWER NX-PWR220
I/P Rated Voltage AC110~220V,Free V AC 220V
I/P Rated Current 540mA max 300mA Max
Allowable V. range AC 85 ~ 264V AC 176 � 264V
I/P Power Frequency 47 ~ 63Hz 47 � 63Hz
Rush Current Below20A Below20A
Rated O/P Current 5V 4.0A, 24V 0.5A 5V 6.0A
Weight Approx. 350g Approx. 300g

Product No. NX-PWRDC


I/P Rated Voltage DC 24V
I/P Rated Current 1.7A man
Allowable Voltage Range DC 21.6�26.4V
Power Unit Rated O/P Current 5V 5.0A
Weight Approx. 320g

Motherboard

3 slot Motherboard 5 slot Motherboard 8 slot Motherboard


(NX-BASE03) (NX-BASE05) (NX-BASE08)

10 slot Motherboard 12 slot Motherboard


(NX-BASE10) (NX-BASE12)

Caution �Number of slots of the motherboard is the number of I/O modules and special modules that can be mounted.
�Motherboard of NX700 PLC is used without distinction between basic and extended motherboards.
�Only 1 panel of motherboard can be added to NX700 PLC.

18 I OEMax NX Series
I/P Unit

■ Characteristics
�16 points, 32 points, 64 points I/P Unit
�DC I/P type can use +, -COMMON for all
�Confirmation of operation by LED display
�Photocoupler Insulation for all modules
�Extended user convenience by separating
Terminal blocks (16 point module)

16point TYPE 32point TYPE 64point TYPE


I/P Unit I/P Unit I/P Unit

■ I/P Unit Specification


Input Mode DC Input AC Input
Product Code NX-X16D NX-X32D NX-X64D NX-X16A110 NX-X16A220
Input Point 16 point 32 point 64 point 16 point
Rated I/P Voltage 12 ~ 24V DC 100 ~ 120V AC 200 ~ 240V AC
Operating V. Range 10.2 ~ 26.4V DC 85 ~ 132V AC 170 ~ 264V AC
Max. I/P Current Below 10ms Below 20ms Below 20ms
Operating ON Voltage Min. 9.6V Min. AC 80V Min. AC 160V
Voltage OFF Voltage Max. 2,5V Max. AC 30V Max. AC 50V
Withstand Voltage Photocoupler Insulation
Responding OFF→ON Below 10ms
10ms 이하 10ms 이하 Below 15ms Below 15ms
Time ON→OFF Below 10ms
10ms 이하 10ms 이하 Below 20ms Below 20ms
Internal Operating Current 65mA 130mA 250mA 60mA 60mA
COMMON Method 8 point/ 1COM(Polarity+,- Common) 32point/ 1COM (Polarity+,- Common) 8 point/ 1COM
Operation Display LED Display (but 64 point is transferred and displayed by 32 points each)
External Interface Method Detachable Terminal Block (M3.5) 40P Connector x 1 40P Connector x 2 Detachable Terminal Block(M3.5)

Caution The numbers(1~40) in the below diagram(NX-X32D/ NX-X64D) indicate the numbers
■ External Electrical Schematic Diagram printed on the front side of the product.

NX-X16D NX-X32D NX-X64D NX-X16A110/ NX-X16A220

(Note)

(Ⅰ) (Ⅱ) (Note1) NX-X16A220: AC 200-240V

OEMax NX Series I 19
O/P Unit

■ Characteristics
�16 points, 32 points, 64 points I/P Unit
�Confirmation of operation by LED display
�Photocoupler Insulation for all modules
�Extended user convenience by separating
Terminal blocks (16 point module)

16point TYPE 32point TYPE 64point TYPE


O/P Unit O/P Unit O/P Unit

■ O/P Unit Specification


O/P Mode Transistor(NPN) Output Relay Output SSR Output
Product Code NX-Y16T NX-Y32T NX-Y64T NX-Y16R NX-Y16RV NX-Y32RV NX-Y16SSR
Output Point 16 point 32 point 16 point 16 point 32 point 16 point
Insulation Method Photocoupler Insulation SSR
Rated Load Voltage 12V ~ 24V DC 250V AC, 30V DC 100V~240V AC
Operating Load Voltage Range 10V ~ 30V DC 85 V ~ 264V AC, 10V~30V DC 85V ~ 264V AC
Max. Load Current 0.6A /point 0.4A /point 0.2A /point 2A/ point, 5A/ COM 1A/point, 3A/COM 0.5A/point, 2A/COM
Responding OFF→ON Below 1㎳ Below 10㎳ Below 1㎳
Time ON→OFF Below 1㎳ Below 10㎳ 0.5CYCLE+below 1m
Internal Operating Current(5V) 120㎃ 180㎃ 250㎃ 120㎃ 180㎃ 250㎃
Surge Killer Zener Diode N/A 바리스터 N/A
Fuse Rating N/A 3.0A
COMMON Method 8point/COM 32point/COM 8point/COM 32point/COM 8point/COM
Operation Display LED Display (But 64 point is transferred and displayed by 32 points each)
External Interface Method Detachable Terminal Block M3.5) 40P Connectorx1 40P Connectorx2 Detachable Terminal Block (M3.5) 40P Connectorx1 Detachable Terminal Block M3.5)

Caution The numbers (1~40) in the below diagram(NX-Y32T/ NX-Y64T, NX-Y32RV) indicate the
■ External Electrical Schematic Diagram numbers printed on the front side of the product.

NX-Y16T NX-Y32T/ NX-Y64T NX-Y16R/ NX-Y16RV NX-Y32RV NX-Y16SSR

250VAC
30VDC

Max.
250V AC AC100~240V
30V DC

20 I OEMax NX Series
*Refer to the attached
■ High Performance CPU (WinFPST S/W adopted)
■NX70-CPU750

■ General Purpose CPU (WinFPST S/W adopted)


■NX70-CPU70

NX70 Series
■ General Purpose Plus CPU (WinGPC S/W adopted)
■NX70-CPU70p1

■NX70-CPU70p2

OEMax NX Series I 21
Basic Configuration of NX70
Basic Configuration and Control I/O point �Basic configuration of system and I/O control point are equal regardless of the CPU types.
(CPUTypes: NX70-CPU750, NX70-CPU70, NX70-CPU70p1, NX70-CPU70p2)

■ 2 Module Type ■ 3 Module Type ■ 4 Module Type ■ 5 Module Type

(NX70-BASE02) (NX70-BASE03) (NX70-BASE04) (NX70-BASE05)


32p:16p I/O configured 48p:16p I/O configured 64p:16p I/O configured 80p:16p I/O configured
64p:32p I/O configured 96p:32p I/O configured 128p:32p I/O configured 160p:32p I/O configured

■ 6 Module Type ■ 8 Module Type

(NX70-BASE06) (NX70-BASE08)
96p:16p I/O configured 128p:16p I/O configured
192p:32p I/O configured 256p:32p I/O configured

■ 10 Module Type ■ 12 Module Type

(NX70-BASE10) (NX70-BASE12)
196p:16p I/O configured
160p:16p I/O configured
384p:32p I/O configured
320p:32p I/O configured

■ Free System Configuration: 7 kinds of Motherboard ( 2 slot, 3 slot, 4 slot, 5 slot, 6 slot, 8 slot, 10slot, 12 slot)
�NX70 PLC has 7 kinds of motherboards which can be mounted with each kinds of I/O units freely.
�I/O Module, Power (Electricity source) Module, Special Module and Motherboard are common regardless of CPU Types.
(CPU Type, 4 kinds: NX70-CPU750, CPU70, CPU70p1, CPU70p2)
■ Slot Number Display
�Display of slot numbers on the motherboard indicates the number of mountable I/O units and special modules.
(ex. 12 slot typed NX70-BASE12 motherboard can mount up to 12 I/O units and special modules.)
■ Maximum Control I/O Point 384 Points
�When 12 slot motherboard is used, NX70 PLC is able to use up to max.(192 points for Terminal Block).
�NX70 PLC can not be used with extension. (Only basic motherboard is available.)

■ Module Compatibility between NX70 PLC and N70 PLC


All modules of N70 PLC and NX70 PLC are mutually compatible except for CPU module, motherboard module and power module.
ex1) CPU(CPL9211A..) and Power Module(CPL9631..) can not be mounted on NX70 motherboard (NX70-BASE02~ NX70-BASE12).
ex2) Existing I/O of N70 and Special Module can be mounted on NX70 (NX70-BASE02~ NX70-BASE12).
ex3) CPU of NX70 and Power Module can not be mounted on N70 motherboard (CPL9502 ~ CPL9508).

22 I OEMax NX Series
System Configuration
■ Configuration of units that can be mounted
CPU Unit Special Unit I/O Unit Peripheral Device
�NX70-CPU70 �A/D, D/A, RTD, TC �8p/8pmixed type �Computer Software
16k Step �CCU, SCU unit �16/16p mixed type - WinFPST S/W(for CPU70, CPU750)
Comment Memory �High Speed Counter (1/ 2CH) �16 point type - WinGPC S/W(for CPU70p)
Comm. port 1port
�High Performance High �32 point type �Computer Interface Cable
�NX70-CPU750 Speed Counter (4CH)
32k Step �Pulse Output unit (4CH)
Comment Memory �Positioning Unit
Comm. port 2port �Remote I/O SYSTEM
�W-LINK SYSTEM
�NX70-CPU70P1
9.6k word �MW-LINK SYSTEM
Comm. port 1port �DeviceNet SYSTEM
Motherboard
�NX70-CPU70P2
20k word �2 slot type
Comm. port 2port �3 slot type
�4 slot type
�5 slot type
�6 slot type
Electricity Source
�8 slot type
(Power) unit �10 slot type
� AC Type �12 slot type
1) NX70-POWER1
(110/ 220V, Free Volt)
5V 4.0, 24V 0.3A ※ NX70 Series can not be extended.
2) NX70-POWER2 ※ Display of slot number indicates the number
(110/ 220V, Free Volt) of mountable I/O and Special Units.
5V 4.5A
� DC Type
1) NX70-PWRDC
(DC24V, Input)
Caution Mutually compatible except for the existing power module, CPU module and motherboard of N70 PLC.
5V 4.5A (Ex. N70 I/O module can be used with NX70 motherboard)
(Ex. N70 CPU(CPL9211A) can not be used with NX70 motherboard)

■ Restrictions according to the types of units


Basic Unit Special Unit Network Unit
Kinds of Common Units
(Open Collector & Line Drive)
Positioning Unit(2,4 axes)
(NX70-BASE02, 03, 05, 06, 08, 10, 12)
Motherboard (2,3,5,6, 8,10,12 slot)
( NX70-POWER1, NX70-POWER2 )

( NX70-PWRDC )
DC Power Unit (for all slots)

Input Unit

Output Unit

A/D, D/A, RTD, TC Unit


High Speed Counter Unit (1, 2CH)

Counter Unit (4CH)*2


High Performance High Speed
Pulse O/P Unit (4CH) *2

SCU Unit (2CH)


CCU Unit (1CH)
CCU+ Unit (1CH)

(W-Mode, W2-Mode) *1*2


MW-Link Unit

REMOTE SLAVE Unit) *


W-Link Unit (W-Mode) *1
AC Power Unit (for all slots)

Use
Programming
Tool
*1
*1

Kinds of CPU Units

Advanced NX70-CPU750 WinFPST S/W


○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ × ○ ○ ○
CPU

NX70-CPU70 ○ ○ ○ ○ ○ ○ ○ × × × ○ ○ × ○ × ○ WinFPST S/W


Common
CPU NX70-CPU70p1 ○ ○ ○ ○ ○ ○ ○ × × × ○ × ○ × × ○
WinGPC S/W
NX70-CPU70p2 ○ ○ ○ ○ ○ ○ ○ △ △ △ ○ × ○ ○ △ ○
○ : Usable △ : Usable according to Version × : Unusable
※1. Restriction on mounting Link-family Units
Kinds of Unit In case of NX70-CPU70 module In case of NX70-CPU70p1, NX70-CPU70p2 module In case of NX70-CPU750 module
CCU unit Only 1 unit can be used Unable to use
CCU+ unit Unable to use Can be used Up to 3 units including CCU unit can be
Up to max. 3 units can be used but used. But, PLC Link function is up to 2
Up to 3 units including CCU unit can
W-Link unit (W-Mode) PLC Link function is up to 2 units only units only
be used. But, PLC Link function is up
to 2 units only (NX70-CPU70p1 can not be used)
WM-Link unit Usable according to versions Up to 5 units can be used(but PLC Link
Unable to use
(W-Mode, W2-Mode) (W-mode) function is up to 2 units only)
※2. High performance high-speed counter (NX70-HSC4) and Pulse O/P Unit (NX70-PULSE4), Positioning Unit (NX70-POSI2/4) and MW-Link Units can be used on
NX70-CPU750 Module only.

OEMax NX Series I 23
CPU Unit (NX70-CPU750)
High speed medium-large scaled PLC with Maximum Processing Speed 0.03us, Capacity of Program 32k, Sharing same
Commands with CPU750 Series for N700 and Comment Memory, PID Auto Tuning Function and two communication
ports basically embedded. In addition, large scaled PLC function is compressed into compact size for easy use.

COM Port
TOOL Port
NX-CBLCPU02,05

NX70-CPU750
C-Language
�32k STEP BASIC WinFPST S/W
�0.35us
�Clock Function
�Comment Memory, PID Auto Tuning T/P
�2 Ports (RS232C)
Computer

■ Characteristics
1. Operation Speed and Sufficient Data Memory
CPU Type NX70-CPU750
6. Clock(RTC : Real Time Clock) Function embedded basically
Item NX70-CPU70
Work process is programmable by hour and day with the
Operation Command Sq. Command 0.35μs 0.4μs embedded clock. .
(per 1 Command) Appl. Command 0.93μs� Tens of μs�
Program Capacity 32k step 16k step
7. RS232C 2 ports mounted on CPU Unit
I/P Relay(X) 2,048 p 2,048 p
O/P Relay(Y) 2,048 p 2,048 p
∙Programming tool(WinFPST S/W) interface with TOOL port
Internal Relay(R) 4,048 p 1,568 p ∙Communication with Touch Panel or computer, etc., with COM Port
Data Register(DT) 6,000 words 2,048 words
File Register(FL) 30,717 words 22,525 words 8. Comm. Port supports up to 115kbps
Data Capacity
Link Relay(L) 2,048 p 1,024 p With drastic improvement of communication speed, program
Link Register(Ld) 256 words 128 words downloading/uploading can be executed speedily. (Comment is
Timer/ Counter(T/C) 1,024 p 256 p embedded basically.)
Pulse Relay(P) 1,024 p N/A
Index Register 14 words 2 words 9. Comment Memory that can attach comments on the Ladder
2. Program Memory 32k step Program is basically embedded
Separate RAM for Comment enables attachment of comments
3. Functions required by the Large scaled PLC mounted. on each interface when preparing programs. Accordingly, it can
∙1ms(0.001 sec.) unit Timer mounted. be used conveniently when reviewing the ladder program or after
∙Floating Point Operation Function (Trigonometric Function, printing.
Index, Algebra, Square Root)
∙Index Register added (14 words, I0~ID) 10. Special Units of NX70 PLC can be used
∙PID Command Words Embedded NX70-CPU750 Unit can use Pulse I/O Unit(4CH) and high
performance high sped counter(4CH), positioning unit(2 axis/4
4. Program Edit(insert, delete and correct) Function during RUN axis) and MW-Link unit. (Impossible with the other CPU
modules)
5. PID Auto Tuning Function
Able to set up Parameter with Command Words, which are
Application Command Words F355(PID)

24 I OEMax NX Series
■ Performance Specification
CPU Type NX70-CPU750
Item
Program Method/Control Method Relay Symbol Method/ Cyclic Operation Method
Control I/O Point 384 point
Program Memory Basic 32k step
Sq. Command 0.35μs/ 1 command ~
Operation
Appl. Command 0.93μs/ 1 command ~
Speed
(Rep. Value) Basic Command 95 kinds
Appl. Command 428 kinds
External I/P (X) 2,048point (X0�X127F)
External O/P (Y) 2,048point (Y0�Y127F) (usable as an Internal Relay)
Interface Data(bit)

Internal Relay (R) 4,048point (R0�R252F)


Link Relay (L) 2,048point (L0�L127F) (usable as an Internal Relay)
Special Internal Relay (R) 176point (R9000�R910F)
Memory for Operation

1,024 point(points changeable)


Timer/ Counter (T/C) 1) Timer: 1000 point (T0~T999), 4 kinds of Timers(0.001sec.,0.01sec.,0.1sec.,1.0sec.,)
2) Counter: 24point (C1000~C1023)

Pulse Relay(P) 1,024point (P0~P63F)


Data Memory(word)

Data Register (DT) 6,000word (DT0~DT5999)


File Register (FL) 0.30.717word (FL0~FL30716)
Link Register (Ld) 256word (Ld0~Ld255) (Usable as an DT)
Timer/Counter Set Value Area (SV) 1,024 word (SV0~SV1,023)
Timer/Counter Exp. Value Area (EV) 1,024word (EV0~EV1,023)
Index Register (IO, DO) 14word (I0~ID)
MCR Point 256 point
No. of Labels (JMP + LOOP No.) Total 256 point
Differential Point Unlimited
Supplementary Timer (Using F137 command) Unlimited( Retractive type 0.01sec.Timer, 0.01sec.~327.67sec.)
Step Ladder 1,000 work process
SUB ROUTINE 100 Sub Routine
Interrupt Program 1 Program (On time Interrupt: Time interval can be set up within the range of 0.5ms ~ 1.5s.)
Comment Memory Basically embedded (12letters x 2,730ea)
Clock Function(Calendar timer function) Basically embedded(y, m, d, h, m, s, week)
Shift Register Max. 253 point
Self Diagnosis Watchdog Timer, Memory error detection, I/O error detection, Battery error detection, Program grammar check, etc.
Link Function PLC Link, Computer Link, Remote Programming, Data Transmission, Modem Function
PID Auto Tuning PID Auto Tuning Function, Use F355(PID) command words
Other Functions User Memory(EPROM & EEPROM Drive Function), Program I/P during RUN, Forced I/O, TEST RUN, Constant Scan Function
Memory Back-up Approx. 8,000 hours

■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited

OEMax NX Series I 25
CPU Unit(NX70-CPU70)
Processing Speed 0.4us, Capacity of Program 16k and convenient functions like program editing during RUN included.
In addition, Comment Memory is basically embedded for convenience of users.

Cable
NX-CBLCPU02,05

NX70-CPU70
�16k STEP Basic Memory
WinFPST S/W
�Comment Memory

■ Characteristics
1. High speed processing and large capacity memory 5. 100 % compatibility with the existing N-Series PLC
Operation speed is 0.4μsec /1command(basic command) and
program capacity can be extended up to 15,871 STEP. I/O 6. Supports the Handy-Loader that BACKs-Up Programs, etc.
control point can be used up to 384 points maximum. NX-CPU700 module can be interfaced with Handy-
Loader(CPL5119) that has memory back-up function. This
2. Forced I/O & Time Chart Monitoring function product(CPL5119) has not only the handy type programming tool
Forced input and output on PROGRAM MODE(against Y,R,L) function but also has back-up memory embedded to store
and on RUN MODE(against X,Y,R, L,T,C) can be done. In ladder program and data so as to store the program(approx. for 3
addition, the function of control execution status of 16 points at days). Accordingly, down loading and up loading of PLC
the same time like time chart of the logic analyzer is provided so program for this and that facility can be done with this loader only
as to be used very conveniently when PLC monitoring and for convenient use.
debugging.
7. Add of diverse Command words
3. Program Edit Function during RUN SET, RST, Data Transfer Instruction (F70~F78), Compressed
Programs can be corrected, deleted and inserted during RUN shift instruction(F98, F99), supplementary timer instruction(F137,
without interruption of PLC. (also available on Ladder Symbol STMR) are added so as to enable more command words to be
mode) used.

4. Password Function 8. Comment Memory that can attach comments on the Ladder
This function sets up Password to protect the User Program, that Program is basically embedded
does not allow access to the program of PLC by anyone except RAM for Comment (12 letters x 2730 ea) is basically embedded
for the person concerned so as to prevent the trouble of program to enable to attach comments on each interface when preparing
in advance and enhance reliability of the system. programs. Because that the contents of comment on interfaces
and the like are recorded inside the CPU module, it is convenient
to investigate the contents of instrumentations and the like after
several years..

26 I OEMax NX Series
■ Performance Specification
CPU Type NX70-CPU70
Item
Control Method Cyclic operation method
Operation Speed 0.4㎲/ 1 Command
Program Capacity Max. 15,871 Step (16K Step)
Max. I/O Processing Speed 384 points
Command Basic Command 45 types
Types Application Command 195 types
External I/P (X) 2,048 p (X0~X127F)
External O/P (Y) 2,048 p (Y0~Y127F)
Interface Data(bit)

Internal Relay (R) 1,568 p (R0~R97F)


Link Relay (L) 1,028 p x 2 (L0~L127F)
Special Relay (R) 176 p (R9000~R910F)
Memory for Operation

Timer/ Counter (T/C) Total 256 point ① Timer(0.01sec.Timer, 0.1sec Timer, 1sec. Timer), T0~T199
(Points changeable) ② Counter(Pre-set Type 1 ~ 32,767Counter), C200~C255
Data Register (DT) 2,048words (DT0~DT2047)
Data Memory(word)

Link Register (Ld) 128 words x 2 (Ld0�Ld255)


File Register (FL) 최대 22,525워드(FL0�FL22524)
Special Register (DT) Max. 22,525 words(FL0~FL22524)
Timer/Counter Set Value Area (SV) 256 words(DT9000~DT9255)
Timer/Counter Exp. Value Area (EV) 256 words(SV0~SV255)
Index Register (IX, IY) 2 words (IX, IY)
Master Control (MC, MCR) 64 points
Label (JMP, LOOP) 256 points each
Differentials Unlimited
Supplementary Timer(use F137 Command) Point Unlimited (Retractive Type 0.01sec. Timer, 0.01sec.~327.67sec.)
Step Ladder 1,000
Sub Routine 100
Interrupt Program 25 ea
Sampling Trace Max. 4,000ea (1,000 sample) (16interface + 3word / sample)
Comment Memory Basically embedded, 12letters x 2,730

Self Diagnosis ① Watchdog Timer ② Memory error detection ③ I/O error detection
④ Battery error detection ⑤ Program grammar check
LINK Function ① PLC Link ② Computer Link ③ Data Transmission ④ REMOTE Programming

Other Functions ① Program editing during RUN ②TEST Drive


③ Forced I/O ④ Interrupt Process
Memory BACK-UP Lithium Battery Operation Hour 8,000 Hr

PID Function No. of control loops: Max. 32 LOOP, RUN Mode: Forward RUN, Reverse RUN
Sampling Time: 0.1~120.0sec., Control Algorithm: PI-D ∙I-PD (Please refer to the PID Manual for more details.)

■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited

OEMax NX Series I 27
General Purpose CPU Unit (NX70-CPU70p1) (NX70-CPU70p2) Caution Programming tool of CPU module for plus is WinGPC S/W.

As a small sized PLC, CPU70p has Processing Speed of 0.2us/ 1 Command and 20k Words of Program Capacity (9.6k
words for CPU70p1) so as to easily process programming and intended high speed and high performance.
WinGPC S/W is supported as a programming tool.

Comm. Cable
NX-CBLCPU02,05

NX70-CPU70p1 NX70-CPU70p2
�9.6kword basic memory �20kword basic memory Computer
�1port (RS232C/ RS485) �2port (RS232C/ RS485) WinGPC
�Clock Function

■ Characteristics
1. Processing Speed of Command Words 7. Diverse I/O and basic special module support
With the leased IC for high speed processing, the processing DC24V I/P(16/32/64 points), AC110V I/P, AC220V I/P, Relay O/P,
speed of basic command words reaches 0.2usec/STEP so as to TR O/P(16points/32points),SSR O/P, A/D(4CH), D/A(4CH),
enable high speed processing. RTD(4CH), TC(4CH), High Speed Counter, SCU(Data
Processing Device) can be processed.
2. Correction of Program during RUN
Program can be corrected during CPU drive without interrupting 8. Preparation of Diverse Motherboards (up to 12 slot motherboard)
the system. 2 slot, 3 slot, 5 slot, 6 slot, 8 slot, 10 slot, 12 slot motherboards
each can be selected when configuring the system.
3. Clock(RTC : Real Time Clock) function
With the embedded clock, the work process is programmable by 9. Maximum Control I/O Point 384 Points
hour and by date. (Supports on NX70-CPU70p2 module only) �When 12 slot motherboard is used, NX70 PLC is able to use up
to max. 384 points(192 points for Terminal Block)
4. Sufficient Program Capacity/ Back-up Function �NX70 PLC can not be used with extension.
Able to program up to Max.20k words(NX70-CPU70p2) and
9.6k words(NX70-CPU70p1). With Flash Back-up method 10. RS232C/ RS485, 2 ports mounted (NX70-CPU70p2 Module)
adopted, programs can be stored separately. With 2 CH Communication Ports embedded, direct interface with
computer and Touch Panel enables large quantity data
5. Self Diagnosis Function exchange, and COM2 port supports user-defined
Self Diagnosis function can be used conveniently for detection of communications mode so that bar code reader, Inverter and
system error or malfunction servo can be linked and controlled by communication.(Binary
communication available).
6. WinGPC Software
With WinGPS S/W, which is a leased graphic software for CPU
control, CPU status check and forced I/O, I/O monitoring and
program downloading/uploading can be done conveniently.

28 I OEMax NX Series
■ Performance Specification Caution Programming tool of CPU module for plus is WinGPC S/W.

CPU Type NX70-CPU70p1 NX70-CPU70p2


Control Method Program Storage, Repetitive Operation Method
Digital 384 point (32 point module / 12 Slots)
External I/O
Analog 48 CH (4 CH Module / 12 Slots)
Command Basic Command 28 kinds
Words Appl. Command 150 kinds
Process Basic Command 0.2 μs/step
Speed Appl. Command 1.0 ~ tens of μs/step 0.8 ~ tens of μs/step
Program Capacity 9.6K word 20K word
I/O Interface (R) 2,048points (R0.0 ~ R127.15)
Link Interface(L) 1,024points (L0.0 ~ L63.15)
Internal Interface (M) 2,048points (M0.0 ~ M127.15), (But, usable as Link Interface range with NX70-CPU70p2, 64 word)
Keep during Blackout(停電維持) Interface (K) 2,048points (K0.0 ~ M127.15)
Special Interface (F) 256points (F0.0 ~ F15.15)
256 CH (Timer+Counter), Set-up value: 0 ~65535
Timer/ Counter
Timer: 0.01sec.: CH000~CH063 (64CH), 0.1sec.: CH064~CH255 (192CH)
Interface (TC or TIM)
Counter: CH000 ~ CH255 (256CH)
Data Word(W) 2,048word (W0000 ~ W2047) 4,096word (W0000~ W2047), (W3072~ W5119)
Special Word (W,SR) 512word W2560(=SR000) ~ W3071(=SR511)
Clock Function (RTC) N/A Y, M, D, H, M, S, Week
Port 1 RS232C/ RS485 Combined Use, 4800/ 9600/ 19200/ 38400bps
Comm.
Port 2 N/A RS232C/ RS485 Combined Use, 4800�38400bps
Function
Can support User definition
FLASH ROM Support(Backup) User PROGRAM Back up embedded

�K, W, Counter PV Register maintain during power failure.


�CPU Unit is able to back-up User Program and some specific registers for 48 hours by embedded Super Capacitor when the Battery is off.

■ General Specification
Item Specification
Surrounding Operating Temp. 0 ~ 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min
Insulation Resistance I/O Terminal <-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs (according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited

OEMax NX Series I 29
POWER(Electricity Source) UNIT

■ Photo of the Product ■ Performance Specification


Product No. NX70-POWER1 NX70-POWER2
I/P Rated Voltage/ Current AC 110�220V, Free Voltage / 450mA max
Permissible Voltage Range AC 85 � 264V
I/P PWR Frequency 47 � 63Hz 47 � 63Hz
Inrush Current Below 20A Below 20A
Rated O/P Current(5V) 5V 4.0A 5V 4.5A
Rated O/P Current(24V) 24V 0.3A N/A

Product No. NX70-PWRDC


I/P Rated Voltage/ Current DC 24V / 1.54A max
Permissible Voltage Range DC 21.6�26.4V
Rated O/P Current(5V) 5V 4.5A
Power Unit

Basic Motherboard

2 slot Motherboard 3 slot Motherboard 4 slot Motherboard


(NX70-BASE02) (NX70-BASE03) (NX70-BASE05)

5 slot Motherboard 6 slot Motherboard


(NX70-BASE05) (NX70-BASE06)

8 slot Motherboard 10 slot Motherboard


(NX70-BASE08) (NX70-BASE10)

12 slot Motherboard
(NX70-BASE12)

Caution �Number of slots of the motherboard is the number of I/O modules and special modules that can be mounted.
�Motherboard of NX70 PLC is the Basic motherboard only. (can not be extended)

30 I OEMax NX Series
I/P Unit

■ Photo of the Product


�16 point, 32 point I/P Unit
�DC I/P Type is able to use both +,
-COMMON
�Confirmation of operation by LED Display
�Photocoupler Insulation for all modules
�Connector Type (32 point) can get much
larger I/O numbers per each area. 16 point TYPE 32 point TYPE

■ I/P Unit Specification


I/P Mode DC I/P AC I/P
Product Code NX70-X16D NX70-X16D1 NX70-X32D NX70-X32D1 NX70-X16A110 NX70-X16A220

I/P Point 16 point 32 point 16 point


Rated I/P Voltage 12 ~ 24V DC 24V DC 12 ~ 24V DC 24V DC 100~120V AC 200~240V AC
Operating Voltage Range 10.2 ~ 26.4V DC 21.6~ 26.4V DC 10.2 ~ 26.4V DC 21.6~ 26.4V DC 85~132V AC 170~ 274V AC
Max. Pressure Current Below 10mA Below 20mA
Operating ON Voltage Above 9.6V DC Above 20V DC Above 9.6V DC Above 20V DC Min. above AC 80V Min. above AC 160V
Voltage OFF Voltage Below 2.5V DC Below 7V DC Below 2.5V DC Below 7V DC Max. below AC30V Max. below 50V
I/P Impedance Approx. 3k Ϊ Approx. 15kΪ
Responding OFF→ON Below 10ms Below 1
Time ON→OFF Below 10ms Below 10ms
Internal Operating Current 65mA Approx. 3k 80mA
COMMON Method 8 point/ 100M(Polarity +,- common) 8 point/ 100M
External Interface Method Terminal Block Interface (M3.0).20P 20 pin connector x 2(option : NX70-CBLDC) Terminal Block Interface (M3.0).20P

Caution The numbers (1~20) in the below diagram(NX70-X16D/ NX70-X32D) indicate the numbers
■ External Electrical Schematic Diagram printed on the front side of the product.

NX70-X16D NX70-X32D NX70-X16A110


NX70-X16D1 NX70-X32D1 NX70-X16A220

(Note1)

※ NC : No Connection ※ Careful interfacing is required because that the directions of


(Note 1) I/P voltage of NX70-X60D1 Connector (Ⅰ) and (Ⅱ) is opposite. (Note1) I/P Voltage of NX70-X16A220
(Note 1). I/P voltage of NX70-X32D1 module is leased DC 24V only module is AC 200-240V only.
module is leased DC 24V only

OEMax NX Series I 31
O/P Unit
■ Characteristics
�16 point, 32 point O/P Unit
�Confirmation of operation by LED Display
�Photocoupler Insulation for all modules
�Connector Type (32 point) can get much
larger I/O numbers per each area.

16 point Type 32 point Type


O/P Unit O/P Unit

■ O/P Unit Specification


Transistor O/P
O/P Type Relay O/P SSR O/P
NPN Type PNP Type

Product Code NX70-Y16T NX70-Y32T NX70-Y32P NX70-Y16R NX70-Y16RV NX70-Y16SSR

O/P Point 16 point 32 point 16 points 16 points


Insulation Method Photocoupler SSR
Rated Pressure Voltage 12V~24V DC 12V~24V DC 250V AC, 30V DC 100V~240V AC
Operating Pressure V. Range 10V~30V DC 10V~30V DC 85~264V AC, 10~30V DC 85V~264V AC
Max. Pressure Current 0.6A/point 1A/COM 0.4A/point 1A/COM 1A/point 3A/COM 0.5A/point 2A/COM
Responding OFF→ON Below 1ms Below 10ms Below 1ms
Time
ON→OFF Below 1ms Below 10ms 0.5CYCLE + Below 1ms
Internal Operating Current(5V) 120mA 180mA 120mA 120mA 250mA
Surge Killer Zener Diode N/A Varistor N/A
Fuse Rating N/A 3.0A
COMMON Method 8 point/COM 16p/COM(-) 16p/COM(+) 8 point/COM 3.0A
RUN Display LED Display
External Interface Method Terminal Block(M3.0) 20pin Connectorx2 (Option:NX70-CBLTR) Terminal Block (M3.0)

Caution TTThe numbers (1~20) in the below diagram(NX70-Y32T) indicate the numbers printed
■ External Electrical Schematic Diagram on the front side of the product.

NX70-Y32T NX70-Y16R
NX70-Y16T NX70-Y16RV NX70-Y16SSR
NX70-Y32P

AC100~240V

32 I OEMax NX Series
I/O Combined Unit
■ Characteristics
�NX70-XY16 : DCIN 8 P/ Relay OUT 8 P
�NX70-XY32 : DCIN 16 P/ TR OUT 16 P
�DC I/P Type is able to use both +, -COMMON
�Confirmation of operation by LED Display
�Photocoupler Insulation for all modules

(NX70-XY16) DC IN 8 p (NX70-XY32) DC IN 16 p
Relay OUT 8 p TR OUT 16 p
Combined Unit Combined Unit

■ I/O Combined Unit Specification


Product Name DC Input/RELAY Output Combined Unit DC Input/TR Output Combined Unit
Product Code NX70-XY16 NX70-XY32
I/O Point I/P 8 p (DC IN) O/P 8 p (Relay Out) I/P 16 p (DC IN) O/P 16 p (TR OUT,NPN)
Insulation Method Photocoupler
Rated I/P Voltage 12~24V DC - 12~24V DC -
Operating Voltage Range 10.2~26.4V DC 250V AC, 30V DC 10.2~26.4V DC 10V~30V DC
Max. I/P Current Below 10mA - Below 10mA -
Rated Operating Current/Voltage - 250V AC, 30V DC, 1A/p - 10V~30V DC, 0.4A/p
ON Vol. / ON Cur. Blw 9.6V/Blw 4mA - Blw 9.6V/Blw 4mA -
OFF Vol. / OFF Cur. Blw2.5V/Blw1.5mA - Blw2.5V/Blw1.5mA -
I/P Impedance Approx. 3KΩ - Approx. 3KΩ -
Ext. PWR Supply Unnecessary Blw 24V 200mA Unnecessary -
Responding OFF→ON Below 2.0ms Below 10ms Below 2.0ms Below 10ms
Time ON→OFF Below 2.0ms Below 10ms Below 2.0ms Below 10ms
Internal Operating Voltage(5V) Below 80mA Below 120mA
COMMON Method 8p/1COM(Polarity+,- Common) 8p/1COM 8p/1COM(Polarity+,- Common) 16p/1COM(-), Sync.
I/O Points Occupied 32p Allocation, I/P 16p, O/P 16p 32p Allocation, I/P 16p, O/P 16p
Operation Display LED Display LED Display
External Line Interface Method Terminal Block (M3.0) 220pin ConnectorX2(Option:I/P=NX70-CBLDC,O/P=NX70-CBLTR)

Caution The numbers (1~20) in the below diagram(NX70-XY32)


■ Internal Circuit and External Electrical Schematic Diagram indicate the numbers printed on the front side of the product.
NX70-XY16 NX70-XY32

I/P 16p (DC Input) O/P 16p (TR Output)

OEMax NX Series I 33
34 I OEMax NX Series
NX700 / NX70 Series Special Module
Analog, HSC, Positioning, Communication, Network, Software
Special Function Modules Refer to the attached

NX70 NX700

Analog
I/O

A/D 4CH D/A 2CH D/A 4CH A/D 8CH D/A 4CH D/A 8CH

Temperature
Control
(RTD,TC)

RTD 4CH TC 4CH RTD 8CH RTD 4CH TC 8CH TC 4CH

High Speed
Counter

HSC 1CH HSC 2CH HSC 4CH HSC 1CH HSC 2CH HSC 4CH

Pulse
Control
Position
Control

Pulse 4 / HSC4 POSI2 POSI4 Pulse 4 / HSC4 POSI1 POSI2 POSI3 POSI4

Serial
Communication

CCU CCU + SCU CCU CCU + SCU

Network

MW-LINK MW-LINK EtherNet

Remote
System

Remote Slave Remote Master Remote Slave

Field bus

DeviceNet DeviceNet
Slave Master

OEMax NX Series I 35
Analog I/P Unit(A/D)

�Diverse Data Process Method


1) Application Command〔READ〕reading method Sensor emperature, speed, pressure, Flux
2) I/P Interface reading method

Transducer Q’ty Electricity(Voltage,


Current, Electric Power,
Frequency)

Instrumentation Each type of Sensors

NX700 A/D Unit NX70 A/D Unit


Displacement Sensor MQ Laser Sensor,
DSA Displacement Sensor, etc.
Fill in with Application Command〔WRITE〕.

■ Characteristics
Deviation can be adjusted without separate volume. Especially, 3. DC/DC and Photocoupler Insulation between Channels
conversion speed and resolution that decide diverse analog I/P
range and performance were processed to high speed and high 4. Diverse Data Process Method
accuracy. There are two methods available for Analog Data Process and
Address Designation① by way of Shared Memory
1. NX70 A/D Module ② by way of I/O Interface, which can be conveniently selected to
NX700 A/D Module fit for purposes to use.

2. Drastically improved Resolution 5. High Speed Process


The level of Resolution is max. 0.153mV with Voltage Type and By adopting 16bit A/D Converter, process is done with high
0.519uA with Current Type. (Resolution can be selected in accuracy conversion Data, as well as with the high speed of
accordance with Dip S/W of module) 1.25ms/CH.

■ Performance Specification
NX70-AI8V (Voltage I/P), 8CH NX70-AI8C (Current I/P), 8CH
NX70 Series
NX70-AI4V (Voltage I/P), 4CH NX70-AI4C (Current I/P), 4CH
NX700 Series NX-AI8V (Voltage I/P), 8CH NX-AI8C (Current I/P), 8CH
Analog I/P Range Voltage: 0�10V, 0�5V, ±10V, ±5V Current : 0�20mA, 4�20mA, ±20mA
Digital Conversion 16 BIT Binary with sign (Complement of 2)
Converter Type 16BIT A/D Converter
0~10V(0~32767), (0~20000), (0~16383).. 0~20mA(0~32767), (0~20000), (0~16383)..
Characteristics of I/O *1 0�5V(0�32767), (0~20000), (0~16383).. 4�20mA(0�32767), (0~20000), (0~16383)..
±10V(-32767�32767), (-20000�20000).... ±20mA(-32767~32767), (-20000�20000)....
±5V(-32767�32767), (-20000�20000)....
Max. Resolution Capacity *1 0.153mV, (0.305mV), ........ 0.519uA, (0.61uA), ......
Overall Accuracy ±0.2%/ F.S (25℃) ±0.3%/ F.S (25℃)
Conversion Speed 1.25ms/ CH
External I/P Imped. 500kΩ 249Ω
Absolute Max. I/P Voltage: ±15V, Current: ±30mA Voltage: ±7.5V, Current:±30mA
Insulation Method �Between I/P CH and Internal Circuit: DC/DC Converter, Photocoupler Insulation �Between I/P CH and I/P CH: No Insulation
I/O Points Occupied �I/O Interface Method �Shared Memory Method
Other Functions CH Conversion ON/ OFF Function
Internal Operating Current (5V) �NX70: Below 5V 290mA, External Power 24VDC Unnecessary �NX700: Below5V 270mA
External Interface Method �NX70: 20pin Terminal Block Interface (M3.0) �NX700: 20pin Detachable Terminal Block Interface (M3.5)
*1. Up to high resolution and general resolution can be selected with regard to I/O characteristics and maximum resolution, which can be selected according to Dip S/W under the product.
Stability of conversion speed and conversion data is different according to the resolution. (Refer to the Manual for details.)
*2. It is recommended that the number of D/A modules on the motherboard to be min. below 8 EA. (There is restriction in operating current when the channels operate simultaneously even though there
is no problem in mounting.)

36 I OEMax NX Series
Analog O/P Unit(D/A)

�Diverse Data Process Method Inverter


1) Application Command[WRT〕filling in Method
2) I/P Interface I/P Method

Speed Control of the Motor

Temperature Recorder
�NX700 D/A Unit �NX70 D/A Unit

Read by writing Appl. Command〔READ〕

■ Characteristics
Deviation can be adjusted without separate volume. Especially, 4. Diverse Data Process Method
conversion speed and resolution that decide diverse analog I/P There are two methods available for Analog Data Process and
range and performance were processed to high speed and high Address Designation ① by way of Shared Memory
accuracy. ② by way of I/O Interface, which can be conveniently selected to
1. NX70 D/A Module fit for purposes to use.
NX700 D/A Module 5. High Speed Process
2. DC/DC Insulation between Channels and Internal Circuits By adopting 14bit D/A Converter, process is done with high
accuracy conversion Data, as well as with the high speed of
3. Drastically improved Resolution 1.25ms/CH.
The level of Resolution is max. 0.153mV with Voltage Type and
0.519uA with Current Type.

■ Performance Specification
Voltage O/P Current O/P
Product Code NX70 NX700 NX70 NX700
NX70-AO2V NX70-AO4V NX-AO4V NX-AO8V NX70-AO2C NX70-AO4C NX-AO4C NX-AO8C
Analog O/P ±10V, 0�10V, ±5V, 0�5V 0�20mA, 4�20mA
No. of Analog O/P CH 2 CH 4 CH 4 CH 8 CH 2 CH 4 CH 4 CH 8 CH
Digital Conversion 16 BIT Binary with sign (Complement of 2)
Converter Type 14BIT D/A Converter
1) ±10V (-16,383�16,383), (-10,000�10,000)
Characteristics Of I/O *1 2) 0�10V (0�16,383), (-0�10,000) 1) 0�20mA (0�16,383), (-0�10,000)
3) ±5V (-16,383�16,383), (-10,000�10,000) 2) 4�20mA (0�16,383), (-0�10,000)
4) 0�5V (0�16,383), (-0�10,000)
Max. Resolution Capacity *1 0.6mV (0.305mV, 0.5mV, 1mV) 1.2uA (1.037uA, 1.7uA, 2uA)
Overall Accuracy ±0.2%/ F.S (25℃) ±0.4%/ F.S (25℃)
Conversion Speed 2.5ms / CH
O/P Impedance Below 0.1Ω Above 10Ω
O/P Allowable Load Resistance Above 5KΩ Below 500Ω
Insulation Method �Between O/P CH and Internal Circuit: DC/DC Converter, Photocoupler Insulation �Between O/P CH and O/P CH: No Insulation
I/O Points Occupied �I/O Interface Method, 8CH:128p O/P, 4CH:64p O/P, 2CH:32p O/P �Shard Memory Method:16p
Internal Operating Current(5V) Below 5V 230mA Below 5V
Below5V 380mA Below 5V 500mA
Below 5V 310mA Below 5V 700mA 900mA
*2 (D/A O/P: (D/A O/P: (D/A O/P:
(D/A O/P:80mA/ CH) (D/A O/P: 20mA/ CH) (D/A O/P:
80mA/ CH) 20mA/ CH) 20mA/ CH)
20mA/ CH)
External Interface Method �NX70 : 20 pin Terminal Block Interface (M3.0) �NX700 : 20 pin Detachable Terminal Block Interface (M3.5)
*1. Up to high resolution and general resolution can be selected with regard to I/O characteristics and maximum resolution, which can be selected according to Dip S/W under the product.
Stability of conversion speed and conversion data is different according to the resolution. (Refer to the Manual for details.)
*2. It is recommended that the number of D/A modules on the motherboard to be min. below 8 EA. (There is restriction in operating current when the channels operate simultaneously even though
there is no problem in mounting.)

OEMax NX Series I 37
RTD Unit(Resistance Temperature Detector Unit)
�Diverse Data Process Method
1) Application Command 〔READ〕 reading method
2) I/P Interface reading method

3 Line Type RTD Sensor


(Pt100, JPt100,
Pt200, JPt200,...)

-200~660℃
NX700 RTD Unit NX70 RTD Unit -200~510℃

Fill in with Application Command〔WRITE〕 ※ RTD: Resistance Temperature Detectors

■ Characteristics
High speed and high accuracy process is enabled by adopting 24bit Σ- 4. Diverse Data Process Method
Δ A/D converter and has diverse I/O range and self calibration function. There are two methods available for Analog Data Process and
Address Designation① by way of Shared Memory ② by way of
1. NX70 RTD Module I/O Interface, which can be conveniently selected to fit for
NX700 RTD Module purposes to use.

2. Types of Temperature Sensor 5. Design Specification resistant to NOISE


Temperature Sensor available for use is 3 line typed Platinum Analog & Digital Noise Filter is designed to be attached inside of
sensor.(Pt100, Pt200, Jpt100, Jpt200......) the unit in order to resist interference from the external
environment. ※ RTD: Resistance Temperature Detector Utilize the
3. All Celsius(℃)Data and Fahrenheit(℉) Data can be used principle that resistance value varies according to change
of temperature. Measure voltage by sending rated
Can be selected according to the DIP switch placed under the unit. current to the changing resistance. V=I*R

■ Performance Specification
NX70 NX70-RTD8 (8CH) *to be released NX70-RTD4 (4CH)
Product Code
NX700 NX-RTD8 (8CH) NX-RTD4 (4CH)
RTD Sensor 3-Wire Method
RTD I/P CH Numbers 8 CH 4 CH
Digital Conversion 16 BIT Binary with symbol (Complement of 2)
Converter Type 24BIT Σ-Δ A/D Converter
① Pt100 (α=0.00385, -200�650℃ => -2,000�6,500 ⑤ 300Ω (10mΩ/ BIT)
Characteristics of I/O ② Pt200, Pt500, Pt1000 ⑥ 600Ω (20mΩ/ BIT)
(Applicable Temperature
③ JPt100 (α=0.00385, -200�600℃ => -2,000�6,000) ⑦ 2000Ω (100mΩ/ BIT)
Sensor & Digital O/P)
④ Jpt200, Jpt500, Jpt1000 ⑧ NI100, NI120, CU10
Max. Resolution Capacity 0.1℃, 0.1℉, 10mΩ, 20mΩ
Overall Accuracy ±0.1%/ F.S (25℃)
Conversion Speed 60ms/ CH
External I/P Impedance 10MΩ
Current Source 1mA (Excitation Current)
Insulation Method �Between O/P CH and Internal Circuit: DC/DC Converter, Photocoupler Insulation �Between O/P CH and O/P CH: No Insulation
�I/O Interface Method: 128 p I/P �I/O Interface Method:64 p I/P,
I/O Points Occupied
�Shared Memory Method:16 p I/P �Shared Memory Method:16 p I/P
Internal Operating Current(5V) Internal Power Source Below 5V 290mA Internal Pwr Source Blw 5V 280mA
External Interface Method �NX70 : 20 pin Terminal Block Interface (M3.0) �NX700 : 20 pin Detachable Terminal Block Interface (M3.5)

38 I OEMax NX Series
TC(ThermoCouple) Unit

�Diverse Data Process Method


1) Application Command 〔READ〕 reading method
2) I/P Interface reading method

Sensor Type
B,R,S,N,K,E,J,T,L,U,C,D
+

Temperature range varies


according to Sensor Types
NX700 TC Unit NX70 TC Unit
Fill in with Application Command〔WRITE〕

※ TC: ThermoCouple
■ Characteristics
High speed and high accuracy process is enabled by adopting 24bit Σ- 4. Diverse Data Process Method
Δ A/D converter and has diverse I/O range and self calibration function. There are two methods available for Analog Data Process and
Address Designation; ① by way of Shared Memory ② by way of
1. NX70 TC Module I/O Interface, which can be conveniently selected to fit for
NX700 TC Module purposes to use.

2. Types of Temperature Sensor 5. TC Unit provides Temperature Compensation Function


Temperature Sensor types available for use are B, R, S, N, K, E, Temperature compensation due to difference of temperatures
J, T, L, U, C, D. between the actual measuring point and unit is required when
ThermoCcouple is connected to the Unit. Accordingly, this Unit
3. All Celsius(℃)Data and Fahrenheit(℉) Data can be used
has embedded the temperature sensor in the unit to
Can be selected according to the DIP switch placed under the unit.
compensate this.

■ Performance Specification
NX70 NX70-TC8 (8CH) to be released NX70-TC4(4CH)
Product Code
NX700 NX-TC8 (8CH) NX-TC8 (4CH)
Digital Conversion 16 BIT Binary with symbol (Complement of 2)
TC Input CH 8 CH 4 CH
Converter Type 24BIT Σ-Δ A/D Converter

Characteristics of I/O Type B/ R/ S/ N/ K/ E/ J/ T/ L/ U/ C/ D(Temperature range varies according to sensor types)


(Applicable Temperature ±30mV (1uV/ BIT)
Sensor & Digital O/P) ±60mV (2uV/ BIT) ±78.0mV (10uV/ BIT)

Max. Resolution Capacity 0.1℃, 0.1℉, 10mΩ, 20mΩ


Overall Accuracy ±0.1%/ F.S (25℃)
Conversion Speed 60ms/ CH
External I/P Impedance 10MΩ
Temperature Compensation Sensor 1mA (Excitation Current)
Insulation Method �Between I/P CH and Internal Circuit: DC/DC Converter, Photocoupler Insulation �Between I/P CH and I/P CH: No Insulation
�I/O Interface Method: 128 p I/P �I/O Interface Method:64 p I/P,
I/O Points Occupied
�Shared Memory Method:16 p I/P �Shared Memory Method:16 p I/P
Internal Operating Current(5V) Internal Power Source Below 5V 290mA Internal Power Source Below 5V 280mA
External Interface Method �NX70 : 20 pin Terminal Block Interface (M3.0) �NX700 : 20 pin Detachable Terminal Block Interface (M3.5)

OEMax NX Series I 39
High Speed Counter Unit(HSC1,2)

As a High Speed Counter with 100Kcps high speed response, monitor and data set-up for the contents of counter is simple and easy.
(NX70-HSC1: High speed counter function and simple pulse O/P function, NX70-HSC2, NX-HSC1, NX-HSC2 : High speed counter function only)
2. 100Kcps high speed response and wide value
I/P response of 100kcps enabled. The range of value has 24 bit sign (binary)
and covers -16,777,216~ 16,777,215.

3. Monitoring the contents of counter and data set-up is easy


With shared memory, random data READ and Write can be done against
PLC.

4. Compared O/P, Corresponding O/P, etc., are available (C=P, C>P)


NX700 HSC Unit NX70 HSC Unit Can be used as deceleration or pause signal during motor control.

5. Simplified Pulse O/P enabled (NX70-HSC1 Module only)


■ Characteristics
Pulse O/P for control of pulse motor and servo motor is available and able to
1. Diverse Counter I/P Mode can be selected adjust and two-step converse between max. frequency (40KHZ) and min.
Able to correspond to Phase Difference I/P mode that can count 2-phase frequency(200HZ). Accordingly, simple motor control and positioning control
pulse of encoder, to individual I/P mode which is CW and CCW I/P mode can be done by combination of pulse and servo motor. Time setting for
and to direction discrimination mode. (DIP SWITCH adjustment) conversion from high to low frequency can be done with the external volume
control.
■ Performance Specification
Product NX70 - NX70-HSC2 NX70-HSC1
Code NX700 NX-HSC1 NX-HSC2 -
I/P Point 3p,(INA, INB, PR/INH) 6p, ( INA, INB, PR/INH) x 2 6p, ( INA, INB, RST, INH, ZERO, SUB )
I/P Voltage 5 ~ 24V DC
I/P Spec.
ON Voltage/Current Below 4.5V / Below 3mA
OFF Voltage/Current Above1.5V / Above 0.6mA
No. of Counter Channels 1 CH (UP-DOWN Counter) 2 CH (UP-DOWN Counter) 1 CH (UP-DOWN Counter)
Range of Factors 24 bit sign available(Binary Type) (-16,777,216~16,777,215)
Counter Max. Factor Speed 100Kcps
Spec. I/P Mode 3 mode {Phase Difference I/P(1 multiplying, 4 multiplying), Direction Discrimination: Pulse + Direction, Individual I/P: CW, CCW}
Min. I/P Pulse width 5us (in case of Individual I/P Mode)
Multiplying Function 1 Multiplying,4 Multiplying (in case of Phase Difference I/P Mode)
Insulation Method Photocoupler
O/P Mode Transistor O/P (NPN, Open Collector)
Rated Operating Volt. 5 ~ 24V
Common
Max. Load Current 50mA
Residual Voltage Below 0.5V
Leakage Current Below 10uA
O/P Point 2points (OUT0, OUT1)
O/P Pulse O/P Frequency 200 ~ 40kHz : Duty 50% ± 25%, Variation ±5%
Spec O/P Low Frequency 200 ~ 5kHz
Function N/A
(OUT0, High Frequency 4k ~ 40kHz
OUT1) Conversion Time 100 ~ 500ms
Up/Down Time Below 2us
O/P Point 2p, (C=P, C>P) 4p, (C=P, C>P) x 2 2p, (C=P, C>P)
Control
O/P Common Terminal 2p / COMMON
(C=P, Fuse N/A
C>P)
Response Time OFF → ON :Below10us, ON → OFF :Below100us
I/O Points Occupied 2words(32p, I/P 16p, O/P 16p)
Others Operation Display LED Display
External Interface Method �NX70 :20pin T/Block Interface (Terminal Screw, M3.0) �NX700 : 20 pin Detachable T/Block Interface(T/Screw, M3.5)
High Speed Counter Data �NX-Series: Process Data READ/WRITE with Application Command F150, F151 Command
Read/ Write �NXplus -Series: Process High Speed Counter Data with Application Command READ/WRITE

40 I OEMax NX Series
■ Examples of Application using High Speed Counter(HSC) �NX700 :NX-HSC1 Unit
NX-HSC2 Unit
Example of Counting RPM at Encoder O/P and compare with RPM at Setup �NX70 :NX70-HSC 1Unit
NX70-HSC 2Unit

Inverter
(HSC Function)

Read Data with Appl. Command(READ)

C=P Conversion I/P Motor

M
C>P Pause I/P

O/P at Encoder to be I/P I/P of O/P from


Encoder with HSC Phase Difference I/P Mode
E
Read Data with Appl. Command(READ) Encoder

HSC

Example of configurating controls of motor driver with 2 pulse O/P and by counting RPM of motor �NX70 : NX70 : Applicable to NX70-HSC1 Unit only

(Pulse O/P Function)

Read Data with Appl. Command(READ)


X-Y Table
Motor Driver

Motor
P.OUT 1 F/V I/P

P.OUT 2 R/V I/P

INA
INB
Encoder O/P

Write down Data with Appl. Command(WRT)


HSC

OEMax NX Series I 41
High performance High Speed Counter(4CH) Units are
High Performance High Speed Counter(4CH) �NX700 : NX-CPU750A/ B/ C/ D, 700P Unit
�NX70 : can be used with NX70-CPU750, CPU70 P2 Unit only

HSC 4CH with high speed response of 200Kcps mounted. Range of Coefficient is 32 Bit with functions of HSC 4CH, Interrupt
I/P 8 and comparative O/P 8 point. In addition, unused interface can be used with common I/O 32 points.

High Performance HSC


unit for NX700 PLC Inverter
(NX70-HSC4)

Read Data with Appl. Command(READ)

C=P Conversion I/P motor

M
C>P Pause I/P

O/P at Encoder to be I/P


I/P of O/P from Encoder
with HSC Phase Difference I/P Mode
E
Write down Data with Appl. Command(WRT)
Encoder
High Speed Counter(4CH)
Count RPM at Encoder O/P and compare
For NX70 PLC with RPM at Setup so as to direct Conversion
High Performance HSC Unit and Pause, etc., by Inverter
(NX70-HSC4)

■ Characteristics
1. High Speed Response with HSC 200K count/s 5. Interrupt I/P 8 points embedded
Enabled precision control with embedded 4CH of HSC I/P with Interrupt program can be activated when the Elapsed Value
max. 200kHz. conforms or in accordance with the timing of external I/P signal.
Control with out delay or disorder can be done when any
2. Wide ranged Coefficient Value(32 bit with symbol attached) malfunction occurs at the device operating at high speed.
Coefficient range is with 32 bit sign(binary) that covers the range
of -2,147,483,648 ~ +2,147,483,647. 6. Conventional I/O Function(I/O combined 32 points)
Operates as a 16 IN/16 OUT I/O Combined Unit at the initial
3. I/P Time Constant Function to prevent Noise-related Count stage when operation of mode setup switch or shared memory
due to I/P of Noise setup are not made. I/O of other functions precedes when using
Sensitivity can be changed by using the I/P Time Constant other functions but the part without function allotment can be
Function in order to prevent mis-counting due to noise. used as I/O.
(4, 8, 16, 32 /us)
7. Enables High-Efficiency System Configuration
4. Compared O/P Interface 8 points embedded With one unit of high performance HSC module, HSC, Interrupt,
High performance HSC(4CH) has embedded 8 points of O/P Compared O/P and conventional I/O functions are all mounted
allotted randomly. Fractions of Counter is changeable. Can be so that economic system configuration can be done.
used at change of speed or pause signal when controlling the
motor by inverter. 8. Enables Selection of Diverse Counter I/P Mode
Able to respond to the phase difference I/P mode that can count
2 phase pulse of rotary encode and direction discrimination
mode, and the separate I/P mode that are CW and CCW I/P.

42 I OEMax NX Series
■ Performance Specification
For NX700 PLC For NX70 PLC
Product Code
NX-HSC4 NX70-HCS4
Insulation Method Photocoupler Insulation
Rated I/P Voltage 24V DC
Rated I/P Current Approx. 7.5mA (when 24V DC is used)
I/P Impedance Approx. 3.2 kΩ
Spec. Operating Voltage Range 20.4V DC � 26.4V DC
of Min. ON Vol. / ON Cur. 19.2V / 6mA
I/P Max. OFF Vol./ OFF Cur. 5.0V / 1.5mA
Response OFF → ON Below 1us
Time ON → OFF Below 2us
I/PTime Constant Setup *1 N/A, 4us, 8us, 16us, 32us (2 I/P Unit Setup)
Common Method 16 points/ COM
No. of Counter Channels 4 CH
Coefficient Range 32bit sign attached ( -2,147,483,648 ~ +2,147,483,647 )
Speed of Max. Coefficient *1 200kHz
Counter I/P Mode 3 Mode(Phase difference I/P mode, Direction Discrimination mode: Pulse + Direction, Separate I/P mode : CW, CCW )
Min. I/P Pulse Width *1 2.5us
Multiply Function 1 Multiply, 2 Multiply, 4 Multiply
Others Compared O/P 8 points
Interrupt Point *2 N/A, 1p/Unit, 8p/Unit (according to mode setup switch)
Interrupt Interrupt Process Delay Below 160 us (when using NX-CPU750A, CPU750B)
Below 160 us
below50 us (when using NX-CPU750C, CPU750D)
Insulation Method Photocoupler Insulation
Rated Load Voltage 5V DC � 24V DC
Rated Load Voltage Range 4.75V DC � 26.4V DC
Max. Load Current 0.1A (A11~A18, B11~B14 Terminal Block), 0.1A【Ⅱ】
( A1�A8,
【Ⅱ】B1�B4 Terminal Block),
0.8A (B15~B18 Terminal Block) 0.8A【Ⅱ】
( B5�B8 Terminal Block)
Leakage Current on OFF Below 1uA
O/P
Max. Voltage Drop on ON Below 0.5V
Spec.
Response OFF → ON Below 1us
Time ON → OFF Below 1us
Surge Killer Zener Diode
Common Method 16 p / Common
External Power Voltage 20.4V DC � 26.4V DC
Supply Current(when 24V DC is used) Below 90mA
Counter Compared O/P 8 p (A11 ~ A18 Terminal Block) 8 p【Ⅱ】
( A1 ~ A18 Terminal Block)
External Terminal Block Interface 40 pin Connector x 1 EA 20 pin Connector x 2 EA

*1. The Value is when I/O Time Constant (filter) Setup is not available.
*2. When using interrupt with 1 point/ unit setup, in case of NX700, interrupt from the external I/P terminal block B1(X8) or interrupt program (one of INT16.INT23) from
compared 0 will be activated.

OEMax NX Series I 43
Pulse I/O Unit(4CH)
Pulse I/O Unit(4CH) �NX700 : NX-CPU750A/ B/ C/ D, 700P Unit
�NX70 :can be used on NX70-CPU750, CPU70P2

Have 4LOOP pulse O/P and HSC embedded at the same time together with all functions of high performance HSC (NX-
HSC4)(200Kcps HSC 4CH mounted, coefficient range 32 bit, Interrupt I/P 8 point, Compared O/P 8 point and Common I/O 32
points). In addition, 100KHz pulse O/P 4CH or 40KHz PWM O/P 4CH can be used.

■HSC Function (4CH)


Inverter
Read Data with Appl. Command(READ)

C=P Conversion I/P Motor

M
C>P Pause I/P

For NX700 PLC


High performance Pulse I/O Unit O/P at Encoder to be I/P
(NX-PULSE4)
E
Read Data with Appl. Command(READ)
Encoder
■Pulse O/P Function(4CH)
Read Data with Appl. Command(READ)

Pulse O//P
1)Direction Discrimination
(pulse+direction)
2)Separated O/P(CW, CCW)

Servo & Stepping


PWM O/P Motor
. 30KHz O/P(1Hz Unit) Servo& Stepping
For NX70 PLC . Duty : 0 ~ 100% Motor Drive
High performance Pulse I/O Uni
(NX70-PULSE4)
Write down Data with Appl. Command(WRT)

■ Characteristics
1. Pulse O/P, 100KHz 4CH 6. Compared O/P Interface 8 points embedded
Maximum Pulse O/P is 100kHz and have 2 types of O/P mode Pulse I/O Unit has embedded 8 points of O/P allotted randomly.
(Direction Discrimination O/P: Pulse + Direction, Separate O/P: CW, Fractions of Counter is changeable. Can be used at change of
CCW). O/P frequency can be setup by 1 Hz units and high speed speed or pause signal when controlling the motor by inverter.
process is enabled because that I/P setup can be done with high
speed counter by internal interface of unit. 7. Interrupt I/P 8 points embedded
Interrupt program can be activated when the Elapsed Value
2. PWM O/P, 30KHz 4CH conforms or in accordance with the timing of external I/P signal.
Maximum 30KHz of PWM O/P can be done and Duty ratio can be Control with out delay or disorder can be done when any malfunction
setup by 1 % units from 0 to 100%. occurs at the device operating at high speed.

3. High Speed Counter 200KHz 4CH 8. Conventional I/O Function (I/O combined 32 points)
Precision control is enabled with the embedded 4CH of maximum Operates as a 16 IN/16 OUT I/O Combined Unit at the initial stage
200kHz high speed I/P. when operation of mode setup switch or shared memory setup are
not made. I/O of other functions precedes when using other
4. Wide ranged Coefficient Value(32 bit with symbol attached) functions but the part without function allotment can be used as I/O.
Coefficient range is with 32 bit sign(binary) that covers the range of -
2,147,483,648 ~ +2,147,483,647. 9. Enables High-Efficiency System Configuration
With one unit of Pulse I/O, HSC, Interrupt, Compared O/P and
5. I/P Time Constant Function to prevent Noise-related Count due conventional I/O functions are all mounted so that economic system
to I/P of Noise configuration can be done. .
Sensitivity can be changed by using the I/P Time Constant Function
in order to prevent mis-counting due to noise. (4, 8, 16, 32 /us)

44 I OEMax NX Series
■ Performance Specification
For NX700 PLC For NX70 PLC
Product Code
NX-PULSE4 NX70-PULSE4
Insulation Method Photocoupler Insulation
Rated I/P Voltage 24V DC
Rated I/P Current Approx. 7.5mA (when 24V DC is used)
I/P Impedance Approx. 3.2 kΩ
Spec. Operating Voltage Range 20.4V DC � 26.4V DC
of Min. ON Vol. / ON Cur. 19.2V / 6mA
I/P Max. OFF Vol./ OFF Cur. 5.0V / 1.5mA
Response OFF → ON Below 1us
Time ON → OFF Below 2us
I/PTime Constant Setup *1 N/A, 4us, 8us, 16us, 32us (2 I/P Unit Setup)
Common Method 16 points/ COM
No. of Counter Channels 4 CH
Coefficient Range 32bit sign attached ( -2,147,483,648 ~ +2,147,483,647 )
Speed of Max. Coefficient *1 200kHz
Counter I/P Mode 3 Mode(Phase difference I/P mode, Direction Discrimination mode: Pulse + Direction, Separate I/P mode : CW, CCW )
Min. I/P Pulse Width *1 2.5us
Multiply Function 1 Multiply, 2 Multiply, 4 Multiply
Others Compared O/P 8 points
Interrupt Point *2 N/A, 1p/Unit, 8p/Unit (according to mode setup switch)
Interrupt Interrupt Process Delay Below 160 us (when using NX-CPU750A, CPU750B)
Below 160 us
below50 us (when using NX-CPU750C, CPU750D)
Insulation Method Photocoupler Insulation
Rated Load Voltage 5V DC � 24V DC
Rated Load Voltage Range 4.75V DC � 26.4V DC
Max. Load Current 0.1A (A11~A18, B11~B14 Terminal Block), 0.1A【Ⅱ】
( A1�A8,
【Ⅱ】B1�B4 Terminal Block),
0.8A (B15~B18 Terminal Block) 0.8A【Ⅱ】
( B5�B8 Terminal Block)
Leakage Current on OFF Below 1uA
O/P
Max. Voltage Drop on ON Below 0.5V
Spec.
Response OFF → ON Below 1us
Time ON → OFF Below 1us
Surge Killer Zener Diode
Common Method 16 p / Common
External Power Voltage 20.4V DC � 26.4V DC
Supply Current(when 24V DC is used) Below 90mA
Counter Compared O/P 8 p (A11 ~ A18 Terminal Block) 8 p (A11 ~ A18 Terminal Block)
External Terminal Block Interface 40 pin Connector x 1 EA 20 pin Connector x 2 EA
No. of Channels 4CH(B11 ~ B18 T/B) 4CH (【Ⅱ】B1 � B8 T/B)
Pulse
Max. O/P Frequency *3 100KHz
O/P
O/P Mode 2 Mode (Direction Discrimination O/P: Pulse + Direction, Separate O/P: CW, CCW )
No. of Channels 4CH (B15 . B18 T/B) 4CH (B15 . B18 T/B)
PWM Max. Load Current 0.8 A
O/P Cycle *3 1Hz � 30KHz (1Hz Unit)
Duty *3 0 � 100% (1% Unit)

*1. The Value is when I/O Time Constant (filter) Setup is not available.
*2. When using interrupt with 1 point/ unit setup, in case of NX700, interrupt from the external I/P terminal block B1(X8) or interrupt program (one of INT16.INT23) from
compared 0 will be activated.
*3. At maximum load current and resistance load, there may be distortion at O/P waveform according to load current or type of load.

OEMax NX Series I 45
Positioning Unit

Positioning Unit �NX700 : NX-CPU750A/ B/ C/ D, 700P Unit


�NX70 : can be used on NX70-CPU750, CPU70P2 Unit only.

1 Axis, 2 Axis, 3 Axis, 4 Axis Unit. Enabled high speed, high accuracy positioning with Speed Command Maximum 1Mpps. Have linear
interpolation, circular interpolation function and able to realize smooth activation/pause with s-shaped acceleration/deceleration
function. In addition, real time O/P was enabled by manual pulse generator with pulse generator I/P function.
■ Kinds of Product ■ Characteristics
1. High speed, high accuracy positioning was enabled
withmaximum 1M pulse/s of pulse speed.
2. Multi axis control was enabled by mounting 4 axes in 1unit.
3. Made Tact-Time reduction possible with high speed activation
time (activation time 0.1ms)
Tact-Time can be reduced by selecting high speed activation mode.

2 axis unit
4. Parameter setup was simplified and automatic acceleration
1 axis unit /deceleration was enabled with data setup.
(NX-POSI2)
(NX-POSI1)
(NX70-POSI2)
5. Smooth activation/pause was realized with s-shaped
acceleration/deceleration function
Speed No. of O/P Pulse
(Pulse/s) 100000

Target Speed
5000

Activation Speed
100 t(ms)
Acc/Deceleration Time
3 axis unit 200ms
4 axis unit
(NX-POSI3) (NX-POSI4)
(NX70-POSI4)
6. Able to select Pulse O/P Method (Open Collector or Line Drive)
Able to respond through interface with pulse I/P method drive
(AC/DC servo drive, stepping drive). This positioning unit can
interface with any kind of drive because it can select and use
Open Collector O/P or Line Drive O/P.

7. Real time O/P was enabled by manual pulse generator with pulse
generator I/P function.(Max. 1,000 multiply with Multiply Function)
■ Kinds of Product

1Axis 2Axis 3Axis 4Axis Drive


(Pulse Train I/P TYPE)
�Servo Drive
�Stepping Drive

Motor Motor Motor


�Servo Motor
Motor Motor �Stepping Motor

46 I OEMax NX Series
■ Performance Specification
4Axis Unit 2Axis Unit
3Axis Unit 1Axis Unit
Item (NX-POSI4) (NX-POSI2)
(NX-POSI3) (NX-POSI1)
(NX70-POSI4) (NX70-POSI2)
Occupied I/O Point 128 P (I/P 64P, O/P 64P) 64 P (I/P 32P, O/P 32P)
Mountable Slot Basic Motherboard (extended motherboard)
No. of Control Axes Independent 4 Axes Independent 3 Axes Independent 2 Axes Independent 1 Axes
Positioning Com. Unit Pulse Unit (Increment, Absolute) is commanded by program
Command Com.Range Sign attached 32 bit (-2,147,483,648 ~+2,147,483,647 pulse)
�When Line Drive is used: 1pulse/s ~ 1M pulse/s
Com. Range �When Open Collector is used: 1pulse/s ~ 200K pulse/s
Speed
(setup can be done by 1pps unit)
Command
Acc/Dec. Method Linear Acc/Deceleration, S-shape Acc/Deceleration
Acc/Dec. Time 0�32,767ms
Return to 0 Point speed Speed setup can be done (return speed, search speed change)
Return to 0 point
I/P Terminal Block 0 Point I/P, Near 0 Point I/P
�E point Control(Linear,S-shaped Acc/Deceleration Select) *1
�P point Control(Linear,S-shaped Acc/Deceleration Select) *1
Operation Mode �Return to 0 Function (Linear,S-shaped Acc/Deceleration Select)
�JOG Drive Function (Linear,S-shaped Acc/Deceleration Select) *1
�Pulse Generator I/P Function (Multiply x1, x2, x5, x10, x50, x100, x500, x1000 can be selected)
Activation Time Below 0.1ms
O/P Mode Pulse/ Sign Mode, CW/CCW Mode (transfer by DIP S/W)
Other Functions Deviation Counter Clear Signal O/P Interface
External Power Supply *3 24V DC (21.6 ~ 26.4V DC)

*1. Each E point control and P point control indicate Acc/Deceleration control as shown in the below picture.

Speed
[pulse/s]
Simple Acc/Deceleration
control moving to END point P Point
Control

E Point Multi Step setup enabled acc/deceleration


Control control that setup PASS point repeatedly

Time [ms]
*2. Target speed change during RUN can be made if linear acc/deceleration RUN is selected.
*3. Power is supplied from the external connector at positioning module.

OEMax NX Series I 47
Computer Communication Unit (CCU)
Caution CCU module can not be used with Plus Series.

This is a leased communication unit that enables 1:1 or 1:N two way communication by using Computer and own CCU
protocol, as well as executing computer link function and data transmission function.

Computer

∙MMI S/W
∙(C-language, BASIC)

Touch Panel etc

NX700 CCU Unit NX70 CCU Unit


(NX-CCU) (NX70-CCU) RS232 Cable

* CCU function is available if“COM”ports of CPU750 for NX700 and NX7-CPU750 module are used.

1. Communication between PLC and Computer can be realized 4. Operating status of PLC can be supervised or monitored from Computer
easily and economically Operation status of each kind of Relay(Bit Data) or Register(Word
1:1 or 1:N interface can be achieved with a computer having RS232C Data) can be supervised or Data WRITE(I/P) can be done from the
port without specific interface and regardless of type of the Computer.
computer. READ/ WRITE of data can be done without complex
system configuration. 5. Modem Transmission enabled
Can be used in long-distance communication by utilizing the
2. Communication between PLC↔Computer with SECTOCOL-COM common public lines because this unit responds to HAYES AT
Communication with computer having RS232C port can be used Comment type modem.
according to SECTOCOL-COM format which is a CCU Protocol.
(Example of configuration: %01#RCSX0000IDcr) 6. Any PLC Data configured with NETWORK can function READ/ WRITE
In particular, this unit can display enormous power because that
3. Communication between PLC(CCU) ↔ Display Panel Device computer link function against any PLC, that is interfaced with LINK
(TOUCH PANEL) LOOP(including LINK LOOP1/LINK LOOP2) with the computer linked
There is no problem in interfacing because most of the famous with CCU when PLC is configured in Network, can be used. (for more
display panel devices (HAKKO, DIGITAL, PATLITE, etc.) have details, please refer to the CCU Manual「LC(Layer Control
protocols embedded Command)」.)
■ Configuration of SECTOCOL-COM Protocol
�Summary for Comments and Functions (SETOCOL) ■ Performance Specification
Comment Explanation of contents Item Specification
RCS Interface Information by 1point unit READ Interface RS232C 1port
WCS Interface Information by 1point unit Write
RCP Interface Information by multi point unit READ Transmission Speed 300 /600/ 1200/ 2400/ 4800/ 9600 / 19200bps
WCP Interface Information by multi point unit Write (with DIP switch under CCU Unit)
RCC Interface Information by Word Unit READ Communication Method FULL DUPLEX Method
WCC Interface Information by Word Unit Write
SC Word Unit Preset of Interface Area Activation Method START - STOP Method
RD Data Area READ Transmission Code ASCII
WD Data Area WRITE
STOP BIT : 1bit / 2bit
SD Preset of Data Area
RS PRESET Value Area READ of Timer/Counter Trans. Data Format Parity : EVEN/ ODD
WS PRESET Value Area Write of Timer/Counter Length of Data : 7bit / 8bit
RK PASS Value Area READ of Timer/Counter
WK PASS Value Area Write of Timer/Counter End Point Code: Carriage Return (cr) Fix
MC Register and Unregister of Monitor Interface Data Transmission Sequence By Character Unit transmit from bit 0
MD Register and Unregister of Monitor Data Trans.Unit
Computer From Header (%) to Terminator (cr)
MG Monitoring Start
RR READ of System Register
Link Max. Length of Message Max. 118 letters/ 1 frame ( % ~ up to cr )
WR Write of System Register Data Trans.Unit From Header (?) to Terminator (cr)
RT Status READ of PLC Link Max. Length of Message Max. 240 letters/ 1 frame ( ? ~ up to cr )
RM Remote Control (RUN/ PROG Mode Transfer)
AB Transmission Pause Command Modem Control Hayes Co. AT Command Method, 2400bps

48 I OEMax NX Series
■ Wiring Diagram �Wiring Diagram is different from those of the existing N70, N700 Series.
Caution �Special caution is required because“SG”of Communication port is No. 5.
(Without FLOW Control Method)
CCU (9P) Computer (9P)
Pin No Mnemonic Pin No Mnemonic
1 FG 1 CD(DCD)
2 SD 2 RD
3 RD 3 SD
4 - 4 DTR
5 SG 5 SG
6 - 6 DSR
7 RTS 7 RTS
8 CTS 8 CTS
9 ER 9 RI

■ Computer Link Function


�Operating sequence of Computer Link Function is computer with the computer linked with CCU when PLC is configured in
sends COMMAND to PLC(CCU) and PLC returns RESPONSE Network, can be used.
according to the format of SECTOCOLCOM, which is a own
protocol. In accordance with this sequence(PROTOCOL), �Software is required only at the side of the Computer in order to
through the intermediation of CCU Module, the computer can use the Computer Link Function. (MMI S/W : C-language,
execute communication with PLC so as to be able to obtain or BASIC....) but, PLC(CCU) itself does not require any programs.
provide each kind of PLC information.
�The Command that can be transmitted at one time and the
�With 1:N Function of CCU, this unit can display enormous power response data that can be received at one time is up to 118
because that computer link function against any PLC, that is BYTE.
interfaced with LINK LOOP(including LINK LOOP1/LINK LOOP2)

■ Example of Configuration

1:1 Communication 1:N Communication (When MW-Link Module is used)


CCU Unit
NX700 Series NX700 Series
NX70 Series

Twist Pair Cable

Command Response ※ Specify LINK No. of


%01#RDD.. %01$RD... Transmitter When
configuring MW-LINK
(01~32)

�BASIC �BASIC
�C Language �PLC Data READ COMMAND �N0.6 PLC Data WRITE �C Language
Transmission (%01#RDD...) COMMAND Transmission
RESPONSE Receipt (%01$RD..) (%06#WCCD....)
RESPONSE Receipt
(%06$WCC....)

OEMax NX Series I 49
Computer Communication Unit(CCU+) Caution CCU+ Module can not be used with αseries.

This is a NX-Plus CPU leased Communication unit that enables 1:1 or 1:N Multi-drop communication by using
Computer and own CCU+ protocol, as well as enabling data transmission/receipt up to 250 bite at one time

CCU+ Module
Computer

∙MMI S/W
∙Programming S/W

Touch Panel etc.

NX700 CCU Unit NX70 CCU Unit


(NX-CCU+) (NX70-CCU+) RS232C/ RS485 Cable

■ Characteristics
1. Communication between PLC and Computer can be realized 3. Communication between PLC↔Touch Panel, MMI Device
easily and economically Can communicate with PLC with N-plus (N70 plus, N700plus,
1:1 or 1:N interface can be achieved with RS232C/485 port without NX-CPU700p) protocol embedded in most of MMI Software and
specific interface and regardless of type. READ/ WRITE information Touch Panel, etc.
of data can be collected without complex system configuration.

2. Communication between PLC ↔ Computer to be N plus


Protocol as it is
When CCU+Unit is short of 2 EA of Communication Port provided
by CPU, mount on I/O slot and can be used according to the
format of N-plus(NX-CPU700p, NX70-CPU70p1/2) Protocol.

■ Performance Specification
Item Specification (NX-CCU+) (NX70-CCU+)
Interface RS232C/ RS485, 1 port
Transmission Speed 4800/ 9600/ 19200/ 38400bps (Select according to DSW1, DSW2)
Communication Method Half-Duplex Method
Synchronous Method Polling Method
Transmission Distance When RS232C is used: Max.15m When RS485 is used: Max. 1.2Km
Transmission Code HEX(Binary)
STOP bit: 1bit
Transmission Data Format Parity: No Parity
Length of Data: 8bit
Data Transmission Seq. By word byte unit transmit from lower byte unit
Transmission Unit From DA(Destination Address) to CRC-16 code Byte unit
Max. Length of Message Up to MAX. 250 Byte
Interface with CPU Unit Internal BUS Interface
I/O Allotment Not allotted
Error Check Method CRC-16 method

50 I OEMax NX Series
■ Wiring Diagram
(Without FLOW Control Method)
PLC(CCU+), 9Pin Male Computer (9Pin Female)
Pin No Mnemonic Pin No Mnemonic
FG 1 1 FG
TXD 2 2 RXD
RXD 3 3 TXD
RTS 4 4 DTR
GND 5 5 GND
485- 6 6 DSR
485+ 7 7 RTS
CTS 8 8 CTS
Vcc 9 9 -

■ Computer Link Function


�Operating sequence of Computer Link Function is computer �Software is required only at the side of the Computer in order to
sends COMMAND to PLC(CCU+) and PLC returns RESPONSE use the Computer Link Function.
according to the protocol format of NX70-CPU, NX-CPU700p, (MMI S/W : C-language, BASIC / Programming S/W, etc.)
which is a own protocol. In accordance with this sequence but, PLC(CCU) itself does not require any programs. .
(PROTOCOL), through the intermediation of CCU Module, the
computer can execute communication with PLC so as to be able �The Data that can be transmitted at one time is up to 250 BYTE.
to obtain or provide each kind of PLC information.

■ Example of Configuration The following picture is an example of configuration for N-Plus Series.

1:1 Communication NX-CPU700P 1:N Communication CCU+ Module

CCU+ Module

RS485
RS232C

T/P
Command Response (RS485)
FF002303.. 00FFA30A..

Computer
�PLC Data READ �BASIC (RS485/RS422)
COMMAND �C언어
Transmission
(FF002303...)
RESPONSE Receipt
RS485
(OOFFA30A..)

OEMax NX Series I 51
Serial Communication Unit(SCU)
Data I/O can be done with devices communicating RS485 and RS232C such as Bar Code Reader (RS232C), Network
Inverter(RS485), etc. ASC11 and HEX(Binary) communication can be done with Ladder Program. (SCU Module =
existing SDU Module Function+485 Communication Function)

Read Data with Appl. Command(READ) Network


Servo Drive

Barcode Reader

Network
Inverter
NX700 SCU Unit NX70 SCU Unit
(NX-SCU) (NX70-SCU)
Write down Data with Appl. Command(WRT) Temperature Controll Temperature Controlle

■ Characteristics
1. 2 Channels (RS232C, RS485 Optional) are mounted in the Unit. 4. Enabled Network-building by using RS232C communication
and RS485 communication
2. Data I/O can be executed with simple Sequence Command only. �Enabled Data I/O with RS232 device: Data I/P can be done by
Reading Data from SCU can be executed with PLC Application interface with IDX displayer, measuring instrument, barcode reader
Command[READ] and writing down data into SCU can be and printer, etc
executed with Application Command[WRT]. Because that CPU �Enabled Data I/O by network with RS485 device: Interface with
UNIT and shared memory of SCU will execute after-measures, Temperature Controller, Network Inverter, Network Servo and Network.
there is no need to prepare complex.
5. Can be mounted on PLC slot without limit. Transmission can be
3. As for SCU unit, use was extended by adding RS-485 Network made 500 Byte at one time.
Function on the previously used Function of N-Series SDU.
6. ASCII or HEX(Binary) can be used as means of usable
Transmission Code
■ Performance Specification
Item Specification
Interface RS232C/ RS485, 2 port
To be selected according to DSW1, DSW2
Transmission Speed 1) When RS232C is used: 300/ 600/ 1200/ 4800/ 9600/ 19200/ 38400bps
2) When RS485 is used: 4800/ 9600/ 19200/ 38400bps
Communication Method Half-Duplex Method
Activation Method Supplementary Activation Method( START - STOP method)
Transmission Distance When RS232C is used : 15m(MAX), When RS485 is used: 1.2Km (MAX)
Transmission Code ASCII or HEX(Binary)
STOP Bit 1bit / 2bit
Transmission Data Format Parity or not (even/odd)
Length of Data 7bit / 8bit
Data Transmission Seq. Transmit from Bit 0 by Character Unit
Transmission Unit Message Unit up to end point code(variable length)
Max. Length of Message MAX. 500 Byte/ Frame (end point, start point code inclusive)
Shared Memory Method �In case of NX-Series: READ, WRITE can be done with Application Command F150(READ), F151(WRT)
Interface with CPU Unit
�In case of NXplus Series: READ, WRITE can be done with READ,WRITE
I/O Allotment I/P 16 p, O/P 16 P allotted
End Point(終端) Code Setup Either select from ①cr ②cr+LF ③ETX or setup random code from shared memory
Start Point(始端) Code Start Point Code /or not
End Point Code Cut Transmission/Receipt Mode(control according to sequence command), convenient for printer O/P.
Other Special Control
Soft reset (Control according to sequence command)

52 I OEMax NX Series
■ Wiring Diagram
(Without FLOW Control Method)
RS-232C equipment
SCU (9Pin Female) & Ex. of Wiring
Pin No Mnemonic Mnemonic
1 FG
2 SD RD
3 RD SD
4 - DTR
5 SG SG
6 485- DSR
7 485+ <RS485 Ex. Of Wiring> RTS
8 CTS 485-T/B CTS
9 Vcc 485+T/B -
485-T/B
485+T/B

■ Communication Protocol Send/Receive Function


�Have function to transmit after setting up communication �1:1 system configuration can be made through RS232C terminal
protocol with ladder program through SCU module and analyze block of SCU and also, 1:N interface through RS485
received protocol to process data. However, own communication communication terminal block can be done. Communication
protocol like CPU is not embedded. Master or Slave Function through each port is also available.

■ Example of Configuration

1:1 Communication 1:N Communication


SCU Module SCU Module

PLC

Leased
Controller

Inverter Network Temp. Controller


Servo Drive Bar Code Reader
Inverter

OEMax NX Series I 53
Multi Wire-Link Unit �NX700 : NX-CPU750A/ B/ C/ D, 700P Unit
�NX70 : Can be used with NX70-CPU750, CPU70P2 Units only

Multi function PLC Network Unit up to maximum 32 EA with Twist-Pair Cable. Having W-Mode with generalized W-Link
Function and W2-Mode with large capacity data transmission and data transmission for PLC Link, diverse network solution can
be provided with one kind of module. 2 layer network enabled (PLC Link, Computer Link, Data Transmission, Remote
Programming function).

■ Wire Link Function (W-Mode) �NX700 PLC does not have W-Link Unit

Max. 32 EA Interface
MW-Link Module MW-Link Module MW-Link Module
NX700 Series (W-Mode) (W-Mode) NX700 Series
NX70 Series

Twist Pair Cable Twist Pair Cable

■ Performance Specification
Item Specification
Comm. Method Token Bus Method
Trans. Method BASE-BAND Method
No. of Interface Stations 32 Stations/ Layer, 2 Layer
Trans. Cable Twist Pair Cable(2 line type)
Trans. Distance 800m (Total Extension )
Trans. Speed 0.5Mbps
① PLC Link Function(Max.16 Stations)
② Computer Link Function (Max.32 Stations)
Function/ -> CCU Unit required
No. of Stations ③ Data Trans.Function(Max.32 Stations)
(局數) ④ Remote Programming Function(Max. 32 Stations)

NX70 PLC ⑤ Layer Link


NX700 PLC
MWLINK Unit MWLINK Unit Capacity of PLC Link Link Relay(L) : 1,024 P x 2 *1
(NX-MWLINK) (NX70-MWLINK) (per 1 Unit) Link Register (Ld) : 128word x 2
Interface RS485 Multi-drop
RAS Function Hardware self diagnosis function

■ Characteristics
1. PLC Network can be configured by interfacing up to 4. Enabled Intensified management function by 2 hierarchy
maximum 32 EA with W-Link Unit of N70, N700, NX70, (layers) of W-LINK Unit.
NX700 Series and“W-Mode” of MW-Link Unit. . Up to 3 EA can be mounted at CPU Unit including MW-Link and
CCU. If configured 2 layers with 2 EA of MW-Link mounted,
2. Network that can be easily connected with Twist Pair Cable intensified management of PLC Interfaces in the layers or data
Interfacing uses economical TWISTED-PAIR Cable so as to information can be achieved. .
configure excellent COST Performance PLC NETWORK.
5. TOKEN-BUS Method, Total Extension 800m
3. Computer Link Function can be used when CCU is mounted Since Network type is BUS method, there is no need of wiring in
Computer Link Function can be used with CCU Unit when PLC is LOOP topology and total extension of 800m can be utilized.
configured in Network. (or "COM" Port of CPU Module can be
used.)

54 I OEMax NX Series
■ Wire Link Function (W-Mode) Below picture is an example of NX-CPU750 program.

�PLC Link Function PLC Link


① Mutual control between each PLC or Data sharing can de done
by cyclic transmission of information. With this, interfaces of
other PLC in network and data information can be shared and
this function is indispensable for consecutive and coherent XO LO
( )
LO Y30
( )
progress of work and in the field of PLC network. RO
F0(MV) RO F0(MV)
② This information exchange is executed by Link Relay(L) and Link WX1 Ld1
Ld1 WY1
Register(Ld) in each PLC.
� Link Relay (L) : 1024 P/ Layer
� Link Register (Ld) : 128 words/ Layer Data Transmission
③ Up to 2 layer can be configured by mounting 2 EA of MW-Link
Unit on 1 EA of CPU Unit.
④ This Function is available up to 16 EA per Layer.

�Data Transmission Function RO


F145(SEND)
RO
F146(RECV)
DT 0 WR 0
This Function is to collectively send/receive each kind of interfaces DT 100 DT 0
FL 0 K0
between PLCs or data information in large quantity on PLC K0 WY 6

NETWORK which is interfaced with MW-Link. Additionally, this


function controls data send/receive with Ladder Command (F145,
F146), which is a User Program of PLC. This Function is available
up to 32 EA per each Layer. �Remote Programming Function
① Programming can be done with whatever PLC on PLC
�Computer Link Function
NETWORK interfaced with MW-Link Unit. Accordingly, edit of
①This Function is to monitor or READ/WRITE interfaces of each
program (correct, delete, add) or READ/ WRITE of data to other
PLC or data information configured on PLC NETWORK when
PLC through programming device (WinFPST S/W) can be
mounted CCU Unit is interfaced with Computer on PLC
executed.
NETWORK interfaced with MW-Link Unit.
② In particular, this function is very convenient in operating PLC on
② This Function requires a separate CCU Unit and executes
the Network without moving programming device.
program in C-Language or BASIC Language, utilizing
③ This Function is available up to 32 EA per each Layer.
SECTOCOL which is a leased protocol of CCU.
③ This Function is available up to 32 EA per each Layer. .

No. 5 PLC No. 6PLC No. 7 PLC No. 9 PLC

Remote Interface with CCU


Interface with up to Computer Link
Programming
Max. 32 EA
C-Language
WinFPST
BASIC
S/W Ladder Program Data READ of NO.5 PLC
For NO.9 PLC COMMAND Trans(%05#RDD.....)
RESPONSE Rec.(%05$WRDD...)

OEMax NX Series I 55
■ Wire Link Function (W2-Mode) MW-Link Unit W2 Mode can be used with
�NX700: NX-CPU750A/ B/ C/ D Unit
■ Configuration Diagram �NX70: NX70-CPU750 Unit

Max.Interface 32 EA

MW-Link Module MW-Link Module


(W2-Mode) MW-Link Module NX700 Series
NX700 Series NX70 Series (W2-Mode) (W2-Mode)

Twist-Pair Cable Twist-Pair Cable

■ Performance Specification
Item Specification (W2-Mode)
Communication Method Token-Bus Method
Transmission Method BASE-BAND Method
No. of Interface Stations 32 Station/ Layer, 2 Layer
Transmission Cable Twist-Pair Cable (2 line type)
Trans. 250Kbps setup 1200m (Total extension)
Distance 500Kbps setup 800m (Total extension)
Transmission Speed 500 Kbps / 250 Kbps
① PLC Link Function (Max. 32 stations)
② Computer Link Function (Max.32 Stations) -> CCU Unit required
Function/No. of Stations ③ Data Trans.Function(Max.32 Stations), 1,020 words/1 Command
④ Remote Programming Function(Max. 32 Stations)
⑤ Layer Link(2 Layer with interface up to 2 EA of MW-Link per 1 CPU)
PLC Link Capacity Link Relay(L) : 4,096 points x 2
(per 1 Unit) Link Register(Ld) : 4,096 words x 2
Interface RS485 Multi-drop
RAS Function Hardware self diagnosis function

■ Characteristics
1. PLC Network up to Maximum 32 EA can be configured with 4. Computer Link Function can be used when CCU is mounted
MW-LINK Unit of NX70, NX700 PLC. Computer Link Function can be used with CCU Unit when PLC
Network is configured. (or "COM"Port of CPU Module can be
2. Large Capacity Data Transmission enabled (1,020 words/ 1 used as well.)
Command)
The capacity of Data to be transmitted by Data Transmission 5. Transmission Cable can be easily connected with Twisted-
COMMAND [F145(SEND)] [F146(RECV)]is drastically extended Pair Cable..
up to 1,020 words per 1 Command so as to improve
inconvenient problems in the existing W-Link Function. 6. Transmission Distance can be extended. (up to 1,200m)
(Capacity of transmission with the existing W-LINK was up to 16 Interface and communicate up to 1,200m according to change
words per 1 command) of Transmission Speed. (In case of 250Kbps, up to 1,200m)

3. Drastic Improvement in PLC Link Function (PLC Link 32 Stations, 7. Enabled Intensified management function by 2 hierarchy
Extension of Link Capacity) (layers) of MW-LINK .
Up to 32 EA can be set up when PLC Link Function is used and Up to 3 EA can be mounted on CPU Unit including MW-Link
in particular, PLC Link capacity is drastically extended. (L: 4,096 and CCU. If configured 2 layers with 2 EA of MW-Link mounted,
points, Ld: 4,096 words) Link Relay (L) and Link Register (Ld) intensified management of PLC Interfaces in the layers or data
Area can be set up with Ladder Program and WinFPST 2.24 S/W. information can be achieved. (Up to 8 EA for NX-CPU750C and
NX-CPU750D Unit)

56 I OEMax NX Series
■ Wire Link Function (W2-Mode) Below picture is an example of NX-CPU750B program

�PLC Link Function PLC Link


① Mutual control between each PLC or Data sharing can de done
by cyclic transmission of information. With this, interfaces of
other PLC in network and data information can be shared and
this function is indispensable for consecutive and coherent XO LO
( )
LO YO
( )
progress of work and in the field of PLC network. RO
F0(MV)
RO
F0(MV)
② This information exchange is executed by Link Relay(L) and Link WX1 Ld1
Ld1 WY1
Register(Ld) in each PLC.
� Link Relay (L) : 4096 P/ Layer
� Link Register (Ld) : 4096 words/ Layer Data Transmission
③ Up to 2 layer can be configured by mounting 2 EA of MW-Link
Unit on 1 EA of CPU Unit.
④ This Function is available up to 32 EA per Layer.

�Data Transmission Function RO


F145(SEND)
RO
F146(RECV)
DT 0 WR 0
This Function is to collectively send/receive each kind of interfaces DT 100 DT 100
FL 0 K0
between PLCs or data information in large quantity on PLC K0 WY 0

NETWORK which is interfaced with MW-Link. Additionally, this


function controls data send/receive with Ladder Command (F145,
F146), which is a User Program of PLC.(1,020 words can be
transmitted with 1 Command) This Function is available up to 32 EA �Remote Programming Function
per each Layer. ① Programming can be done with whatever PLC on PLC
NETWORK interfaced with MW-Link Unit. Accordingly, edit of
�Computer Link Function
program (correct, delete, add) or READ/ WRITE of data to other
① This Function is to monitor or READ/WRITE interfaces of each
PLC through WinFPST S/W can be executed.
PLC or data information configured on PLC NETWORK when
② In particular, this function is very convenient in operating PLC on
mounted CCU Unit is interfaced with Computer on PLC
the Network without moving programming device.
NETWORK interfaced with MW-Link Unit.
③This Function is available up to 32 EA per each Layer.
② This Function requires a separate CCU Unit and executes
program in C-Language or BASIC Language, utilizing
SECTOCOL which is a leased protocol of CCU. With this
function, up to maximum 32 EA of PLC interfaced with MW Link
Unit can be controlled from the Computer.“COM”
( Port of CPU
can be used as well))
③ This Function is available up to 32 EA per each Layer

No. 5 PLC No. 6PLC No. 7 PLC No. 9 PLC

Remote Interface with CCU


Interface with up to Computer Link
Programming
Max. 32 EA
C-Language
WinFPST
BASIC
S/W Ladder Program Data READ of NO.5 PLC
For NO.9 PLC COMMAND Trans(%05#RDD.....)
RESPONSE Rec.(%05$WRDD...)

OEMax NX Series I 57
Remote I/O System �Remote system can be used with NX-CPU750A/B/C/D, 700P Units only

I/O Information can be exchanged with 2 line wiring to Remote Control System
2 Channel Wiring per 1 Master Unit enabled so as to effectively handle the dispersed I/O Devices.
(32 Units of Slave Units per 1 Master Unit can be interfaced)

REMOTE I/O Master Module REMOTE I/O Slave Module


REMOTE I/O Slave Module
(NX-MASTER) (NX70-SLAVE)
(NX-SLAVE)

NX-MASTER
Base Station B.Station : MASTER Unit
L.Station : Slave Unit

Easy wiring with Up to Max. 32


Twisted-Pair L.S. can be
Cable of RS485 interfaced per 1
Master

L.S L.S L.S ■Solenoid Valve that can be interfaced

NX70 Series NX70 Series

SMC(Co.) CKD(Co.) 小�井 Manuf.(Co.)


Slave Unit Slave Unit

L.S L.S L.S

NX700 Series NX70 Series NX700 Series NX70 Series

Slave Unit Slave Unit Slave Unit Slave Unit

58 I OEMax NX Series
■ Characteristics ■ Performance Specification
1. Remote Control of I/O Information with 2 Channel Wiring Item Specification
For wiring convenience, transmission line can respond to up Communication Method 2 Line type Half-Duplex
to 2 channels per 1 Master Unit. In addition, 1 CPU can Activation Method Supplementary (調步) Activation Method
Transmission Line Twisted-Pair Cable (VCTF Cable)
control I/O of maximum 8 CH because 1CPU can mount up
Transmission Distance Total extension 700m
to 4 Master units. Designing the wiring route can be easily
Transmission Speed 0.5Mbps
executed because layout can be done freely. No. of MASTER 4 EA/ CPU 1 EA
No. of SLAVE Max. 32 Stations (per 1 Master Unit)
2. High Speed, Long Distance Transmission �Max. 1,024 P (per 1 Master Unit)
Transmission Speed of 0.5Mbps, total extension can be Control I/O Point �Max. 2,048 P (per 1 CPU Unit)
transmitted up to 700m. 2 line type can be used for cable ※CPU750C, D Module can control up to 8,192P
wiring which is economical. Interface RS485 (Multi-drop ), 2Port
Trans. Error Check CRC Method
3. Maximum 1,024 Point I/O Control per 1 unit of Master Module Combined Use of Products NX70, NX700 SLAVE Unit

(CPU750A, CPU750B)
Maximum 4,096 Point I/O Control per 1 unit of Master
Module (CPU750C, CPU750D)
■ Pointer of REMOTE I/O System
Maximum 1,024 point I/O Control can be achieved because 1
Master Unit can interface 32 EA of Local Stations (Slave �REMOTE I/O System is a system that can control dispersed I/O
Unit). (But, CPU750C, CPU750D Module can control up to with 2 line type cable.
8,192 point per 1 Unit of CPU) �Up to 4 wiring routes can be selected so as to be able to respond
to the complex layout of local stations.
�This Network is recommended when you want to place I/O at this
■ Product Configuration Summary or that place, like when you install control box at a remote location.
Type of Product Mounting Method PLC Product No. (Use of extended Motherboard is recommended when high speed
REMOTE I/O Mount on Basic, Extended process is required.)
NX700 NX-MASTER
MASTER Unit Motherboard to use (up to 4 units)
REMOTE I/O Mount on the existing CPU Unit NX700 NX-SLAVE
SLAVE Unit of Basic Motherboard NX70 NX70-SLAVE

OEMax NX Series I 59
EtherNet System
■ Characteristics
�Ethernet System is a leased Open Network System for CPU750 of NX700.
�This is a Communication Unit to interface NX700 PLC with Ethernet (100BASE -TX,
10BASE-T, 10BASE5), according to TCP/IP and UDP/IP.
�Maximum 8 portion of connection communication can be achieved with 1EA so as to be
able to interface with multiple opposite NODE.
�When interfaced with LAN by using Ethernet Unit of NX700, Computer Link Function, Data
Transmission Function, Remote Programming and Permeable Communication Function
can be used between other PLC on the Network(LAN) and Computer at transmission speed
of maximum 100M bit/s.
�When interfaced with LAN by using Ethernet Unit of NX700, programming at
Computer(WinFPST S/W)interfaced with LAN Network can be done so that programming
EtherNet Unit
edit can be done from anywhere.(Remote Programming)
�Communication Setup can be done easily by using "Control Configurator ET" which is a
Setup software. Accordingly, Communication Setup being executed on Ladder Program
■ Network Configuration Diagram can be used easily by utilizing this software.

Ethernet Unit

Remote
Programming WinFPST S/W Computer Link

Ethernet LAN Ethernet LAN

Router Computer Link


Router

Ethernet LAN Permeable Comm

Ethernet LAN

W-Link Unit

MW-Link Unit Data Transmission

Ethernet Unit

MW-Link Network(W2Mode) W-Link Network(WMode)

MW-Link Unit MW-Link Unit


W-Link Unit

60 I OEMax NX Series
■ Characteristics ■ Performance Specification
■ Corresponds to TCP/IP and UDP/IP Item Specification
Corresponds to 2 Protocols(TCP/IP and UDP/IP) so as to be able to I/O Occupancy Point 32SX/ 32SY ※1
communicate widely with computer and the like on Network(LAN). Mountable up to 3 units on the basic motherboard
Location of Mount/ (including W@-Mode of MW-Link Unit)
■ 8 Connection Communication with 1 EA Restriction on number of
units �When CPU750A, CPU750B are used: 3 EA
Maximum 8 portion of connection communication can be achieved
�When CPU750C, CPU750D are used: 8 EA
with 1 EA so as to be able to interface with multiple opposite NODE
�Computer Link: Max. 2K Byte
■ Corresponds to 3 kinds of Communication Interface Communication Function
�Data Transmission: Max.1020 words
Corresponds to 3 kinds of Communication Interface(100BASE-TX, �Remote Programming ※2
10BASE-T and 10BASE5). (Only one kind of Interface can be used). �Permeable Communication
1) 100BASE-TX and 10BASE-T: Use UTP Cable (switch transfer) NO. of Comm. System Connection Max. 3 Connection ※3
2) 10BASE5: Use Transceiver Cable Connections Connection Max. 8 Connection
Buffer for Permeable For Transmit. Setup on ex-factory: (1k word /1 Connection)×3
■ Supports Diverse Communication Function
Communication ※3 For Receive Setup on ex-factory: (1k word /1 Connection)×3
Supports SECTOCOL Communication Function (Computer Link
and Data Transmission) that can communicate between PLC NX ※1. Setup of「0E」can be done by use of WinFRST S/W.
※2. LAN Circuit pass Interface is not supported at "Configurator ET" setup S/W.
Series and Permeable Communication Function that can ※3. System Connection is used only with a computer interfaced with LAN circuit by using
communicate with General Purpose Devices like Computer. WinFPST S/W.
※4. Send/Receive combined 6K word can be randomly assigned to 8 connections.
1) Computer Link Function
�I/O Interface, contents of Register and contents of Program of PLC ■ Transmission Specification
interfaced with remote Computer or Work Station can be freely READ/Write.
Item 100BASE-TX 10BASE-T 10BASE5
�Maximum length of message for 1 frame is 2k Byte.
Data Trans. Speed 100M bit/s 10M bit/s 10M bit/s
2) Remote Programming Function Trans. Method Base Band
�With WinFPST S/W, which is a SAMSUNG PLC Software Tool, Max. Length of Segment 100m 500m
programming edit(insert, delete, correct)or monitoring at PLC from Max. Distance between Nodes 205m 500m 2,500m
remote Computer through LAN Network can be done. Communication Cable UTP Cable Transceiver Cable
Transceiver Cable 50m
3) Data Transmission Function
Ma. NO. of Nodes 100 Node/Segment
�Following execution of SEND/RECV Command of PLC, exchange of
Node Interval Integer Multiple of 2.5m
I/O(Interface) and Register Information between Computer interfaced
with Ethernet Unit or Work Station and PLC can be achieved

SEND Command WRITE with Register of the opposite Node � Interface of Network
RECV Command READ with Register of the opposite Node (1) 100BASE-TX / 10BASE-T (T)

4) General Purpose Communication by Permeable


Communication Function enabled
�Permeable Communication can be achieved between PLC interfaced AUI
with Ethernet Unit and Computer or Work Station can be achieved. Not in Use.
�SEND/RECV Data Storage and Read in PLC is executed by UTP Cable
SEND/RECV Buffer of Shared Memory inside NX-EtherNet Module. T
100BASE-TX �
SEND/RECV requests and the like are executed by Bit ON/OFF at 12V
10BASE-T
Connector Not in Use.
Shared Memory Handshake Area.

■ Simple Communication Setup


Communication Setup can be done easily by using "Control (2) 100BASE5 (AUI)
Configurator ET" which is a Setup software.
�Communication Setup being executed on Ladder Program can be Retainer
Check if pressed
easily set up by utilizing this software. downward
�The existing Ladder Program setup can be used by conversion of
Mode Switch. (Auto Connection Function) AUI 10BASE5 �
(AUI) Connector
■ Perfect Self Diagnosis Function Transceiver Cable
T 12V DC
Occurrence of mal-function can be easily dealt with according to (below1A)
the following Self Diagnosis Function. 12V External Power Supply
�Hardware under transmission and communication status check Terminal Block
function.
�Hardware and communication status check function followed by
Test Mode execution.
�Error log function for each type of check result can be used.

OEMax NX Series I 61
DeviceNet Master Unit
NX700 PLC DeviceNet Master Unit provides Network and Master Connection configured with NX700 PLC and
DeviceNet I/O Products. ( ODVA 2.0 )

Read Data with Appl. Command(READ)

NX700 PLC
Write Data with Appl. Command(WRT)
DeviceNet Master Unit
(NX-DEVICE)

■ Characteristics ■ Performance Specification


1. Have RS232C Communication Port and DeviceNet
Item Specification
Communication Port.
DeviceNet I/O Slave messaging (Group 2 Only Slave)

2. Multi mounting of DeviceNet Master Unit (DNM) in the same I/O Exchange
PLC can be achieved. �Poll Command :Y
Communication Method
�Bit Strobe Command : Y
3. Shared Memory is retained inside of DNM Unit so as to �Cyclic Command :Y
exchange Data between PLC CPU and DeviceNet Devices by �COS Command :Y
using WRITE, READ Commands supported by NX700 PLC NO. of Interface Node Max. 64 Nodes/ 1 Network (Including Master)
Command Word Set. (Maximum I/P of 4096 point and O/P of Distance/Trans. Speed 100m/ 500kbps, 250m/ 250kbps, 500m/ 125kbps
4096 point can be controlled) - Supports automatic setup
Max. Data Trans.Speed 500kbps
4. DNM Unit follows ODVA (Open DeviceNet Vendor Association) 500m
Guaranteed Transmission
DeviceNet Specification 2.0. Distance
Transmission Line DeviceNet Cable
5. Bit-Strobe, Polling, Cyclic I/O control method is provided for
Communication Method Polling , Strobe , Change-of-State , Cyclic
control of DeviceNet I/O products.
Comm. Speed Setup Method Automatic Setup Max. 500Kbps
6. Limited Device Configuration can be done by use of Explicit Rated Voltage: 24V DC Nominal
Messages. DeviceNet Power Voltage Range: 11V ~ 28.8V DC
Power Consumption : 1.5W Max.
7. Configuration Tool is provided for communication speed and I/O Approval ODVA Conformance Test Authentication under way
allotment.
(Configuration Tool for SYCON TOOLS Windows 95/NT that can
configure Network Information and Scan List)

8. Configuration Tool executes configuration through Serial Port on


DNM Unit.

9. DNM Unit stores Configuration Information in Flash Memory.

10. DNM Unit supports automatic, consecutive Scan Function.

62 I OEMax NX Series
■ DeviceNet Communication Configuration
DeviceNet is trademark of ODVA.

NX700 PLC
Computer

DeviceNet
(Master) Computer

NCS-DN(S/W)
(Contiguration)

NCS-DN(S/W)
NX-DEVICE Network
(Configuration Tool) Power(24)

Terminating DeviceNet
Resistance

Devicenet
(Slave)

Devicenet(Slave) Devicenet
(Slave)
DeviceNet
Terminating
Resistance
DeviceNet
(Slave)

■ Wiring Method
(1) RS232C Comm. Connector Type D-Sub, 9Pin Female
1 N.C
Interface with Computer
2 TxD
(Configuration Tool)
3 RxD
Pin
4 N.C
5 GND
6-9 N.C

(1) DeviceNet Comm. Connector Type


DeviceNet, 5Pin
Male
Interface with DeviceNet Network 1 V-
2 CAN_L
DeviceNet Comm.Connector, 5 pin
Pin 3 Shield Female
4 CAN_H
5 V+

OEMax NX Series I 63
64 I OEMax NX Series
■ NX7 PLC 마크 취득제품

NX7 Basic Model (10/14/28 Points)


(NX7S-10ADR, NX7S-10ADT)
(NX7S-14ADR, NX7S-14ADT)
(NX7-28ADR, NX7-28ADT)
(NX7-28DDR, NX7-28DDT)

NX7 Basic Model (48 Points)


(NX7-48ADR)
(NX7-48ADT)
(NX7-48DDR)
(NX7-48DDT)

NX7 Series
NX7 Extended Model (14/28 Points)
(NX7-14EDR, NX7-14EDT)
(NX7-28EDR, NX7-28EDT)

■ Peripheral Devices
User Software

OEMax NX Series I 65
NX7 Series
NX7 Series is a single packaged miniature PLC suitable for controlling the small sized machinery unit with basic 28
points and 48 points in compact size available, which can be extended up to 104 points. HSC, Pulse O/P and PID
Process Function, 2 Communication Ports (RS232/485) are included. All Command words(excluding Data Link) of
SPC10 and N-plus Series support Programming (Software and Command Words) and the existing Programs can be
Downloaded as it is.

■ Product Configuration

NX7 Basic Model (10/14/28Points) NX7 Extended Model(14/28Points)


(NX7S-10ADR, NX7S-10ADT) (NX7-14EDR, NX7-14EDT)
(NX7S-14ADR, NX7S-14ADT) (NX7-28EDR, NX7-28EDT)
(NX7-28ADR, NX7-28ADT)
(NX7-28DDR, NX7-28DDT)

[Peripheral Device]
NX7 Basic Model (48Points) User Software
(NX7-48ADR)
(NX7-48ADT)
(NX7-48DDR)
(NX7-48DDT)

■ Configuration Diagram ■ Product Model Configuration

NX7-□□□□□-□A
4=Analog 4p(4In)
WinGPC Series 6=Analog 6p(4In/2Out)
(NX7=확장가능, O/P Mode(R=Relay, T=Transistor)
NX7S=확장불가) I/P Mode(D=DC I/P)
Pwr Spec. or Classification of Extension
I/O Point (A=AC Pwr I/P, D=DC24V Pwr, E=Extension Module)
■ Kinds of Product Model
RS232C
Name of Unit Product Code Product Spec. I/P Power Spec.
Basic Model NX7S-10ADR 10p(DC IN 6p, Relay Out 4p) AC110/220V
(10 Points) NX7S-10ADT 10p(DC IN 6p, Tr Out 4p) Free Voltage
Basic Model NX7S-14ADR 14p(DC IN 8p, Relay Out 6p) AC110/220V
(14 Points) NX7S-14ADT 14p(DC IN 8p, Tr Out 6p) Free Voltage
NX7-28ADR 28p(DCIN 16p, Relay Out 12p) AC110�220V
Basic Model NX7-28ADT 28p(DCIN 16p, TR Out 12p) Free Voltage
(28 Points) NX7-28DDR 28p(DCIN 16p, Relay Out 12p) DC 24V Power
NX7-28DDT 28p(DCIN 16p, TR Out 12p) Supply
NX7-48ADR 48p(DCIN 28p, Relay Out 20p) AC110�220V
Basic Model NX7-48ADT 48p(DCIN 28p, TR Out 20p) Free Voltage
(48 Points) NX7-48DDR 48p(DCIN 28p, Relay Out 20p) DC 24V Power
NX7-48DDT 48p(DCIN 28p, TR Out 20p) Supply
NX7-20ADR-4A 24p(DCIN 12p, Relay Out 8p) Analog 4p(4 In) AC110�220V
NX7-20ADT-4A 24p(DCIN 12p, Relay Out 8p) Analog 4p(4 In) Free Voltage
Analog
NX7-20ADR-6A 26p(DCIN 12p, Relay Out 8p) Analog 6p(4IN / 2Out) AC110�220V
NX7-20ADT-6A 26p(DCIN 12p, TR Out 8p) Analog 6p(4IN / 2Out) Free Voltage
NX7-14EDR 14p (DC In 8p, Relay Out 6p)
Extended NX7-14EDT 14p (DC In 8p,Tr 6p)
Model NX7-28EDR 28p(DCIN 16p, Relay Out 12p)
NX7-28EDT 28p(DCIN 16p, TR Out 12p)

66 I OEMax NX Series
■ Function and Characteristics of the Product
1. Compatibility Secured 8. Excellent Extendibility (Minimum 28 points ~ up to Maximum 104 points available)
All Command Words of SPC10 and N-plus Series are supported
and the existing Programs can be downloaded. 56
Points
2. High Speed Counter Function
Economical Control System can be built with the basically
embedded HSC 2 CH/24 BIT. 76
Points

3. Pulse O/P Function


Simple Positioning and Stepping Motor can be operated with 104
the Pulse I/P Function of TR O/P Products. Points

4. Pulse I/P Catch


Normal Process can be executed by catching the signal with 9. Diverse Application to Industrial Sites
short I/P Pulse up to Max. 4 Points. Best suited for small-sized control installations. System building
with extendibility and flexibility applicable to I/O Dispersion
5. PID Control Function Embedded System is available.
8Loop Control is available with the embedded 8 Loops PID Function.
10. Clock unction Embedded
6. Compact Size With miniature sized clock function embedded, diverse daily
With miniature size, Basic 28 Points, 48 Points Control is scheduling management program is available.
available and 56,76, 84,104 Points configuration is available with
the Extended Configuration. 11. Powerful Communication Network
Diverse System Configuration is available with the basically
7. Convenient Use embedded each 2 Ports of RS232C and RS485. User Defined
Support Users with easy and accustomed Command Words. Communication Designation is available so as to control Inverter
and Bar Code, etc., by interfacing. User convenience was
extended with automatic Communication Speed Control up to
■ Basic I/O Configuration Diagram 4800~38400bps.
�The below is an example of System Configuration using Basic and Extended Module.

I/P 16 p (R0.0~R1.7) I/P 32 p (R0.0~R1.7) (R8.0~R9.7) I/P 44 p (R0.0~R3.3) (R8.0~R9.7)


O/P 12 p (R16.0~R17.3) O/P 24 p (R16.0~R17.3) (R24.0~R25.3) O/P 32 p (R16.0~R18.3) (R24.0~R25.3)

I/P 28 p (R0.0~R3.3) I/P 60 p (R0.0~R3.3) (R8.0~R9.7) (R12.0~R13.7)


O/P 20 p (R16.0~R18.3) O/P 44 p (R16.0~R18.3) (R24.0~R25.3) (R28.0~R29.3)

OEMax NX Series I 67
■ Performance Specification
Item Specification
Control Method Program Storage, Repetitive Operation Method
Basic 28 p(I/P 16/ O/P 12 p), Basic 48 p(I/P 28/ O/P 20 p),
External I/O
Extension 28 p up to 2 EA(56p) extendable, (ext. 28p: In 16p /Out 12p)
Command Basic Command 28 kinds
Word Application Command Approx. 150 kinds
Process Basic Command Tens of μ
s/step
Speed Application Command A few ~ tens of μs/step
Program Capacity 9K Word
I/O(R) R000.00 ~ R31.15 (512p, 32word) (R32 ~ R127: Setup Range when Special Function is used)
Link Interface (L) L000.00 ~ L063.15 (1024p, 64word)
Internal Interface (M) M000.00 ~ M127.15 (2048p, 128word)
停電維持(Keep-alive During Blackout (K) K000.00 ~ K127.15 (2048p, 128word)
Special Interface(F) F000.00 ~ F015.15 (256p, 16word)
Memory
Capacity 256CH (Timer+Counter, Preset Value: 0 ~65535
Timer/ Counter Timer : 0.01sec: TC000 ~ TC063 (64CH), 0.1sec.: TC064 ~ TC255 (192CH)
Counter : TC000 ~ TC255 (256CH)
Data Word (W) W0000 ~ W2047 (2048word)
Special Word (W, SR) W2560(=SR000)~W3071(=SR511) (512word)
Communication Port 1 Port 1: RS232C/ RS485 Combined Use(D-SUB 9pin), 4800~38400bps Auto select
Function Port 2 Port 2: RS232C/ RS485 Combined Use(8Pin MJ T/B), 4800~38400bps Auto Select
Memory Back-Up User PROGRAM Back-up(FlashROM) Function Basically Embedded,
HSC I CH Embedded(Single Phase 8KHz, 2-Phase 4KHz) Pulse O/P 2 CH Embedded,
Special Function
Pulse Catch unction Embedded(4 Contacts)
Others User Definition Comm., Clock Function, PID Function

■ General Specification ■ Power Supply Specification (AC I/P Type PLC)


Item Specification Item Specification
Power Voltage AC110V, AC220V (50/60Hz) Free Voltage Rated Voltage/ Current AC110V~220V, Free Voltage / 0.4A max
Allowable Instantaneous Below 20ms Allowable Voltage Range AC85~132V, AC170~264V
Interruption AC
Frequency 47 ~ 63Hz,
Power
Surrounding Operational Temp. 0~55℃ Supply Power Consumption Max 33 Watts
Surrounding Storing Temp. -10 ~ 75℃ For Internal Use: 5V, 2.0A
O/P Current Capacity
Surrounding Operational Humidity 30 ~ 85%, (without condensing) For External Use(for Service): 24V, 0.4A
Surrounding Area Humidity 30 ~ 85%, (without condensing)
Frequency 16.7Hz, Amplitude 3mm. X.Y.Z. 2 (DC I/P Type PLC)
Vibration Resistance
Hours to each directions Item Specification
Impact Resistance 10G, X, Y, Z 2 times to each directions Rated Voltage/ Current DC24V / 1.6A max
DC Power
Noise Voltage 1500Vp-p, Noise Pulse Width 100ns, Allowable Voltage Range DC21.6~26.4V
Noise Resistance Supply
1μs. Test Method follows Company Regulation. O/P Current For Internal Use: 5V 2.0A
AC External T/B-Case Earth(FG)between T/Bs
Insulation Resistance
above 20MΩ Test Method follows DC 500V Mega
AC External T/B -Case Earth(FG) between T/Bs
Withstand Voltage
AC 1500V for 1 Min.
Earth More than 3 kinds of Earth
Other Conditions for Use Corrosive gases and thick dust prohibited
Structure Open-Wall Installation Type
停電維持(keep-alive during Blackout) 10일 25℃ (KEEP Relay Preservation)

68 I OEMax NX Series
■ I/P Specification Internal Circuit (DC I/P)

Item DC I/P
I/P Spec. DC Voltage (all types)
Rated Voltage DC12 ~ 24V I/P
Operating Volt. Range 10.8 ~ 26.4V
Max. I/P Current Below 10mA
Min. ON Vol./Current Above 10.0V / above 3.0mA
Max. OFF Vol./Current Below 5.0V / Below 0.6mA
I/P Impedance Approx. 3.6KΩ
Response OFF→ON Below 2ms
Time ON→OFF Below 2ms
Internal Current
Below 50mA
Consumption (5V)
Polarity No Polarity Internal Circuit (Relay O/P)
COMMON Method 8p/ 1COM, 16p/ 1COM
within 2A

Load
■ O/P Specification
Item TR O/P RY O/P
NX7-28ADT NX7-48ADT NX7-28ADR NX7-48ADR
Product Code
NX7-28DDT NX7-48DDT NX7-28DDR NX7-48DDR
O/P Point 12 p 20 p 12 p 20 p
or
Rated Loaded Vol. 12 ~ 24V DC 250V AC, 30V DC
Operating Loaded Vol.
10 ~ 30V DC 85 V ~ 264V AC
Range
Polarity Common (Sink Type, NPN) No Polarity
Internal Circuit (TR O/P)
Max. Load Current 0.4A / point, 1A /Common 2A / point, 6A /COM
Response OFF→ON Below 1ms Below 10ms
Time ON→OFF Below 1ms Below 10ms
Int. PWR
Internal Current Consumption (5V) Below 80mA Load
COMMON Method 1, 4, 6p/1COM 1, 4, 6p/1COM

Int.

Ext. Supply

기본사양

OEMax NX Series I 69
Peripheral Device
WinFPST Software (for N Series)
Software that supports Programming from Computer. Mounted Diverse Functions like Ladder Edit, Monitor, De-Bugging, File
Management, Time Chart Monitoring, etc. Corresponds to all types of NX, N-Series. (excluding N-plus Series)
■ Configuration Diagram

PLC Series Corresponding CPU Type


Product: NX70 NX70-CPU70, NX70-CPU750
Rockwell Automation Korea
Product:

WinFPST S/W NX-CPU750A, NX-CPU750B,


Rockwell Automation Korea

NX700 NX-CPU750C, NX-CPU750D


NX-CPU700
WinFPST S/W (for Windows N7 CPL02343C, CPL02543C..........
N70 CPL9211A
N70 CPL7211A, CPL6215A, CPL6210A,.....

■ Characteristics
1. Diverse Functions are mounted from preparation of program, 4. There are 3 types of Command Word I/P methods: Mnemonic
de-bugging, adjustment and up to various monitorings. Method, Ladder Method and Ladder Symbol Method. Uses can
freely select one from these three.
2. Selection of each function can be done by easy to understand
HANGEUL Menu Method (WinFPST) in simple operation. In 5. Edit, Interface, Forced ON/OFF Function, Interface Search
addition, not only file management function but also printed out Function from ON-LINE RUN Mode.
LIST can be used as a program specification directly.
6. Functions such as Data Monitoring, Time Chart Monitoring, Error
3. Setup of PLC Environment and I/O allotment can be set up in Occurrence Monitoring, File Management.
simple manner
MAIN Menu Multi Program Screen Program Preparation Screen (Ladder Edit)

Forced I/O Screen Status Display Screen Print Management Screen

70 I OEMax NX Series
WinGPC Software (for N-plus Series)
Software for Windows that supports Programming from Computer. Mounted Diverse Functions like Ladder Edit,
Monitor, De-Bugging, File Management, Time Chart Monitoring, etc. User Ladder Software corresponding to Plus
models (N70plus, N700plus, NX700(CPU700p), NX70(CPU70p), NX7, SPC-10 PLC Series).

■ Configuration Diagram

PLC Series Corresponding CPU Model


NX7 NX7-28ADR, NX7-48ADR........
Product:

Product:

Rockwell Automation Korea


NX70 NX70-CPU70p1, NX70-CPU70p2
Rockwell Automation Korea
WinGPC
NX700 NX-CPU700p
WinGPC S/W (for Windows) SPC SPC-10ADR, SPC-10ADT....
N70Plus CPL9215A, CPL9216A
N700Plus CPL7215A

■ Characteristics
1. Convenient Functions of Windows can be utilized by application 4. Diverse types of monitoring such as Ladder, Mnemonic, Time
of WINDOWS Environment . Chart, Register Monitoring are available.

2. Programming can be done while executing mutual comparison 5. Ladder and Mnemonic programs are conversed automatically.
or printing because several programs can be edited
6. On-line interfaced PLC can be automatically discerned.
simultaneously.
7. Program correction and change can be done conveniently on
3. Programming is very convenient because diverse TOOLs for
on-line.
programming are provided.

Ladder Monitoring Screen Mnemonic Edit Screen Projector Management Screen

Register Monitoring Screen Time Chart Monitoring Screen Status Monitoring Screen

OEMax NX Series I 71
Cable for CPU of NX70 PLC, NX700 PLC
Cable for TOOL PORT of NX70, NX700 CPU

CPU Unit TOOL PORT, 9pin WinFPST(Comptr Side),9pin

CPU Unit TOOLPORT,9pin WinFPST(Comtr Side),9pin

Signal PIN No. PIN No. Signal NX-CBLCPU02


TXD 2 2 RXD NX-CBLCPU05

RXD 3 3 TXD
- 4 4 DTR Computer
■ Corresponding CPU Module
S.G 5 5 S.G
PLC Series Corres. CPU Model
- 6 6 DSR
NX70 NX70-CPU70, NX70-CPU750
- 7 7 RTS NX-CPU750A, NX-CPU750B,
- 8 8 CTS NX700 NX-CPU750C, NX-CPU75
17JE-23090-02(D1),DDK (Male) 17JE-13090-02(D1),DDK(Female) NX-CPU700

Ref TOOL PORT of CPU Module for NX70, NX700 CPU of the bove diagram can use CPL5530, CPL5531 cable.

Cab le for COM PORT of NX70, NX700 CPU Unit and for CCU Unit of NX Series

�NX70-CCU (9pin)
�NX-CCU (9pin)
�CPU Unit COM PORT (9pin) �D-SUB (9pin)

�NX70-CCU Com.Port(9pin) Communication Cable


�NX-CCU Com.Port(9pin) Computer
�CPU Unit COM Port(9pin) D-SUB(9pin)

PIN No. Signal PIN No. Signal


1 F.G 1 CD(DCD) C-Language
Computer Visual Basic
2 TXD 2 RXD MMI S/W
3 RXD 3 TXD T/P
4 - 4 DTR (Touch Panel)
5 SG 5 SG
6 - 6 DSR
7 RTS 7 RTS ■ Corresponding CPU Module
8 CTS 8 CTS PLC Series Corres. CPU Model
NX70 NX70-CPU750
9 ER 9 -
NX-CPU750A, NX-CPU750B,
17JE-23090-02(D1),DDK (Male) 17JE-13090-02(D1),DDK(Female) NX700
NX-CPU750C, NX-CPU750D

Ref COM PORT of CPU Module of NX70, NX700 in the above diagram have same Communication specification
ith NX Series CCU Module

72 I OEMax NX Series
■ Cable for Plus CPU (SPC10, NX7, N70plus, N700plus, NX70, NX700)
Model Cable Length Contents of Application Applicable Products Remarks

1) NX7 PLC
- To interface with Handy-Loader(PGM500) �NX7 PLC (NX7-28ADR, NX7-48ADR...)
NX-CBLCPU02 2m
- To Interface with Computer �N70plus (CPL9215A, CPL9216A)
2) N70plus, N700plus PLC �N700plus (CPL7215A)
- To Interface with Handy-Loader(PGM500) �NX70p
- To Interface with Computer �NX700p
3) NX700 PLC �SPC10 PLC
- To Interface with Computer
4) NX70 PLC
- To Interface with Computer
NX-CBLCPU05 5m 5) PC10 PLC *1
- To Interface with Computer
(RS485/232 Adapter not necessary)

The below picture is for NX-CPU700p.


Cable Wiring and Configuration Diagram

CPU Unit side,9p Computer and PGM500 side, 9pin

2m/ 5m

COM. Cable
CPU Unit side, 9 pin Computer & PGM500 side, 9 pin

Signal PIN No. PIN No. Signal


TXD 2 2 RXD
Computer
RXD 3 3 TXD
- 4 4 DTR
S.G 5 5 S.G
485(-) 6 6 DSR
485(+) 7 7 RTS
- 8 8 CTS
Vcc 9 9
17JE-23090-02(D1),DDK (Male) 17JE-13090-02(D1),DDK(Female)

■ Corresponding CPU Module


PLC Series Corresponding CPU Model COM. Cable
NX7 NX7-28ADR, NX7-48ADR........
NX70
CPU all
NX700
SPC10 SPC-28ADR, SPC-28ADT....
PGM-500 Programmer
N70plus CPL9215A, CPL9216A
N700plus CPL7215A

OEMax NX Series I 73
■ Cable for SCU Module for N700, NX70, NX700 PLC
Contents of Application Applicable Module Remarks
COM Port of SCU Module SCU Module: for NX700 PLC(NX-SCU), for NX70 PLC(NX70-SCU), for N700 PLC(CPL7461)

Communication Wiring Diagram of SCU Module

COM Port of SCU Module ■RS232C Wiring Method


(3 line method without FLOW Control)
PIN
No. Signal Name Mnemonic SCU Unit (9 pin) RS232 Device (9 pin)
1 FRAME GROUND F.G Signal PIN No. PIN No. Signal
F.G 1 1 -
2 SEND DATA TxD
TXD 2 2 RXD
3 RECEIVE DATA RxD RXD 3 3 TXD
4 - - S.G 5 5 S.G
5 SIGNAL GROUND S.G 17JE-13090-02(D1),DDK 17JE-23090-02(D1),DDK
6 485 TRANSIVER - 485 - (Male) (Female)

7 485 TRANSIVER + 485+


8 - - ■Wiring Method of RS485
9 POWER +5V SCU Unit (9 pin) RS485 Device
Signal PIN No. Signal
F.G 1
485- 6 485-
485+ 7 485+

NX Series (Cable for Extension and I/O Unit)


■ Extended Motherboard for NX700 PLC ■ Cable Harness for Connector Type I/O Unit
Product NO. Cable Length Applicable Contents Applicable Products 제품
Kinds 종류
of Product Applicable적용
PLCPLC Applicable Unit
PLC 제품 번호
Product NO.
NX-EXPCBL15 1.5m Cable to connect when All CPU Models of 케이블 하우스 NX70 PLC For DC IN 32 point NX70-CBLDC
NX-EXPCBL08 0.8m Motherboard is used NX700 PLC
N70 PLC
For TR OUT 32 point NX70-CBLTR
N700 PLC
Cable Harness
N700 PLC For RELAY OUT 32 point NX-CBLRY20
For DC IN 32, 64 point NX-CBLDC
NX700 PLC For TR OUT 32,64 point NX-CBLTR
For RELAY OUT 32 point NX-CBLRY
NX70 PLC
N70 PLC 20Pin Ass’y NX-PIN 20
Pin Ass’y N700 PLC

NX700 PLC 40Pin Ass’y NX-PIN 40

■ Explanation of the Product


These are Cable Harness and Pin Assembly for easy interface with
the external devices at connector type 32 point and 64 point
Modules among I/O Units of SAMSUNG PLSs. (If you experience
any difficulty in purchasing from other manufacturers or direct use,
you are advised to purchase from us for better convenience)

74 I OEMax NX Series
External Dimensions
NX700 External Dimensions Diagram
■ Diagram of Dimensions for System (mm)

115.5 118.5

Unit(mm)
Dimensions
Slot Type
L P
3 Slot Type 205.0 183.8
111.0
5 Slot Type 276.0 254.2
8 Slot Type 381.0 359.8
10 Slot Type 452.0 430.2
12 Slot Type 522.0 500.6

L
27.5

115.5

■ Diagram of Motherboard Installation (mm)

Unit(mm)

SLOT A B
3 Slot Type 153.8 81.0
5 Slot Type 224.2 81.0
8 Slot Type 329.8 81.0
10 Slot Type 400.2 81.0
12 Slot Type 470.6 81.0

OEMax NX Series I 75
■ Diagram of Dimensions for Power Unit (mm)

■ Diagram of Dimensions for CPU, I/O and Special Unit (mm)

NX-CPU750B NX-X16D NX-X64D NX-MWLINK NX-SCU

INI1
NS1
RUN
RM1 00 RESET
PROG
LINK NO
0

COM COM1
RS232C RS232C
RS485

-
100L COM2
RS232C RS232C
FG RS485

76 I OEMax NX Series
Diagram of External Dimensions for NX70
■ Diagram of Dimensions for System (mm)
A

105.0

88.0

Slot Type Product NO. Dimensions(A) Dimensions(B) Dimensions (C)


2 Slot Type NX70-BASE02 157.2 128.6 114.6
3 Slot Type NX70-BASE03 192.4 153.8 149.8
4 Slot Type NX70-BASE04 227.6 189.0 185.0
5 Slot Type NX70-BASE05 262.8 234.2 220.2
6 Slot Type NX70-BASE06 298.0 269.4 255.4
8 Slot Type NX70-BASE08 368.4 339.8 325.8
10 Slot Type NX70-BASE10 438.8 410.2 396.2
12 Slot Type NX70-BASE12 508.6 480.6 466.6

OEMax NX Series I 77
■ Diagram of Dimensions for Power Unit (mm)

■ Diagram of Dimensions for CPU, I/O Special Unit (mm)

RESET
INI1 RUN
RM1
LES1 PROG 00
LINK NO
20 19 1 2 0
COM1
COM RS232C
RS232C RS485

+ COM2
100L RS232C
RS232C _
RS485
2 1 19 20 FG

78 I OEMax NX Series
Diagram of External Dimensions for NX7
■ 28 Point PLC

DIN Rail for


35 mm Mounted

■ 48 Point PLC

■ Diagram of Dimensions for Installation (단위 = mm)


�For 28 Point �For 48 Point
100.0mm 146.0mm
Φ4.2 Φ4.2

•’ 4.2 •’ 4.2
9.5
10.0

81.0 126.0
90.0
87.0 87.0

9.5 10.0

1.5 1.5

3.0
3.0

OEMax NX Series I 79
Product Catalog
NX700 PLC Series
■ CPU Unit
Unit Name Product Spec. Product Spec. Remarks
16k Step Embedded, 0.35㎲/ STEP, 2 Port, PID Auto Tuning Function,
NX-CPU750A Clock Function, Command Word is same with N700a CPU (In case of Extended
Memory, 32k Step & Comment Memory)
32k Step Embedded, 0.35㎲/ STEP, 2 Port, PID Auto Tuning Function, Floating-Point
NX-CPU750B Clock Function, Comment Memory & EPROM Socket Embedded, Command Operation
Word is same with N700a CPU. Clock Function
High Performance
60k Step Embedded, 0.03㎲/ STEP, 2 Port, PID Auto Tuning Function, PID AutoTuning
NX-CPU750C Clock Function, Comment Memory & EPROM Socket Embedded, 0.001s Timer
Command Word is same with N700a CPU.
120k Step Embedded, 0.03㎲/ STEP, 2 Port, PID Auto Tuning Function,
NX-CPU750D Clock Function, Comment Memory & EPROM Socket Embedded,
Command Word is same with N700a CPU.

Unit
유니트명 Name 제품 코드
Product Spec. 제품 사양
Product Spec. 비고
Remarks
증설메모리 16K STEP(Basically Embedded), 0.4㎲/ STEP, Trace Function, PID Function,
General Purpose Use NX-CPU700
Comment Memory basically embedded

Unit Name Product Spec. Product Spec. Remarks


General Purpose Use NX-CPU700P 20K Word(Basically Embedded), 0.2㎲/ STEP, 2 Port, PID Function, Clock Function

■ Memory Unit for CPU750A


Unit Name Product Spec. Product Spec. Remarks
Extended Memory NX-MEM750A xtended Memory 16K Step + Comment Memory + EEPROM Socket Embedded For NX-CPU750A

■ Communication Cable for CPU Unit


Unit Name Product Spec. Product Spec. Remarks
Com Cable for NX-CBLCPU02 Common Use with TOOL Port
Communication Cable for NX Series of CPU Modules of NX700
CPU NX-CBLCPU05

■ Motherboard
Unit Name Product Spec. Product Spec. Remarks
NX-BASE03 3 slot type
NX-BASE05 5 slot type Common use with Basic
Basic Motherboard and extended
Motherboard NX-BASE08 8 slot type
Motherboard (No distinction)
NX-BASE10 10 slot type
NX-BASE12 12 slot type

■ Power Supply Unit


Unit Name Product Code Product Spec. Remarks
NX-POWER AC 110/ 220V Free Voltage, 5V 4A, 24V 0.5A
Power Supply Unit AC I/P Type
NX-PWR220 AC 220V Input, 5V 6A
NX-PWRDC DC 24V Input, 5V 5A DC I/P Type

80 I OEMax NX Series
■ I/O Unit
Slot Type Product Code Product Spec. Remarks
NX-X16D DC 12~24V, Terminal Block 20pin, 8 p/ COM, (Polarity +,- Common)
Terminal Block Type
16 P NX-X16A110 AC 100~120V, Terminal Block 20pin, 8 p/ COM 20pin(Split Type)
I/P Unit NX-X16A220 AC 200~240V, Terminal Block 20pin, 8 p/ COM
32 P NX-X32D DC 12~24V, Connector 40pin, 32 p/ COM, (Polarity +,- Common) Connector Type
64 P NX-X64D DC 12~24V, Connector 40pin x 2, 32 p/ COM, (Polarity +,- Common) 40pin
NX-Y16R RELAY O/P, Terminal Block 20pin, 250V 2A, 8 p/ COM
16 P NX-Y16RV RELAY O/P, Terminal Block 20pin, 250V 2A, 8 p/ COM, with Varistor Terminal Block Type
NX-Y16T TR O/P(NPN), Terminal Block 20pin, 12~24V 0.6A, 8 p/ COM 20pin(Split Type)
NX-Y16SSR SSR O/P, Terminal Block 20pin, 100~220V, 0.5A, 8 p/ COM
O/P Unit
32 P NX-Y32T TR O/P(NPN), Connector 40pin, 12~24V 0.4A, 32 p/ COM
NX-Y32RV RELAY O/P, Connector 40pin x 1, 250VAC /1A, 32 p/ COM, with Varistor Connector Type
NX-Y32R RELAY O/P, Connector 20pin x 2, 250VAC /1A, 30VDC, 16 p/ COM
64 P NX-Y64T TR O/P(NPN), Connector 40pin x 2, 12~24VAC 0.2A, 32 p/ COM
O/P Unit NX-DUMMY Dummy Unit

■ Analog Unit
Analog Product Code Product Spec. Remarks
8CH, Voltage Input, 16Bit A/D Converter, ±5V, ±10V, 0�5V,
NX-AI8V
Analog I/P 0~10V Resolution (0.153mV~1.0mV), Conversion Speed 1.25ms/Ch
(AD) 8CH, Current Input, 16Bit A/D Converter, ±20mA, 0�20mA,
NX-AI8C
4~20mA Resolution (0.519uA~2.0uA) Conversion Speed 1.25ms/Ch
4CH, Voltage Output, 14bit D/A Converter, ±10V, ±5V, 0�10V,
NX-AO4V
0~5V Resolution (0.305mV~1.0mV), Conversion Speed 2.5ms/ Ch
8CH, Voltage Output, 14bit D/A Converter, ±10V, ±5V, 0�10V,
NX-AO8V
Analog O/P 0~5V Resolution (0.305mV~1.0mV), Conversion Speed 2.5ms/ Ch
(DA) 4CH, Current Output, 14bit D/A Converter, 0�20mA, 4�20mA
NX-AO4C
Resolution (0.037uA~2.0uA) 4uA, Conversion Speed 2.5ms/ Ch
8CH, Current Output, 14bit D/A Converter,, 0�20mA, 4�20mA Terminal Block Type
NX-AO8C
Resolution (0.037uA~2.0uA) 4uA, Conversion Speed 2.5ms/ Ch 20pin(Split Type)
4CH, 3-Wire Method, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,
NX-RTD4 JPt500,JPt1000, NI100, NI120, CU50, 300Ω, 600Ω, 2000Ω
Resistance Temperature Detector Resolution 0.1℃, 0.1℉,
(RTD) 8CH, 3-Wire Method, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,
NX-RTD8 JPt500, JPt1000, NI100, NI120, CU50, 300Ω, 600Ω, 2000Ω
Resolution 0.1℃, 0.1℉, 10mΩ, 20mΩ, Conversion Speed 60ms/Ch

4CH, Type : B/ R/ S/ N/ K/ E/ J/ T(Temperature Range differs according to


Sensor Types)
NX-TC4 ±30mV (1uV /Bit), ±60mV (2uV /Bit)
Resolution 0.1℃/ 0.1℉/ 1uV/ 2uV, Conversion Speed 60ms/Ch
ThermoCouple I/P
8CH, Type : B/ R/ S/ N/ K/ E/ J/ T(Temperature Range differs according to
Sensor Types)
NX-TC8 ±30mV (1uV /Bit), ±60mV (2uV /Bit)
Resolution 0.1℃/ 0.1℉/ 1uV/ 2uV, Conversion Speed 60ms/Ch

OEMax NX Series I 81
■ Communication Unit
Unit Name Product Code Product Spec. Remarks
RS232C/ RS485 x 2Port (Data process with Ladder Program)
∙Data Send/Recv enabled with each type of RS232C/ RS485 Device RS485 Function is added on
Serial Communication
NX-SCU (Binary/ ASCII Code process) the existing SDU Function
Unit (SCU)
∙For Interface with Network Inverter and NetworkServo, Network Temperature Controller, etc.
∙Module of existing SDU Function + RS485 Network Function

Communication Unit with RS-232C x 1Port Computer and Touch Panel


Computer Use C, BASIC Language, "SECTOCOL" N-Series Protocol Basically mounted
Communication NX-CCU ① 1:1 Leased Communication Unit For Interface with
Unit (CCU) ② 1:N Communication Function: Unit for Interface with Computer on PLC Computer or T/P
NETWORK(Optical-LINK, W-LINK)

Communication Unit with RS232C/ RS485 x 1Port Computer and Touch Panel Unit
Computer For Computer or T/P Interface
∙NX-CCU+ ↔ Computer Communication ( 1:1 or 1:N Communication )
Communication NX-CCU+ (For use of CPU700p
∙NX-CCU+ ↔ Use N-Plus Protocol for Computer Communication
Unit (CCU+) Module only)
∙NX-CCU+ ↔ Communication with Touch Panel, MMI Unit

■ Unit for Motion Control


Unit Name Product Code Product Spec. Remarks
1CH HSC I/P Function 100kcps I/PMode (3 Mode)
NX-HSC1 1) Direction Discrimination Mode
Binary 24Bit Up/Down Counter(-16,777,216~16,777,215)
HSC Unit 2) Individual I/PMode(CW, CCW)
2CH HSC I/P Function 100kcps 3) Phase Difference I/P Mode
NX-HSC2
Binary 24Bit Up/Down Counter(-16,777,216~16,777,215) (Rotary Encode I/P)

HSC I/P 4CH, Interrupt I/P 8p, Compared O/P 8 p


High Performance ∙200kcps, Binary 32Bit Up/Down Counter(-2,147,483,648~2,147,483,647) Leased for CPU750
NX-HSC4
HSC Unit ∙Multiply Function(1, 2, 4 Multiply), I/P Time Constant Function(4, 8, 16, 32 W/us), Module only
Pulse Width: 2.5us

Module with diverse functions such as; Pulse O/P 4CH, PWM O/P 4CH, HSC I/P 4CH,
Pulse I/O Interrupt I/P 8 p, Compared O/P 8 p. Leased for CPU750
NX-PULSE4 ∙Pulse O/P: 100KHz O/P(1Hz Unit ), Direction Discrimination and Individual I/P(CW, CCW)
Unit Module only
∙PWM O/P: 30KHz O/P(1Hz Unit ), Duty: 0~100% (1% Unit )

∙High Speed. High Accuracy Positioning, Pulse Command Method.


NX-POSI1 1 Axis Type
∙Line Drive or Open Collector O/P Method selectable
∙Line Drive Method : 1pulse ~ 1M pulse/s
∙Open Collector Method : 1pulse ~ 200k pulse/s
NX-POSI2 ∙With High Speed activation(0.1ms), Tack Time can be reduced. 2 Axis Type
Open Collector /
Positioning ∙Simple Parameter Setup, Automatic acc/deceleration by Data Setup Line Drive Selectable
Unit ∙S-shaped Acc/Deceleration Function, Linear Acc/Deceleration Function
NX-POSI3 ∙E point Control, P point Control, Return to Zero, JOG Drive, 3 Axis Type Leased for CPU750Module
∙Pulse I/P Function: With Pulse I/P Function and Manual Pulse only
Generator(MPG Function), Real Time Transmission can be done
(Max. 1,000 Multiply according to Multiply Function)
NX-POSI4 ∙Servo Drive, Stepping Drive Interface 4 Axis Type

82 I OEMax NX Series
■ Unit for Network (Open Network)
Analog Product Code Product Spec. Remarks
1) W-Link Function (W Mode)
∙Mount on Basic Motherboard to use
∙Mount up to 3 EA including CCU(5 EA in case of CPU750C Module)
∙Function: PLC Link(16 EA, L: 1,024 p, Ld: 128 Word), Computer Link,
Data Transmission(16Word/ 1Command), Remote Programming,
Layer Link(Refer to F145, F146)
∙PLC 32 EA/ Layer, 2 Layer, Transmission Speed : 0.5Mbps
∙Transmission Distance: Total 800m, Interface: RS485 Multi-drop
Use Twist-Pair Cable
MW-Link Unit NX-MWLINK
2) W-Link2 Function (W2 Mode) Leased for
(Multi Wire-Link)
∙Mount on Basic Motherboard to use CPU750Module only
∙Mount up to 3 EA including CCU(8 EA in case of CPU750C Module)
∙Function: PLC Link (32 EA, L: 4,096 p, Ld: 4,096 Word), Computer Link Function,
Data Transmission (1,020Word/1Command), Remote Programming,
Layer Link (Refer to F145, F146)
∙PLC 32 EA/ Layer, 2 Layer, Transmission Speed: 0.5Mbps
∙Transmission Distance: Total 800m (up to 1,200 m in case of 250Kbps)
∙Interface: RS485 Multi-drop

■ Unit for Network (Open Network)


Unit Name Product Code Product Spec. Remarks
1) Can be used with 100BASE-TX and 10BASE-T (Conversion executed automatically);
Use UTP Cable

NX-ETHERNET 2) 10BASE5; Use Transceiver Cable


EtherNet Unit Leased for
∙Data Transmission Speed : 100M bit/s (in case of 100BASE-TX)
∙Correspond to TCP/ IP and UDP/ IP, 8 Connection Communication per 1 EA CPU750Module only
∙Up to 3 EA EtherNet Module can be mounted on 1 PLC
∙Computer Link. Data Transmission, Permeable Communication, Remote Programming,
Self Diagnosis Function

DeviceNet Master Unit for NX700 PLC


DeviceNet Master NX-DEVICE High Speed Photocoupler, 125K, 250K, 500Kbps,
Unit
Support S/W : SYCON(NCS-DN) S/W

■ REMOTE I/O System


Unit Name Product Code Product Spec. Remarks
∙Mount at Basic side, extended side of Motherboard to use(up to 4 EA)
REMOTE MASTER
NX-MASTER ∙Interface up to 32 stations of LAVE Unit per 1 Master For use of NX700 PLC
Unit
∙Transmission Distance: Total 700m, Transmission Speed: 0.5Mbps

REMOTE SLAVE NX-SLAVE For use of NX700 PLC


Mount at the location of CPU Unit on the Basic Motherboard.
Unit NX70-SLAVE For use of NX70 PLC

OEMax NX Series I 83
NX70 PLC
NX70 시리즈
PLC Series
■ CPU Unit (N-Series)
Use WinFPST S/W
Unit Name Product Code Product Spec. Remarks
∙0.35㎲/ STEP, 32k STEP(Basically Embedded), 2 Port, PID AutoTuning Function,
Floating Point Operation
Clock Function
NX70-CPU750 Clock Function
∙Comment Memory, EPROM (EEPROM) Operation Function
PID Auto Tuning
CPU Unit ∙High Performance CPU Module

∙0.4㎲/ STEP, 16K STEP(Basically Embedded), Trace Function, PID Function


NX70-CPU70 ∙Comment Memory Basically Embedded. Communication Pin 9 Pin
∙Common CPU Module

■ CPU Unit (plus-Series) Use WinGPC S/W

Unit Name Product Code Product Spec. Remarks


∙9.6K STEP(Basically Embedded), 0.2㎲/ STEP, FLASH ROM Embedded
NX70-CPU70p1
∙Common CPU Module
CPU Unit ∙20K STEP(Basically Embedded), 0.2㎲/ STEP, 2 Port, Clock Function,
NX70-CPU70p2 FLASH ROM Embedded, PID Function
∙Advanced CPU Module

■ CPU Unit Communication Cable


Unit Name Product Code Product Spec. Remarks
Communication NX-CBLCPU02 2m
Cable CPU Unit NX70, NX700 CPU Unit Communication Cable
for CPU NX-CBLCPU05 5m

■ Motherboard
Unit Name Product Code Product Spec. Remarks
NX70-BASE02 2 Slot Type
NX70-BASE03 3 Slot Type
NX70-BASE04 4 Slot Type
5 Slot Type NX70 PLC has
Basic NX70-BASE05
Motherboard Basic Motherboard
NX70-BASE06 6 Slot Type
only
NX70-BASE08 4 Slot Type
NX70-BASE10 5 Slot Type
NX70-BASE12 6 Slot Type

■ Power Unit
Unit Name Product Code Product Spec. Remarks
NX70-POWER1 AC 110/ 220V Free Voltage, 5V 4A, 24V 0.3A NX70 PLC has
Power Unit NX70-POWER2 AC 110/ 220V Free Voltage, 5V 4.5A Basic Motherboard
NX70-PWRDC DC 24V Input, 5V 4.5A only

Caution Product Compatibility between NX70 PLC and N70 PLC


1) NX70 PLC and N70 PLC ha no compatibility at all with CPU Unit, Basic Motherboard and Power Unit. (Ladder Programs are mutually compatible)
2) Other I/O Unit and Special Unit, Cables, Programming Device and User Software are mutually compatible.

84 I OEMax NX Series
■ I/O Unit
Slot Type Product Code Product Spec. Remarks
NX70-X16D DC 12~24V, Terminal Block 20 Pin, 8 p/ COM, (Polarity +,- Common )
NX70-X16D1 DC 24V, Terminal Block 20 Pin, 8 p/ COM, (Polarity +,- Common )
16 p Terminal Block Type
NX70-X16A110 AC 100~120V, Terminal Block 20 Pin, 8 p/ COM
I/P Unit
NX70-X16A220 AC 200~240V, Terminal Block 20 Pin, 8 p/ COM
NX70-X32D DC 12~24V, Connector 20 Pin x 2, 8 p/ COM, (Polarity +,- Common )
32 p Connector Type
NX70-X32D1 DC 24V, Connector 20 Pin x 2, 8 p/ COM, (Polarity +,- Common )
NX70-Y16R RELAY O/P, Terminal Block 20 Pin, 250V 1A, 8 p/ COM
NX70-Y16RV RELAY O/P, Terminal Block 20 Pin, 250V 1A, 8 p/ COM, Varistor available
16 p Terminal Block Type
NX70-Y16T TR O/P(NPN), Terminal Block 20 Pin, 12~24V 0.6A, 8 p/ COM
O/P Unit
NX70-Y16SSR SSR O/P, Terminal Block 20 Pin, 100~220V, 0.5A, 8 p/ COM
NX70-Y32T TR O/P(NPN), Connector 20 Pin x 2, 12~24V 0.4A, 16 p/ COM(-)
32 p Connector Type
NX70-Y32P TR O/P(PNP), Connector 20 Pin x 2, 12~24V 0.4A, 16 p/ COM(+)
.DC12~24V, 8 p, 8 p/ COM, (Polarity +,- Common ), I/P 8 p
16 p NX70-XY16
.RELAY O/P, 8 p, 250V 1A, 8 p/ COM, Terminal Block 20 Pin O/P 8 p
Combined Unit
.DC12~24V, 16 p, 16 p/ COM, (Polarity +,- Common ), Connector 20 Pin x 2 I/P 16 p
32 p NX70-XY32
.TR O/P(NPN) 16 p, ,12~24V 0.4A, 16 p/ COM O/P 16 p
Dummy Unit NX70-DUMMY Dummy Unit

■ Analog Unit
Analog Product Code Product Spec. Remarks
4CH Voltage Input, 16Bit A/D Converter, ±5V, ±10V, 0�5V, 0�10V
NX70-AI4V
Resolution (0.153mV~1.0mV), Conversion Speed 1.25ms/Ch

8CH Voltage Input, 16Bit A/D Converter, ±5V, ±10V, 0�5V, 0�10V
NX70-AI8V
Analog I/P Resolution (0.153mV~1.0mV), Conversion Speed 1.25ms/Ch
(AD) 4CH Current Input, 16Bit A/D Converter, ±20mA, 0�20mA, 4�20m
NX70-AI4C Resolution (0.519uA~2.0uA), Conversion Speed 1.25ms/Ch

8CH Current Input, 16Bit A/D Converter, ±20mA, 0�20mA, 4�20m


NX70-AI8C
Resolution (0.519uA~2.0uA), Conversion Speed 1.25ms/Ch
4CH Voltage Output, 14bit D/A Converter, ±10V, ±5V, 0�10V, 0�5V
NX70-AO4V
Resolution (0.305mV~1.0mV), Conversion Speed 2.5ms/ Ch

4CH Current Output, 14bit D/A Converter, 0�20mA, 4�20mA


NX70-AO4C
Resolution (0.037uA~2.0uA) 4uA, Conversion Speed 2.5ms/Ch
Analog O/P
Terminal Block Type
(DA) NX70-AO2V 2CH Voltage Output, 14bit D/A Converter, ±10V, ±5V, 0�10V, 0�5V
Resolution (0.305mV~1.0mV), Conversion Speed 2.5ms/Ch 20 Pin
(Split Type)
NX70-AO2C 2CH Current Output, 14bit D/A Converter, 0�20mA, 4�20mA
Resolution (0.037uA~2.0uA) 4uA, Conversion Speed 2.5ms/Ch

4CH 3-Wire Method, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,


NX70-RTD4 JPt500, JPt1000, NI100, NI120, CU50, 300Ω, 600Ω, 2000Ω
Resistance Temperature Resolution 0.1℃, 0.1℉, 10mΩ, 20mΩ, Conversion Speed 60ms/Ch
Detector I/P
(RTD) 8CH 3-Wire Method, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,
NX70-RTD8
JPt500, JPt1000, NI100, NI120, CU50, 300Ω, 600Ω, 2000Ω
(To be released) Resolution 0.1℃, 0.1℉, 10mΩ, 20mΩ, Conversion Speed 60ms/Ch
4CH Type : B/ R/ S/ N/ K/ E/ J/ T(Temperature Range varies according to Sensor Type)
NX70-TC4 ±30mV (1uV /Bit), ±60mV (2uV /Bit)
Resolution 0.1℃/ 0.1℉/ 1uV/ 2uV, Conversion Speed 60ms/Ch
ThermoCouple I/P
8CH Type : B/ R/ S/ N/ K/ E/ J/ T(Temperature Range varies according to Sensor Type)
NX70-TC8 ±30mV (1uV /Bit), ±60mV (2uV /Bit)
(To be released) Resolution 0.1℃/ 0.1℉/ 1uV/ 2uV, Conversion Speed 60ms/Ch

OEMax NX Series I 85
■ Communication Unit
Unit Name Product Code Product Spec Remarks

RS232C/ RS485 x 2Port (Data process with Ladder Program)


∙Data Send/Recv enabled with each type of RS232C/ RS485 Device (Binary/ ASCII Code process) RS485 Function is added
Serial Communication
NX70-SCU on the existing
Unit (SCU) ∙For Interface with Network Inverter and NetworkServo, Network Temperature Controller, etc.
∙Module of existing SDU Function + RS485 Network Function. SDU Function

Communication Unit with RS-232C x 1Port Computer and Touch Panel For Interface with
Use C, BASIC Language, "SECTOCOL" N-Series Protocol Basically mounted Computer or T/P
NX70-CCU ① 1:1 Leased Communication Unit (for leased use of N-Series)
② 1:N Communication Function: Unit for Interface with Computer - NX70-CPU70
Computer
on PLC NETWORK(Optical-LINK, W-LINK) - NX70-CPU750
Communication
Unit (CCU)
Communication Unit with RS232C/ RS485 x 1Port Computer and Touch Panel Unit
∙NX70-CCU+ ↔ Computer Communication ( 1:1 or 1:N Communication ) - NX70-CPU70P1
NX70-CCU+
∙NX70-CCU+ ↔ Use N-Plus Protocol for Computer Communication - NX70-CPU70P2
∙NX70-CCU+ ↔ Communication with Touch Panel, MMI Unit

■ Unit for Motion Control


Unit Name Product Code Product Spec Remarks

1CH HSC I/P Function(100kcps) + Simplified Pulse O/P Function (200Hz . 40kHz)
NX70-HSC1 I/P Mode (3 Mode)
Binary 24Bit Up/Down Counter(-16,777,216~16,777,215)
1)Direction Discrimination Mode
HSC Unit 2)Individual I/P Mode(CW, CCW)
2CH HSC I/P Function (100kcps) 3)Phase Difference I/P Mode
NX70-HSC2 Binary 24 Bit Up/Down Counter(-16,777,216~16,777,215) (Rotary Encode I/P)

HSC I/P 4CH, Interrupt I/P 8p, Compared O/P 8 p


High Performance �200kcps, Binary 32Bit Up/Down Counter(-2,147,483,648~2,147,483,647) For use of NX70-CPU750,
NX70-HSC4
HSC Unit �Multiply Function(1, 2, 4 Multiply), I/P Time Constant Function(4, 8, 16, 32 W/us), NX70-CPU70p2
Pulse Width: 2.5us

Module with diverse functions such as; Pulse O/P 4CH, PWM O/P 4CH, HSC I/P 4CH,
Interrupt I/P 8 p, Compared O/P 8 p.
Pulse I/O �HSC I/P: 200kcps, Binary 32Bit Up/Down Counter..... For use of NX70-CPU750,
NX70-PULSE4 �Pulse O/P: 100KHz O/P(1Hz Unit), Direction Discrimination and Individual I/P(CW, CCW)
Unit NX70-CPU70p2
�PWM O/P: 30KHz O/P(1Hz Unit ), Duty: 0~100% (1% Unit )
* Function: NX70-HSC4+Pulse O/P(4CH)+PWM O/P(4CH)

�High Speed. High Accuracy Positioning, Pulse Command Method.


�Line Drive or Open Collector O/P Method selectable
NX70-POSI2 �Line Drive Method : 1pulse ~ 1M pulse/s 2Axes
�Open Collector Method : 1pulse ~ 200k pulse/s Type Open Collector /
�With High Speed activation(0.1ms), Tack Time can be reduced. Line Drive selectable
Positioning �Simple Parameter Setup, Automatic acc/deceleration by Data Setup
Unit �S-shaped Acc/Deceleration Function, Linear Acc/Deceleration Function For use of NX70-CPU750,
�E point Control, P point Control, Return to Zero, JOG Drive, NX70-CPU70p2
�Pulse I/P Function: With Pulse I/P Function and Manual Pulse Generator(MPG 4Axes
NX70-POSI4 Function), Real Time Transmission can be done (Max. 1,000 Multiply according Type
to Multiply Function)
�Servo Drive, Stepping Drive Interface

86 I OEMax NX Series
■ Unit for Network (Network for PLC)
Analog Product Code Product Spec Remarks
1) W-Link Function (W Mode)
�Mount on Basic Motherboard to use
�Mount up to 3 EA including CCU
�Function: PLC Link(16 EA, L: 1,024 p, Ld: 128 Word), Computer Link, Data Transmission
(16Word/ 1Command), Remote Programming, Layer Link(Refer to F145, F146)
�PLC 32 EA/ Layer, 2 Layer, Transmission Speed: 0.5Mbps
�Transmission Distance: Total 800m, Interface: RS485 Multi-drop
2) W-Link2 Function (W2 Mode) Use Twist-Pair
MW-Link Unit
NX70-MWLINK �Mount on Basic Motherboard to use Cable
(Multi Wire-Link)
�Mount up to 3 EA including CCU Leased used for
�Function: PLC Link (32 EA, L: 4,096 p, Ld: 4,096 Word), Computer Link Function, Data Transmission NX70-CPU750
(1,020Word/1Command), Remote Programming, Layer Link (Refer to F145, F146) NX70-CPU70p2
�PLC 32 EA/ Layer, 2 Layer, Transmission Speed: 0.5Mbps
�Transmission Distance: Total 800m (up to 1,200 m in case of 250Kbps)
�Interface: RS485 Multi-drop
※ Applicable Model: NX70-CPU750

W-Link Function (W Mode)


�Mount on Basic Motherboard to use
�Mount up to 3 EA including CCU
�Function: PLC Link(16 EA, L: 1,024 p, Ld: 128 Word), Computer Link, Data Transmission Use Twisted-Pair
W-Link Unit NX70-WLINK Cable
(16Word/ 1Command), Remote Programming, Layer Link(Refer to F145, F146)
�PLC 32 EA/ Layer, 2 Layer, Transmission Speed: 0.5Mbps
�Transmission Distance: Total 800m, Interface: RS485 Multi-drop
※ Applicable Model: NX70-CPU750, NX70-CPU70, NX70-CPU70p2

■ Unit for Network (Open Network)


Unit Name Product Code Product Spec Remarks
DeviceNet Slave Unit for NX70 PLC
DeviceNet Master High Speed Photocoupler, 125K, 250K, 500Kbps,
NX70-DNS
Unit Support S/W: SYCON(NCS-DN) S/W

■ Unit for Network (PLC Network)


Kind of Product Product Code (Previous Code) Product Spec Remarks
Mount on the CPU of Motherboard
REMOTE I/O NX70-SLAVE - Upper Master Module: Communicate with N700 PLC (CPL7740) and NX700 PLC
SLAVE Unit (NX-MASTER)Module

OEMax NX Series I 87
NX7Series(All-in One Type PLC)
Unit Name Product Code Product Spec Product Spec Remarks
Basic Type NX7S-10ADR 10점 (DCIN 6점, Relay Out 4점)
(10 p) NX7S-10ADT 10점 (DCIN 6점, TR Out 4점) 2K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
AC110�220V Free Voltage, 24V 0.3A
Basic Type NX7S-14ADR 14점 (DCIN 8점, Relay Out 6점) 확장불가
(14 p) NX7S-14ADT 14점 (DCIN 8점, TR Out 6점)
NX7-28ADR 28점 (DCIN 16점, TR Out 12점) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
Basic Type NX7-28ADT 28점 (DCIN 16점, Relay Out 12점) AC110�220V Free Voltage, 5V 2.0A, 24V 0.4A
(28 p) NX7-28DDR 28점 (DCIN 16점, TR Out 12점) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
NX7-28DDT 28점 (DCIN 16점, Relay Out 12점) DC 24V 입력전원
NX7-48ADR 48점 (DCIN 28점, Relay Out 20점) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
Basic Type NX7-48ADT 48점 (DCIN 28점, TR Out 20점) AC110�220V Free Voltage, 5V 2.0A, 24V 0.4A
(48 p) NX7-48DDR 48점 (DCIN 28점, Relay Out 20점) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
NX7-48DDT 48점 (DCIN 28점, TR Out 20점) DC 24V 입력전원
20점 (DCIN 12점, Relay Out 8점)
NX7-20ADR-6A
Analog 6점(AD 4CH, DA 2CH) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
20점 (DCIN 12점, TR Out 8점) AC110�220V Free Voltage, 5V 2.0A, 24V 0.4A
NX7-20ADT-6A
Basic Type Analog 6점(AD 4CH, DA 2CH)
(Analog) 20점 (DCIN 12점, Relay Out 8점)
NX7-20ADR-4A
Analog 4점(AD 4CH) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
20점 (DCIN 12점, TR Out 8점) AC110�220V Free Voltage, 5V 2.0A, 24V 0.4A
NX7-20ADT-4A
Analog 4점(AD 4CH)
NX7-14EDR 14점 (DCIN 8점, Relay Out 6점)
NX7-14EDT 14점 (DCIN 8점, TR Out 6점)
Extension Type 증설 모듈
NX7-28EDR 28점 (DCIN 16점, Relay Out 12점)
NX7-28EDT 28점 (DCIN 16점, TR Out 12점)

88 I OEMax NX Series
■ Programming Device
�For N-Series, N70, N700, N700a, NX70, NX700 PLC
Unit Name Product Code Product Spec Product Spec Remarks
�Computer S/W with Function of PLC Program Preparation and PLC �N7 PLC
Status Check from Computer/ Network Check Function/ I/O MAP �N70 PLC
WinFPST S/W �NX70 PLC
User S/W and Monitoring , FILE Management/ Storage Function/ ONLINE Edit Above Windows 95
(for Window) �N700, N700H,
Function /Error Check Function / TIME CHART Monitoring Function N700a
�Same to the current WinFPST (for Window) Ver 2.xx �NX700 PLC

�For N-plus Series, SPC10, N70plus, N700plus, NX7, NX70(CPU70p), NX700(CPU700p) PLC
Unit Name Product Code Product Spec Product Spec Remarks
�SPC10 PLC
�Computer S/W with Function of PLC Program Preparation and �N70plus (CPL9215A)
PLC Status Check from Computer/ Network Check Function/ I/O (CPL9216A)
WinGPC MAP and Monitoring , FILE Management/ Storage Function/ �N700plus (CPL7215A)
User S/W Above Windows 95
(for Window) �NX7 PLC
ONLINE Edit Function /Error Check Function / TIME CHART
�NX70 PLC (NX70-CPU70p1)
Monitoring Function (NX70-CPU70p2)
�Same to the current WinFPST (for Window) Ver 2.xx �NX700PLC (NX-CPU700p)

■ Cable for Programming


Unit Name Product Code Product Spec Corresponding Model Remarks

NX-CBLCPU02 2m
Communication �For SPC10, N70plus, N700plus PLC Common use with Communication
Cable for CPU �For NX7, NX70, NX700 PLC Ports of NX70, NX700 CPU Unit
NX-CBLCPU05 5m

■ Cables for Extension


Unit Name Product Code Product Spec Corresponding Model Remarks
NX-EXPCBL15 1.5m Common use with Communication
Extension Cable Use for Interface with Extended Motherboard of NX700 Series
Ports of NX70, NX700 CPU Unit
NX-EXPCBL08 0.8m

OEMax NX Series I 89
■ I/O Harnesses
Unit Name Product Code Product Spec Remarks
NX70 I/O NX70-CBLDC DC IN 32 p Connector Harness Length of Harness 1.5m
(Connector Type) NX70-CBLTR TR OUT 32 p Connector Harness NO. of Pin: 20 Pin
NX-CBLDC DC IN 32 p Connector Harness
I/O Cable ASS'Y NX700 I/O Length of Harness 1.5m
NX-CBLTR TR OUT 32 p/ 64 p Connector Harness
(Connector Type) NO. of Pin: 40 Pin
NX-CBLRY RELAY OUT 32 p Connector Harness
NX70 I/O For Connector Type Unit of
NX-PIN20 20Pin (PIN 20 EA, Connector Hood Included)
(Connector Type) NX70, N70, N700 I/O
I/O Connector ASS'Y
NX700 I/O For Connector Type Unit of
NX-PIN40 40Pin (PIN 20 EA, Connector Hood Included)
(Connector Type) N700 I/O
Remark) Order made acceptable if the length of I/O Cable exceeds 1.5m. Please inquire our Head Office if required.

Remarks
�We have N-Series and N-plus Series. Please pay attention because Command language and User S/W is different.)
�DeviceNet Module can be used regardless of N-Series, N-plus Series.

Unit Name Product Code Name of CPU Module Remarks


N7 Series CPL02323, CPL02343C, CPL02543C.....
N70 Series CPL9210A, CPL9211A
N-Series N700 Series CPL7210A, CPL7211A, CPL6210A, CPL6210B, CPL6215A WinFPST S/W used
NX70 Series NX70-CPU70, NX70-CPU750
NX700 Series NX-CPU750A, NX-CPU750B, NX-CPU750C, NX-CPU750D, NX-CPU700
SPC10 Series SPC-10ADR, SPC-10ADT, SPC-10DR.......
NX7 Series NX7-28ADR, NX7-28ADT, NX7-48ADR, NX7-48ADR.....
N70 Series CPL9215A, CPL9216A
N-plus Series WinGPC S/W used
N700 Series CPL7215A
NX70 Series NX70-CPU70p1, NX70-CPU70p2
NX700 Series NX-CPU700p

90 I OEMax NX Series
OEMax NX Series I 91
NX-CA001A-EN-P 2007. 10

You might also like