Professional Documents
Culture Documents
Contents
■ Characteristics of NX Series 3
■ System of PLC Type 4
■ Network Configuration Chart 6
■ Basic Configuration of NX700 10
■ Basic Configuration of NX70 22
■ Special Modules of NX700/NX70 35
Analog Module 36
Special Module 40
Communication and Network Module 48
Field bus 64
■ Configuration Chart of NX7 67
■ Program Device and Software 72
■ External Dimension 79
■ Product Catalog 84
2 I OEMax NX Series
NX Series
NX700 / NX70 / NX7 Series
OEMAX NX Series I 3
Structure of OEMax Types The OEMax PLC lineup which ranges in size from the
applications. Because of it’s programming (NX-Series,
customers an opportunity to choose the ideal product
NX7-48
CPU70p1
�Single Unit Type with 48points
�384 points
�Communication 2 port
�0.2us
�9k STEP (Expandable)
Alternative Relay �9.6K words
Sequence
Small Scale Control NX7-28
�Single Unit Type with 28points
�Communication 2 port
�9k STEP (Expandable)
4 I OEMax NX Series
small NX7 to the medium-size NX700 is scalable in order to be applicable to a wide range of
NX-plus Series), module, and network diversity and compatibility, OEMax PLC provides
for their application.
NX700 Series
Series
CPU750
�384 points
�0.35us
�32K Step
CPU750A CPU750B CPU750C CPU750D
�Comment Memory �2,048 points �2,048 points �8,192 points �8,192 points
�PID Auto Tuning, etc. (Remote inclusive) (Remote inclusive) (Remote inclusive) (Remote inclusive)
�0.35us �0.35us �0.03us(30ns) �0.03us(30ns)
�16K Step �32K Step �60K Step �120K Step
�PID Auto Tuning, etc. �Comment Memory �Comment Memory �Comment Memory
CPU70p2 �PID Auto Tuning, etc. �PID Auto Tuning, etc.
�384 points
�0.2us
�20K words
CPU700 CPU700p
�1,6 ,600 points �2,048 points(Remote inclusive)
�0.4us �0.2us
�16K Step �20K words
�Comment Memory �2Port
OEMAX NX Series I 5
OEMax PLC Network Configuration Diagram A variety of OEMax PLC network options
low-cost serial networks to Ethernet for
Multi Drop
Small Scale Network
wiring with
Twist Pair Cable
Remote I/O System
SLAVE Unit
SLAVE Unit
6 I OEMax NX Series
are available to meet a wide variety of requirements and environments, ranging from small
large scale control systems.
EtherNet Network
EtherNet Corresponds to TCP/IP and UDP/IP, and widely communicable with
computers and the like on the Network (LAN) through interface with 10BASE5
(for N700a), 100BASE-TX, 10BASE-T, 10BASE5 (for NX700) LAN.
★ Corresponding PLC: N700a PLC, N700H PLC, NX700(CPU750) PLC
■ Have functions like Computer Link, Data Transmission, Remote Programming
between other PLCs interfaced with EtherNet Network and computers
NX700 Series Transmission Speed: 100M bit/s(NX700), 10M bit/s(N700a)
EtherNet Unit Maximum No. of NODEs: 100Node/ Segment, Transmission Method: Base Band
No. of Communication Connections: Maximum 8 Connections, Maximum
Distance between Nodes: 2500m~205m
W-Link Network
NX70 Series PLC Network with Twisted-Pair Cable, economical decentralized
MW-Link Unit
control can be established.
★ Corresponding PLC: Supports NX700, NX70 Series (Excluding NX-
CPU700, NX70-CPU70, NX70-CPU70p1)
■ With Multi-Drop wiring of Twisted-Pair Cable, easily established and
high speed-long distance transmission can be achieved.
Transmission Speed: 0.5MBps, 800m Number of Stations: 32 stations/ 1 layer
Layer: 2 layers Transmission Line: Twisted-Pair Cable
NX70 Series NX70 Series
DeviceNet Network
Scanner Card for
Computer (PC) As a DeviceNet product which is a Open Network, Device Level
DeviceNet Master Card for
PLC Scanner Card (ISA, PCI, PCMCIA) function is standardized with the Open Architecture and mutually
(Master)
(for NX700)
interfaced with the products that has adopted DeviceNet Profile so as
to enable transmitting and /receiving data.
★ Scanner(Master): N700 PLC, NX700 PLC, Computer Cards (PCI, ISA..)
DeviceNet NX70 Series
(Slave) ■ Slip Type, Micro size (104 x 43 x 52mm)
■ Able to interface between different types of DeviceNet products
Transmission Speed: 0.5MBps No. of Nodes: 64 nodes/ Network
Terminal Type Terminal Type Connector Type
(38 pin) (20 pin) (37 pin) NETWORK Protocol: I/O Slave messaging( Group 2 only)
Robot
DeviceNet(Slave) Inverter ODVA Approval: Granted Standard Test of DeviceNet Conformance
OEMax NX Series I 7
High Tech CPU (WinFPST adopted)
■CPU750A *Refer to the attached
■CPU750B
■CPU750C
NX700 Series
■CPU750D
OEMax NX Series I 9
Basic Configuration of NX700
Basic Configuration and Control I/O Point �Basic configuration and Control I/O Point remain unchanged regardless of CPU Type.
(CPU Type : CPU750A, CPU750B, CPU750C, CPU750D, CPU700, CPU700p)
48 points: when configured with 16 points I/O 80 points: when configured with 16 points I/O
192 points: when configured with 64 points I/O 320 points: when configured with 64 points I/O
128 points: when configured with 16 points I/O 160 points: when configured with 16 points I/O
512 points: when configured with 64 points I/O 640 points: when configured with 64 points I/O
10 I OEMax NX Series
Caution Commands and programming tools for CPU700p is different from those of CPU750 series
System Configuration
■ Configuration of units that can be mounted
CPU Unit Special Unit I/O unit Peripheral Device
�NX-CPU750A �A/D, D/A, RTD, TC �16 point type �Computer Software
16k Step, 0.35μ
s
�CCU, SCU unit �32 point type - WinFPST S/W(for CPU750, CPU700)
Communication port 2port
�Positioning (1, 2, 3, 4 axis) �64 point type - WinGPC S/W(for CPU700p)
�NX-CPU750B (Open Collector & LineDrive) �Computer Interface Cable
32k Step, 0.35μ
s �High Speed Counter (1/ 2CH) - NX-CBLCPU02,05
Comment Memory �High Performance High
Communication Port 2port
Speed Counter (4CH)
�NX-CPU750C �Pulse Output unit (4CH)
60k Step, 0.03μ
s �Remote I/O SYSTEM
Comment Memory �MW-LINK SYSTEM
Communication Port 2port �EtherNet SYSTEM
�NX-CPU750D �DeviceNet SYSTEM Motherboard
120k Step, 0.03μ
s
Comment Memory �3 slot type
Communication Port 2port �5 slot type
�8slot type
�NX-CPU700
16k Step, 0.4μ
sμs �10slot type
Comment Memory �12 slot type
Communication Port 1port
※ Combined use for Basic/
�NX-CPU700p Additional setup
20k Step, 0.2μ
s
Communication Port 2port
Use WinGPC S/W ※ Display of slot numbers indicates the
number of I/O and special units mounted
Electricity Source (Power) unit ※ CPU module is not necessary when
motherboard is used for extension
�NX-POWER (AC110/220V) purpose and thus one more slot can be
5V 4A, 24V 0.5A used additionally
�NX-PWR220 (AC 220V) 5V 6A
�NX-PWRDC (DC 24V) 5V 5A
■ Restrictions according to the types of units ○ : Usable △ : Usable according to Version × : Unusable
Input Unit
Output Unit
Type of Units
(W, W2-Mode)
MW-Link Unit
EtherNet Unit
Computer Software
Mountable
*1
*1
*1
modules
*1
�NX-CPU700 ○ ○ ○ ○ ○ × ○ × × ○ ○ × × × × ○
Prototype
CPU �NX-CPU700p (Plus Type) ○ ○ ○ ○ ○ △ ○ △ △ ○ × ○ △ △ × ○ WinGPC
Note) NX-CPU700p type supports some special functions above OS version 2.0.
OEMax NX Series I 11
High Performance CPU Unit (CPU750)
High speed medium-large scaled PLC with Maximum Processing Speed 0.03us(30ns), Capacity of Program 16k~120k,
Sharing same Commands with N700_series and PID Auto Tuning Function and two communication ports mounted. In
addition, large scaled PLC function is compressed into compact size for easy use.
Memory unit
(NX-MEM750A)
�16k STEP(Extended Memory)
�Comment Memory
COM Port Communication Cable
�EPROM Socket TOOL Port
NX-CPU750A NX-CPU750B (Applicable only to CPU750A) NX-CBLCPU02
�16k STEP �32k STEP NX-CBLCPU05
�0.35us �0.35us
�Clock Function �Clock Function C-Language
�Comment Memory BASIC
WinFPST S/W
NX-CPU750C NX-CPU750D
�60k STEP �120k STEP T/P
�0.03us (30ns) �0.03us (30ns)
�Clock Function �Clock Function
�Comment Memory �Comment Memory Computer Computer
■ Characteristics
1. Super high-speed operation speed and sufficient data memory 5. Program edit(insert, delete, correct) function during RUN
CPU TYPE NX700 PLC NX700 PLC NX700 PLC
Item (CPU750A, B) (CPU750C, D) (CPU700) 6. PID Auto tuning function
Operation Command Sequence command 0.35μs 0.03μs 0.4μs Parameter set-up can be done by using command of F355(PID),
(per 1 command) Application command 0.93μs� 0.06μs� Tens of μs� which is an application command
Program capacity 16k,32k step 60k,120kstep 16k step
I/P relay(X) 2,048points 8,192points 2,048points 7. Clock(RTC : Real Time Clock) function basically mounted
O/P relay(Y) 2,048points 8,192points 2,048points Progress of work is programmable by hours and dates with the
Internal relay(R) 4,048points 14,192points 1,568points embedded clock.
Data Capacity
12 I OEMax NX Series
■ Performance Specification
CPU Type NX-CPU750C
Items NX-CPU750A NX-CPU750B NX-CPU750D
항목
Programming Method/Control Method Relay Symbol Method/ Cyclic Operation Method
Control I/O Point 1,600 point (2,048 points when using REMOTE) 1,600points(8,192points when using REMOTE)
Program Memory Basic 16k step (32k steps when extended) Basic 32k step 750C Basic:60k step 750D:Basic 120k
Operation Speed Sq. command 0.35μs/ 1 command ~ 0.03μs/ 1 command ~
(Rep. Value) Appl. command 0.93μs/ 1 command ~ 0.06μs/ 1 command ~
Command Basic command 95 types 95 types
Type Appl. command 428 types 434 types
External I/P(X) 2,048 points (X0�X127F) 8,192p (X0�X511F)
External O/P(Y) 2,048 points (Y0�Y127F) (Usable as internal relay) 8,192p (Y0�Y511F)
Internal Relay(R) 4,048 points (R0�R252F) 14,192p (R0�R886F)
Interface Data(bit)
Link Relay(L) 2,048 points (L0�L127F) (Usable as internal relay) 10,240p (L0�L639F)
Special Internal Relay (R) 176 points (R9000�R910F)
Memory for Operation
File Register(FL) 14.333 words(30717words with extended memory) 30.717words (FL0~FL30716) 32.765words (FL0�FL32764) x 3bank
Link Register(Ld) 256 words (Ld0�Ld255) (Usable as Data Register) 8,448words (Ld0�Ld8447)
Timer/Counter Set Value Area(SV) 1,024 words (SV0�SV1,023) 3,072words (SV0�SV3,071)
Timer/Counter Exp. Value Area(EV) 1,024 words (EV0�EV1,023) 3,072words (EV0�EV3,071)
Index Register (I0~ID) 14 words (I0�ID) 14words (I0�ID) x 16bank
Error Report Relay(E) N/A 2,048points (E0�E2047)
MCR point 256point
No. of Labels (JMP + LOOP No.) Total 256points
Differential Point Unlimited points
Supplementary Timer (Using F137 Command) Unlimited points (Subtractive 0.01 sec. Timer, 0.01 sec.~ 327.67 sec.)
No. of Step Ladder 1,000 process
No. of Subroutine 100 Subroutine
No. of Interrupt Program 1 program (Timed Interrupt: Time interval range 0.5ms ~ 1.5s .)
Comment Memory Usable(but extended memory is required) Basically embedded (12words x 2,730ea)
Clock Function(Calendar Timer) Basically embedded(year, month, day, hour, min., sec., week)
Shift Register Max. 253points
Self Diagnosis Watchdog Timer, Memory error detection, I/O error detection, Battery error detection, Program grammar check, etc.
Link Function PLC Link, Computer Link, Remote Programming, Data Transmission, Modem Function
PID Auto Tuning PID Auto Tuning Function, Using F355(PID) command
Other Functions User Memory(EPROM & EEPROM execution Function), Programming I/P during RUN, Forced I/O, TEST RUN, Constant Scan function
Memory Backup Approx.10,000 hours, Time saving when using extended memory Approx. 8,000 hours Approx. 3,500 hours
■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited
OEMax NX Series I 13
General Purpose CPU Unit(CPU700)
Processing speed 0.4us, programming capacity 16k Step, basic unit of NX700 PLC usable, convenient functions like
program editing during RUN are available. In addition, Comment Memory is basically embedded for easy use.
WinFPST S/W
CPU Unit(NX-CPU700)
�16k STEP Basic Memory
�Comment Memory
■ Characteristics
1. High speed processing and large capacity memory 6. Supports the Handy-Loader that BACKs-Up Programs, etc.
Operation speed is 0.4μsec /1command(basic command), NX-CPU700 module can be interfaced with Handy-
equivalent to that of medium sized PLC and program capacity can Loader(CPL5119) that has memory back-up function. This
be extended up to 15,871 STEP. I/O control point can be used up to product(CPL5119) has not only the handy type programming tool
1,600 points maximum. function but also has back-up memory embedded to store ladder
program and data so as to store the program(approx. for 3 days).
2. Forced I/O & Time Chart Monitoring function Accordingly, down loading and up loading of PLC program for this
Forced input and output on PROGRAM MODE(against Y,R,L) and and that facility can be done with this loader only for convenient use.
on RUN MODE(against X,Y,R, L,T,C) can be done. In addition, the
function of control execution status of 16 points at the same time like 7. Add of diverse Command words
time chart of the logic analyzer is provided so as to be used very SET, RST, Data Transfer Instruction(F70~F78), Compressed shift
conveniently when PLC monitoring and debugging. instruction(F98, F99), supplementary timer instruction(F137, STMR)
are added so as to enable more command words to be used.
3. Program Edit Function during RUN
Programs can be corrected, deleted and inserted during RUN without 8. Comment Memory that can attach comments on the Ladder
interruption. (also available on Ladder Symbol mode) Program is basically embedded
RAM 16K Word(12 letters x 2730 ea) is basically embedded to enable
4. Password Function to attach comments on each interface when preparing programs.
This function sets up Password to protect the User Program, that Because that the contents of comment on interfaces and the like are
does not allow access to the program of PLC by anyone except for recorded inside the CPU module, it is convenient to investigate the
the person concerned so as to prevent the trouble of program in contents of instrumentations and the like after several years.
advance and enhance reliability of the system.
9. EPROM Function(User Memory) is optional
5. 100 % compatibility with the existing N-Series PLC EPROM Socket is optional and the user of EPROM can directly
Compatibility of Commands with the existing N-Series PLC purchase and input the Ladder Program. Accordingly, PLC program
can be driven with EPROM.
(EPROM Socket: NX-ROM700, EPROM IC : 27C256-12
equivalent, 2 ea required)
14 I OEMax NX Series
■ Performance Specification
Item Specification
Control Method Cyclic operation method
Operation Speed 0.4㎲/ 1 Command
Program Capacity Max. 15,871 step(16K Step)
Max. I/O Processing Point 1,600 points
Command Basic Command 45 types
Type Application Command 195 types
External I/P (X) 2,048 points (X0~X127F)
External O/P (Y) 2,048 points (Y0~Y127F)
Interface Data(bit)
Timer. Counter (T/C) Total 256 points ① Timer(0.01 sec. Timer, 0.1 sec Timer, 1 sec. Timer), T0~T199
(points changeable) ② Counter(Pre-set type 1 ~ 32,767Counter) , C200~C255
Data Register (DT) 2,048 words (DT0~DT2047)
Data Memory(word)
■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited
OEMax NX Series I 15
General Purpose CPU Unit(CPU700P) Plus Family Caution Commands and programming tools for CPU700p
is different from those of CPU750 series
Processing Speed 0.2us/1 command, Program capacity 20k words, CPU Unit for plus that can use the basic
unit of NX700 PLC.(Uses WinGPC S/W.)
Comm. Cable
NX-CBLCPU02
NX-CBLCPU05
CPU Unit
(NX-CPU700p)
Computer
WinGPC S/W MMI S/W
T/P, etc.
■ Characteristics
NX-CPU700p is a medium-small sized PLC product intended to provide diverse special modules such as function for high speed processing
of the user program, analog and network module in order to respond suitably to the control environments.
�Control Point 100~1000 point high speed processing for optimal control in the medium scaled control environment
<Basic Command: 0.2us>, productivity improvement intended by embedding the PID function, etc.
�High-speed, large capacity data exchange by direct interface with TOUCH PANNEL is enabled by embedding Da2 channel communication
port and the basic special modules of NX700 can be used.(CCU+ unit, SCU unit, Analog unit, high-speed counter(1CH, 2CH) unit)
�By adopting the diverse I/O modules and detachable terminal block, maintenance/repair and design can be done easily.
Note) High performance special modules(HSC4, Pulse4, Posi 1~4, MW-Link) can be used at above CPU OS Version2.0.
1. Correction of program during RUN 6. Diverse I/O and basic special module support
Correction of program can be done during CPU operation DC24V I/P(16/32/64 points), AC110V I/P, AC220V I/P, Relay
without stopping the system. O/P, TR O/P(16points/32/64points),SSR O/P, A/D, D/A, RTD,
TC, High Speed Counter (1CH, 2CH), CCU+(Comm. leased),
2. PID Processor Embedded SCU(Data Processing Device) can be used.
PID control Logic of 8 loop is embedded so that application of
analog control environment such as temperature/RUN control is 7. Diverse Peripheral Device
exceedingly easy. Equipped with a leased graphic software(WinGPC S/W) for CPU
control, CPU status check and forced I/O, I/O monitoring and
3. Clock(RTC : Real Time Clock) function embedded program download/upload can be done conveniently.
Work process is programmable by hour and day with the
embedded clock. 8. Diverse Communication Function
By providing 2 high speed communication ports, computer link
4. Sufficient program capacity/ back-up function and peripheral devices link without separate module became not
Able to program up to max. 20K words and programs can be only easier but also COM2 port supports user-defined
stored forever by providing ROM Pack module with FLASH communications mode so that bar code reader, Inverter and
back-up method adopted. servo can be linked and controlled by communication.(Binary
communication available)
5. Self Diagnosis Function
Convenient for system error and mal-function detection with the
self diagnosis function.
16 I OEMax NX Series
■ Performance Specification
CPU Type NX-CPU700p
Control Method Program storing, repetitive operation method
External I/O 1,600 points (2,048 points when Remote I/O is used)
Basic Command 28 kinds
Command
Appl. Command 150 kinds
Processing Basic Command 0.2us/step
Speed Appl. Command 0.4~tens of us/step
Program Capacity 20K words
I/O Interface (R) R0.0 ~ R127.15 (2048 points, 128 words)
Link Interface (L) L0.0 ~ L63.15 (1024 points, 64 words)
Internal Interface(M) M0.0 ~ M127.15 (2048 points, 128 words) However, M0.0~ M63.15 can be used as Link Interface
Electrostatic maintenance Interface (K) K0.0 ~ K127.15 (2048 points, 128 words)
Capacity of Special Interface (F F0.0 ~ F15.15 (256 points)
Data Memory
Timer/ Counter 256 channel (timer+counter), set value: 0 ~65535
�Timer: 0.01sec.: CH000 ~ CH063 (64 Ch.), 0.1sec.: CH064 ~ CH255 (192Ch.)
Interface(TC or TIM) �Counter: CH000 ~ CH255 (256 Ch.)
Communication Port 2 : User Memory(EPROM & EEPROM Drive Function), Program I/P during RUN, Forced I/O, TEST RUN,
Port 2
Function Constant Scan Function
■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited
OEMax NX Series I 17
Power(Electricity Source)Unit
Motherboard
Caution �Number of slots of the motherboard is the number of I/O modules and special modules that can be mounted.
�Motherboard of NX700 PLC is used without distinction between basic and extended motherboards.
�Only 1 panel of motherboard can be added to NX700 PLC.
18 I OEMax NX Series
I/P Unit
■ Characteristics
�16 points, 32 points, 64 points I/P Unit
�DC I/P type can use +, -COMMON for all
�Confirmation of operation by LED display
�Photocoupler Insulation for all modules
�Extended user convenience by separating
Terminal blocks (16 point module)
Caution The numbers(1~40) in the below diagram(NX-X32D/ NX-X64D) indicate the numbers
■ External Electrical Schematic Diagram printed on the front side of the product.
(Note)
OEMax NX Series I 19
O/P Unit
■ Characteristics
�16 points, 32 points, 64 points I/P Unit
�Confirmation of operation by LED display
�Photocoupler Insulation for all modules
�Extended user convenience by separating
Terminal blocks (16 point module)
Caution The numbers (1~40) in the below diagram(NX-Y32T/ NX-Y64T, NX-Y32RV) indicate the
■ External Electrical Schematic Diagram numbers printed on the front side of the product.
250VAC
30VDC
Max.
250V AC AC100~240V
30V DC
20 I OEMax NX Series
*Refer to the attached
■ High Performance CPU (WinFPST S/W adopted)
■NX70-CPU750
NX70 Series
■ General Purpose Plus CPU (WinGPC S/W adopted)
■NX70-CPU70p1
■NX70-CPU70p2
OEMax NX Series I 21
Basic Configuration of NX70
Basic Configuration and Control I/O point �Basic configuration of system and I/O control point are equal regardless of the CPU types.
(CPUTypes: NX70-CPU750, NX70-CPU70, NX70-CPU70p1, NX70-CPU70p2)
(NX70-BASE06) (NX70-BASE08)
96p:16p I/O configured 128p:16p I/O configured
192p:32p I/O configured 256p:32p I/O configured
(NX70-BASE10) (NX70-BASE12)
196p:16p I/O configured
160p:16p I/O configured
384p:32p I/O configured
320p:32p I/O configured
■ Free System Configuration: 7 kinds of Motherboard ( 2 slot, 3 slot, 4 slot, 5 slot, 6 slot, 8 slot, 10slot, 12 slot)
�NX70 PLC has 7 kinds of motherboards which can be mounted with each kinds of I/O units freely.
�I/O Module, Power (Electricity source) Module, Special Module and Motherboard are common regardless of CPU Types.
(CPU Type, 4 kinds: NX70-CPU750, CPU70, CPU70p1, CPU70p2)
■ Slot Number Display
�Display of slot numbers on the motherboard indicates the number of mountable I/O units and special modules.
(ex. 12 slot typed NX70-BASE12 motherboard can mount up to 12 I/O units and special modules.)
■ Maximum Control I/O Point 384 Points
�When 12 slot motherboard is used, NX70 PLC is able to use up to max.(192 points for Terminal Block).
�NX70 PLC can not be used with extension. (Only basic motherboard is available.)
22 I OEMax NX Series
System Configuration
■ Configuration of units that can be mounted
CPU Unit Special Unit I/O Unit Peripheral Device
�NX70-CPU70 �A/D, D/A, RTD, TC �8p/8pmixed type �Computer Software
16k Step �CCU, SCU unit �16/16p mixed type - WinFPST S/W(for CPU70, CPU750)
Comment Memory �High Speed Counter (1/ 2CH) �16 point type - WinGPC S/W(for CPU70p)
Comm. port 1port
�High Performance High �32 point type �Computer Interface Cable
�NX70-CPU750 Speed Counter (4CH)
32k Step �Pulse Output unit (4CH)
Comment Memory �Positioning Unit
Comm. port 2port �Remote I/O SYSTEM
�W-LINK SYSTEM
�NX70-CPU70P1
9.6k word �MW-LINK SYSTEM
Comm. port 1port �DeviceNet SYSTEM
Motherboard
�NX70-CPU70P2
20k word �2 slot type
Comm. port 2port �3 slot type
�4 slot type
�5 slot type
�6 slot type
Electricity Source
�8 slot type
(Power) unit �10 slot type
� AC Type �12 slot type
1) NX70-POWER1
(110/ 220V, Free Volt)
5V 4.0, 24V 0.3A ※ NX70 Series can not be extended.
2) NX70-POWER2 ※ Display of slot number indicates the number
(110/ 220V, Free Volt) of mountable I/O and Special Units.
5V 4.5A
� DC Type
1) NX70-PWRDC
(DC24V, Input)
Caution Mutually compatible except for the existing power module, CPU module and motherboard of N70 PLC.
5V 4.5A (Ex. N70 I/O module can be used with NX70 motherboard)
(Ex. N70 CPU(CPL9211A) can not be used with NX70 motherboard)
( NX70-PWRDC )
DC Power Unit (for all slots)
Input Unit
Output Unit
Use
Programming
Tool
*1
*1
OEMax NX Series I 23
CPU Unit (NX70-CPU750)
High speed medium-large scaled PLC with Maximum Processing Speed 0.03us, Capacity of Program 32k, Sharing same
Commands with CPU750 Series for N700 and Comment Memory, PID Auto Tuning Function and two communication
ports basically embedded. In addition, large scaled PLC function is compressed into compact size for easy use.
COM Port
TOOL Port
NX-CBLCPU02,05
NX70-CPU750
C-Language
�32k STEP BASIC WinFPST S/W
�0.35us
�Clock Function
�Comment Memory, PID Auto Tuning T/P
�2 Ports (RS232C)
Computer
■ Characteristics
1. Operation Speed and Sufficient Data Memory
CPU Type NX70-CPU750
6. Clock(RTC : Real Time Clock) Function embedded basically
Item NX70-CPU70
Work process is programmable by hour and day with the
Operation Command Sq. Command 0.35μs 0.4μs embedded clock. .
(per 1 Command) Appl. Command 0.93μs� Tens of μs�
Program Capacity 32k step 16k step
7. RS232C 2 ports mounted on CPU Unit
I/P Relay(X) 2,048 p 2,048 p
O/P Relay(Y) 2,048 p 2,048 p
∙Programming tool(WinFPST S/W) interface with TOOL port
Internal Relay(R) 4,048 p 1,568 p ∙Communication with Touch Panel or computer, etc., with COM Port
Data Register(DT) 6,000 words 2,048 words
File Register(FL) 30,717 words 22,525 words 8. Comm. Port supports up to 115kbps
Data Capacity
Link Relay(L) 2,048 p 1,024 p With drastic improvement of communication speed, program
Link Register(Ld) 256 words 128 words downloading/uploading can be executed speedily. (Comment is
Timer/ Counter(T/C) 1,024 p 256 p embedded basically.)
Pulse Relay(P) 1,024 p N/A
Index Register 14 words 2 words 9. Comment Memory that can attach comments on the Ladder
2. Program Memory 32k step Program is basically embedded
Separate RAM for Comment enables attachment of comments
3. Functions required by the Large scaled PLC mounted. on each interface when preparing programs. Accordingly, it can
∙1ms(0.001 sec.) unit Timer mounted. be used conveniently when reviewing the ladder program or after
∙Floating Point Operation Function (Trigonometric Function, printing.
Index, Algebra, Square Root)
∙Index Register added (14 words, I0~ID) 10. Special Units of NX70 PLC can be used
∙PID Command Words Embedded NX70-CPU750 Unit can use Pulse I/O Unit(4CH) and high
performance high sped counter(4CH), positioning unit(2 axis/4
4. Program Edit(insert, delete and correct) Function during RUN axis) and MW-Link unit. (Impossible with the other CPU
modules)
5. PID Auto Tuning Function
Able to set up Parameter with Command Words, which are
Application Command Words F355(PID)
24 I OEMax NX Series
■ Performance Specification
CPU Type NX70-CPU750
Item
Program Method/Control Method Relay Symbol Method/ Cyclic Operation Method
Control I/O Point 384 point
Program Memory Basic 32k step
Sq. Command 0.35μs/ 1 command ~
Operation
Appl. Command 0.93μs/ 1 command ~
Speed
(Rep. Value) Basic Command 95 kinds
Appl. Command 428 kinds
External I/P (X) 2,048point (X0�X127F)
External O/P (Y) 2,048point (Y0�Y127F) (usable as an Internal Relay)
Interface Data(bit)
■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited
OEMax NX Series I 25
CPU Unit(NX70-CPU70)
Processing Speed 0.4us, Capacity of Program 16k and convenient functions like program editing during RUN included.
In addition, Comment Memory is basically embedded for convenience of users.
Cable
NX-CBLCPU02,05
NX70-CPU70
�16k STEP Basic Memory
WinFPST S/W
�Comment Memory
■ Characteristics
1. High speed processing and large capacity memory 5. 100 % compatibility with the existing N-Series PLC
Operation speed is 0.4μsec /1command(basic command) and
program capacity can be extended up to 15,871 STEP. I/O 6. Supports the Handy-Loader that BACKs-Up Programs, etc.
control point can be used up to 384 points maximum. NX-CPU700 module can be interfaced with Handy-
Loader(CPL5119) that has memory back-up function. This
2. Forced I/O & Time Chart Monitoring function product(CPL5119) has not only the handy type programming tool
Forced input and output on PROGRAM MODE(against Y,R,L) function but also has back-up memory embedded to store
and on RUN MODE(against X,Y,R, L,T,C) can be done. In ladder program and data so as to store the program(approx. for 3
addition, the function of control execution status of 16 points at days). Accordingly, down loading and up loading of PLC
the same time like time chart of the logic analyzer is provided so program for this and that facility can be done with this loader only
as to be used very conveniently when PLC monitoring and for convenient use.
debugging.
7. Add of diverse Command words
3. Program Edit Function during RUN SET, RST, Data Transfer Instruction (F70~F78), Compressed
Programs can be corrected, deleted and inserted during RUN shift instruction(F98, F99), supplementary timer instruction(F137,
without interruption of PLC. (also available on Ladder Symbol STMR) are added so as to enable more command words to be
mode) used.
4. Password Function 8. Comment Memory that can attach comments on the Ladder
This function sets up Password to protect the User Program, that Program is basically embedded
does not allow access to the program of PLC by anyone except RAM for Comment (12 letters x 2730 ea) is basically embedded
for the person concerned so as to prevent the trouble of program to enable to attach comments on each interface when preparing
in advance and enhance reliability of the system. programs. Because that the contents of comment on interfaces
and the like are recorded inside the CPU module, it is convenient
to investigate the contents of instrumentations and the like after
several years..
26 I OEMax NX Series
■ Performance Specification
CPU Type NX70-CPU70
Item
Control Method Cyclic operation method
Operation Speed 0.4㎲/ 1 Command
Program Capacity Max. 15,871 Step (16K Step)
Max. I/O Processing Speed 384 points
Command Basic Command 45 types
Types Application Command 195 types
External I/P (X) 2,048 p (X0~X127F)
External O/P (Y) 2,048 p (Y0~Y127F)
Interface Data(bit)
Timer/ Counter (T/C) Total 256 point ① Timer(0.01sec.Timer, 0.1sec Timer, 1sec. Timer), T0~T199
(Points changeable) ② Counter(Pre-set Type 1 ~ 32,767Counter), C200~C255
Data Register (DT) 2,048words (DT0~DT2047)
Data Memory(word)
Self Diagnosis ① Watchdog Timer ② Memory error detection ③ I/O error detection
④ Battery error detection ⑤ Program grammar check
LINK Function ① PLC Link ② Computer Link ③ Data Transmission ④ REMOTE Programming
PID Function No. of control loops: Max. 32 LOOP, RUN Mode: Forward RUN, Reverse RUN
Sampling Time: 0.1~120.0sec., Control Algorithm: PI-D ∙I-PD (Please refer to the PID Manual for more details.)
■ General Specification
Item Specification
Surrounding Operating Temp. 0 � 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min.
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min.
Insulation Resistance I/O Terminal<-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. Acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs(according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited
OEMax NX Series I 27
General Purpose CPU Unit (NX70-CPU70p1) (NX70-CPU70p2) Caution Programming tool of CPU module for plus is WinGPC S/W.
As a small sized PLC, CPU70p has Processing Speed of 0.2us/ 1 Command and 20k Words of Program Capacity (9.6k
words for CPU70p1) so as to easily process programming and intended high speed and high performance.
WinGPC S/W is supported as a programming tool.
Comm. Cable
NX-CBLCPU02,05
NX70-CPU70p1 NX70-CPU70p2
�9.6kword basic memory �20kword basic memory Computer
�1port (RS232C/ RS485) �2port (RS232C/ RS485) WinGPC
�Clock Function
■ Characteristics
1. Processing Speed of Command Words 7. Diverse I/O and basic special module support
With the leased IC for high speed processing, the processing DC24V I/P(16/32/64 points), AC110V I/P, AC220V I/P, Relay O/P,
speed of basic command words reaches 0.2usec/STEP so as to TR O/P(16points/32points),SSR O/P, A/D(4CH), D/A(4CH),
enable high speed processing. RTD(4CH), TC(4CH), High Speed Counter, SCU(Data
Processing Device) can be processed.
2. Correction of Program during RUN
Program can be corrected during CPU drive without interrupting 8. Preparation of Diverse Motherboards (up to 12 slot motherboard)
the system. 2 slot, 3 slot, 5 slot, 6 slot, 8 slot, 10 slot, 12 slot motherboards
each can be selected when configuring the system.
3. Clock(RTC : Real Time Clock) function
With the embedded clock, the work process is programmable by 9. Maximum Control I/O Point 384 Points
hour and by date. (Supports on NX70-CPU70p2 module only) �When 12 slot motherboard is used, NX70 PLC is able to use up
to max. 384 points(192 points for Terminal Block)
4. Sufficient Program Capacity/ Back-up Function �NX70 PLC can not be used with extension.
Able to program up to Max.20k words(NX70-CPU70p2) and
9.6k words(NX70-CPU70p1). With Flash Back-up method 10. RS232C/ RS485, 2 ports mounted (NX70-CPU70p2 Module)
adopted, programs can be stored separately. With 2 CH Communication Ports embedded, direct interface with
computer and Touch Panel enables large quantity data
5. Self Diagnosis Function exchange, and COM2 port supports user-defined
Self Diagnosis function can be used conveniently for detection of communications mode so that bar code reader, Inverter and
system error or malfunction servo can be linked and controlled by communication.(Binary
communication available).
6. WinGPC Software
With WinGPS S/W, which is a leased graphic software for CPU
control, CPU status check and forced I/O, I/O monitoring and
program downloading/uploading can be done conveniently.
28 I OEMax NX Series
■ Performance Specification Caution Programming tool of CPU module for plus is WinGPC S/W.
■ General Specification
Item Specification
Surrounding Operating Temp. 0 ~ 55℃
Temperature Storage Temp. -25 � 70℃
Surrounding Operating Humidity 30 � 85% RH (without condensing)
Humidity Storing Humidity 30 � 85% RH (without condensing)
I/O Terminal(AC) <-> Frame Ground(Power Unit), AC 1500V 1 min
Withstand Voltage
I/O Terminal(DC) <-> Frame Ground(Power Unit), AC 500V 1 min
Insulation Resistance I/O Terminal <-> Frame Ground(Power Unit), Above100MΩ(at DC 500V Mega)
Vibration Resistance 10 ~ 55Hz 1 sweep/ for I min., Dual Vibration Width 0.75mm , X,Y,Z for 10 minutes to each direction
Impact Resistance Max. acc. Impact Speed & time allowance 15g/ 11ms, X, Y, Z directions 3 times each
Noise Resistance 1500Vp-p Pulse width 50ns, 1μs (according to Noise Simulator)
Operating Environment Corrosive gases and thick dust prohibited
OEMax NX Series I 29
POWER(Electricity Source) UNIT
Basic Motherboard
12 slot Motherboard
(NX70-BASE12)
Caution �Number of slots of the motherboard is the number of I/O modules and special modules that can be mounted.
�Motherboard of NX70 PLC is the Basic motherboard only. (can not be extended)
30 I OEMax NX Series
I/P Unit
Caution The numbers (1~20) in the below diagram(NX70-X16D/ NX70-X32D) indicate the numbers
■ External Electrical Schematic Diagram printed on the front side of the product.
(Note1)
OEMax NX Series I 31
O/P Unit
■ Characteristics
�16 point, 32 point O/P Unit
�Confirmation of operation by LED Display
�Photocoupler Insulation for all modules
�Connector Type (32 point) can get much
larger I/O numbers per each area.
Caution TTThe numbers (1~20) in the below diagram(NX70-Y32T) indicate the numbers printed
■ External Electrical Schematic Diagram on the front side of the product.
NX70-Y32T NX70-Y16R
NX70-Y16T NX70-Y16RV NX70-Y16SSR
NX70-Y32P
AC100~240V
32 I OEMax NX Series
I/O Combined Unit
■ Characteristics
�NX70-XY16 : DCIN 8 P/ Relay OUT 8 P
�NX70-XY32 : DCIN 16 P/ TR OUT 16 P
�DC I/P Type is able to use both +, -COMMON
�Confirmation of operation by LED Display
�Photocoupler Insulation for all modules
(NX70-XY16) DC IN 8 p (NX70-XY32) DC IN 16 p
Relay OUT 8 p TR OUT 16 p
Combined Unit Combined Unit
OEMax NX Series I 33
34 I OEMax NX Series
NX700 / NX70 Series Special Module
Analog, HSC, Positioning, Communication, Network, Software
Special Function Modules Refer to the attached
NX70 NX700
Analog
I/O
A/D 4CH D/A 2CH D/A 4CH A/D 8CH D/A 4CH D/A 8CH
Temperature
Control
(RTD,TC)
High Speed
Counter
HSC 1CH HSC 2CH HSC 4CH HSC 1CH HSC 2CH HSC 4CH
Pulse
Control
Position
Control
Pulse 4 / HSC4 POSI2 POSI4 Pulse 4 / HSC4 POSI1 POSI2 POSI3 POSI4
Serial
Communication
Network
Remote
System
Field bus
DeviceNet DeviceNet
Slave Master
OEMax NX Series I 35
Analog I/P Unit(A/D)
■ Characteristics
Deviation can be adjusted without separate volume. Especially, 3. DC/DC and Photocoupler Insulation between Channels
conversion speed and resolution that decide diverse analog I/P
range and performance were processed to high speed and high 4. Diverse Data Process Method
accuracy. There are two methods available for Analog Data Process and
Address Designation① by way of Shared Memory
1. NX70 A/D Module ② by way of I/O Interface, which can be conveniently selected to
NX700 A/D Module fit for purposes to use.
■ Performance Specification
NX70-AI8V (Voltage I/P), 8CH NX70-AI8C (Current I/P), 8CH
NX70 Series
NX70-AI4V (Voltage I/P), 4CH NX70-AI4C (Current I/P), 4CH
NX700 Series NX-AI8V (Voltage I/P), 8CH NX-AI8C (Current I/P), 8CH
Analog I/P Range Voltage: 0�10V, 0�5V, ±10V, ±5V Current : 0�20mA, 4�20mA, ±20mA
Digital Conversion 16 BIT Binary with sign (Complement of 2)
Converter Type 16BIT A/D Converter
0~10V(0~32767), (0~20000), (0~16383).. 0~20mA(0~32767), (0~20000), (0~16383)..
Characteristics of I/O *1 0�5V(0�32767), (0~20000), (0~16383).. 4�20mA(0�32767), (0~20000), (0~16383)..
±10V(-32767�32767), (-20000�20000).... ±20mA(-32767~32767), (-20000�20000)....
±5V(-32767�32767), (-20000�20000)....
Max. Resolution Capacity *1 0.153mV, (0.305mV), ........ 0.519uA, (0.61uA), ......
Overall Accuracy ±0.2%/ F.S (25℃) ±0.3%/ F.S (25℃)
Conversion Speed 1.25ms/ CH
External I/P Imped. 500kΩ 249Ω
Absolute Max. I/P Voltage: ±15V, Current: ±30mA Voltage: ±7.5V, Current:±30mA
Insulation Method �Between I/P CH and Internal Circuit: DC/DC Converter, Photocoupler Insulation �Between I/P CH and I/P CH: No Insulation
I/O Points Occupied �I/O Interface Method �Shared Memory Method
Other Functions CH Conversion ON/ OFF Function
Internal Operating Current (5V) �NX70: Below 5V 290mA, External Power 24VDC Unnecessary �NX700: Below5V 270mA
External Interface Method �NX70: 20pin Terminal Block Interface (M3.0) �NX700: 20pin Detachable Terminal Block Interface (M3.5)
*1. Up to high resolution and general resolution can be selected with regard to I/O characteristics and maximum resolution, which can be selected according to Dip S/W under the product.
Stability of conversion speed and conversion data is different according to the resolution. (Refer to the Manual for details.)
*2. It is recommended that the number of D/A modules on the motherboard to be min. below 8 EA. (There is restriction in operating current when the channels operate simultaneously even though there
is no problem in mounting.)
36 I OEMax NX Series
Analog O/P Unit(D/A)
Temperature Recorder
�NX700 D/A Unit �NX70 D/A Unit
■ Characteristics
Deviation can be adjusted without separate volume. Especially, 4. Diverse Data Process Method
conversion speed and resolution that decide diverse analog I/P There are two methods available for Analog Data Process and
range and performance were processed to high speed and high Address Designation ① by way of Shared Memory
accuracy. ② by way of I/O Interface, which can be conveniently selected to
1. NX70 D/A Module fit for purposes to use.
NX700 D/A Module 5. High Speed Process
2. DC/DC Insulation between Channels and Internal Circuits By adopting 14bit D/A Converter, process is done with high
accuracy conversion Data, as well as with the high speed of
3. Drastically improved Resolution 1.25ms/CH.
The level of Resolution is max. 0.153mV with Voltage Type and
0.519uA with Current Type.
■ Performance Specification
Voltage O/P Current O/P
Product Code NX70 NX700 NX70 NX700
NX70-AO2V NX70-AO4V NX-AO4V NX-AO8V NX70-AO2C NX70-AO4C NX-AO4C NX-AO8C
Analog O/P ±10V, 0�10V, ±5V, 0�5V 0�20mA, 4�20mA
No. of Analog O/P CH 2 CH 4 CH 4 CH 8 CH 2 CH 4 CH 4 CH 8 CH
Digital Conversion 16 BIT Binary with sign (Complement of 2)
Converter Type 14BIT D/A Converter
1) ±10V (-16,383�16,383), (-10,000�10,000)
Characteristics Of I/O *1 2) 0�10V (0�16,383), (-0�10,000) 1) 0�20mA (0�16,383), (-0�10,000)
3) ±5V (-16,383�16,383), (-10,000�10,000) 2) 4�20mA (0�16,383), (-0�10,000)
4) 0�5V (0�16,383), (-0�10,000)
Max. Resolution Capacity *1 0.6mV (0.305mV, 0.5mV, 1mV) 1.2uA (1.037uA, 1.7uA, 2uA)
Overall Accuracy ±0.2%/ F.S (25℃) ±0.4%/ F.S (25℃)
Conversion Speed 2.5ms / CH
O/P Impedance Below 0.1Ω Above 10Ω
O/P Allowable Load Resistance Above 5KΩ Below 500Ω
Insulation Method �Between O/P CH and Internal Circuit: DC/DC Converter, Photocoupler Insulation �Between O/P CH and O/P CH: No Insulation
I/O Points Occupied �I/O Interface Method, 8CH:128p O/P, 4CH:64p O/P, 2CH:32p O/P �Shard Memory Method:16p
Internal Operating Current(5V) Below 5V 230mA Below 5V
Below5V 380mA Below 5V 500mA
Below 5V 310mA Below 5V 700mA 900mA
*2 (D/A O/P: (D/A O/P: (D/A O/P:
(D/A O/P:80mA/ CH) (D/A O/P: 20mA/ CH) (D/A O/P:
80mA/ CH) 20mA/ CH) 20mA/ CH)
20mA/ CH)
External Interface Method �NX70 : 20 pin Terminal Block Interface (M3.0) �NX700 : 20 pin Detachable Terminal Block Interface (M3.5)
*1. Up to high resolution and general resolution can be selected with regard to I/O characteristics and maximum resolution, which can be selected according to Dip S/W under the product.
Stability of conversion speed and conversion data is different according to the resolution. (Refer to the Manual for details.)
*2. It is recommended that the number of D/A modules on the motherboard to be min. below 8 EA. (There is restriction in operating current when the channels operate simultaneously even though
there is no problem in mounting.)
OEMax NX Series I 37
RTD Unit(Resistance Temperature Detector Unit)
�Diverse Data Process Method
1) Application Command 〔READ〕 reading method
2) I/P Interface reading method
-200~660℃
NX700 RTD Unit NX70 RTD Unit -200~510℃
■ Characteristics
High speed and high accuracy process is enabled by adopting 24bit Σ- 4. Diverse Data Process Method
Δ A/D converter and has diverse I/O range and self calibration function. There are two methods available for Analog Data Process and
Address Designation① by way of Shared Memory ② by way of
1. NX70 RTD Module I/O Interface, which can be conveniently selected to fit for
NX700 RTD Module purposes to use.
■ Performance Specification
NX70 NX70-RTD8 (8CH) *to be released NX70-RTD4 (4CH)
Product Code
NX700 NX-RTD8 (8CH) NX-RTD4 (4CH)
RTD Sensor 3-Wire Method
RTD I/P CH Numbers 8 CH 4 CH
Digital Conversion 16 BIT Binary with symbol (Complement of 2)
Converter Type 24BIT Σ-Δ A/D Converter
① Pt100 (α=0.00385, -200�650℃ => -2,000�6,500 ⑤ 300Ω (10mΩ/ BIT)
Characteristics of I/O ② Pt200, Pt500, Pt1000 ⑥ 600Ω (20mΩ/ BIT)
(Applicable Temperature
③ JPt100 (α=0.00385, -200�600℃ => -2,000�6,000) ⑦ 2000Ω (100mΩ/ BIT)
Sensor & Digital O/P)
④ Jpt200, Jpt500, Jpt1000 ⑧ NI100, NI120, CU10
Max. Resolution Capacity 0.1℃, 0.1℉, 10mΩ, 20mΩ
Overall Accuracy ±0.1%/ F.S (25℃)
Conversion Speed 60ms/ CH
External I/P Impedance 10MΩ
Current Source 1mA (Excitation Current)
Insulation Method �Between O/P CH and Internal Circuit: DC/DC Converter, Photocoupler Insulation �Between O/P CH and O/P CH: No Insulation
�I/O Interface Method: 128 p I/P �I/O Interface Method:64 p I/P,
I/O Points Occupied
�Shared Memory Method:16 p I/P �Shared Memory Method:16 p I/P
Internal Operating Current(5V) Internal Power Source Below 5V 290mA Internal Pwr Source Blw 5V 280mA
External Interface Method �NX70 : 20 pin Terminal Block Interface (M3.0) �NX700 : 20 pin Detachable Terminal Block Interface (M3.5)
38 I OEMax NX Series
TC(ThermoCouple) Unit
Sensor Type
B,R,S,N,K,E,J,T,L,U,C,D
+
※ TC: ThermoCouple
■ Characteristics
High speed and high accuracy process is enabled by adopting 24bit Σ- 4. Diverse Data Process Method
Δ A/D converter and has diverse I/O range and self calibration function. There are two methods available for Analog Data Process and
Address Designation; ① by way of Shared Memory ② by way of
1. NX70 TC Module I/O Interface, which can be conveniently selected to fit for
NX700 TC Module purposes to use.
■ Performance Specification
NX70 NX70-TC8 (8CH) to be released NX70-TC4(4CH)
Product Code
NX700 NX-TC8 (8CH) NX-TC8 (4CH)
Digital Conversion 16 BIT Binary with symbol (Complement of 2)
TC Input CH 8 CH 4 CH
Converter Type 24BIT Σ-Δ A/D Converter
OEMax NX Series I 39
High Speed Counter Unit(HSC1,2)
As a High Speed Counter with 100Kcps high speed response, monitor and data set-up for the contents of counter is simple and easy.
(NX70-HSC1: High speed counter function and simple pulse O/P function, NX70-HSC2, NX-HSC1, NX-HSC2 : High speed counter function only)
2. 100Kcps high speed response and wide value
I/P response of 100kcps enabled. The range of value has 24 bit sign (binary)
and covers -16,777,216~ 16,777,215.
40 I OEMax NX Series
■ Examples of Application using High Speed Counter(HSC) �NX700 :NX-HSC1 Unit
NX-HSC2 Unit
Example of Counting RPM at Encoder O/P and compare with RPM at Setup �NX70 :NX70-HSC 1Unit
NX70-HSC 2Unit
Inverter
(HSC Function)
M
C>P Pause I/P
HSC
Example of configurating controls of motor driver with 2 pulse O/P and by counting RPM of motor �NX70 : NX70 : Applicable to NX70-HSC1 Unit only
Motor
P.OUT 1 F/V I/P
INA
INB
Encoder O/P
OEMax NX Series I 41
High performance High Speed Counter(4CH) Units are
High Performance High Speed Counter(4CH) �NX700 : NX-CPU750A/ B/ C/ D, 700P Unit
�NX70 : can be used with NX70-CPU750, CPU70 P2 Unit only
HSC 4CH with high speed response of 200Kcps mounted. Range of Coefficient is 32 Bit with functions of HSC 4CH, Interrupt
I/P 8 and comparative O/P 8 point. In addition, unused interface can be used with common I/O 32 points.
M
C>P Pause I/P
■ Characteristics
1. High Speed Response with HSC 200K count/s 5. Interrupt I/P 8 points embedded
Enabled precision control with embedded 4CH of HSC I/P with Interrupt program can be activated when the Elapsed Value
max. 200kHz. conforms or in accordance with the timing of external I/P signal.
Control with out delay or disorder can be done when any
2. Wide ranged Coefficient Value(32 bit with symbol attached) malfunction occurs at the device operating at high speed.
Coefficient range is with 32 bit sign(binary) that covers the range
of -2,147,483,648 ~ +2,147,483,647. 6. Conventional I/O Function(I/O combined 32 points)
Operates as a 16 IN/16 OUT I/O Combined Unit at the initial
3. I/P Time Constant Function to prevent Noise-related Count stage when operation of mode setup switch or shared memory
due to I/P of Noise setup are not made. I/O of other functions precedes when using
Sensitivity can be changed by using the I/P Time Constant other functions but the part without function allotment can be
Function in order to prevent mis-counting due to noise. used as I/O.
(4, 8, 16, 32 /us)
7. Enables High-Efficiency System Configuration
4. Compared O/P Interface 8 points embedded With one unit of high performance HSC module, HSC, Interrupt,
High performance HSC(4CH) has embedded 8 points of O/P Compared O/P and conventional I/O functions are all mounted
allotted randomly. Fractions of Counter is changeable. Can be so that economic system configuration can be done.
used at change of speed or pause signal when controlling the
motor by inverter. 8. Enables Selection of Diverse Counter I/P Mode
Able to respond to the phase difference I/P mode that can count
2 phase pulse of rotary encode and direction discrimination
mode, and the separate I/P mode that are CW and CCW I/P.
42 I OEMax NX Series
■ Performance Specification
For NX700 PLC For NX70 PLC
Product Code
NX-HSC4 NX70-HCS4
Insulation Method Photocoupler Insulation
Rated I/P Voltage 24V DC
Rated I/P Current Approx. 7.5mA (when 24V DC is used)
I/P Impedance Approx. 3.2 kΩ
Spec. Operating Voltage Range 20.4V DC � 26.4V DC
of Min. ON Vol. / ON Cur. 19.2V / 6mA
I/P Max. OFF Vol./ OFF Cur. 5.0V / 1.5mA
Response OFF → ON Below 1us
Time ON → OFF Below 2us
I/PTime Constant Setup *1 N/A, 4us, 8us, 16us, 32us (2 I/P Unit Setup)
Common Method 16 points/ COM
No. of Counter Channels 4 CH
Coefficient Range 32bit sign attached ( -2,147,483,648 ~ +2,147,483,647 )
Speed of Max. Coefficient *1 200kHz
Counter I/P Mode 3 Mode(Phase difference I/P mode, Direction Discrimination mode: Pulse + Direction, Separate I/P mode : CW, CCW )
Min. I/P Pulse Width *1 2.5us
Multiply Function 1 Multiply, 2 Multiply, 4 Multiply
Others Compared O/P 8 points
Interrupt Point *2 N/A, 1p/Unit, 8p/Unit (according to mode setup switch)
Interrupt Interrupt Process Delay Below 160 us (when using NX-CPU750A, CPU750B)
Below 160 us
below50 us (when using NX-CPU750C, CPU750D)
Insulation Method Photocoupler Insulation
Rated Load Voltage 5V DC � 24V DC
Rated Load Voltage Range 4.75V DC � 26.4V DC
Max. Load Current 0.1A (A11~A18, B11~B14 Terminal Block), 0.1A【Ⅱ】
( A1�A8,
【Ⅱ】B1�B4 Terminal Block),
0.8A (B15~B18 Terminal Block) 0.8A【Ⅱ】
( B5�B8 Terminal Block)
Leakage Current on OFF Below 1uA
O/P
Max. Voltage Drop on ON Below 0.5V
Spec.
Response OFF → ON Below 1us
Time ON → OFF Below 1us
Surge Killer Zener Diode
Common Method 16 p / Common
External Power Voltage 20.4V DC � 26.4V DC
Supply Current(when 24V DC is used) Below 90mA
Counter Compared O/P 8 p (A11 ~ A18 Terminal Block) 8 p【Ⅱ】
( A1 ~ A18 Terminal Block)
External Terminal Block Interface 40 pin Connector x 1 EA 20 pin Connector x 2 EA
*1. The Value is when I/O Time Constant (filter) Setup is not available.
*2. When using interrupt with 1 point/ unit setup, in case of NX700, interrupt from the external I/P terminal block B1(X8) or interrupt program (one of INT16.INT23) from
compared 0 will be activated.
OEMax NX Series I 43
Pulse I/O Unit(4CH)
Pulse I/O Unit(4CH) �NX700 : NX-CPU750A/ B/ C/ D, 700P Unit
�NX70 :can be used on NX70-CPU750, CPU70P2
Have 4LOOP pulse O/P and HSC embedded at the same time together with all functions of high performance HSC (NX-
HSC4)(200Kcps HSC 4CH mounted, coefficient range 32 bit, Interrupt I/P 8 point, Compared O/P 8 point and Common I/O 32
points). In addition, 100KHz pulse O/P 4CH or 40KHz PWM O/P 4CH can be used.
M
C>P Pause I/P
Pulse O//P
1)Direction Discrimination
(pulse+direction)
2)Separated O/P(CW, CCW)
■ Characteristics
1. Pulse O/P, 100KHz 4CH 6. Compared O/P Interface 8 points embedded
Maximum Pulse O/P is 100kHz and have 2 types of O/P mode Pulse I/O Unit has embedded 8 points of O/P allotted randomly.
(Direction Discrimination O/P: Pulse + Direction, Separate O/P: CW, Fractions of Counter is changeable. Can be used at change of
CCW). O/P frequency can be setup by 1 Hz units and high speed speed or pause signal when controlling the motor by inverter.
process is enabled because that I/P setup can be done with high
speed counter by internal interface of unit. 7. Interrupt I/P 8 points embedded
Interrupt program can be activated when the Elapsed Value
2. PWM O/P, 30KHz 4CH conforms or in accordance with the timing of external I/P signal.
Maximum 30KHz of PWM O/P can be done and Duty ratio can be Control with out delay or disorder can be done when any malfunction
setup by 1 % units from 0 to 100%. occurs at the device operating at high speed.
3. High Speed Counter 200KHz 4CH 8. Conventional I/O Function (I/O combined 32 points)
Precision control is enabled with the embedded 4CH of maximum Operates as a 16 IN/16 OUT I/O Combined Unit at the initial stage
200kHz high speed I/P. when operation of mode setup switch or shared memory setup are
not made. I/O of other functions precedes when using other
4. Wide ranged Coefficient Value(32 bit with symbol attached) functions but the part without function allotment can be used as I/O.
Coefficient range is with 32 bit sign(binary) that covers the range of -
2,147,483,648 ~ +2,147,483,647. 9. Enables High-Efficiency System Configuration
With one unit of Pulse I/O, HSC, Interrupt, Compared O/P and
5. I/P Time Constant Function to prevent Noise-related Count due conventional I/O functions are all mounted so that economic system
to I/P of Noise configuration can be done. .
Sensitivity can be changed by using the I/P Time Constant Function
in order to prevent mis-counting due to noise. (4, 8, 16, 32 /us)
44 I OEMax NX Series
■ Performance Specification
For NX700 PLC For NX70 PLC
Product Code
NX-PULSE4 NX70-PULSE4
Insulation Method Photocoupler Insulation
Rated I/P Voltage 24V DC
Rated I/P Current Approx. 7.5mA (when 24V DC is used)
I/P Impedance Approx. 3.2 kΩ
Spec. Operating Voltage Range 20.4V DC � 26.4V DC
of Min. ON Vol. / ON Cur. 19.2V / 6mA
I/P Max. OFF Vol./ OFF Cur. 5.0V / 1.5mA
Response OFF → ON Below 1us
Time ON → OFF Below 2us
I/PTime Constant Setup *1 N/A, 4us, 8us, 16us, 32us (2 I/P Unit Setup)
Common Method 16 points/ COM
No. of Counter Channels 4 CH
Coefficient Range 32bit sign attached ( -2,147,483,648 ~ +2,147,483,647 )
Speed of Max. Coefficient *1 200kHz
Counter I/P Mode 3 Mode(Phase difference I/P mode, Direction Discrimination mode: Pulse + Direction, Separate I/P mode : CW, CCW )
Min. I/P Pulse Width *1 2.5us
Multiply Function 1 Multiply, 2 Multiply, 4 Multiply
Others Compared O/P 8 points
Interrupt Point *2 N/A, 1p/Unit, 8p/Unit (according to mode setup switch)
Interrupt Interrupt Process Delay Below 160 us (when using NX-CPU750A, CPU750B)
Below 160 us
below50 us (when using NX-CPU750C, CPU750D)
Insulation Method Photocoupler Insulation
Rated Load Voltage 5V DC � 24V DC
Rated Load Voltage Range 4.75V DC � 26.4V DC
Max. Load Current 0.1A (A11~A18, B11~B14 Terminal Block), 0.1A【Ⅱ】
( A1�A8,
【Ⅱ】B1�B4 Terminal Block),
0.8A (B15~B18 Terminal Block) 0.8A【Ⅱ】
( B5�B8 Terminal Block)
Leakage Current on OFF Below 1uA
O/P
Max. Voltage Drop on ON Below 0.5V
Spec.
Response OFF → ON Below 1us
Time ON → OFF Below 1us
Surge Killer Zener Diode
Common Method 16 p / Common
External Power Voltage 20.4V DC � 26.4V DC
Supply Current(when 24V DC is used) Below 90mA
Counter Compared O/P 8 p (A11 ~ A18 Terminal Block) 8 p (A11 ~ A18 Terminal Block)
External Terminal Block Interface 40 pin Connector x 1 EA 20 pin Connector x 2 EA
No. of Channels 4CH(B11 ~ B18 T/B) 4CH (【Ⅱ】B1 � B8 T/B)
Pulse
Max. O/P Frequency *3 100KHz
O/P
O/P Mode 2 Mode (Direction Discrimination O/P: Pulse + Direction, Separate O/P: CW, CCW )
No. of Channels 4CH (B15 . B18 T/B) 4CH (B15 . B18 T/B)
PWM Max. Load Current 0.8 A
O/P Cycle *3 1Hz � 30KHz (1Hz Unit)
Duty *3 0 � 100% (1% Unit)
*1. The Value is when I/O Time Constant (filter) Setup is not available.
*2. When using interrupt with 1 point/ unit setup, in case of NX700, interrupt from the external I/P terminal block B1(X8) or interrupt program (one of INT16.INT23) from
compared 0 will be activated.
*3. At maximum load current and resistance load, there may be distortion at O/P waveform according to load current or type of load.
OEMax NX Series I 45
Positioning Unit
1 Axis, 2 Axis, 3 Axis, 4 Axis Unit. Enabled high speed, high accuracy positioning with Speed Command Maximum 1Mpps. Have linear
interpolation, circular interpolation function and able to realize smooth activation/pause with s-shaped acceleration/deceleration
function. In addition, real time O/P was enabled by manual pulse generator with pulse generator I/P function.
■ Kinds of Product ■ Characteristics
1. High speed, high accuracy positioning was enabled
withmaximum 1M pulse/s of pulse speed.
2. Multi axis control was enabled by mounting 4 axes in 1unit.
3. Made Tact-Time reduction possible with high speed activation
time (activation time 0.1ms)
Tact-Time can be reduced by selecting high speed activation mode.
2 axis unit
4. Parameter setup was simplified and automatic acceleration
1 axis unit /deceleration was enabled with data setup.
(NX-POSI2)
(NX-POSI1)
(NX70-POSI2)
5. Smooth activation/pause was realized with s-shaped
acceleration/deceleration function
Speed No. of O/P Pulse
(Pulse/s) 100000
Target Speed
5000
Activation Speed
100 t(ms)
Acc/Deceleration Time
3 axis unit 200ms
4 axis unit
(NX-POSI3) (NX-POSI4)
(NX70-POSI4)
6. Able to select Pulse O/P Method (Open Collector or Line Drive)
Able to respond through interface with pulse I/P method drive
(AC/DC servo drive, stepping drive). This positioning unit can
interface with any kind of drive because it can select and use
Open Collector O/P or Line Drive O/P.
7. Real time O/P was enabled by manual pulse generator with pulse
generator I/P function.(Max. 1,000 multiply with Multiply Function)
■ Kinds of Product
46 I OEMax NX Series
■ Performance Specification
4Axis Unit 2Axis Unit
3Axis Unit 1Axis Unit
Item (NX-POSI4) (NX-POSI2)
(NX-POSI3) (NX-POSI1)
(NX70-POSI4) (NX70-POSI2)
Occupied I/O Point 128 P (I/P 64P, O/P 64P) 64 P (I/P 32P, O/P 32P)
Mountable Slot Basic Motherboard (extended motherboard)
No. of Control Axes Independent 4 Axes Independent 3 Axes Independent 2 Axes Independent 1 Axes
Positioning Com. Unit Pulse Unit (Increment, Absolute) is commanded by program
Command Com.Range Sign attached 32 bit (-2,147,483,648 ~+2,147,483,647 pulse)
�When Line Drive is used: 1pulse/s ~ 1M pulse/s
Com. Range �When Open Collector is used: 1pulse/s ~ 200K pulse/s
Speed
(setup can be done by 1pps unit)
Command
Acc/Dec. Method Linear Acc/Deceleration, S-shape Acc/Deceleration
Acc/Dec. Time 0�32,767ms
Return to 0 Point speed Speed setup can be done (return speed, search speed change)
Return to 0 point
I/P Terminal Block 0 Point I/P, Near 0 Point I/P
�E point Control(Linear,S-shaped Acc/Deceleration Select) *1
�P point Control(Linear,S-shaped Acc/Deceleration Select) *1
Operation Mode �Return to 0 Function (Linear,S-shaped Acc/Deceleration Select)
�JOG Drive Function (Linear,S-shaped Acc/Deceleration Select) *1
�Pulse Generator I/P Function (Multiply x1, x2, x5, x10, x50, x100, x500, x1000 can be selected)
Activation Time Below 0.1ms
O/P Mode Pulse/ Sign Mode, CW/CCW Mode (transfer by DIP S/W)
Other Functions Deviation Counter Clear Signal O/P Interface
External Power Supply *3 24V DC (21.6 ~ 26.4V DC)
*1. Each E point control and P point control indicate Acc/Deceleration control as shown in the below picture.
Speed
[pulse/s]
Simple Acc/Deceleration
control moving to END point P Point
Control
Time [ms]
*2. Target speed change during RUN can be made if linear acc/deceleration RUN is selected.
*3. Power is supplied from the external connector at positioning module.
OEMax NX Series I 47
Computer Communication Unit (CCU)
Caution CCU module can not be used with Plus Series.
This is a leased communication unit that enables 1:1 or 1:N two way communication by using Computer and own CCU
protocol, as well as executing computer link function and data transmission function.
Computer
∙MMI S/W
∙(C-language, BASIC)
* CCU function is available if“COM”ports of CPU750 for NX700 and NX7-CPU750 module are used.
1. Communication between PLC and Computer can be realized 4. Operating status of PLC can be supervised or monitored from Computer
easily and economically Operation status of each kind of Relay(Bit Data) or Register(Word
1:1 or 1:N interface can be achieved with a computer having RS232C Data) can be supervised or Data WRITE(I/P) can be done from the
port without specific interface and regardless of type of the Computer.
computer. READ/ WRITE of data can be done without complex
system configuration. 5. Modem Transmission enabled
Can be used in long-distance communication by utilizing the
2. Communication between PLC↔Computer with SECTOCOL-COM common public lines because this unit responds to HAYES AT
Communication with computer having RS232C port can be used Comment type modem.
according to SECTOCOL-COM format which is a CCU Protocol.
(Example of configuration: %01#RCSX0000IDcr) 6. Any PLC Data configured with NETWORK can function READ/ WRITE
In particular, this unit can display enormous power because that
3. Communication between PLC(CCU) ↔ Display Panel Device computer link function against any PLC, that is interfaced with LINK
(TOUCH PANEL) LOOP(including LINK LOOP1/LINK LOOP2) with the computer linked
There is no problem in interfacing because most of the famous with CCU when PLC is configured in Network, can be used. (for more
display panel devices (HAKKO, DIGITAL, PATLITE, etc.) have details, please refer to the CCU Manual「LC(Layer Control
protocols embedded Command)」.)
■ Configuration of SECTOCOL-COM Protocol
�Summary for Comments and Functions (SETOCOL) ■ Performance Specification
Comment Explanation of contents Item Specification
RCS Interface Information by 1point unit READ Interface RS232C 1port
WCS Interface Information by 1point unit Write
RCP Interface Information by multi point unit READ Transmission Speed 300 /600/ 1200/ 2400/ 4800/ 9600 / 19200bps
WCP Interface Information by multi point unit Write (with DIP switch under CCU Unit)
RCC Interface Information by Word Unit READ Communication Method FULL DUPLEX Method
WCC Interface Information by Word Unit Write
SC Word Unit Preset of Interface Area Activation Method START - STOP Method
RD Data Area READ Transmission Code ASCII
WD Data Area WRITE
STOP BIT : 1bit / 2bit
SD Preset of Data Area
RS PRESET Value Area READ of Timer/Counter Trans. Data Format Parity : EVEN/ ODD
WS PRESET Value Area Write of Timer/Counter Length of Data : 7bit / 8bit
RK PASS Value Area READ of Timer/Counter
WK PASS Value Area Write of Timer/Counter End Point Code: Carriage Return (cr) Fix
MC Register and Unregister of Monitor Interface Data Transmission Sequence By Character Unit transmit from bit 0
MD Register and Unregister of Monitor Data Trans.Unit
Computer From Header (%) to Terminator (cr)
MG Monitoring Start
RR READ of System Register
Link Max. Length of Message Max. 118 letters/ 1 frame ( % ~ up to cr )
WR Write of System Register Data Trans.Unit From Header (?) to Terminator (cr)
RT Status READ of PLC Link Max. Length of Message Max. 240 letters/ 1 frame ( ? ~ up to cr )
RM Remote Control (RUN/ PROG Mode Transfer)
AB Transmission Pause Command Modem Control Hayes Co. AT Command Method, 2400bps
48 I OEMax NX Series
■ Wiring Diagram �Wiring Diagram is different from those of the existing N70, N700 Series.
Caution �Special caution is required because“SG”of Communication port is No. 5.
(Without FLOW Control Method)
CCU (9P) Computer (9P)
Pin No Mnemonic Pin No Mnemonic
1 FG 1 CD(DCD)
2 SD 2 RD
3 RD 3 SD
4 - 4 DTR
5 SG 5 SG
6 - 6 DSR
7 RTS 7 RTS
8 CTS 8 CTS
9 ER 9 RI
■ Example of Configuration
�BASIC �BASIC
�C Language �PLC Data READ COMMAND �N0.6 PLC Data WRITE �C Language
Transmission (%01#RDD...) COMMAND Transmission
RESPONSE Receipt (%01$RD..) (%06#WCCD....)
RESPONSE Receipt
(%06$WCC....)
OEMax NX Series I 49
Computer Communication Unit(CCU+) Caution CCU+ Module can not be used with αseries.
This is a NX-Plus CPU leased Communication unit that enables 1:1 or 1:N Multi-drop communication by using
Computer and own CCU+ protocol, as well as enabling data transmission/receipt up to 250 bite at one time
CCU+ Module
Computer
∙MMI S/W
∙Programming S/W
■ Characteristics
1. Communication between PLC and Computer can be realized 3. Communication between PLC↔Touch Panel, MMI Device
easily and economically Can communicate with PLC with N-plus (N70 plus, N700plus,
1:1 or 1:N interface can be achieved with RS232C/485 port without NX-CPU700p) protocol embedded in most of MMI Software and
specific interface and regardless of type. READ/ WRITE information Touch Panel, etc.
of data can be collected without complex system configuration.
■ Performance Specification
Item Specification (NX-CCU+) (NX70-CCU+)
Interface RS232C/ RS485, 1 port
Transmission Speed 4800/ 9600/ 19200/ 38400bps (Select according to DSW1, DSW2)
Communication Method Half-Duplex Method
Synchronous Method Polling Method
Transmission Distance When RS232C is used: Max.15m When RS485 is used: Max. 1.2Km
Transmission Code HEX(Binary)
STOP bit: 1bit
Transmission Data Format Parity: No Parity
Length of Data: 8bit
Data Transmission Seq. By word byte unit transmit from lower byte unit
Transmission Unit From DA(Destination Address) to CRC-16 code Byte unit
Max. Length of Message Up to MAX. 250 Byte
Interface with CPU Unit Internal BUS Interface
I/O Allotment Not allotted
Error Check Method CRC-16 method
50 I OEMax NX Series
■ Wiring Diagram
(Without FLOW Control Method)
PLC(CCU+), 9Pin Male Computer (9Pin Female)
Pin No Mnemonic Pin No Mnemonic
FG 1 1 FG
TXD 2 2 RXD
RXD 3 3 TXD
RTS 4 4 DTR
GND 5 5 GND
485- 6 6 DSR
485+ 7 7 RTS
CTS 8 8 CTS
Vcc 9 9 -
■ Example of Configuration The following picture is an example of configuration for N-Plus Series.
CCU+ Module
RS485
RS232C
T/P
Command Response (RS485)
FF002303.. 00FFA30A..
Computer
�PLC Data READ �BASIC (RS485/RS422)
COMMAND �C언어
Transmission
(FF002303...)
RESPONSE Receipt
RS485
(OOFFA30A..)
OEMax NX Series I 51
Serial Communication Unit(SCU)
Data I/O can be done with devices communicating RS485 and RS232C such as Bar Code Reader (RS232C), Network
Inverter(RS485), etc. ASC11 and HEX(Binary) communication can be done with Ladder Program. (SCU Module =
existing SDU Module Function+485 Communication Function)
Barcode Reader
Network
Inverter
NX700 SCU Unit NX70 SCU Unit
(NX-SCU) (NX70-SCU)
Write down Data with Appl. Command(WRT) Temperature Controll Temperature Controlle
■ Characteristics
1. 2 Channels (RS232C, RS485 Optional) are mounted in the Unit. 4. Enabled Network-building by using RS232C communication
and RS485 communication
2. Data I/O can be executed with simple Sequence Command only. �Enabled Data I/O with RS232 device: Data I/P can be done by
Reading Data from SCU can be executed with PLC Application interface with IDX displayer, measuring instrument, barcode reader
Command[READ] and writing down data into SCU can be and printer, etc
executed with Application Command[WRT]. Because that CPU �Enabled Data I/O by network with RS485 device: Interface with
UNIT and shared memory of SCU will execute after-measures, Temperature Controller, Network Inverter, Network Servo and Network.
there is no need to prepare complex.
5. Can be mounted on PLC slot without limit. Transmission can be
3. As for SCU unit, use was extended by adding RS-485 Network made 500 Byte at one time.
Function on the previously used Function of N-Series SDU.
6. ASCII or HEX(Binary) can be used as means of usable
Transmission Code
■ Performance Specification
Item Specification
Interface RS232C/ RS485, 2 port
To be selected according to DSW1, DSW2
Transmission Speed 1) When RS232C is used: 300/ 600/ 1200/ 4800/ 9600/ 19200/ 38400bps
2) When RS485 is used: 4800/ 9600/ 19200/ 38400bps
Communication Method Half-Duplex Method
Activation Method Supplementary Activation Method( START - STOP method)
Transmission Distance When RS232C is used : 15m(MAX), When RS485 is used: 1.2Km (MAX)
Transmission Code ASCII or HEX(Binary)
STOP Bit 1bit / 2bit
Transmission Data Format Parity or not (even/odd)
Length of Data 7bit / 8bit
Data Transmission Seq. Transmit from Bit 0 by Character Unit
Transmission Unit Message Unit up to end point code(variable length)
Max. Length of Message MAX. 500 Byte/ Frame (end point, start point code inclusive)
Shared Memory Method �In case of NX-Series: READ, WRITE can be done with Application Command F150(READ), F151(WRT)
Interface with CPU Unit
�In case of NXplus Series: READ, WRITE can be done with READ,WRITE
I/O Allotment I/P 16 p, O/P 16 P allotted
End Point(終端) Code Setup Either select from ①cr ②cr+LF ③ETX or setup random code from shared memory
Start Point(始端) Code Start Point Code /or not
End Point Code Cut Transmission/Receipt Mode(control according to sequence command), convenient for printer O/P.
Other Special Control
Soft reset (Control according to sequence command)
52 I OEMax NX Series
■ Wiring Diagram
(Without FLOW Control Method)
RS-232C equipment
SCU (9Pin Female) & Ex. of Wiring
Pin No Mnemonic Mnemonic
1 FG
2 SD RD
3 RD SD
4 - DTR
5 SG SG
6 485- DSR
7 485+ <RS485 Ex. Of Wiring> RTS
8 CTS 485-T/B CTS
9 Vcc 485+T/B -
485-T/B
485+T/B
■ Example of Configuration
PLC
Leased
Controller
OEMax NX Series I 53
Multi Wire-Link Unit �NX700 : NX-CPU750A/ B/ C/ D, 700P Unit
�NX70 : Can be used with NX70-CPU750, CPU70P2 Units only
Multi function PLC Network Unit up to maximum 32 EA with Twist-Pair Cable. Having W-Mode with generalized W-Link
Function and W2-Mode with large capacity data transmission and data transmission for PLC Link, diverse network solution can
be provided with one kind of module. 2 layer network enabled (PLC Link, Computer Link, Data Transmission, Remote
Programming function).
■ Wire Link Function (W-Mode) �NX700 PLC does not have W-Link Unit
Max. 32 EA Interface
MW-Link Module MW-Link Module MW-Link Module
NX700 Series (W-Mode) (W-Mode) NX700 Series
NX70 Series
■ Performance Specification
Item Specification
Comm. Method Token Bus Method
Trans. Method BASE-BAND Method
No. of Interface Stations 32 Stations/ Layer, 2 Layer
Trans. Cable Twist Pair Cable(2 line type)
Trans. Distance 800m (Total Extension )
Trans. Speed 0.5Mbps
① PLC Link Function(Max.16 Stations)
② Computer Link Function (Max.32 Stations)
Function/ -> CCU Unit required
No. of Stations ③ Data Trans.Function(Max.32 Stations)
(局數) ④ Remote Programming Function(Max. 32 Stations)
■ Characteristics
1. PLC Network can be configured by interfacing up to 4. Enabled Intensified management function by 2 hierarchy
maximum 32 EA with W-Link Unit of N70, N700, NX70, (layers) of W-LINK Unit.
NX700 Series and“W-Mode” of MW-Link Unit. . Up to 3 EA can be mounted at CPU Unit including MW-Link and
CCU. If configured 2 layers with 2 EA of MW-Link mounted,
2. Network that can be easily connected with Twist Pair Cable intensified management of PLC Interfaces in the layers or data
Interfacing uses economical TWISTED-PAIR Cable so as to information can be achieved. .
configure excellent COST Performance PLC NETWORK.
5. TOKEN-BUS Method, Total Extension 800m
3. Computer Link Function can be used when CCU is mounted Since Network type is BUS method, there is no need of wiring in
Computer Link Function can be used with CCU Unit when PLC is LOOP topology and total extension of 800m can be utilized.
configured in Network. (or "COM" Port of CPU Module can be
used.)
54 I OEMax NX Series
■ Wire Link Function (W-Mode) Below picture is an example of NX-CPU750 program.
OEMax NX Series I 55
■ Wire Link Function (W2-Mode) MW-Link Unit W2 Mode can be used with
�NX700: NX-CPU750A/ B/ C/ D Unit
■ Configuration Diagram �NX70: NX70-CPU750 Unit
Max.Interface 32 EA
■ Performance Specification
Item Specification (W2-Mode)
Communication Method Token-Bus Method
Transmission Method BASE-BAND Method
No. of Interface Stations 32 Station/ Layer, 2 Layer
Transmission Cable Twist-Pair Cable (2 line type)
Trans. 250Kbps setup 1200m (Total extension)
Distance 500Kbps setup 800m (Total extension)
Transmission Speed 500 Kbps / 250 Kbps
① PLC Link Function (Max. 32 stations)
② Computer Link Function (Max.32 Stations) -> CCU Unit required
Function/No. of Stations ③ Data Trans.Function(Max.32 Stations), 1,020 words/1 Command
④ Remote Programming Function(Max. 32 Stations)
⑤ Layer Link(2 Layer with interface up to 2 EA of MW-Link per 1 CPU)
PLC Link Capacity Link Relay(L) : 4,096 points x 2
(per 1 Unit) Link Register(Ld) : 4,096 words x 2
Interface RS485 Multi-drop
RAS Function Hardware self diagnosis function
■ Characteristics
1. PLC Network up to Maximum 32 EA can be configured with 4. Computer Link Function can be used when CCU is mounted
MW-LINK Unit of NX70, NX700 PLC. Computer Link Function can be used with CCU Unit when PLC
Network is configured. (or "COM"Port of CPU Module can be
2. Large Capacity Data Transmission enabled (1,020 words/ 1 used as well.)
Command)
The capacity of Data to be transmitted by Data Transmission 5. Transmission Cable can be easily connected with Twisted-
COMMAND [F145(SEND)] [F146(RECV)]is drastically extended Pair Cable..
up to 1,020 words per 1 Command so as to improve
inconvenient problems in the existing W-Link Function. 6. Transmission Distance can be extended. (up to 1,200m)
(Capacity of transmission with the existing W-LINK was up to 16 Interface and communicate up to 1,200m according to change
words per 1 command) of Transmission Speed. (In case of 250Kbps, up to 1,200m)
3. Drastic Improvement in PLC Link Function (PLC Link 32 Stations, 7. Enabled Intensified management function by 2 hierarchy
Extension of Link Capacity) (layers) of MW-LINK .
Up to 32 EA can be set up when PLC Link Function is used and Up to 3 EA can be mounted on CPU Unit including MW-Link
in particular, PLC Link capacity is drastically extended. (L: 4,096 and CCU. If configured 2 layers with 2 EA of MW-Link mounted,
points, Ld: 4,096 words) Link Relay (L) and Link Register (Ld) intensified management of PLC Interfaces in the layers or data
Area can be set up with Ladder Program and WinFPST 2.24 S/W. information can be achieved. (Up to 8 EA for NX-CPU750C and
NX-CPU750D Unit)
56 I OEMax NX Series
■ Wire Link Function (W2-Mode) Below picture is an example of NX-CPU750B program
OEMax NX Series I 57
Remote I/O System �Remote system can be used with NX-CPU750A/B/C/D, 700P Units only
I/O Information can be exchanged with 2 line wiring to Remote Control System
2 Channel Wiring per 1 Master Unit enabled so as to effectively handle the dispersed I/O Devices.
(32 Units of Slave Units per 1 Master Unit can be interfaced)
NX-MASTER
Base Station B.Station : MASTER Unit
L.Station : Slave Unit
58 I OEMax NX Series
■ Characteristics ■ Performance Specification
1. Remote Control of I/O Information with 2 Channel Wiring Item Specification
For wiring convenience, transmission line can respond to up Communication Method 2 Line type Half-Duplex
to 2 channels per 1 Master Unit. In addition, 1 CPU can Activation Method Supplementary (調步) Activation Method
Transmission Line Twisted-Pair Cable (VCTF Cable)
control I/O of maximum 8 CH because 1CPU can mount up
Transmission Distance Total extension 700m
to 4 Master units. Designing the wiring route can be easily
Transmission Speed 0.5Mbps
executed because layout can be done freely. No. of MASTER 4 EA/ CPU 1 EA
No. of SLAVE Max. 32 Stations (per 1 Master Unit)
2. High Speed, Long Distance Transmission �Max. 1,024 P (per 1 Master Unit)
Transmission Speed of 0.5Mbps, total extension can be Control I/O Point �Max. 2,048 P (per 1 CPU Unit)
transmitted up to 700m. 2 line type can be used for cable ※CPU750C, D Module can control up to 8,192P
wiring which is economical. Interface RS485 (Multi-drop ), 2Port
Trans. Error Check CRC Method
3. Maximum 1,024 Point I/O Control per 1 unit of Master Module Combined Use of Products NX70, NX700 SLAVE Unit
(CPU750A, CPU750B)
Maximum 4,096 Point I/O Control per 1 unit of Master
Module (CPU750C, CPU750D)
■ Pointer of REMOTE I/O System
Maximum 1,024 point I/O Control can be achieved because 1
Master Unit can interface 32 EA of Local Stations (Slave �REMOTE I/O System is a system that can control dispersed I/O
Unit). (But, CPU750C, CPU750D Module can control up to with 2 line type cable.
8,192 point per 1 Unit of CPU) �Up to 4 wiring routes can be selected so as to be able to respond
to the complex layout of local stations.
�This Network is recommended when you want to place I/O at this
■ Product Configuration Summary or that place, like when you install control box at a remote location.
Type of Product Mounting Method PLC Product No. (Use of extended Motherboard is recommended when high speed
REMOTE I/O Mount on Basic, Extended process is required.)
NX700 NX-MASTER
MASTER Unit Motherboard to use (up to 4 units)
REMOTE I/O Mount on the existing CPU Unit NX700 NX-SLAVE
SLAVE Unit of Basic Motherboard NX70 NX70-SLAVE
OEMax NX Series I 59
EtherNet System
■ Characteristics
�Ethernet System is a leased Open Network System for CPU750 of NX700.
�This is a Communication Unit to interface NX700 PLC with Ethernet (100BASE -TX,
10BASE-T, 10BASE5), according to TCP/IP and UDP/IP.
�Maximum 8 portion of connection communication can be achieved with 1EA so as to be
able to interface with multiple opposite NODE.
�When interfaced with LAN by using Ethernet Unit of NX700, Computer Link Function, Data
Transmission Function, Remote Programming and Permeable Communication Function
can be used between other PLC on the Network(LAN) and Computer at transmission speed
of maximum 100M bit/s.
�When interfaced with LAN by using Ethernet Unit of NX700, programming at
Computer(WinFPST S/W)interfaced with LAN Network can be done so that programming
EtherNet Unit
edit can be done from anywhere.(Remote Programming)
�Communication Setup can be done easily by using "Control Configurator ET" which is a
Setup software. Accordingly, Communication Setup being executed on Ladder Program
■ Network Configuration Diagram can be used easily by utilizing this software.
Ethernet Unit
Remote
Programming WinFPST S/W Computer Link
Ethernet LAN
W-Link Unit
Ethernet Unit
60 I OEMax NX Series
■ Characteristics ■ Performance Specification
■ Corresponds to TCP/IP and UDP/IP Item Specification
Corresponds to 2 Protocols(TCP/IP and UDP/IP) so as to be able to I/O Occupancy Point 32SX/ 32SY ※1
communicate widely with computer and the like on Network(LAN). Mountable up to 3 units on the basic motherboard
Location of Mount/ (including W@-Mode of MW-Link Unit)
■ 8 Connection Communication with 1 EA Restriction on number of
units �When CPU750A, CPU750B are used: 3 EA
Maximum 8 portion of connection communication can be achieved
�When CPU750C, CPU750D are used: 8 EA
with 1 EA so as to be able to interface with multiple opposite NODE
�Computer Link: Max. 2K Byte
■ Corresponds to 3 kinds of Communication Interface Communication Function
�Data Transmission: Max.1020 words
Corresponds to 3 kinds of Communication Interface(100BASE-TX, �Remote Programming ※2
10BASE-T and 10BASE5). (Only one kind of Interface can be used). �Permeable Communication
1) 100BASE-TX and 10BASE-T: Use UTP Cable (switch transfer) NO. of Comm. System Connection Max. 3 Connection ※3
2) 10BASE5: Use Transceiver Cable Connections Connection Max. 8 Connection
Buffer for Permeable For Transmit. Setup on ex-factory: (1k word /1 Connection)×3
■ Supports Diverse Communication Function
Communication ※3 For Receive Setup on ex-factory: (1k word /1 Connection)×3
Supports SECTOCOL Communication Function (Computer Link
and Data Transmission) that can communicate between PLC NX ※1. Setup of「0E」can be done by use of WinFRST S/W.
※2. LAN Circuit pass Interface is not supported at "Configurator ET" setup S/W.
Series and Permeable Communication Function that can ※3. System Connection is used only with a computer interfaced with LAN circuit by using
communicate with General Purpose Devices like Computer. WinFPST S/W.
※4. Send/Receive combined 6K word can be randomly assigned to 8 connections.
1) Computer Link Function
�I/O Interface, contents of Register and contents of Program of PLC ■ Transmission Specification
interfaced with remote Computer or Work Station can be freely READ/Write.
Item 100BASE-TX 10BASE-T 10BASE5
�Maximum length of message for 1 frame is 2k Byte.
Data Trans. Speed 100M bit/s 10M bit/s 10M bit/s
2) Remote Programming Function Trans. Method Base Band
�With WinFPST S/W, which is a SAMSUNG PLC Software Tool, Max. Length of Segment 100m 500m
programming edit(insert, delete, correct)or monitoring at PLC from Max. Distance between Nodes 205m 500m 2,500m
remote Computer through LAN Network can be done. Communication Cable UTP Cable Transceiver Cable
Transceiver Cable 50m
3) Data Transmission Function
Ma. NO. of Nodes 100 Node/Segment
�Following execution of SEND/RECV Command of PLC, exchange of
Node Interval Integer Multiple of 2.5m
I/O(Interface) and Register Information between Computer interfaced
with Ethernet Unit or Work Station and PLC can be achieved
SEND Command WRITE with Register of the opposite Node � Interface of Network
RECV Command READ with Register of the opposite Node (1) 100BASE-TX / 10BASE-T (T)
OEMax NX Series I 61
DeviceNet Master Unit
NX700 PLC DeviceNet Master Unit provides Network and Master Connection configured with NX700 PLC and
DeviceNet I/O Products. ( ODVA 2.0 )
NX700 PLC
Write Data with Appl. Command(WRT)
DeviceNet Master Unit
(NX-DEVICE)
2. Multi mounting of DeviceNet Master Unit (DNM) in the same I/O Exchange
PLC can be achieved. �Poll Command :Y
Communication Method
�Bit Strobe Command : Y
3. Shared Memory is retained inside of DNM Unit so as to �Cyclic Command :Y
exchange Data between PLC CPU and DeviceNet Devices by �COS Command :Y
using WRITE, READ Commands supported by NX700 PLC NO. of Interface Node Max. 64 Nodes/ 1 Network (Including Master)
Command Word Set. (Maximum I/P of 4096 point and O/P of Distance/Trans. Speed 100m/ 500kbps, 250m/ 250kbps, 500m/ 125kbps
4096 point can be controlled) - Supports automatic setup
Max. Data Trans.Speed 500kbps
4. DNM Unit follows ODVA (Open DeviceNet Vendor Association) 500m
Guaranteed Transmission
DeviceNet Specification 2.0. Distance
Transmission Line DeviceNet Cable
5. Bit-Strobe, Polling, Cyclic I/O control method is provided for
Communication Method Polling , Strobe , Change-of-State , Cyclic
control of DeviceNet I/O products.
Comm. Speed Setup Method Automatic Setup Max. 500Kbps
6. Limited Device Configuration can be done by use of Explicit Rated Voltage: 24V DC Nominal
Messages. DeviceNet Power Voltage Range: 11V ~ 28.8V DC
Power Consumption : 1.5W Max.
7. Configuration Tool is provided for communication speed and I/O Approval ODVA Conformance Test Authentication under way
allotment.
(Configuration Tool for SYCON TOOLS Windows 95/NT that can
configure Network Information and Scan List)
62 I OEMax NX Series
■ DeviceNet Communication Configuration
DeviceNet is trademark of ODVA.
NX700 PLC
Computer
DeviceNet
(Master) Computer
NCS-DN(S/W)
(Contiguration)
NCS-DN(S/W)
NX-DEVICE Network
(Configuration Tool) Power(24)
Terminating DeviceNet
Resistance
Devicenet
(Slave)
Devicenet(Slave) Devicenet
(Slave)
DeviceNet
Terminating
Resistance
DeviceNet
(Slave)
■ Wiring Method
(1) RS232C Comm. Connector Type D-Sub, 9Pin Female
1 N.C
Interface with Computer
2 TxD
(Configuration Tool)
3 RxD
Pin
4 N.C
5 GND
6-9 N.C
OEMax NX Series I 63
64 I OEMax NX Series
■ NX7 PLC 마크 취득제품
NX7 Series
NX7 Extended Model (14/28 Points)
(NX7-14EDR, NX7-14EDT)
(NX7-28EDR, NX7-28EDT)
■ Peripheral Devices
User Software
OEMax NX Series I 65
NX7 Series
NX7 Series is a single packaged miniature PLC suitable for controlling the small sized machinery unit with basic 28
points and 48 points in compact size available, which can be extended up to 104 points. HSC, Pulse O/P and PID
Process Function, 2 Communication Ports (RS232/485) are included. All Command words(excluding Data Link) of
SPC10 and N-plus Series support Programming (Software and Command Words) and the existing Programs can be
Downloaded as it is.
■ Product Configuration
[Peripheral Device]
NX7 Basic Model (48Points) User Software
(NX7-48ADR)
(NX7-48ADT)
(NX7-48DDR)
(NX7-48DDT)
NX7-□□□□□-□A
4=Analog 4p(4In)
WinGPC Series 6=Analog 6p(4In/2Out)
(NX7=확장가능, O/P Mode(R=Relay, T=Transistor)
NX7S=확장불가) I/P Mode(D=DC I/P)
Pwr Spec. or Classification of Extension
I/O Point (A=AC Pwr I/P, D=DC24V Pwr, E=Extension Module)
■ Kinds of Product Model
RS232C
Name of Unit Product Code Product Spec. I/P Power Spec.
Basic Model NX7S-10ADR 10p(DC IN 6p, Relay Out 4p) AC110/220V
(10 Points) NX7S-10ADT 10p(DC IN 6p, Tr Out 4p) Free Voltage
Basic Model NX7S-14ADR 14p(DC IN 8p, Relay Out 6p) AC110/220V
(14 Points) NX7S-14ADT 14p(DC IN 8p, Tr Out 6p) Free Voltage
NX7-28ADR 28p(DCIN 16p, Relay Out 12p) AC110�220V
Basic Model NX7-28ADT 28p(DCIN 16p, TR Out 12p) Free Voltage
(28 Points) NX7-28DDR 28p(DCIN 16p, Relay Out 12p) DC 24V Power
NX7-28DDT 28p(DCIN 16p, TR Out 12p) Supply
NX7-48ADR 48p(DCIN 28p, Relay Out 20p) AC110�220V
Basic Model NX7-48ADT 48p(DCIN 28p, TR Out 20p) Free Voltage
(48 Points) NX7-48DDR 48p(DCIN 28p, Relay Out 20p) DC 24V Power
NX7-48DDT 48p(DCIN 28p, TR Out 20p) Supply
NX7-20ADR-4A 24p(DCIN 12p, Relay Out 8p) Analog 4p(4 In) AC110�220V
NX7-20ADT-4A 24p(DCIN 12p, Relay Out 8p) Analog 4p(4 In) Free Voltage
Analog
NX7-20ADR-6A 26p(DCIN 12p, Relay Out 8p) Analog 6p(4IN / 2Out) AC110�220V
NX7-20ADT-6A 26p(DCIN 12p, TR Out 8p) Analog 6p(4IN / 2Out) Free Voltage
NX7-14EDR 14p (DC In 8p, Relay Out 6p)
Extended NX7-14EDT 14p (DC In 8p,Tr 6p)
Model NX7-28EDR 28p(DCIN 16p, Relay Out 12p)
NX7-28EDT 28p(DCIN 16p, TR Out 12p)
66 I OEMax NX Series
■ Function and Characteristics of the Product
1. Compatibility Secured 8. Excellent Extendibility (Minimum 28 points ~ up to Maximum 104 points available)
All Command Words of SPC10 and N-plus Series are supported
and the existing Programs can be downloaded. 56
Points
2. High Speed Counter Function
Economical Control System can be built with the basically
embedded HSC 2 CH/24 BIT. 76
Points
OEMax NX Series I 67
■ Performance Specification
Item Specification
Control Method Program Storage, Repetitive Operation Method
Basic 28 p(I/P 16/ O/P 12 p), Basic 48 p(I/P 28/ O/P 20 p),
External I/O
Extension 28 p up to 2 EA(56p) extendable, (ext. 28p: In 16p /Out 12p)
Command Basic Command 28 kinds
Word Application Command Approx. 150 kinds
Process Basic Command Tens of μ
s/step
Speed Application Command A few ~ tens of μs/step
Program Capacity 9K Word
I/O(R) R000.00 ~ R31.15 (512p, 32word) (R32 ~ R127: Setup Range when Special Function is used)
Link Interface (L) L000.00 ~ L063.15 (1024p, 64word)
Internal Interface (M) M000.00 ~ M127.15 (2048p, 128word)
停電維持(Keep-alive During Blackout (K) K000.00 ~ K127.15 (2048p, 128word)
Special Interface(F) F000.00 ~ F015.15 (256p, 16word)
Memory
Capacity 256CH (Timer+Counter, Preset Value: 0 ~65535
Timer/ Counter Timer : 0.01sec: TC000 ~ TC063 (64CH), 0.1sec.: TC064 ~ TC255 (192CH)
Counter : TC000 ~ TC255 (256CH)
Data Word (W) W0000 ~ W2047 (2048word)
Special Word (W, SR) W2560(=SR000)~W3071(=SR511) (512word)
Communication Port 1 Port 1: RS232C/ RS485 Combined Use(D-SUB 9pin), 4800~38400bps Auto select
Function Port 2 Port 2: RS232C/ RS485 Combined Use(8Pin MJ T/B), 4800~38400bps Auto Select
Memory Back-Up User PROGRAM Back-up(FlashROM) Function Basically Embedded,
HSC I CH Embedded(Single Phase 8KHz, 2-Phase 4KHz) Pulse O/P 2 CH Embedded,
Special Function
Pulse Catch unction Embedded(4 Contacts)
Others User Definition Comm., Clock Function, PID Function
68 I OEMax NX Series
■ I/P Specification Internal Circuit (DC I/P)
Item DC I/P
I/P Spec. DC Voltage (all types)
Rated Voltage DC12 ~ 24V I/P
Operating Volt. Range 10.8 ~ 26.4V
Max. I/P Current Below 10mA
Min. ON Vol./Current Above 10.0V / above 3.0mA
Max. OFF Vol./Current Below 5.0V / Below 0.6mA
I/P Impedance Approx. 3.6KΩ
Response OFF→ON Below 2ms
Time ON→OFF Below 2ms
Internal Current
Below 50mA
Consumption (5V)
Polarity No Polarity Internal Circuit (Relay O/P)
COMMON Method 8p/ 1COM, 16p/ 1COM
within 2A
Load
■ O/P Specification
Item TR O/P RY O/P
NX7-28ADT NX7-48ADT NX7-28ADR NX7-48ADR
Product Code
NX7-28DDT NX7-48DDT NX7-28DDR NX7-48DDR
O/P Point 12 p 20 p 12 p 20 p
or
Rated Loaded Vol. 12 ~ 24V DC 250V AC, 30V DC
Operating Loaded Vol.
10 ~ 30V DC 85 V ~ 264V AC
Range
Polarity Common (Sink Type, NPN) No Polarity
Internal Circuit (TR O/P)
Max. Load Current 0.4A / point, 1A /Common 2A / point, 6A /COM
Response OFF→ON Below 1ms Below 10ms
Time ON→OFF Below 1ms Below 10ms
Int. PWR
Internal Current Consumption (5V) Below 80mA Load
COMMON Method 1, 4, 6p/1COM 1, 4, 6p/1COM
Int.
Ext. Supply
기본사양
OEMax NX Series I 69
Peripheral Device
WinFPST Software (for N Series)
Software that supports Programming from Computer. Mounted Diverse Functions like Ladder Edit, Monitor, De-Bugging, File
Management, Time Chart Monitoring, etc. Corresponds to all types of NX, N-Series. (excluding N-plus Series)
■ Configuration Diagram
■ Characteristics
1. Diverse Functions are mounted from preparation of program, 4. There are 3 types of Command Word I/P methods: Mnemonic
de-bugging, adjustment and up to various monitorings. Method, Ladder Method and Ladder Symbol Method. Uses can
freely select one from these three.
2. Selection of each function can be done by easy to understand
HANGEUL Menu Method (WinFPST) in simple operation. In 5. Edit, Interface, Forced ON/OFF Function, Interface Search
addition, not only file management function but also printed out Function from ON-LINE RUN Mode.
LIST can be used as a program specification directly.
6. Functions such as Data Monitoring, Time Chart Monitoring, Error
3. Setup of PLC Environment and I/O allotment can be set up in Occurrence Monitoring, File Management.
simple manner
MAIN Menu Multi Program Screen Program Preparation Screen (Ladder Edit)
70 I OEMax NX Series
WinGPC Software (for N-plus Series)
Software for Windows that supports Programming from Computer. Mounted Diverse Functions like Ladder Edit,
Monitor, De-Bugging, File Management, Time Chart Monitoring, etc. User Ladder Software corresponding to Plus
models (N70plus, N700plus, NX700(CPU700p), NX70(CPU70p), NX7, SPC-10 PLC Series).
■ Configuration Diagram
Product:
■ Characteristics
1. Convenient Functions of Windows can be utilized by application 4. Diverse types of monitoring such as Ladder, Mnemonic, Time
of WINDOWS Environment . Chart, Register Monitoring are available.
2. Programming can be done while executing mutual comparison 5. Ladder and Mnemonic programs are conversed automatically.
or printing because several programs can be edited
6. On-line interfaced PLC can be automatically discerned.
simultaneously.
7. Program correction and change can be done conveniently on
3. Programming is very convenient because diverse TOOLs for
on-line.
programming are provided.
Register Monitoring Screen Time Chart Monitoring Screen Status Monitoring Screen
OEMax NX Series I 71
Cable for CPU of NX70 PLC, NX700 PLC
Cable for TOOL PORT of NX70, NX700 CPU
RXD 3 3 TXD
- 4 4 DTR Computer
■ Corresponding CPU Module
S.G 5 5 S.G
PLC Series Corres. CPU Model
- 6 6 DSR
NX70 NX70-CPU70, NX70-CPU750
- 7 7 RTS NX-CPU750A, NX-CPU750B,
- 8 8 CTS NX700 NX-CPU750C, NX-CPU75
17JE-23090-02(D1),DDK (Male) 17JE-13090-02(D1),DDK(Female) NX-CPU700
Ref TOOL PORT of CPU Module for NX70, NX700 CPU of the bove diagram can use CPL5530, CPL5531 cable.
Cab le for COM PORT of NX70, NX700 CPU Unit and for CCU Unit of NX Series
�NX70-CCU (9pin)
�NX-CCU (9pin)
�CPU Unit COM PORT (9pin) �D-SUB (9pin)
Ref COM PORT of CPU Module of NX70, NX700 in the above diagram have same Communication specification
ith NX Series CCU Module
72 I OEMax NX Series
■ Cable for Plus CPU (SPC10, NX7, N70plus, N700plus, NX70, NX700)
Model Cable Length Contents of Application Applicable Products Remarks
1) NX7 PLC
- To interface with Handy-Loader(PGM500) �NX7 PLC (NX7-28ADR, NX7-48ADR...)
NX-CBLCPU02 2m
- To Interface with Computer �N70plus (CPL9215A, CPL9216A)
2) N70plus, N700plus PLC �N700plus (CPL7215A)
- To Interface with Handy-Loader(PGM500) �NX70p
- To Interface with Computer �NX700p
3) NX700 PLC �SPC10 PLC
- To Interface with Computer
4) NX70 PLC
- To Interface with Computer
NX-CBLCPU05 5m 5) PC10 PLC *1
- To Interface with Computer
(RS485/232 Adapter not necessary)
2m/ 5m
COM. Cable
CPU Unit side, 9 pin Computer & PGM500 side, 9 pin
OEMax NX Series I 73
■ Cable for SCU Module for N700, NX70, NX700 PLC
Contents of Application Applicable Module Remarks
COM Port of SCU Module SCU Module: for NX700 PLC(NX-SCU), for NX70 PLC(NX70-SCU), for N700 PLC(CPL7461)
74 I OEMax NX Series
External Dimensions
NX700 External Dimensions Diagram
■ Diagram of Dimensions for System (mm)
115.5 118.5
Unit(mm)
Dimensions
Slot Type
L P
3 Slot Type 205.0 183.8
111.0
5 Slot Type 276.0 254.2
8 Slot Type 381.0 359.8
10 Slot Type 452.0 430.2
12 Slot Type 522.0 500.6
L
27.5
115.5
Unit(mm)
SLOT A B
3 Slot Type 153.8 81.0
5 Slot Type 224.2 81.0
8 Slot Type 329.8 81.0
10 Slot Type 400.2 81.0
12 Slot Type 470.6 81.0
OEMax NX Series I 75
■ Diagram of Dimensions for Power Unit (mm)
INI1
NS1
RUN
RM1 00 RESET
PROG
LINK NO
0
COM COM1
RS232C RS232C
RS485
-
100L COM2
RS232C RS232C
FG RS485
76 I OEMax NX Series
Diagram of External Dimensions for NX70
■ Diagram of Dimensions for System (mm)
A
105.0
88.0
OEMax NX Series I 77
■ Diagram of Dimensions for Power Unit (mm)
RESET
INI1 RUN
RM1
LES1 PROG 00
LINK NO
20 19 1 2 0
COM1
COM RS232C
RS232C RS485
+ COM2
100L RS232C
RS232C _
RS485
2 1 19 20 FG
78 I OEMax NX Series
Diagram of External Dimensions for NX7
■ 28 Point PLC
■ 48 Point PLC
•’ 4.2 •’ 4.2
9.5
10.0
81.0 126.0
90.0
87.0 87.0
9.5 10.0
1.5 1.5
3.0
3.0
OEMax NX Series I 79
Product Catalog
NX700 PLC Series
■ CPU Unit
Unit Name Product Spec. Product Spec. Remarks
16k Step Embedded, 0.35㎲/ STEP, 2 Port, PID Auto Tuning Function,
NX-CPU750A Clock Function, Command Word is same with N700a CPU (In case of Extended
Memory, 32k Step & Comment Memory)
32k Step Embedded, 0.35㎲/ STEP, 2 Port, PID Auto Tuning Function, Floating-Point
NX-CPU750B Clock Function, Comment Memory & EPROM Socket Embedded, Command Operation
Word is same with N700a CPU. Clock Function
High Performance
60k Step Embedded, 0.03㎲/ STEP, 2 Port, PID Auto Tuning Function, PID AutoTuning
NX-CPU750C Clock Function, Comment Memory & EPROM Socket Embedded, 0.001s Timer
Command Word is same with N700a CPU.
120k Step Embedded, 0.03㎲/ STEP, 2 Port, PID Auto Tuning Function,
NX-CPU750D Clock Function, Comment Memory & EPROM Socket Embedded,
Command Word is same with N700a CPU.
Unit
유니트명 Name 제품 코드
Product Spec. 제품 사양
Product Spec. 비고
Remarks
증설메모리 16K STEP(Basically Embedded), 0.4㎲/ STEP, Trace Function, PID Function,
General Purpose Use NX-CPU700
Comment Memory basically embedded
■ Motherboard
Unit Name Product Spec. Product Spec. Remarks
NX-BASE03 3 slot type
NX-BASE05 5 slot type Common use with Basic
Basic Motherboard and extended
Motherboard NX-BASE08 8 slot type
Motherboard (No distinction)
NX-BASE10 10 slot type
NX-BASE12 12 slot type
80 I OEMax NX Series
■ I/O Unit
Slot Type Product Code Product Spec. Remarks
NX-X16D DC 12~24V, Terminal Block 20pin, 8 p/ COM, (Polarity +,- Common)
Terminal Block Type
16 P NX-X16A110 AC 100~120V, Terminal Block 20pin, 8 p/ COM 20pin(Split Type)
I/P Unit NX-X16A220 AC 200~240V, Terminal Block 20pin, 8 p/ COM
32 P NX-X32D DC 12~24V, Connector 40pin, 32 p/ COM, (Polarity +,- Common) Connector Type
64 P NX-X64D DC 12~24V, Connector 40pin x 2, 32 p/ COM, (Polarity +,- Common) 40pin
NX-Y16R RELAY O/P, Terminal Block 20pin, 250V 2A, 8 p/ COM
16 P NX-Y16RV RELAY O/P, Terminal Block 20pin, 250V 2A, 8 p/ COM, with Varistor Terminal Block Type
NX-Y16T TR O/P(NPN), Terminal Block 20pin, 12~24V 0.6A, 8 p/ COM 20pin(Split Type)
NX-Y16SSR SSR O/P, Terminal Block 20pin, 100~220V, 0.5A, 8 p/ COM
O/P Unit
32 P NX-Y32T TR O/P(NPN), Connector 40pin, 12~24V 0.4A, 32 p/ COM
NX-Y32RV RELAY O/P, Connector 40pin x 1, 250VAC /1A, 32 p/ COM, with Varistor Connector Type
NX-Y32R RELAY O/P, Connector 20pin x 2, 250VAC /1A, 30VDC, 16 p/ COM
64 P NX-Y64T TR O/P(NPN), Connector 40pin x 2, 12~24VAC 0.2A, 32 p/ COM
O/P Unit NX-DUMMY Dummy Unit
■ Analog Unit
Analog Product Code Product Spec. Remarks
8CH, Voltage Input, 16Bit A/D Converter, ±5V, ±10V, 0�5V,
NX-AI8V
Analog I/P 0~10V Resolution (0.153mV~1.0mV), Conversion Speed 1.25ms/Ch
(AD) 8CH, Current Input, 16Bit A/D Converter, ±20mA, 0�20mA,
NX-AI8C
4~20mA Resolution (0.519uA~2.0uA) Conversion Speed 1.25ms/Ch
4CH, Voltage Output, 14bit D/A Converter, ±10V, ±5V, 0�10V,
NX-AO4V
0~5V Resolution (0.305mV~1.0mV), Conversion Speed 2.5ms/ Ch
8CH, Voltage Output, 14bit D/A Converter, ±10V, ±5V, 0�10V,
NX-AO8V
Analog O/P 0~5V Resolution (0.305mV~1.0mV), Conversion Speed 2.5ms/ Ch
(DA) 4CH, Current Output, 14bit D/A Converter, 0�20mA, 4�20mA
NX-AO4C
Resolution (0.037uA~2.0uA) 4uA, Conversion Speed 2.5ms/ Ch
8CH, Current Output, 14bit D/A Converter,, 0�20mA, 4�20mA Terminal Block Type
NX-AO8C
Resolution (0.037uA~2.0uA) 4uA, Conversion Speed 2.5ms/ Ch 20pin(Split Type)
4CH, 3-Wire Method, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,
NX-RTD4 JPt500,JPt1000, NI100, NI120, CU50, 300Ω, 600Ω, 2000Ω
Resistance Temperature Detector Resolution 0.1℃, 0.1℉,
(RTD) 8CH, 3-Wire Method, Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200,
NX-RTD8 JPt500, JPt1000, NI100, NI120, CU50, 300Ω, 600Ω, 2000Ω
Resolution 0.1℃, 0.1℉, 10mΩ, 20mΩ, Conversion Speed 60ms/Ch
OEMax NX Series I 81
■ Communication Unit
Unit Name Product Code Product Spec. Remarks
RS232C/ RS485 x 2Port (Data process with Ladder Program)
∙Data Send/Recv enabled with each type of RS232C/ RS485 Device RS485 Function is added on
Serial Communication
NX-SCU (Binary/ ASCII Code process) the existing SDU Function
Unit (SCU)
∙For Interface with Network Inverter and NetworkServo, Network Temperature Controller, etc.
∙Module of existing SDU Function + RS485 Network Function
Communication Unit with RS232C/ RS485 x 1Port Computer and Touch Panel Unit
Computer For Computer or T/P Interface
∙NX-CCU+ ↔ Computer Communication ( 1:1 or 1:N Communication )
Communication NX-CCU+ (For use of CPU700p
∙NX-CCU+ ↔ Use N-Plus Protocol for Computer Communication
Unit (CCU+) Module only)
∙NX-CCU+ ↔ Communication with Touch Panel, MMI Unit
Module with diverse functions such as; Pulse O/P 4CH, PWM O/P 4CH, HSC I/P 4CH,
Pulse I/O Interrupt I/P 8 p, Compared O/P 8 p. Leased for CPU750
NX-PULSE4 ∙Pulse O/P: 100KHz O/P(1Hz Unit ), Direction Discrimination and Individual I/P(CW, CCW)
Unit Module only
∙PWM O/P: 30KHz O/P(1Hz Unit ), Duty: 0~100% (1% Unit )
82 I OEMax NX Series
■ Unit for Network (Open Network)
Analog Product Code Product Spec. Remarks
1) W-Link Function (W Mode)
∙Mount on Basic Motherboard to use
∙Mount up to 3 EA including CCU(5 EA in case of CPU750C Module)
∙Function: PLC Link(16 EA, L: 1,024 p, Ld: 128 Word), Computer Link,
Data Transmission(16Word/ 1Command), Remote Programming,
Layer Link(Refer to F145, F146)
∙PLC 32 EA/ Layer, 2 Layer, Transmission Speed : 0.5Mbps
∙Transmission Distance: Total 800m, Interface: RS485 Multi-drop
Use Twist-Pair Cable
MW-Link Unit NX-MWLINK
2) W-Link2 Function (W2 Mode) Leased for
(Multi Wire-Link)
∙Mount on Basic Motherboard to use CPU750Module only
∙Mount up to 3 EA including CCU(8 EA in case of CPU750C Module)
∙Function: PLC Link (32 EA, L: 4,096 p, Ld: 4,096 Word), Computer Link Function,
Data Transmission (1,020Word/1Command), Remote Programming,
Layer Link (Refer to F145, F146)
∙PLC 32 EA/ Layer, 2 Layer, Transmission Speed: 0.5Mbps
∙Transmission Distance: Total 800m (up to 1,200 m in case of 250Kbps)
∙Interface: RS485 Multi-drop
OEMax NX Series I 83
NX70 PLC
NX70 시리즈
PLC Series
■ CPU Unit (N-Series)
Use WinFPST S/W
Unit Name Product Code Product Spec. Remarks
∙0.35㎲/ STEP, 32k STEP(Basically Embedded), 2 Port, PID AutoTuning Function,
Floating Point Operation
Clock Function
NX70-CPU750 Clock Function
∙Comment Memory, EPROM (EEPROM) Operation Function
PID Auto Tuning
CPU Unit ∙High Performance CPU Module
■ Motherboard
Unit Name Product Code Product Spec. Remarks
NX70-BASE02 2 Slot Type
NX70-BASE03 3 Slot Type
NX70-BASE04 4 Slot Type
5 Slot Type NX70 PLC has
Basic NX70-BASE05
Motherboard Basic Motherboard
NX70-BASE06 6 Slot Type
only
NX70-BASE08 4 Slot Type
NX70-BASE10 5 Slot Type
NX70-BASE12 6 Slot Type
■ Power Unit
Unit Name Product Code Product Spec. Remarks
NX70-POWER1 AC 110/ 220V Free Voltage, 5V 4A, 24V 0.3A NX70 PLC has
Power Unit NX70-POWER2 AC 110/ 220V Free Voltage, 5V 4.5A Basic Motherboard
NX70-PWRDC DC 24V Input, 5V 4.5A only
84 I OEMax NX Series
■ I/O Unit
Slot Type Product Code Product Spec. Remarks
NX70-X16D DC 12~24V, Terminal Block 20 Pin, 8 p/ COM, (Polarity +,- Common )
NX70-X16D1 DC 24V, Terminal Block 20 Pin, 8 p/ COM, (Polarity +,- Common )
16 p Terminal Block Type
NX70-X16A110 AC 100~120V, Terminal Block 20 Pin, 8 p/ COM
I/P Unit
NX70-X16A220 AC 200~240V, Terminal Block 20 Pin, 8 p/ COM
NX70-X32D DC 12~24V, Connector 20 Pin x 2, 8 p/ COM, (Polarity +,- Common )
32 p Connector Type
NX70-X32D1 DC 24V, Connector 20 Pin x 2, 8 p/ COM, (Polarity +,- Common )
NX70-Y16R RELAY O/P, Terminal Block 20 Pin, 250V 1A, 8 p/ COM
NX70-Y16RV RELAY O/P, Terminal Block 20 Pin, 250V 1A, 8 p/ COM, Varistor available
16 p Terminal Block Type
NX70-Y16T TR O/P(NPN), Terminal Block 20 Pin, 12~24V 0.6A, 8 p/ COM
O/P Unit
NX70-Y16SSR SSR O/P, Terminal Block 20 Pin, 100~220V, 0.5A, 8 p/ COM
NX70-Y32T TR O/P(NPN), Connector 20 Pin x 2, 12~24V 0.4A, 16 p/ COM(-)
32 p Connector Type
NX70-Y32P TR O/P(PNP), Connector 20 Pin x 2, 12~24V 0.4A, 16 p/ COM(+)
.DC12~24V, 8 p, 8 p/ COM, (Polarity +,- Common ), I/P 8 p
16 p NX70-XY16
.RELAY O/P, 8 p, 250V 1A, 8 p/ COM, Terminal Block 20 Pin O/P 8 p
Combined Unit
.DC12~24V, 16 p, 16 p/ COM, (Polarity +,- Common ), Connector 20 Pin x 2 I/P 16 p
32 p NX70-XY32
.TR O/P(NPN) 16 p, ,12~24V 0.4A, 16 p/ COM O/P 16 p
Dummy Unit NX70-DUMMY Dummy Unit
■ Analog Unit
Analog Product Code Product Spec. Remarks
4CH Voltage Input, 16Bit A/D Converter, ±5V, ±10V, 0�5V, 0�10V
NX70-AI4V
Resolution (0.153mV~1.0mV), Conversion Speed 1.25ms/Ch
8CH Voltage Input, 16Bit A/D Converter, ±5V, ±10V, 0�5V, 0�10V
NX70-AI8V
Analog I/P Resolution (0.153mV~1.0mV), Conversion Speed 1.25ms/Ch
(AD) 4CH Current Input, 16Bit A/D Converter, ±20mA, 0�20mA, 4�20m
NX70-AI4C Resolution (0.519uA~2.0uA), Conversion Speed 1.25ms/Ch
OEMax NX Series I 85
■ Communication Unit
Unit Name Product Code Product Spec Remarks
Communication Unit with RS-232C x 1Port Computer and Touch Panel For Interface with
Use C, BASIC Language, "SECTOCOL" N-Series Protocol Basically mounted Computer or T/P
NX70-CCU ① 1:1 Leased Communication Unit (for leased use of N-Series)
② 1:N Communication Function: Unit for Interface with Computer - NX70-CPU70
Computer
on PLC NETWORK(Optical-LINK, W-LINK) - NX70-CPU750
Communication
Unit (CCU)
Communication Unit with RS232C/ RS485 x 1Port Computer and Touch Panel Unit
∙NX70-CCU+ ↔ Computer Communication ( 1:1 or 1:N Communication ) - NX70-CPU70P1
NX70-CCU+
∙NX70-CCU+ ↔ Use N-Plus Protocol for Computer Communication - NX70-CPU70P2
∙NX70-CCU+ ↔ Communication with Touch Panel, MMI Unit
1CH HSC I/P Function(100kcps) + Simplified Pulse O/P Function (200Hz . 40kHz)
NX70-HSC1 I/P Mode (3 Mode)
Binary 24Bit Up/Down Counter(-16,777,216~16,777,215)
1)Direction Discrimination Mode
HSC Unit 2)Individual I/P Mode(CW, CCW)
2CH HSC I/P Function (100kcps) 3)Phase Difference I/P Mode
NX70-HSC2 Binary 24 Bit Up/Down Counter(-16,777,216~16,777,215) (Rotary Encode I/P)
Module with diverse functions such as; Pulse O/P 4CH, PWM O/P 4CH, HSC I/P 4CH,
Interrupt I/P 8 p, Compared O/P 8 p.
Pulse I/O �HSC I/P: 200kcps, Binary 32Bit Up/Down Counter..... For use of NX70-CPU750,
NX70-PULSE4 �Pulse O/P: 100KHz O/P(1Hz Unit), Direction Discrimination and Individual I/P(CW, CCW)
Unit NX70-CPU70p2
�PWM O/P: 30KHz O/P(1Hz Unit ), Duty: 0~100% (1% Unit )
* Function: NX70-HSC4+Pulse O/P(4CH)+PWM O/P(4CH)
86 I OEMax NX Series
■ Unit for Network (Network for PLC)
Analog Product Code Product Spec Remarks
1) W-Link Function (W Mode)
�Mount on Basic Motherboard to use
�Mount up to 3 EA including CCU
�Function: PLC Link(16 EA, L: 1,024 p, Ld: 128 Word), Computer Link, Data Transmission
(16Word/ 1Command), Remote Programming, Layer Link(Refer to F145, F146)
�PLC 32 EA/ Layer, 2 Layer, Transmission Speed: 0.5Mbps
�Transmission Distance: Total 800m, Interface: RS485 Multi-drop
2) W-Link2 Function (W2 Mode) Use Twist-Pair
MW-Link Unit
NX70-MWLINK �Mount on Basic Motherboard to use Cable
(Multi Wire-Link)
�Mount up to 3 EA including CCU Leased used for
�Function: PLC Link (32 EA, L: 4,096 p, Ld: 4,096 Word), Computer Link Function, Data Transmission NX70-CPU750
(1,020Word/1Command), Remote Programming, Layer Link (Refer to F145, F146) NX70-CPU70p2
�PLC 32 EA/ Layer, 2 Layer, Transmission Speed: 0.5Mbps
�Transmission Distance: Total 800m (up to 1,200 m in case of 250Kbps)
�Interface: RS485 Multi-drop
※ Applicable Model: NX70-CPU750
OEMax NX Series I 87
NX7Series(All-in One Type PLC)
Unit Name Product Code Product Spec Product Spec Remarks
Basic Type NX7S-10ADR 10점 (DCIN 6점, Relay Out 4점)
(10 p) NX7S-10ADT 10점 (DCIN 6점, TR Out 4점) 2K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
AC110�220V Free Voltage, 24V 0.3A
Basic Type NX7S-14ADR 14점 (DCIN 8점, Relay Out 6점) 확장불가
(14 p) NX7S-14ADT 14점 (DCIN 8점, TR Out 6점)
NX7-28ADR 28점 (DCIN 16점, TR Out 12점) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
Basic Type NX7-28ADT 28점 (DCIN 16점, Relay Out 12점) AC110�220V Free Voltage, 5V 2.0A, 24V 0.4A
(28 p) NX7-28DDR 28점 (DCIN 16점, TR Out 12점) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
NX7-28DDT 28점 (DCIN 16점, Relay Out 12점) DC 24V 입력전원
NX7-48ADR 48점 (DCIN 28점, Relay Out 20점) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
Basic Type NX7-48ADT 48점 (DCIN 28점, TR Out 20점) AC110�220V Free Voltage, 5V 2.0A, 24V 0.4A
(48 p) NX7-48DDR 48점 (DCIN 28점, Relay Out 20점) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
NX7-48DDT 48점 (DCIN 28점, TR Out 20점) DC 24V 입력전원
20점 (DCIN 12점, Relay Out 8점)
NX7-20ADR-6A
Analog 6점(AD 4CH, DA 2CH) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
20점 (DCIN 12점, TR Out 8점) AC110�220V Free Voltage, 5V 2.0A, 24V 0.4A
NX7-20ADT-6A
Basic Type Analog 6점(AD 4CH, DA 2CH)
(Analog) 20점 (DCIN 12점, Relay Out 8점)
NX7-20ADR-4A
Analog 4점(AD 4CH) 9K 워드(기본내장), 수㎲/ STEP, 2포트 (RS232/ 485)
20점 (DCIN 12점, TR Out 8점) AC110�220V Free Voltage, 5V 2.0A, 24V 0.4A
NX7-20ADT-4A
Analog 4점(AD 4CH)
NX7-14EDR 14점 (DCIN 8점, Relay Out 6점)
NX7-14EDT 14점 (DCIN 8점, TR Out 6점)
Extension Type 증설 모듈
NX7-28EDR 28점 (DCIN 16점, Relay Out 12점)
NX7-28EDT 28점 (DCIN 16점, TR Out 12점)
88 I OEMax NX Series
■ Programming Device
�For N-Series, N70, N700, N700a, NX70, NX700 PLC
Unit Name Product Code Product Spec Product Spec Remarks
�Computer S/W with Function of PLC Program Preparation and PLC �N7 PLC
Status Check from Computer/ Network Check Function/ I/O MAP �N70 PLC
WinFPST S/W �NX70 PLC
User S/W and Monitoring , FILE Management/ Storage Function/ ONLINE Edit Above Windows 95
(for Window) �N700, N700H,
Function /Error Check Function / TIME CHART Monitoring Function N700a
�Same to the current WinFPST (for Window) Ver 2.xx �NX700 PLC
�For N-plus Series, SPC10, N70plus, N700plus, NX7, NX70(CPU70p), NX700(CPU700p) PLC
Unit Name Product Code Product Spec Product Spec Remarks
�SPC10 PLC
�Computer S/W with Function of PLC Program Preparation and �N70plus (CPL9215A)
PLC Status Check from Computer/ Network Check Function/ I/O (CPL9216A)
WinGPC MAP and Monitoring , FILE Management/ Storage Function/ �N700plus (CPL7215A)
User S/W Above Windows 95
(for Window) �NX7 PLC
ONLINE Edit Function /Error Check Function / TIME CHART
�NX70 PLC (NX70-CPU70p1)
Monitoring Function (NX70-CPU70p2)
�Same to the current WinFPST (for Window) Ver 2.xx �NX700PLC (NX-CPU700p)
NX-CBLCPU02 2m
Communication �For SPC10, N70plus, N700plus PLC Common use with Communication
Cable for CPU �For NX7, NX70, NX700 PLC Ports of NX70, NX700 CPU Unit
NX-CBLCPU05 5m
OEMax NX Series I 89
■ I/O Harnesses
Unit Name Product Code Product Spec Remarks
NX70 I/O NX70-CBLDC DC IN 32 p Connector Harness Length of Harness 1.5m
(Connector Type) NX70-CBLTR TR OUT 32 p Connector Harness NO. of Pin: 20 Pin
NX-CBLDC DC IN 32 p Connector Harness
I/O Cable ASS'Y NX700 I/O Length of Harness 1.5m
NX-CBLTR TR OUT 32 p/ 64 p Connector Harness
(Connector Type) NO. of Pin: 40 Pin
NX-CBLRY RELAY OUT 32 p Connector Harness
NX70 I/O For Connector Type Unit of
NX-PIN20 20Pin (PIN 20 EA, Connector Hood Included)
(Connector Type) NX70, N70, N700 I/O
I/O Connector ASS'Y
NX700 I/O For Connector Type Unit of
NX-PIN40 40Pin (PIN 20 EA, Connector Hood Included)
(Connector Type) N700 I/O
Remark) Order made acceptable if the length of I/O Cable exceeds 1.5m. Please inquire our Head Office if required.
Remarks
�We have N-Series and N-plus Series. Please pay attention because Command language and User S/W is different.)
�DeviceNet Module can be used regardless of N-Series, N-plus Series.
90 I OEMax NX Series
OEMax NX Series I 91
NX-CA001A-EN-P 2007. 10