Professional Documents
Culture Documents
MEASURING SYSTEM
MANUAL
PROCESS LINE
CONTENTS
PART
WARRANTY
A: TENSIOMETERS
B: ELECTRONICS
CONTENTS
Section
2 Specifications
3 Installation
4 Calibration
5 Maintenance
Installation Drawings
Monobloc(209) 2010/09
A
KELK TENSIOMETER
1.0 INTRODUCTION
The information presented in the following pages is of a general nature and may vary to
meet specific requirements.
The system measures tension in processing lines by sensing the force exerted by the
moving strip on a roll. This is achieved by using two Monobloc Transducers, one at each
end of the roll, which produce signals accurately proportional to strip tension.
Monobloc model and capacity are selected depending on the magnitude and direction of
the force, Fn or Fp, to be measured. Two distinct sensors are available; one, designated
by MDN0020-01model number, measures only Fn, force normal to the mounting surface
(see Fig. 1.1) ; the second, designated by MDP0020-01model number, measures only Fp,
i.e., force parallel to the mounting surface in the longitudinal direction (see Fig. 1.2).
Kelk Monoblocs are strain gage transducers machined from a one-piece forged steel
block. The geometry of the block is such that the sensor has very low hysteresis,
excellent linearity and is insensitive to forces other than in the sensing direction. The
sensors are hermetically sealed, with cables protected by hydraulic hoses, to withstand
harsh mill environments.
To complete the system, a Kelk amplifier is required to provide excitation and signal
amplification for the sensor. The system calibration depends on the strip to roll geometry
and outputs are normally provided scaled to represent strip tension directly.
Monobloc(209) 2010/09
A
KELK TENSIOMETER
Sensing Direction
T1 T2
Fn
Fn
T1 T2
Fn = T1 sin a + T2 sin b - w Fn = T1 sin a + T2 sin b + w
Sensing Direction
T2
Fp
Fp
T1
T1
T2
Monobloc(209) 2010/09
A
KELK TENSIOMETER
Hysteresis and Linearity Error Less than 0.1% of full scale output for hysteresis
and linearity combined.
Zero Drift With Temperature: Less than 0.005% of full scale /oC.
Monobloc(209) 2010/09
A
KELK TENSIOMETER
3.0 INSTALLATION
For mechanical details, refer to the load cell installation drawing; for electrical details,
refer to the general system drawing and the cabinet wiring diagram, if supplied
Each load cell is supplied with a calibration card attached to its cable. A copy of this
card is also in the manual. The load cell is identified by a model and serial number.
Caution
The cables are sealed in the cells and their replacement requires factory
service. In most cases, the load cell is supplied with a hydraulic hose to
protect the cable from mechanical damage and the environment. The
cable and hose must be routed to avoid mechanical damage; installation in
metal conduit is preferred. If the load cells are mounted on a retractable
support, the provision must be made to control the movement of the cable
and hose assemblies. The cables are composed of Teflon-coated wires for
chemical protection and are not easily spliced.
For this reason, cables should be fitted in the junction boxes before
cutting. A special splicing kit Part No. 045696 is available for splicing
cables which are damaged in service.
Monoblocs are designed to be bolted to the top of a frame usually supplied by the
customer. The sensor mounting faces have been drilled and tapped to facilitate mounting
to such a frame and for the mounting of the roll and bearing assemblies to the sensor.
The electrical connection of the sensor leads to the junction boxes completes the
installation.
Monobloc(209) 2010/09
A
KELK TENSIOMETER
1. Test load cell and cable for continuity. Using an ohmmeter with a resolution of
0.1 ohms, measure:
(a) the input resistance between the green and black conductors,
(b) the output resistance between the red and white conductors,
and compare both values with those given on the calibration card. The values should
correspond.
Caution
Do not use any insulation tester with test voltages in excess of 50V.
Permanent damage to the load cell may result if this voltage is exceeded.
Measure leakage resistance between any conductor and the load cell body, any
conductor and the cable shield, and the shield and the load cell body; the result in
each case should be greater than 100 megohms.
3. Locate the Monobloc on the respective frame. The polarity of the output depends on
the direction of the applied force. It is most important, therefore, to orientate the
sensors in accordance with the information given on the Signal polarity diagram for
this type.
4. The tension signal is dependent upon geometry, therefore, check that the installation
of the sensors in relation to the strip angles is as detailed on the Tensiometer
application data forms #858.
Caution: If sensors are not correctly installed, as detailed in items 3 and 4 above,
incorrect tension indication will result.
Monobloc(209) 2010/09
A
KELK TENSIOMETER
6. Lower the rolls with bearings on to the sensors; additional wear or mounting plates
may be used. Check that the rolls are correctly aligned and positioned to provide the
specified geometry. Adjust, if necessary, with shims.
3.3 Wiring
A general system drawing, figure 1.3, is included in this manual illustrating the main
components of a tension measuring system and their interconnecting cabling. More
specific information may be obtained from the cabinet wiring diagram if supplied.
The load cell is fitted with a 4 conductor shielded cable of suitable length. Typically this
cable is permanently attached to the load cell and protected from mechanical damage by
a hydraulic hose.
When the load cell is equipped with two bridges, the bridge 1 cable is labelled.
The hydraulic hose, protecting the cables, should be routed for minimum exposure to
danger of crushing during plant maintenance.
Load cell wires should be fitted with spade or ring type terminal lugs.
The preferred location for the Electronic enclosure and junction box if used is one that
provides easy accessibility and precludes the accumulation of water or oil.
It is advisable to repeat the continuity and insulation test given in 3.2.1 upon completion
of each stage of the wiring.
To facilitate calibration, when connecting wiring between the junction box and the
readout amplifier, identify each bridge circuit both at the amplifier and junction boxes, by
cell model number, serial number and location, e.g., MDN0020-01, Serial 24, Location
XYZ, operator side.
In the most cases integral load cell cable run directly to the electronic enclosure. When
the junction box is used, interconnection cables should be run by themselves in metallic
conduit, and discretion used in routing the conduit in relation to heavy current cables. It
Monobloc(209) 2010/09
A
KELK TENSIOMETER
has been found satisfactory to maintain at least 1 m spacing between load cell cables and
heavy power cables where a parallel run of up to 30 m (100 ft) exists.
Cables should be four conductor twisted shielded cable with an insulating jacket overall,
which must insulate the shield from the metal conduit to avoid circulating currents.
THE SHIELD IS CONNECTED AT THE AMPLIFIER ONLY. Four conductor cable of
this type is available from Kelk (AWG#16 Part No. 28280 and AWG#14 Part No.
43899).
Monobloc(209) 2010/09
A
ELECTRONIC
KELK
Monobloc(209) 2010/09
INTERCONNECTION
CABLE AND CONDUIT
(IF USED)
JUNCTION BOX
(IF USED)
ANALOG / DIGITAL
OUTPUTS
AND LOGIC INPUT
TENSION ROLL
A
ASSEMBLY
CABLE & HOSE
STANDARD LENGTH 6m (20FT.)
MOUNTING
SCREWS
ADAPTER
120/240 VAC SUPPLY PLATE
(IF USED)
70659A
KELK LOAD CELLS
4.0 OPERATION
When installation is complete, it is necessary to calibrate the load measuring system prior
to actual operation.
To gain a basic understanding of the operation and use of the General Purpose Amplifier,
Model GPA2, read Section B of this manual (Sections 1 through 6) before proceeding.
The GPA2, as supplied from the factory, is setup in terms of functionality and features
either with a default setup or a specific setup as defined at the time of order. This is fully
described in Section B, Appendix A. The user is advised to check that the supplied setup
is correct for the specific application. The procedure for doing this check is given in
Section B, Part 4 of this system manual.
To fully configure the GPA2 for measurement operation, the user must enter data,
including the load cell calibration target load and system parameters such as analog
outputs setting and load limits. The user is guided through this process in Section B,
Parts 4 and 5.
4.3 Calibration
Every KELK load cell is supplied with a calibration card giving the full load output stated
in millivolts per volt of bridge excitation.
For convenient system calibration, the card also specifies (in percent of rated load) the bridge
output resulting from the application of a precision shunt resistor across one bridge arm.
In KELK load cell systems, a simulated load, produced by precision resistors, is used to
calibrate the load measuring system. The value of the precision resistor is given on the
calibration card and a resistor of that value is available in the GPA2. The user must select
the same value when required during GPA2 Channel Configuration process described in
Section B, Part 5.4.
Also in Part 5.4 of Section B, the user is prompted to enter a 'Calibration Target Load' for
each load cell. This figure is the simulated output expressed as a percent of rated load.
LC/GPA2 (318)
Revised 2008/04
A
KELK LOAD CELLS
If the calibration card gives a figure of 79.73% of rated load as the figure to be used for
"Full Routine Mill Calibration of the Load Metering System", this is the Calibration
Target Load to be entered into the GPA2.
Note: During calibration, the metal (or paper) strip, the tension of which is being
measured, must be removed from the tensiometer roll.
The design of KELK Tensiometers is such that calibration is accomplished through the
trimming of the transducer amplifiers alone. Field calibration of the tensiometer sensors
by means of dead weights is not required since the necessary transfer reference in the
form of shunt calibration resistance has been established at the factory for each sensor.
For load cells incorporated into tensiometers, the simulated load is converted to a
simulated tension and expressed as a percentage of the full rated tension for that location.
The conversion of tension to load is illustrated on the Tension Application Data Sheet
Form 858. The resulting calibration data is given on the Tensiometer Calibration Data
Sheet, Form 855. Both forms are given at the end of Section A of this manual. A
complete explanation of the Forms 855 and 858 is given in Appendix C in Section B of
this manual.
In Part 5.4 of Section B, entering a 'Calibration Target Load' for each load cell is
described. Refer to the Tensiometer Calibration Data Sheet for the value of simulated
tension, expressed as a percentage, for the appropriate load cell. As an example, if this
value is 81.53%, then this is the Calibration Target Load to be entered into the GPA2.
It is important to note that the calculation of simulated tension is carried out based on
fixed tensiometer geometry and specific strip angles. If the geometry of the system, as
installed, does not correspond to that on the Tensiometer Application Data Sheet, then
consult George Kelk Corporation to obtain new forms and percentage values.
The value of the calibration constant given on the calibration card is measured with only
short cables linking the cell to its amplifier. Installation in the mill sometimes involves
the use of long interconnecting cables. The additional resistance added by long cables
affects the cell output in response to the application of the shunt resistance and correction
of the 'Calibration Target Load' may be required.
LC/GPA2 (318)
Revised 2008/04
A
KELK LOAD CELLS
1. Determine the resistance of one conductor of the interconnecting cable. This can be
done using Figure 1 if the length and gauge of wire are known or, by direct
measurement as follows:
(b) Using an ohmmeter with 0.1 Ohm resolution, measure the resistance between the
interconnection cable leads corresponding to red and white wires of the load cell
cable with either:
The interconnection cable leads shorted at the junction box,
or
The interconnection cable connected to the load cell at the junction box. In
this case subtract the value of 'Output Resistance' given on the load cell
calibration card from the measurement.
For both cases, divide the result by 2 to obtain a value, RL, which is the
individual lead resistance.
c) Using Figure 2 and the value of RL obtained above, determine the Cable
Correction Factor, ‘Cf'.
For a six conductor connecting cable where 2 conductors are used for remote
sensing of excitation voltage (typically done in weighing systems),
Cf = 1 + 2 RL
RBR
LC/GPA2 (318)
Revised 2008/04
A
KELK LOAD CELLS
CTL1= Cf x CTL
Where:
CTL is the output obtained from the calibration shunt resistor being applied during
factory calibration, expressed as a percentage of the full scale output for force and
pressure (found on the Calibration Card). For Tension applications, it is the
percentage of the full scale tension from the Tensiometer Calibration Data Sheet;
and
CTL1 is the Calibration Target Load corrected for the interconnecting cable resistance.
Example:
For a load cell with a bridge resistance of 240 ohms, connected to the amplifier by
90 meters of 16 AWG cable
If the calibration card gives a figure of 79.73% of rated load as the figure to be
used for "For Routine Mill Calibration of Load Metering System", then the
corrected calibration constant to be used to accurately calibrate the load measuring
system is:
= 81.3%
The GPA2 has a diagnostic feature that allows the user to conduct a Load Simulation,
forcing the unit to output a known value. This feature facilitates a check of external
connections. It is strongly recommended that this check be carried out before putting the
complete system into operation. Refer to Parts 6.7 of Section B for full details.
LC/GPA2 (318)
Revised 2008/04
A
KELK LOAD CELLS
WG
14 A RL
RL
RL
RL
0 LOAD CELL
0 30 m 60 m 90 m 120 m 150 m
(100ft) (200ft) (300ft) (400ft) (500ft)
CABLE LENGTH - L
1.10
RBR = LOAD CELL OUTPUT BRIDGE RESISTANCE
1.09
CABLE CORRECTION FACTOR - Cf*
* CORRECTED CALIBRATION
1.08 VALUE = GIVEN SHUNT
RL CAL. x Cf
Cf = 1 + 4
RBR
R)
1.07
B
(R
Ω
0
12
1.06
1.05
Ω
1.04 240
1.03 Ω
360
1.02 480 Ω
720 Ω
1.01
1.00
0 1 2 3
INDIVIDUAL LEAD RESISTANCE - R L (Ω)
5.0 MAINTENANCE
5.1 Mechanical
KELK load cells are typically mounted in locations where regular inspection is not
practical, for example, above a screwdown nut. The load cell itself requires no
mechanical maintenance but it is important for reliable operation of the cell that the
conditions and tolerances given on the installation drawing are maintained. Additional
maintenance notes may be contained in this manual.
5.2 Electrical
Electrically, the load cell is a simple circuit containing only passive devices. The load
measuring system, including the cell, connecting cable and amplifier can be checked by
observing the stability of the output with no load applied and checking the repeatability
and stability of the output when the shunt resistor used to calibrate the system is engaged.
If instabilities of zero, shunt resistor generated output, or indicated load are experienced,
then the tests given in 5.2.1 and 5.2.2 should be carried out.
A potential source of faults in a load measuring system is the occurrence of leakage paths
to ground in the load cell to electronics wiring. The most common cause is moisture in
the load cell cable and/or junction box. Related preventive measures are listed in
Section 3.
The presence of excessive leakage will usually reveal itself by causing drift in the zero
reading under conditions of no load.
Caution
Do not use any insulation tester with test voltages in excess of 50V.
Permanent damage to the load cell can result if this voltage is exceeded.
To check for leakage, disconnect all load cell leads and their shield from the electronics
and measure the resistance from any lead to ground (refer to Part 3, Installation). A ten
megohm leakage would introduce a maximum error of about 0.3%. However, such a
reading suggests a condition that should be corrected.
LC/GPA2 (318)
Revised 2008/04
A
KELK LOAD CELLS
To localize the leakage, open the junction box at the mill stand and, having disconnected
all leads, pinpoint the source by taking individual readings from each terminal. If there
are other junction boxes in the cable circuit, repeat the procedure for each of them.
To check bridge resistance, disconnect load cell leads at the junction box and, using an
ohmmeter with a resolution of 0.1 Ohms, measure
(a) the input resistance between the black and green conductors
(b) the output resistance between the red and white conductors.
The values obtained should correspond to those given on the cell calibration card. If the
measurement is made at the amplifier to check the condition and continuity of the
interconnecting cable, then allowance must be made for the additional cable resistance
when comparing with the values on the calibration card.
Load cell cables are fixed and sealed to the load cell. In the event of damage to the cable
near to the load cell body (within 6 inches, or 150 mm), the cell should be returned to
KELK for service. If the cable is damaged at some point further along its length, then a
repair can be performed using the KELK Splicing Kit, part number 20311. This kit is
specifically for splicing teflon cables and is the only method recommended.
LC/GPA2 (318)
Revised 2008/04
A
LOAD CELL CALIBRATION CARD
MODEL No. MDN0012-15 SERIAL No. 11
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8340 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1003.1 [W] AT 23° C OUTPUT RES. 1003.1 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 25-Oct-2018
BY: RM
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDN0012-15 SERIAL No. 12
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8331 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1002.8 [W] AT 23° C OUTPUT RES. 1002.8 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 27-Oct-2018
BY: RM
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDN0012-15 SERIAL No. 13
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8423 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1008.1 [W] AT 23° C OUTPUT RES. 1008.1 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 27-Oct-2018
BY: RM
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDN0012-15 SERIAL No. 14
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8353 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1003.9 [W] AT 23° C OUTPUT RES. 1003.9 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 25-Oct-2018
BY: EP
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDN0012-15 SERIAL No. 15
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8350 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1004.2 [W] AT 23° C OUTPUT RES. 1004.2 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 26-Oct-2018
BY: EP
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDN0012-15 SERIAL No. 16
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8359 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1004.2 [W] AT 23° C OUTPUT RES. 1004.2 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 27-Oct-2018
BY: RM
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDN0012-15 SERIAL No. 17
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8349 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1005.6 [W] AT 23° C OUTPUT RES. 1005.6 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 25-Oct-2018
BY: EP
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDP0020-05 SERIAL No. 11
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8351 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1004.3 [W] AT 23° C OUTPUT RES. 1002.1 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 24-Oct-2018
BY: RM
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDP0020-05 SERIAL No. 12
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8349 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1004.5 [W] AT 23° C OUTPUT RES. 1002.2 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 23-Oct-2018
BY: EP
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDP0020-05 SERIAL No. 13
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8347 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1003.9 [W] AT 23° C OUTPUT RES. 1001.7 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 26-Oct-2018
BY: EP
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDP0020-05 SERIAL No. 14
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8342 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1003.6 [W] AT 23° C OUTPUT RES. 1001.4 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 13-Oct-2018
BY: EP
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDP0020-05 SERIAL No. 15
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8349 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1003.7 [W] AT 23° C OUTPUT RES. 1001.6 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 25-Oct-2018
BY: EP
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
LOAD CELL CALIBRATION CARD
MODEL No. MDP0020-05 SERIAL No. 16
48 LESMILL ROAD
OUTPUT WITH 300,000 [W] SHUNT RESISTOR 0.8349 mV/V*
APPLIED ACROSS BLACK AND WHITE LEADS
INPUT RES. 1004.2 [W] AT 23° C OUTPUT RES. 1002.0 [W] AT 23° C
GREEN (+), BLACK(-) (77° F) RED (+), WHITE(-) (77° F)
* OPEN CIRCUIT MEASUREMENT (AMPLIFIER DISCONNECTED) DATE: 23-Oct-2018
BY: EP
KELK Form# 887
Rev. 2016-07-15 Work Order: JT9050
PART B
GENERAL PURPOSE AMPLIFIER
Manual # 90472
Revision C
July 2018
All rights reserved. No part of this manual may be reproduced or stored as data,
in whole or in part, without the prior written permission of KELK. No license,
express, implied, or otherwise, to any intellectual property rights is granted by
this document, or by any conduct of KELK.
KELK disclaims any and all liability for errors or omissions in this manual or their
consequences. KELK makes no warranty, representation or guarantee other than
as set forth in the terms and conditions of purchase.
KELK Warranty
WARRANTY
Table of Contents
Table of Figures
Figure 2.1 GPA2-12 (NEMA 12) with Profibus Option 3
Figure 2.2 Main Module Functionality 5
Figure 3.1 GPA2 Enclosure 12
Figure 3.2 GPA2 Wiring 13
Figure 3.3 Main Module Connections 14
Figure 3.4 Analog Output Circuit 18
Figure 3.5 Zero Function Input Circuit 19
Figure 3.6 System Healthy and Load Level Relay Circuits 20
Figure 3.7 Serial Communications Connections for RS232 21
Figure 3.8 Serial Communications Connections for RS485 21
Figure 3.9 Ferrite Chokes Installation 23
Figure 4.1 Front Panel Interface 25
Figure 4.2 FPI Menu 27
Figure 4.3 Function Setup Loop 28
Figure 4.4 Operation Loop 29
Figure 4.5 Modbus Mode Setting 31
Figure 5.1 Digital Filter Response 35
Figure 5.2 Working Range Definition 40
Figure 5.3 GPA2 Web Page 49
Figure 8.1 GPA2 Module removal from DIN Rail 71
Figure 9.1 Dimensions of GPA2 Enclosures 76
Figure A.1 GPA2 Ordering Form 80
Figure B.1 Communication Action Selection 83
Figure B.2 Serial Communication Setup Panel 84
Figure B.3 Directory Path Panel 84
Figure B.4 Navigation Panel 86
Figure B.5 Operations Panel 87
Figure B.6 Configure & Set Panel 89
Figure B.7 Input Configuration Panel 90
Figure B.8A Mode of Data Entry 90
Figure B.9 Cable Calculator 92
Figure B.10 Application Wizard Image 93
Figure B.11 Setup Panel 94
Figure B.12 Status Panel 96
Figure B.13 Configuration Data Panel 97
Figure B.14 Simulation and Output Test Panel 98
Figure B.15 UAP System Setting Panel 99
Figure B.16 Sample of ‘Print GPA2 Configuration Report’ 100
Figure C.1 Example of a Calibration Card 101
Figure C.2 Form 858, Tensiometer Application Data Sheet 102
Figure C.3 Form 855, Tensiometer Calibration Data Sheet 104
Precautions
Intended Use
The General Purpose Amplifier, Model GPA2, is intended for use only with factory
calibrated KELK strain gage sensors in load measuring systems. Do not use the
GPA2 in a manner not expressly described in this manual or approved by
authorized KELK personnel or their agents. The outputs and the alarms will be
unpredictable, both the GPA2 and the equipment to which it is connected may be
damaged and the protection provided by the GPA2 may be impaired.
Accessibility
The GPA2 enclosure is tool accessible and should only be opened by qualified
service personnel. Always disconnect the GPA2 from the power source before
removing the cover. Do not reconnect power until the cover has been replaced
and secured. The only permissible user service, the replacement of printed
circuit boards, does not require the application of power while the cover is
removed.
The GPA2 is marked with IEC 61010 symbols to warn the user of items requiring
particular attention for safety reasons.
Electrostatic Damage
Users of this manual must pay particular attention to the Precautions section at
the front of the manual and to all Warnings and Cautions contained herein.
Translation of this manual into another language may result in loss of meaning
and content; in all cases, the content of the English version upon which the
translation was based prevails.
2.0 Introduction
The General Purpose Amplifier Model, GPA2-E, is a two channel strain gage
sensor signal conditioner for use in industrial applications. The GPA2-E is
referred as GPA2 throughout this manual.
The GPA2 is used together with KELK strain gage sensors for:
Tension measurement, particularly in metals process lines and paper
machines
Force measurement
Weight measurement
Pressure measurement
To service the wide variety of applications and sensors, the main module can be
supplied with either the standard excitation voltage of 10 VDC or the optional 20
VDC. The higher excitation voltage is provided for applications requiring sensors
providing higher than the standard 500% overload ratings.
2.1 Features
The GPA2 is an electronics unit comprising DIN rail mounted modules contained
within a steel enclosure. NEMA 12 and NEMA 4X enclosures are available.
Figure 2.1 illustrates the NEMA 12 option. The enclosure contains a circuit
breaker serving as an ON/OFF switch and all the necessary terminals for AC
connection. The user must provide power and signal exit holes. Sensor entries
to fit KELK load cell cables with 1/2” NPT hose adapter are provided. The basic
configuration consists of:
GPA2 Module
This provides the sensor excitation, signal conditioning, a direct user interface
including an eight-button keypad, and an LCD panel for manual monitoring and
setup. The LCD panel can display 2 lines by 8 alphanumeric characters. Sensor
connections and system inputs and outputs are located on the side of the
module. Additional connections are also provided for interfacing with a PC or an
optional Fieldbus module (see Figure 3-2).
Figure 2-2 details the functions of the main module, in addition to the inputs and
outputs.
2.3.2 Configuration
Channel Calibration
Every KELK load cell is supplied with calibration data giving the cell full load
output (sensitivity) stated in millivolts per volt of bridge excitation. The data also
includes the bridge output resulting from the application of a precision shunt
resistor across one bridge arm (in percent of rated load), used for calibration of
load measuring systems. For tension measurement applications, KELK provides
additional information to assist the user in the setup and calibration of individual
sensor channels; refer to Appendix C for details.
Configuration
The Configuration function uses data input by the user for each channel to:
a) Establish the input working range to ensure the best measurement
resolution while providing adequate zero compensation and over range.
b) Correct for any tare load not included in the measurement range.
c) Establish a measurement zero reference.
d) Set the channel fine gain in accordance with the load cell calibration data.
Zero adjustment can be made via the Front Panel Interface, the Logic Input, the
User Access Program, Modbus/TCP interface or the optional Profibus module.
GPA2-E Manual 90472 RevC
July 2018 6
KELK GPA2 Description
2.3.4 Analog Data Outputs for Control Purposes
Two programmable, group isolated analog outputs are provided which can be
configured for either current or voltage mode. These outputs can be user-
programmed to represent either the loads of the two individual sensors or the
sum and difference of the two sensors (i.e. either as A and B or A+B, A-B). Each
output can be scaled to represent a user selected percentage of Full Scale Input
defined by the calibration parameters.
For operational purposes, by the logic outputs, and through the user and
communications interfaces as described in Part 7.
For troubleshooting purposes, through the user and communications
interfaces as described in Part 7.
2.4 Interfaces
Interface
Serial Communications
Logic Outputs
Sensor Ports
Logic Inputs
Fieldbus 1
Function
Inputs
Sensors x
Load Outputs (for control) x x
Load Alarm Indication x x x x
Operations
Load Monitoring and Display x x x x
Status Indication - System Healthy x x x x
Status Indication - Channel A Fault x x x
Status Indication - Channel B Fault x x x
Status Indication - Single Sensor Operation x x x
Single Sensor Operation Function x x x x
2
Zero Function x x x x x
Configuration (span and zero reference) x x x x 2
Diagnostics
System Status x x x x
Calibration Data x
Load Simulation x x
Hardware and Firmware Data x
1
Accurate for the following GPA2 Fieldbus interfaces Modbus, Profibus, PROFINET
2
Factory enabled, access may be disabled by User Access Program
or
Note that only the UAP, not the FPI, can be used to select between current or
voltage outputs. However, another option is for the output type to be specified at
the time of order via the model number choice. As such, the GPA2 main module
will be programmed accordingly at KELK (see Section 0).
Provide access to the load measurement set at a rate suitable for mill control.
Provide access for monitoring and controlling unit operation.
There are two serial communications modes available: RS232 and RS485.
The load data output over this interface are intended for data logging and
monitoring purposes only. For mill control, the Fieldbus Interface is
recommended.
Part 3 Installation
3.1 Introduction
KELK load measuring systems are designed, and have been proven over many
years, to provide excellent performance in the demanding environments of the
metals industry. However, to achieve their full potential for high accuracy and
long service life, they must be properly installed.
Following installation, the system must be set up and configured before being
placed in online service (see Part 5: Setup and Configuration).
Caution
If the system is not properly set up and configured, the digital and
! analog outputs, and the load alarm are unpredictable and their use
for control purposes may cause the production of off-specification
product or equipment damage.
3.2 Enclosures
All conduit entries should be caulked to prevent dust from entering the enclosure.
The AC power required is specified in Section 9.13. The power supply module
adjusts automatically to the voltage range, typically 120 or 240 VAC, to which it is
connected. It must be properly grounded.
For a new measuring system, recommended wiring practices and instructions are
included in the documentation supplied with the system.
Sensor wiring must be rated for at least 300V. Terminations must be clean so as
not to introduce contact resistance or leakage to ground. Cables must be routed
to avoid exposure to power cables and other potential sources of electromagnetic
interference. Good wiring practices and a dry environment are essential. Typical
sensor wiring is shown in Figure 3-2 and the connections in Figure 3-3;
connector pin-outs are listed in Table 3-1.
A four conductor twisted (in pairs or all together) shielded cable, with
insulating jacket is recommended; 16 AWG (1.5mm2) cable is available
from KELK, Part Number 28280.
The preferred routing is through metal conduit. However, the cable
may, after leaving the junction box in a conduit, be run in low signal
cable trays. When run parallel to heavy power cables, a minimum
separation of 1 m (3.3 ft) is required for runs of up to 30 m (100 ft). For
longer runs, a minimum separation of 2 m (6.6 ft) is required.
4. With the interconnecting cable not connected to the main module, check
the sensor and interconnecting cable wiring for:
Continuity. Using an Ohmmeter with a resolution of 0.1 Ohm, measure
the input resistance between the green and black conductors and the
output resistance between the red and white conductors. The
measured values should be within 1 Ohm of those given on the
GPA2-E Manual 90472 RevC
July 2018 16
KELK Installation
calibration card supplied with the sensor, plus the resistance of the
interconnecting cable.
Leakage Resistance:
Measure leakage resistance between any conductor and the cable
shield, between any conductor and ground, and between the cable
shield and ground. The result should be greater than 100 M in each
case.
Caution
The Main Module provides two analog outputs, Out1 and Out2 that can be
connected for voltage or current; both are shown in Figure 3.4. An output must
not be connected for both current and voltage at the same time. Outputs
are to be connected in accordance with the mode selection made, as described
in Appendix B, or as defined by the model number ordered (refer to the model
numbering scheme in Appendix A). Connector pinouts are listed in Table 3-2.
Connecting cables must be rated for at least 300V.
Connections include:
Input: Zero function input; see Figure 3-5
Outputs: System Healthy relay; see Figure 3-6
Load Level Relay; see Figure 3-6
Connecting cables must be rated for at least 300V. The following cable, or its
equivalent is recommended:
For the logic input, a user supplied voltage of 10-24 VDC and contact closure, or
equivalent, is required.
The serial communications wiring is shown in Figure 3-7 and Figure 3-8.
The COM1 connector pinouts are listed in Table 3-3.
GPA2 SIGNAL
CONNECTO
R-PIN RS232 RS485
1 No Connection No Connection
2 TXD -TXD
3 RXD -RXD
4 No Connection No Connection
5 Serial Common Serial Common
6 No Connection No Connection
7 No Connection +RXD
8 No Connection +TXD
9 No Connection No Connection
Connect the CAT5 Ethernet network cable to the RJ45 connector on top of the
GPA2 module.
Upon completing the connections to GPA2 main module, place one ferrite choke
across each of the following cables: Sensor Inputs A&B, Analog Output, and
Ethernet (if this function is available). The ferrite chokes can be found in a
ziplock bag inside GPA2 enclosure.
Refer to Figure 3-9: Ferrite Chokes Installation, for details on applying the ferrite
chokes.
4.1 Introduction
The GPA2 has two user interfaces used to set up the load, tension, or pressure
measuring system:
The User Access Program (UAP)
The Front Panel Interface (FPI)
The GPA2 module can be set up, configured and monitored using either the FPI
or the UAP.
The FPI provides limited access and is used primarily for load cell input
configuration and monitoring.
The User Access Program (UAP) is a software application for use with any PC
operating in a Windows environment. It communicates with the GPA2 via the
serial port of the main module. The UAP, together with a copy of the GPA2-E
User’s Manual in PDF format, is supplied on the Load Cell Electronics Utilities
CD.
Features
Navigation via the FPI is accomplished using a structured menu. The FPI menu
is divided into two loops; the Function Setup Loop and the Operation Loop, as
shown in Figure 4-2.
The Function Setup Loop displays the current setup of the unit as shown in
Figure 4.3. This loop allows these setting changes: Filter, Modbus address
(same as Serial Communication Address), and Modbus mode. All other settings
can be as supplied from the factory or as set by the user via the UAP (refer to
Appendix A: GPA2 Model Numbering Scheme).
The Operation Loop (Figure 4-4) is used to define the operational mode of the
unit, to display load data and status information, and for the input and selection of
the sensor Calibration Target Load and shunt resistor values, respectively.
The keypad contains eight input keys and they have the following functions:
The GPA2 main module is equipped with a serial port for communication with a
PC or PLC in one of two modes: RS232 or RS485. The factory default is RS232.
RS485 is used when it is desired to have multiple main modules connected to the
PC at the same time. To change the mode of operation for communication port:
1. Make sure that FPI is in Function Setup Loop by pressing the SET A or SET
B button (Figure 4-3).
2. Use the or key to go down or up the Function Setup loop until the
Modbus Mode setting is displayed as shown in Figure 4-5.
3. To enter edit mode, press the SET A and SET B keys at the same time. Note
that in edit mode, the setting is blinking.
5.1 Introduction
Prior to operating the tension, load, or pressure measuring system, the GPA2
and sensors must be correctly set up and configured to provide accurate
measurement data in the required format.
All GPA2 Modules are supplied with factory default settings or in accordance with
customer specifications at the time of order. The user is directed to Appendix A
for the full range of options available.
Read Section 5.3: Setup and Section 5.4: Configuration of Input Channels,
before attempting setup and configuration.
The sensors and wiring are properly installed and connected to the correct
sensor ports
All analog outputs are correctly connected to the appropriate current or
voltage terminals
Logic I/O, and Fieldbus cables are correctly installed
Any equipment in the mill that responds automatically to the outputs is not
active.
Caution
5.3 Setup
The GPA2 setup defines the functionality of the unit. The user is advised to
check the settings of the GPA2 module, described in the following sections, prior
to system calibration. They can be checked using the Front Panel Interface or
checked and modified as required via the User Access Program. Instructions for
using these interfaces are provided in Part 4: User Interfaces.
To use the FPI, refer to Section 4.3, Figure 4-3 and Figure 4-4.
To use the UAP, refer to Section 4.2, Appendix B, and Section B.6.2.2: Setup.
Two factory-set excitation voltage options, 10 VDC and 20 VDC, are available for
the GPA2 main module. The standard is 10 VDC, whereas 20 VDC is a
customized excitation used in cases when a load cell is designed to have a lower
output for a given application (in most cases, a tensiometer application). GPA2
modules with the 20 VDC option must only be used for applications that require
this higher level of excitation. After powering up the GPA2, measure the
excitation voltage at terminals E+ and E- of sensor inputs A and B to ensure it is
correct for the application.
NOTE:
The GPA2 20 VDC excitation option is for designated applications only.
It must not be connected to load cells with strain gage bridges under 350.
5, 10, 20, 25, 40, 50, 100, or 200 % of Full Scale (FS) input.
Default settings:
Data Source: Output 1=‘A’, Output 2=‘B’
Output Mode: 0-10V
Scaling: 100%
Although the data source cannot be changed, the user can select the threshold
at which the alarm is asserted. The threshold is expressed as a percentage of
A+B in a range from 1-327%. The user is advised to choose a value within the
defined working range (see section 5.4.2). The recommended range is 1-110%.
Default setting:
Threshold 100%
The amplifier has both fixed and user-selectable filtering available. Fixed anti-
aliasing input filtering, with a cut off frequency of 2.8 kHz, is applied to each input
signal to ensure signal quality. The input signal is sampled at a rate of 78.125
kHz and processed at 9.765 kHz. In addition, there is an analog output
smoothing filter with a bandwidth of approximately 1.5 kHz.
700 Hz, 300 Hz, 150 Hz, 75 Hz, 40 Hz, 20 Hz, 10 Hz, 5 Hz
Default setting:
Cut off frequency: 10 Hz
0 700 Hz
1 300 Hz
2 150 Hz
3 75 Hz
4 40 Hz
5 20 Hz
6 10 Hz
7 5 Hz
The time response for a step rise to 98% of the full scale input with the selected
filter is given by the following formula:
This filter signals the source data for the analog outputs and load alarm relay.
5.3.5 Communication
The factory default address for serial communication is 15. The GPA2 FPI
displays the address in decimal format. The address can be changed to any
integer value in the range of 1-15 using the FPI or UAP. The new address does
not become active until the GPA2 is reset (power OFF then ON).
The user must select to use either an RS232 or RS485 protocol; see section 4.4
for details to change the communication mode.
For sensors used in force and pressure applications, the ratio of this forced
output to the full load output is referred to as a Calibration Target Load (CTL),
and is in the range 20.1 to 150.0. The user must program this value into the
GPA2, which uses it to calibrate the force or pressure measuring system onsite.
The CTL, along with the value of the calibration shunt resistor, appears on the
sensor calibration card, which is attached to the sensor when shipped. A
complete list of information appearing on the calibration card appears below.
Each sensor is supplied with a calibration card (see Appendix C, Figure C-1)
listing:
Model number
Serial number
Bridge number (where applicable)
Sensor capacity
Sensitivity - sensor output, in millivolts per volt of applied excitation, at
sensor capacity
The value of the shunt resistor
Output with shunt resistor, in millivolts per volt
Calibration Target Load
Input resistance
Output resistance
In tension measuring systems, the CTL is not based solely on the sensor output
from a directly applied load, as is the case for the force and pressure sensors
previously described. This is because the magnitude of the load applied to the
sensor is dependent on strip tension and the angles at which the strip
approaches and leaves the tensiometer roll. These ‘wrap angles’ must be
accurately known as they are factored into the calibration of the system. KELK
uses the user-defined wrap angles and the geometry of the tensiometer
assembly, in addition to the output measured during the sensor factory
calibration, to compute a Calibration Target Load for the tensiometer.
In addition, the shunt resistor used for system calibration is referred to as the
application shunt resistor, and may be different from the shunt resistor used
during factory calibration of the sensor.
The application shunt resistor value and the tension measurement CTL are listed
in a separate Tensiometer Calibration Data Sheet, Form 855, supplied with each
tensiometer (refer to Appendix C). Individual sensor calibration cards, as
described above, are also supplied with the tensiometer. Typically, such systems
are calibrated such that Full Scale Input for each channel represents 100% of the
user-defined rated tension, not the sensor capacity.
Caution
The shunt resistor value and Calibration Target Load (from the calibration cards
for roll force, pressure and load measuring applications, and from the Calibration
Data Sheets for tension measuring applications) must be entered into the GPA2
prior to system calibration (for reference, the factory default setting for the shunt
resistor is 300 K, while the Calibration Target Load default is 99.9). The user-
selectable shunt resistor values are in a range between 50 and 800 K, in 50 K
steps. Both the resistor and the CTL can be entered via the FPI or the UAP;
refer to Figure 4.4 or Appendix B, respectively. Using the UAP simplifies the
correction of the CTL if long interconnecting cables are used (refer to Appendix
B).
After entering the resistor and CTL values, the user must initiate the
Configuration function, causing the GPA2 to compute and set the tare correction,
offset, and the analog and fine gains for the sensor signals, thereby providing a
calibrated output for the force, tension, or pressure measuring system. It is
important that there is no active load (besides the tare load) on the sensor prior
to applying the Configuration function.
Caution
If Configuration is not performed after parameter change, the measuring system
is not calibrated. The Digital and Analog Outputs and the Load Alarms are
unpredictable and use of the system for mill control purposes may cause the
production of off-specification product or mill damage.
This procedure must also be invoked whenever changes are made to the shunt
resistor value or the Calibration Target Load, or if a sensor has been replaced.
Tare Correction
In many applications, there is force applied to the sensor that the user does not
want to measure. One example is the weight of ancillary equipment supported
by the sensor. It is advantageous to cancel out the sensor offsets caused by
such static loads to maximize the system measurement range. This is referred to
as ‘correction’ and uses the same principle as the shunt resistor to create an
opposing offset.
The ADC utilization is organized such that there is a working range that is defined
for both the positive and negative directions from a zero reference point:
135% or CTL+25%
whichever is greater
10%+20%+5%
100% 100%
WORKING RANGE:
+20%+5%
GAIN < 65280
Working range
MAX > 135% (100% +10% + 20%+ 5%= 135%) shunt CTL
MAX > CTL + 25% (20%+ 5%= 25%)
MIN < -25% (-20% - 5%= -25%)
0
Where:
GAIN = CTL/(shunt - offset)*32768
MAX = 32767 * GAIN - offset
MIN =-32768 * GAIN - offset
+10% - analog output dynamic range offset 0% 0%
±20% - zero allowance
± 5% - overhead -20%-5%
- 25%
NOTE:
The safety margin and zero allowances are in % of FSI, therefore, the selection
of hardware gain and the setting of tare correction have a significant impact on
the ADC utilization. The working range relative to the ADC range is illustrated in
Figure 5-2.
The GPA2 determines the practical ADC working range by stepping through eight
hardware gain selections, starting with maximum gain. The largest gain that
produces a working range within the limits described above is deemed the
optimal gain and is used by the GPA2 for application to the input signals. If even
the minimum available gain setting does not produce a working range within the
above limits, the minimum gain is still applied by the GPA2, however, part of the
working range will be truncated.
The Serial Communications Interface (SCI) can be used to monitor and control
the General Purpose Amplifier, model GPA2.
Caution
Load measurement data accessed through the Serial Communications Interface
are intended for monitoring purposes only. For process control, there is a
dedicated serial port is used to transfer data over an external communicator to
Ethernet, Profibus or PROFINET Fieldbus Interfaces.
The SCI interface functions as a Modbus slave device. Once the SCI is
configured, it waits for a query (message) from a Modbus master. The GPA2
processes the request and, if required, returns an appropriate response. While
processing a query, the GPA2 ignores any new query.
If RS485 mode has been selected, the GPA2 normally configures the port
hardware for receive, switching to the transmission configuration only when
sending a response.
The GPA2 supports the remote terminal unit (RTU) serial transmission mode of
the Modbus protocol only. The GPA2 always requires a ‘silent time’ of at least 3.5
character times as an indication of the end of a query. Characters received with
less than this time separating them will be deemed part of a single query.
Only queries containing 25 characters (10 registers) or less are supported. Any
query longer than this is ignored.
Characters that have a framing error are ignored. This will typically cause any
associated query to be rejected (as missing characters will normally cause the
CRC validation check to fail).
Caution
Reads of undocumented registers will return indeterminate
values. Writing to undocumented registers may cause the
Digital and Analog Outputs and the Load Alarms to be
unpredictable and use of the system for mill control purposes
may cause the production of off-specification product or mill
damage.
NOTE
During certain IO functions such as pressing a key on the FPI or
requesting remote Zero, all read/write operations to Modbus
registers are delayed for 200 ms.
The following is an example of the use of the ‘read holding registers’ function to
read Load and/or Load Alarm. Note that these parameters have been grouped in
the memory map (Table 5-5) so that data for both sensors may be obtained with
a single command.
00 Starting Address Lo
00 Number of Points Hi Number of points = 0002 Hex
02 Number of Points Lo
C5 CRC Lo
E9 CRC Hi
5.5.4 Communications
For bitmapped formats, the condition is enabled (or ‘on’) when the bit is set and
disabled (or ‘off’) when the bit is clear, unless stated otherwise.
The nomenclature used for each format reflects the basic type and size (in eight-
bit bytes) of the format. The size of each format is always an integral multiple of
one byte. Regardless of their size, data are interpreted as ‘big-endian’ (i.e., the
least significant bit is bit 0 and the most significant bit is the highest-numbered bit
for the format).
For formats that do not use all of the available bits, the unused bits are ignored
by the format and are set to zero during transmission.
I - Signed Integer
U - Unsigned Integer
B - Bitmapped
AAA is Additional Format Information
For signed/unsigned integer types, this is the number of implied decimal
digits:
0 - No decimal digits (no decimal point appears)
1 - One decimal digit (decimal point before last digit)
2 - Two decimal digits (decimal point before last two digits)
Etc.
Example: 16I2 is 16 bits, signed integer, 2 decimal points. For a bitmap, this
is a bitmap order number.
Logic Inputs/Outputs
Load Simulation
Configuration Parameters
Single Sensor Operation
0F 2E1 - - -
(Load doubling)
Serial Control Communication
Notes:
1. The Zero and Configuration register is normally in 0 state. The Zero (1) or
Configuration (2) instruction is required to initiate a function. When the
function is complete, the register is automatically set to 0 by the GPA2.
2. Sensor Input Configuration register set to value 3 will invert inputs A and B
and the ‘Single sensor operation measurement status code’ will be
triggered for both A and B channels.
The Modbus/ TCP (Ethernet) Interface provides the process control computer
with access to:
Load measurement data at the rate necessary for process control.
System and Measurement Status.
Monitor and control the GPA2.
The RJ45 Ethernet connector on the GPA2 allows the host computer to access
the GPA2 using the Modbus/TCP protocol.
Note: All registers are accessible through the Ethernet interfaces: Modbus
TCP/UDP. Maximum polling interval for Modbus TCP/IP is 4 seconds. The
communication must be reopened after this interval.
For bitmapped formats, the condition is enabled (or “on”) when the bit is set to 1
and disabled (or “off”) when the bit is 0, unless stated otherwise.
The nomenclature used for each format reflects the basic type and size (in eight-
bit bytes) of the format. The size of each format is always an integral multiple of
one byte. Regardless of their size, data are interpreted as “big-endian” (i.e., the
least significant bit is bit 0 and the most significant bit is the highest-numbered bit
for the format).
For formats that do not use all of the available bits, the unused bits are ignored
by the format and are set to zero during transmission.
The following table defines the data that may be accessed via the Fieldbus
interface. The grouping of the data reflects the manner in which it is treated by
the GPA2. Process variables are updated from the GPA2 to the Fieldbus
memory at 50 Hz. Configuration parameters are updated and could be changed
at a rate of 5 Hz.
Host
Host Write
Read Min Max
Address Name Format Units Notes
Address Value Value
(Hex)
(Hex)
Process Variables (Read-Only, Volatile)
Input A Load
0000 16I2 % -327.68 327.67 1
Input B Load
0001 16I2 % -327.68 327.67 1
System Status
0002 4B2 - - - 1
Channel A&B Measurement
0003 16B3 - - - 1
Status
Receive /Transmit Statistic (Read-Only, Volatile)
Relay Outputs Transmit 8U0
- - -
0004 Count 1
Logic Inputs Receive Count 8U0
Configuration Parameters (Read-Write, Nonvolatile)
0005 0005 Configuration, Zero 2B4 - - - 2
Sensor Input Configuration
0006 0006 2E1 - - - 2
(Load doubling)
Notes:
1. These variables are updated by the GPA2 every 20 ms.
2. These variables are updated by the GPA2 every 200 ms.
Part 6 Operation
6.1 Introduction
The General Purpose Amplifier GPA2, provides the user with the following
features for system monitoring and control:
Load display
Load level alarm
Single sensor operation
Channel configuration
Zero
Channel test & load simulation
System status and online diagnostics
Measured loads are displayed via the Front Panel Interface (FPI) alphanumeric
display and the User Access Program (UAP) Operations screen. (Throughout
the rest of this section, any descriptor in parentheses indicates how the
parameter is shown on the FPI, i.e. uppercase or lowercase.)
During normal operation (when both Sensors A and B are operational), the
individual A and B, sum S) and difference d) loads can be displayed on the
FPI as follows:
Loads A, B, S and d are in the numerical range -327.60 to 327.60, the limits
representing negative and positive input saturation. The display range is limited
such that the negative values are limited to -0.1 to -199.9. Numbers below -
199.9 do not have a preceding negative sign.
During Single Sensor Operation (i.e. 2 x Sensor A or 2 x Sensor B), the load
values will be based on the single operational sensor selected.
The user can select the load parameter to be displayed from the Operations
Loop menu by using the keys.
The load alarm activates when the user-set load threshold of the SUM load is
exceeded. The condition is indicated by:
Refer to Section 9.5 for more details regarding the alarm relay.
System status includes status of the signal processing electronics, the sensor
excitation currents, and the input signals, which are all continuously monitored.
System status is indicated by:
The input signal level is monitored, and if it is high enough in either the positive
or negative direction to cause saturation, a fault condition and error message are
displayed.
Status: xxyy
Note the hexadecimal code can represent a single error code or the sum of error
codes. If a fault is indicated, refer to Part 7: Diagnostics & Troubleshooting, or
the UAP system status list panel for details of error codes.
For further information regarding status messages in the UAP, see Appendix B.
During input channel configuration, as detailed in Section 5.4, the user enters the
value of Calibration Target Load and selects an application shunt resistor. When
the Configuration command is invoked, this value and shunt resistor are used to
set the gain of each channel, a process that determines the relation between full
scale input and full scale output for each channel.
Channel configuration establishes both the channel gain and the channel zero
reference. This function is typically applied immediately following the sensor
parameter (CTL) entry procedure as described in Part 5 of this manual. It is
recommended that the CFG button, and its equivalent in the UAP, only be used
to re-configure the channel when initializing a sensor or in the event of a fault
indication. It can be invoked at any time, however, when the system is not online
to re-establish the zero reference and to confirm the internal gain settings.
A successful CFG is indicated for each channel when activation of the CFG
command does not return an error indication for either channel. The absence of
an error confirms that the span for each channel has been set and both channels
are at zero.
Caution
During a Configuration (CFG) operation, the digital and analog
outputs, and the load alarm continue to function normally.
Ensure they are not in use for control as this may cause the
production of off-specification product or equipment damage.
To prevent against unwanted Configuration under load, FPI access to the CFG
function may be disabled using the UAP (see Appendix B, sub-section B.6.3.3).
6.6 Zero
Zero adjusts the fine offset of both channels to set their outputs to zero. It is
normally used to compensate for small changes in tare load.
Configuration (CFG) establishes a zero reference at the input stage. The Zero
command will successfully zero the outputs provided that the total offset, relative
to the zero reference established during CFG, does not exceed ±20% of the full
scale input. This limit serves to advise the user of the accumulation of small
offsets successively corrected or to alert the user to a single large change in
offset. Exceeding the 20% limit results in a ‘zero out of margin’ error. It is
recommended that in the event of a ‘zero out of margin’ error message, the
cause be investigated prior to further operation. To continue operation, invoke
Configuration by pressing CFG to establish a new zero reference. See Part 7:
Diagnostics & Troubleshooting, for further assistance with troubleshooting.
To prevent against performing an unwanted Zero function under load, FPI access
to the Zero function may be disabled using the UAP (see Appendix B, sub-
section B.6.3.3).
Caution
During a Zero operation, the digital and analog outputs, and the
load alarm continue to function normally. Ensure they are not in
use for control as this may cause the production of off-
specification product or equipment damage.
Channel Test / Load Simulation is a feature provided to check the GPA2 setup
and the load output (analog or digital) to the user’s control system interface. It
can be invoked via the FPI or the UAP.
With Channel Test / Load Simulation initiated, the shunt resistor previously
applied during the Configuration is now applied to the sensor bridge. The level of
the load output will correspond to the Calibration Target Load (including any
corrections for interconnecting cable resistance entered during Configuration).
Caution
During Channel Test / Load Simulation, the digital and analog
outputs, and the load alarms are forced to user selected levels
until normal operation is resumed. Ensure that they are not in
use for control during this time as this may cause the production
of off-specification product or equipment damage.
Note that if the Calibration Target Load or the selected value is greater than
110% and if the analog output scale factor is equal to or smaller than 100, the
analog outputs may saturate.
GPA2-E Manual 90472 RevC
July 2018 58
KELK Operation
When invoked:
Both individual outputs show the same value as the source selected, A or B.
The sum load (A+B) is twice the selected sensor load and the difference load
(A-B)
is zero.
The front panel ‘Single Sensor’ LED indicator is illuminated and the
appropriate Sensor Fault indicator will be set. These responses will also be
indicated in the UAP and through the Fieldbus.
Note 2. Note that the Single Sensor Operation condition is non-volatile and
is, therefore, retained even if the GPA2 power is cycled off and on.
7.1 Overview
When a fault is detected, indicators are set to alert the user and status messages
are posted to assist in identification and correction of the fault condition.
Note 1 The GPA2 is supplied with channel and system fault indicators
asserted. The user must apply valid channel configurations to
remove the fault indications prior to placing the unit into operation.
Note 2 Single Sensor Operation is the only fault condition under which the
system can remain operational.
For troubleshooting purposes, error codes can be obtained through the user
and communications interfaces.
These are referred to as the Error Codes and they are presented in the following
locations:
In the UAP Diagnostics Status screen (Figure B-13 Status Panel)
In the Serial Communications Interface (Section 5.5) and Fieldbus Interface
(Section 5.6 and Appendix D) by bitmapped messages (Table 7-1)
In the FPI as Hex sums of individual faults (Table 7-1)
Error Code
Fault Mode Set condition or test Fault Condition
[HEX]
Simulation active Test condition 80
User Set condition Single Sensor Operation A or B input data disabled 40
active
Sensor excitation test Excitation OFF 20
GPA2 Monitoring
Channel input condition test Input Saturation +/- 10
Zero Zero out of margin 08
Auxiliary Function- Gain out of range 04
User activated Zero out of range 02
Configuration
Shunt input or FSI out of 01
range
Table 7-1: Fault Conditions and Resulting Error Codes
From the displayed fault number, subtract the largest Error Code number (in
Hex format), identified in the table above, which is equal to or less than the
displayed number. That error for that largest Error Code is present.
Repeat the above, subtracting next largest Error Code from the remainder,
until the remainder is reduced to zero.
Note that the Error Code is a number in hexadecimal format.
Example:
For Status Message 0630:
Important Note
A single fault condition can result in several error codes combining to produce a
Status message. When deciphering a status code into its component error
codes, the faults are revealed in descending identification number order. This
indicates the order of importance of the fault. The user is advised to identify the
cause of each component error and apply corrective action. Correction of the
larger numbered fault conditions may automatically remove those with smaller
identifying numbers.
The GPA2 has user selectable conditions that result in fault indication.
When invoked:
Both individual outputs show the same value as the source selected, A or B.
The sum load (A+B) is twice the selected sensor load and the difference load
(A-B) is zero.
The front panel Single Sensor indicator is illuminated; the appropriate Sensor
Fault indicator will be set. These responses will also be indicated on the UAP
and through the Fieldbus.
Note that System Healthy indication is not affected by this fault (which can only
be applied to one channel at a time). The active error code is masked by the
System Healthy logic.
This allows the amplifier to be operated under this fault condition but the user is
advised that any differential signal will show zero.
Note the Single Sensor Operation condition is non-volatile and is, therefore,
retained even if the GPA2 power is cycled off and on.
The channel input signal levels and the sensor excitation supplies are
continuously monitored and, in the event of problems, fault indications are set.
These indications are volatile; existing only while the fault is detected.
This fault occurs if the sensor excitation supply is not within specification: 10
VDC for models E1 or 20 VDC for models E2.
7.4 Faults detected by Auxiliary Function Checks (Error codes 08, 04, 02, 01)
Note that fault conditions resulting from these diagnostics are non-volatile. The
fault indications will remain until corrected even if the GPA2 power is cycled off
and on. A successful application of the auxiliary function, CFG or ZERO, is
required to clear the fault.
In this case, offset is not adjusted, the fault indicator is illuminated, and an error
message is displayed for that channel:
Corrective action:
Check load condition
Check sensor and sensor connections
If the zero offset is permanent, then apply CFG to adjust the
tare correction and re-establish the zero reference point
7.4.2 Channel Configuration CFG Faults (Error codes 04, 02, 01)
These faults would occur after a channel configuration (CFG), which is user-
initiated via the FPI, the UAP or the Fieldbus.
This Configuration function checks that the sensor working range, as defined in
Section 5.4.2 and illustrated in Figure 5-2, is within the operating range of the
internal Analog-to-Digital (A/D) converter and that the resolution of the defined
full scale input (FSI) is acceptable.
The existing tare and gain settings place the working range zero allowance
outside the A/D operating range in the negative direction.
In this case, the working range has been checked and found to exceed the
positive limit of the operating range of the A/D converter. The cause is incorrect
channel configuration.
Error Codes: Sensor A 0100, Sensor B 0001
Corrective action:
Check the sensor and its connections; see Section 7.5
Check the excitation supply.
Check the Calibration Target Load value set.
Check the shunt resistor value selected.
Reapply CFG.
Note
1. Ensure the suspect channel is either not loaded or only tare loaded.
2. Switch off the GPA2.
3. Disconnect the red and white interconnecting cable wires. Switch on the
GPA2.
4. With a digital voltmeter (DVM) or multimeter, measure the excitation
voltage between the GPA2 terminals that the green (+) and black (-) wires
are connected to. This should be 10 VDC ±0.5 VDC or 20 VDC ±0.5 VDC
depending on the model type (‘D1’ is the identifier in the GPA2 model
number for 10 VDC excitation, whereas ‘D2’ is for the 20 VDC excitation
model). A low reading indicates current leakage in the cable or sensor, or
an excitation supply problem.
5. With the DVM set to millivolts, measure between the red (+) and white (-)
wires. The reading will normally be less than 3 mV. Values above 15 mV
are unusual. If the value is high, it may be beyond the range of the zero
control. A reading of ±5V (or ±10V for ‘D2’ type) indicates sensor failure.
6. Switch off the GPA2, disconnect the green (+) and black (-) wires (this
completely disconnects the cable from the main module) and conduct the
following tests in order:
a) Input resistance: using an Ohmmeter with a resolution of 0.1 measure
between the green and black wires. The reading should be within 1 of
the resistance specified on the sensor calibration card, plus the
resistance of the interconnecting cable.
b) Output resistance: repeat (a) between the red and white wires.
High or low readings for tests (a) - (b) indicate cable problems or a
damaged sensor.
c) Using a DVM set to millivolts, measure between any wire and ground.
The reading should be less than 5 mVDC.
d) Repeat (c) between any wire and the internal cable shield.
GPA2-E Manual 90472 RevC
July 2018 67
KELK Diagnostics & Troubleshooting
Caution
g) Measure bridge to shield resistance by repeating (f) for any sensor wire to
the cable shield.
If all readings were normal for tests 5 and 6, then the excitation supply is faulty.
Replace the GPA2 module and/or power supply.
If any readings were abnormal for tests 5 and 6, the problem is caused by the
interconnecting cable or the sensor.
1. Disconnect the cable at the junction box and at the main module.
2. Test all conductors for continuity.
3. Measure the resistance to ground of all conductors.
4. Measure the resistance to shield of all conductors.
5. Measure shield to ground resistance.
6. When reconnecting the cable:
Replace all dirty and corroded terminal blocks and lugs. Ensure that there
are no frayed wires to cause momentary shorts to ground.
Ensure that the box and all internal components are dry. If moisture is
seen or suspected, dry with alcohol.
Ensure that the cable shield is electrically isolated from the box ground.
Ensure, when closing, that the box is properly sealed, checking the cover
and all cable entry points.
Note: KELK load cells can be returned to the KELK factory for evaluation and
repair. KELK also offers a full range of after-sales services to assist
customers in the maintenance of their systems and troubleshooting should
problems arise.
Part 8 Maintenance
8.1 Introduction
Service is only required if a failure occurs. Repair of the GPA2 main module on-
site is not possible. In the event of a failure, the GPA2 module must be sent to
KELK for inspection and repair if possible. Module that cannot be repaired will
be replaced as per warranty.
Caution
Do not touch any components on the PCB; handle the board by the edges
only.
Note that a new GPA2 Module means that all previous Setup and Configuration
has been lost. It is necessary to configure the new GPA2 Module; refer to Part 5:
Setup and Configuration, for setup and configuration and Part 6: Operation for
operation use.
Part 9 Specifications
9.1 Performance
*Note: Spaces in above model number (“ ”) denote enclosure type and are
not related to GPA2 performance.
See Section 9.12 for enclosure specification
Sensitivity range: GPA2- -E1 0.50 - 5.0 mV/V per volt full
scale.
GPA2- -E2 0.25 - 2.5 mV/V per volt full
scale.
Qty 1 Load Level Alarm2 Form ‘A’ 2 activation when threshold exceeded.
Threshold can be specified at the time of order via the model number
and programmed at KELK, or can be programmed by the user with
the UAP only (default 100.0%) exceeded
Imax = 80 mA, Vmax = 30 VDC/VAC
Qty 2
Measurement data: A, B, A+B, A-B, selectable via UAP only, can be
defined at the time of order by model number
choice.
Mode: Current or voltage selectable via UAP only, can
be defined at the time of order by model
number choice as:
±10VDC into a resistive load of 2000 ohms
minimum
or
4-20 mA into a resistive load not exceeding 500
ohms
Saturation: 110% for voltage (11VDC) and 105% for
current (21mA)
Scaling: 5-200% of Full Scale Input
Isolation: group (2)
External connections: screw terminal for signal and shield. Voltage
and current output share common ground
terminal.
Resolution: 16 bit
9.7 Filtering
9.13 Physical
Power requirements 100 - 240 VAC, 50 VA, 50-60 Hz
Power Supply Module Input 85 - 264 VAC, 0.65 - 0.25 A, 45-65 Hz
Power Supply Module Output 24 VDC, 1.3A
Main Module Input 24 VDC, 300 mA
Profibus Communication Module 24 VDC, 300 mA
PROFINET Communication Module 24 VDC, 280 mA
Ambient Operating temperature -10°C to +55 °C
Operating Humidity 90% at 55 °C
Storage temperature -20 °C to +80 °C
Storage humidity 70% at 40 °C
Weight 33 lbs. (15 kg)
9.14 Dimensions
Appendix A
GPA2 Model Numbering Scheme
To simplify ‘on site’ setup, the model number includes extensions to allow customers to
order GPA2 units preset to specific requirements.
Functionality Setup
Analog Output scaling
Load Alarm Threshold
Digital filter
where ‘a’ denotes an alphanumeric character and ‘n’ or ‘nm’ denotes single and
double-digit numbers, respectively. Subscripts, when included, identify the
specific analog output. Leading characters ‘o’, ‘C’, ‘P’, ‘t’, and ‘F’ identify
parameters as specified below in detailed Functionality Setup.
Note that the order of the model number component parts must be maintained.
Hardware Identification
Enclosure: - aa
- 12 Nema 12 - Painted Steel
- 4X Nema 4X - Stainless Steel
- 00 Cabinet Mounting Kit
- RE P640 to GPA2 conversion kit. Applicable only if a P655
cabinet was previously supplied by KELK.
Hardware Description: - yz
-y E - Hardware Revision (on the FPI displayed ‘E’)
-z 1 - 10VDC excitation voltage, standard
2 - 20VDC excitation voltage, option
Functionality Setup
-o Parameter identifier for Data Source and Operational Mode for Analog
Output #1 -(nm)1 and Analog Output #2 -(nm)2 .
-C Parameter identifier for the scale factor for Analog Output #1 -(nm)1 and
Analog Output #2 -(nm)2 .
-(nm) 01 = 200%
02 = 100%
04 = 50%
05 = 40%
08 = 25%
0A = 20%
14 = 10%
28 = 5%
Load Alarm
-P0031 Alarm triggered by SUM(A+B) factory set; closed above user-set
threshold, as described below
This setup will be factory applied in the event that the customer does not request
a specific setup at the time of order.
To define a specific setup, use the GPA2 Ordering Form #881; see Figure A-1.
NOTE: In the event that any component is not fully defined by the customer
when ordering, the default for that component will be applied.
Appendix B
User Access Program
B.1 Introduction
The General Purpose Amplifier (GPA2) is designed to function with a large range
of strain gage type sensors throughout various applications. Many features and
options are available and the amplifier can be set up to operate in a number of
distinct modes depending on the application. The main module of the amplifier is
normally ordered fully setup to match the user defined operation mode. The
model number includes extensions to allow the customer to order the unit
specifically preset as per their requirements.
The function setup, as defined by the model number, is applied to the unit at the
factory since the Front Panel Interface (FPI) has limited functionality and,
therefore, factory definition is preferred to ‘on site’ setup. A User Access
Program (UAP) has been developed to provide the user with friendly and more
comprehensive tools by which to set up, configure and monitor the GPA2. In
addition, it permits the user to change the SETUP of the unit for a different
application or set of circumstances, if required.
The User Access Program (UAP) is supplied on a CD together with a copy of the
GPA2 Manual in portable document format (.pdf). The program is designed for
use with any PC operating in a Windows environment; connection to the amplifier
is through the serial port connector on the main module.
B.2 Features
The UAP can also be used without a connection to the GPA2. This mode, using
a default GPA2 configuration file, allows the user to familiarize themselves with
the program and its navigation.
B.3 Installation
For use with Windows 98, ME, 2000, or XP. Refer to Section 9.12 for minimum
computer requirements.
Insert the KELK Load Cell Electronic Utilities CD in the CD drive and follow the
'NEXT' prompts to complete installation of the program.
If the CD does not automatically start the installation process, open the CD icon
and double click on SETUP.EXE. Load Cell Electronic Utilities menu will appear
with options to install the GPA2UAP program and to view the GPA2 User’s
Manual. To display the GPA2 User’s Manual, the Acrobat Reader available on
this CD is required.
NOTE: If there is already an earlier version of the program installed on the PC,
the installation program will prompt you before uninstalling it. When the uninstall
is complete, remove and re-insert the CD to start the install process.
Once the program is installed, navigate through: Start\Programs\GPA2UAP and
click on GPA2UAP to launch the program.
B.4 Communication
The GPA2 must be suitably configured for communication with the host
computer. Communication is via the main module serial port.
The GPA2 supports two communication protocols: RS232 and RS485. The
default communication protocol is RS232. To change the communication
protocol to RS485, refer to the procedure in Section 4.4. The GPA2 default
address is 15; this can be changed to any value in the range of 1 to 15 after
communication has been established with the host computer via the UAP. Note
that the new address, applied via the SETUP Panel will not be valid until the
GPA2 is reset by Power OFF/ON.
The right hand portion of this panel is for the host computer setup. Select the
COM port to be used for the GPA2 connection and select the GPA2 address.
Ensure the GPA2 is connected to the computer and press scan to search for the
unit.
If the address is correctly configured, the UAP will recognize the device, extract
its assigned serial number and function Setup, and return the panel shown in
Figure B-3. This panel indicates the directory path for Configuration files and
prompts the user to select a Configuration file from the list or to name a new file
*.[GPA2serial#].cfg.
Assign a name to the indicated file and click OK. Ensure to keep the
*.[GPA2serial#].cfg extension in the name of the file (ie. Tension.26.cfg). The
panel shown in Figure B-2 will be displayed again with row 1 completed with the
GPA2 communications data and file name.
NOTE: To open multiple files for more than one unit (RS485 Connection) the
user can open each subsequent file using ‘Open Configuration File’ and use
‘Communication Setup’ under the ‘File’ of the Menu bar similar as above.
Active communication with an operational GPA2 gives the user access to all the
UAP features and panels. All panels include the Navigation Panel to assist the
user.
NOTE: Data entry into any data field in any panel will result in the background
of that field changing color to yellow to indicate that the field has been edited.
The field background will remain yellow until the data is applied to the GPA2
using the ‘Apply to GPA2’ command on the GPA2 ‘CONFIGURE & SET’ Panel.
Data entered via the ‘Input Configuration’ panel become active after the ‘CFG’
command is executed from the FPI or from the ‘CONFIGURE & SET’ Panel.
Changes entered via ‘Setup’ Panel are made active immediately after the ‘Apply
to GPA2’.
A diagnostic log file with data time and error code records can be automatically
created on the hard drive, see Section B.7.2. This feature is active when the
Status Logging is selected and the GPA2 connected to a host computer.
All panels available are summarized in the Navigation Panel to assist and guide
the user.
Navigation Panel
The Navigation panel, Figure B-4, displays a list, headed by the GPA2
*.[serial#].cfg file name, of the UAP Main panels and sub-panels that can be
accessed by the user as shown below.
All main panels and sub panels can be selected and directly accessed by the
user and always include the Navigation Panel.
B.6.1 Operations
Selection of either ‘GPA2: (name)’ or ‘OPERATIONS’ will display the Operations
panel, Figure B-5.
‘Name’ is user applied for a connected GPA2, otherwise the ‘name’ field contains
a file name.
1) Load Units [#], switch the channel output level on the bar graph from percent
of Full Scale to Load Units of the users choice.
2) Status List, see Part 7
3) Single Sensor Operation, see Section 6.8
4) Zero, see Section 6.6
Activation of any button changes the dialogue box to reference the chosen
operation and displays further options for invoking that operation.
Basic Entry
In this mode the user cannot access most of the features on this panel. Load
Cell Calibration Card Information is largely for record only and is not accessible
under ‘Basic Entry’ with the exception of ‘Input Bridge Resistance’. The principal
purpose of this panel is an alternate method to using the FPI to enter the
Calibration Target Load value. A default value is first displayed. The user can edit
this value, go to the previous panel and select ‘Apply to GPA2’ followed by ‘CFG’.
Extended Entry
This is the recommended mode of data entry as it makes all features available to
the user. This is particularly useful for applications such as Tension Measurement
where Application Calibration Target Load is different from that given on the Load
Cell Calibration Card. The user is directed to Appendix C for a description of
Application related Form 855.
Using Application, Figure B-9, the user can select the type of application for
which the sensors are used. With Tension selected, the user can access the
Application Wizard to calculate the strip and roll geometries and sensor
arrangements.
Cable Calculator
This feature is provided for CTL correction in the case of long interconnecting
cables.
Application Wizard
This feature is for tension applications, refer to Appendix C for further details.
The Wizard includes libraries of strip to roll geometries and various KELK sensor
arrangements. This feature can be used to calculate wrap angles, derive Force/
Tension relationships and calculate parameters Application Calibration Target
Loads; see Figure B-11.
This feature is particularly useful when changes are made to the geometry of the
strip/roll/sensor system.
Apply Corrections.
Activation of this feature applies Corrections derived using the Cable Calculator
and the Application Wizard.
B.6.2.2 Setup
This panel, Figure B-11, represents the Function Setup Loop (Refer to Section
4.4) of the Front Panel Interface. Using this panel the user can select and
define all programmable functions of the GPA2. Pull down menus are provided
to simplify the process.
Analog Outputs
For each of two analog outputs the user can select
Data source
Mode, current or voltage
Scaling
Load Alarm
The Load Alarm is preconfigured to represent the SUM of both channels in the
case of a Force application or the average of the two channels for Tension or
Pressure applications.
The user can enter a “Load Alarm Threshold Limit’ value at which the alarm will
be asserted in the range of ±327%. If the value entered is out of the GPA2
range it will not be accepted.
The user is advised to select a value within the operating range of the ADC as
determined during Channel Configuration
UAP Display
The OPERATIONS panel includes two bar graphs showing active loads. The
default display is as a percentage of defined Full Scale. Using UAP Display the
user can define Full Scale in terms of ‘load units’ of their choice.
B.6.3 Diagnostics
B.6.3.1 Status
The Diagnostics Status panel, Figure B-13, displays the current status of the
GPA2.
See Part 7: Diagnostics & Troubleshooting for a full explanation of all displayed
fault conditions.
A diagnostic log file is automatically created on the hard drive. Log file created is
a text file that records date time and error code. This file will have same name as
unit configuration file with .log extension and can be accessed independently of
the UAP using Notepad.
Note that this feature is only active when the Status Logging is selected and the
GPA2 connected to a host computer.
B.7.3 Help
A full copy of the GPA2 manual in .pdf format is included with the GPA2 UAP and
it is accessible through the ‘Help’ on the Main Menu bar or independently
navigated through Windows: Start\Programs\GPAuap.
Appendix C
Tensiometer Calibration Information Sheets, Forms 858 and 855
C.1 Introduction
KELK load cells can be used to measure force or tension. Each load cell is
factory calibrated to determine its full load sensitivity, or output at its rated
capacity. Following this, a precision resistor of known value (calibration shunt
resistor) is placed across one arm of the load cell bridge to force a fixed and
repeatable output. The forced output is expressed as a percentage of the full
scale output for force, pressure or tension, depending on the application. This
provides a precise transfer reference that allows the system to be calibrated on-
site, effectively removing the need to use dead weight or auxiliary calibration
equipment that may be difficult to apply in the actual installation.
Onsite, a field reference value is inputted by the user into the GPA2, which is
then used during the ‘Configuration’ operation to adjust GPA2 offset and gain to
provide the expected output for the rated load or tension (see Section 5.4 and 6.5
or Appendix B, Section B.6.2).
Each KELK load cell is supplied with a calibration card giving details of the model
and serial number, its full load sensitivity, and the value of field transfer reference
and the value of shunt resistor applied to create it. An example of a calibration
card is given in Figure C-1: Example of a Calibration Card.
Load cell systems that require outputs in terms of force or load can be calibrated
directly using the information given on the calibration card. In the cases of
systems designed to measure tension, however, additional information is
required to assist the user to calibrate the system.
This form is generated by KELK by inputting application wrap angles and specific
system parameters, as given on the application installation drawing, into the
GPA2 User Access Program (UAP) supplied with the system. An example is
given in Figure C-2: Form 858, Tensiometer Application Data Sheet.
This feature of the UAP can be accessed by clicking on the ‘Application Wizard’
button in the ‘Input Configuration’ screen (Note: the ‘Application Wizard’ button is
only active if the ‘Tension’ application and ‘Extended Entry’ selections are
chosen). Refer to Appendix B for full details.
All above information is displayed, and can be readily interpreted, using the
comprehensive legend.
KELK generates Form 858 using the user supplied data. In the event of system
changes, the user can use the UAP feature to update the system information and
generate new data.
C.3
This form, supplied for each application, uses the data derived using Form 858
and the load cell calibration card to determine the Calibration Target Load to be
entered into the Main Module to correctly calibrate each sensor channel. As a
result, the amplifier outputs a signal directly representing tension.
The form also includes information to assist the user in the setup of each input
channel as follows:
Application information
Row 1. Location in mill
2. Sensor position; for example, Drive or Operator side
3. Rated tension for the application
4. KELK reference information (installation drawing number)
IMPORTANT NOTE
The content of Forms 855 and 858, as supplied with the manual, is derived from the
information given on the installation drawing and/or supplied by the customer. This data
should be checked against the ‘as built’ or ‘as installed’ situation at the time of system
calibration. If the data on the forms do not correspond to the ‘as installed’ situation, a
new Tensiometer Calibration Data Sheet should be created. This can either be done by
KELK or by the customer using the UAP Input Configuration screen and the Application
Wizard.
Appendix D
Fieldbus - Profibus Protocol
D.1 Introduction
The optional Fieldbus Interface provides the mill control computer with access to:
Load measurement data at the rate necessary for mill control.
System and measurement status
Monitor and control the GPA2.
GPA2 uses an Anybus Communicator (ABC) Gateway to connect to the fieldbus. This
appendix describes the Profibus DP protocol version.
Configure GPA2 device address to 15 (factory default) using UAP or FPI (see
Appendix B or Figure 4-3)
D.2.1 Connections
Anybus Communicator
A. Profibus Connector
This connector is used to connect the ABC to the fieldbus.
B. PC Connector
This connector is used to connect the ABC to a PC for configuration and
monitoring purposes.
C. GPA2 connector
This connector is used to connect the ABC to GPA2.
D. 24V Power connector
Use this connector to apply power to the ABC.
E. DIN Rail connection
The din rail connector is internally connected to PE.
Connect the GPA2 fieldbus cable between the ABC’s GPA2 connector and GPA’s
fieldbus connector. The cable connections are described in the next picture.
Connect the Anybus Communicator Gateway for Profibus to the fieldbus as indicated
below.
Pin Description
1 +24V DC
2 GND
D.2.2 Termination
If the AnyBus Communicator is the last node on a Profibus segment, it is necessary to
use an external termination.
The configuration switches are used to set the Profibus node address.
Normally, these switches are covered by a plastic hatch. Note that the node address
cannot be changed during runtime, i.e., the ABC requires a reset for any changes to
have effect.
D.2.4 Indicators
NOTE: At 'power ON', the GPA2 Link Status will be red, changing to green after all transactions
have been active at least once. This includes any transactions using “change of state” or
“change of state on trigger” (read or write commands performed to all registers).
Uninitialized registers will not influence communication. Communication will be correct while
the GPA2 Link Status is red.
D.3 Processing
The ABC cannot determine exactly which variable has been updated by the host in the
dual port memory so it operates by identifying changes in variable values sent by the
host.
Normally, this is completely transparent to the host but there are two cases where care
must be taken:
At startup the current value buffer, used to identify changes, is set to 0. If the host
tries to write a zero to a GPA2 register, no action will be taken and the GPA2
register will remain at its default power-on value.
If the host tries to write the same value twice to a GPA2 register, no action will be
taken and the GPA2 register will remain unchanged. This is only a problem if the
register has been changed by the UAP between the first and second writes.
Functions such as Configuration and Zero, that are initiated by changing a register
value from 0 to 1 and indicate completion by the GPA2 changing the value back to
zero, must be handled as follows:
D.4 Communications
Bitmapped Types
4B2 System Status Bit 0 - System Healthy
Bit 1 - B Fault
Bit 2 - A Fault
Bit 3 - Single Sensor
16B3 Channel A&B Measurement Bit 0 - Channel B: Shunt or FS out of range
Status Bit 1 - Channel B: Zero out of range
Bit 2 - Channel B: Gain out of range
Bit 3 - Channel B: Zero out of margin
Bit 4 - Channel B: Saturation +/-
Bit 5 - Channel B: Excitation current overload
Bit 6 - Channel B: Single Sensor Operation (Double
A)
Bit 7 - Channel B: Simulation
Bit 8 - Channel A: Shunt or FS out of range
Bit 9 - Channel A: Zero out of range
Bit 10 - Channel A: Gain out of range
Bit 11 - Channel A: Zero out of margin
Bit 12 - Channel A: Saturation +/-
Bit 13 - Channel A: Excitation current overload
Bit 14 - Channel A: Single Sensor Operation (Double
B)
Bit 15 - Channel A: Simulation
2B4 Configuration, Zero Bit 0 - Zero
Bit 1 - Configuration
Enumerated Type
2E1 Sensor Input Configuration 0- A &B
(Load doubling) 1- 2*B
2- 2*A
3- B &A
byte. Regardless of their size, data are interpreted as “big-endian” (i.e., the least
significant bit is bit 0 and the most significant bit is the highest-numbered bit for the
format).
For formats that do not use all of the available bits, the unused bits are ignored by the
format and are set to zero during transmission.
Notes:
1. These variables are updated by the GPA2 every 20 ms.
2. These variables are updated by the GPA2 every 200 ms.
Appendix E
PROFINET Fieldbus Protocol
E.1 Introduction
The optional PROFINET Fieldbus Interface provides the mill control computer with
access to:
Load measurement data at the rate necessary for mill control
System and measurement status
Monitor and control the GPA2
The GPA2 uses an Anybus Communicator protocol converter gateway to connect to
the GPA2 to the PROFINET fieldbus. This appendix describes the Anybus
Communicator Gateway converter used by the GPA2 to provide an interface to the
PROFINET fieldbus.
E.2 PROFINET
PROFINET is the open Industrial Ethernet standard for Automation from PROFIBUS
International. The AnyBus Communicator Gateway for PROFINET currently supports
the following protocol features:
Soft Real-Time (RT) communication
Cyclic data exchange (10 ms cycle time)
Acyclic Data exchange (Record Data Requests)
Up to 64 slots / 1 subslot
Up to 512 bytes of I/O in each direction
TCP/IP Configuration via DCP (Discovery and Configuration Protocol)
Reference Description
Status LEDs:
B
Refer to section E.3.5: Indicators.
PC Connector:
This connector is used to connect the HMS Anybus Communicator for PROFINET
C
to a PC for configuration and monitoring purposes; refer to section E.3.2: PC
Connector.
Power Connector:
E This connector is used to apply power to the HMS Anybus Communicator for
PROFINET; refer to section E.3.4: Power Connector.
DIN-rail Connector:
F This connector is used to mount the HMS Anybus Communicator for PROFINET to
a DIN-rail and connects the module to ground, refer to
Pin Signal
Housing Cable Shield
1 TD+
2 TD-
3 RD+
4 Termination
5 Termination
6 RD-
7 Termination
8 Termination
E.3.2 PC Connector
3
Provided with HMS Anybus Communicator for PROFINET module.
Pin 2 Pin 4
Pin 3 Pin 3
Pin 5 Pin 2
N/C Pin 1
Cable
Shield
Pin Signal
1 Signal Ground
2 Signal Ground
3 RS232 RX
4 RS232 TX
Table E-3: RJ-9 Connector Pin Out Details
Pin Signal
Housing Shield, connected to PE
1 N/C
2 RS232 Rx (Input)
3 RS232 Tx (Output)
4 N/C
5 Signal Ground
6-9 N/C
Setting Value
15
Unit Address
(factory default)
Mode RS232
Bit Rate 19200 baud
Parity None
Data 8 bits
Stop 1 bit
The subnetwork connector (refer to Figure E-1, ‘D’) on the HMS Anybus
Communicator for PROFINET uses a DB9-female connector. The pinout and details
for this connector is shown in and Table E-6, respectively.
Pin Signal
Housing Shield, Connected to PE
1 +5 VDC
2 RS232 Rx
3 RS232 Tx
4 N/C
5 Signal Ground4
6 RS422 Rx+
7 RS422 Rx-
8 RS485+ / RS422 Tx+
9 RS485- / RS422 Tx-
Table E-6: DB-9 Female Connector Pin Out Details on PROFINET Module
The subnetwork connector (refer to KELK Drawing 46799) on the HMS Anybus
Communicator for PROFINET uses a 5-position terminal block style plugin connector.
The pinout and details for this connector is shown in Figure E-8 and Table E-7,
respectively.
4
Connecting this signal directly to Protective Earth (PE) of other nodes may, in case of grounding loops etc., cause damage to the on-board serial
transceivers of the HMS Anybus module. It is therefore generally recommended to connect it only to Signal Ground (if available) of other nodes.
Pin Signal
1 RS232 Tx
2 N/C
3 Signal Ground
4 N/C
5 RS232 Rx
Table E-7: GPA2 Fieldbus Connector Pin Out Details
The schematic for the GPA2 PROFINET fieldbus cable (PL044014-6IN) is shown in
Figure E-9.
Pin 2 Pin 1
Pin 5 Pin 3
Pin 3 Pin 5
Cable
Shield
Figure E-9: GPA2 PROFINET Fieldbus Cable Schematic
Pin Signal
1 +24 VDC
2 GND
Table E-8: Power Connector Pin Out Details for PROFINET Converter
E.3.5 Indicators
NOTE: At 'power ON', the GPA2 Link Status will be red, changing to green after all transactions have been
active at least once. This includes any transactions using “change of state” or “change of state on
trigger” (read or write commands performed to all registers).
5
This LED turns green when all transactions have been active at least once. This includes any transactions using “change of state” or “change of state on
trigger”. If a timeout occurs on a transaction, this LED will turn red.
6
If the gateway is in bootloader mode, then firmware must be restored in order for it to work properly. Start up the Anybus Configuration Manager and
connect to the Anybus Communicator. Choose Tools/Options/Module. Click “Factory Restore” to restore firmware.
This series of steps are only required if the Anybus Communicator Gateway must be
reconfigured. The Anybus Configuration Manager is a Windows-based application
used to supply the Anybus Communicator Gateway with a description of the sub-
network protocol.
6. Verify that the COM port settings on the PC; select the appropriate serial port from
the Tools menu in the Anybus Configuration Manager application; refer Figure
E-13.
Figure E-13: COM Port Setting in the Anybus Configuration Manager Tool Menu
10. Once the configuration file has been downloaded, disconnect and close the
Anybus Configuration Manager application
On PROFINET, all devices are associated with a GSDML file. The GSDML file is the
equivalent of the PROFIBUS GSD file, and is based on the EXtensible Markup
Language (XML). This file holds information about the device (in this case the Anybus
Communicator), its features, and possible I/O configurations.
A version of the GSDML file for the Anybus Communicator can be found on the KELK
Utilities CD (044303-1) by navigating to the following subdirectory:
\GPA2\PROFINET\; the latest version can also be downloaded from the HMS website,
www.anybus.com.
E.7 Communications
Bitmapped Types
Bit 0 - System Healthy
Bit 1 - B Fault
4B2 System Status
Bit 2 - A Fault
Bit 3 - Single Sensor
Bit 0 - Channel B: Shunt or FS out of range
Bit 1 - Channel B: Zero out of range
Bit 2 - Channel B: Gain out of range
Bit 3 - Channel B: Zero out of margin
Bit 4 - Channel B: Saturation +/-
Bit 5 - Channel B: Excitation current overload
Bit 6 - Channel B: Single Sensor Operation (Double
A)
Channel A&B Measurement Bit 7 - Channel B: Simulation
16B3
Status Bit 8 - Channel A: Shunt or FS out of range
Bit 9 - Channel A: Zero out of range
Bit 10 - Channel A: Gain out of range
Bit 11 - Channel A: Zero out of margin
Bit 12 - Channel A: Saturation +/-
Bit 13 - Channel A: Excitation current overload
Bit 14 - Channel A: Single Sensor Operation
(Double B)
Bit 15 - Channel A: Simulation
Bit 0 - Zero
2B4 Configuration, Zero
Bit 1 - Configuration
Enumerated Type
0- A &B
Sensor Input Configuration 1- 2*B
2E1
(Load doubling) 2- 2*A
3- B &A
2. For bitmapped formats, the condition is enabled (or “on”) when the bit is set to 1
and disabled (or “off”) when the bit is 0, unless stated otherwise.
3. The nomenclature used for each format reflects the basic type and size (in eight-bit
bytes) of the format. The size of each format is always an integral multiple of one
byte. Regardless of their size, data are interpreted as “big-endian” (i.e., the least
significant bit is bit 0 and the most significant bit is the highest-numbered bit for the
format).
4. For formats that do not use all of the available bits, the unused bits are ignored by
the format and are set to zero during transmission.
o SSS is the Data Size (for the GPA2, this is always 16 bits)
o TTT is the Format Type, where:
I Signed Integer
U Unsigned Integer
E Enumerated
B Bitmapped
Example:
6U2 is 16 bits, unsigned integer, 2 decimal points.
6. For a bitmap, this is a bitmap order number.
Host
Host Read
Write Min Max
Address Name Format Units Notes
Address Value Value
(Dec)
(Dec)
Process Variables (Read-Only, Volatile)
Input A Load
0001:2 16I2 % -327.68 327.67 1
Input B Load
0003:4 16I2 % -327.68 327.67 1
System Status
0005:6 4B2 - - - 1
Channel A&B
0007:8 16B3 - - - 1
Measurement Status
Receive /Transmit Statistic (Read-Only, Volatile)
Relay Outputs Transmit
0009 8U0 - - - 1
Count
Logic InputsReceive
0010 8U0 - - - 1
Count
Configuration Parameters (Read-Write, Nonvolatile)
0011:12 0011:12 Configuration, Zero 2B4 - - - 2
Sensor Input Configuration
0013:14 0013:14 2E1 - - - 2
(Load doubling)
Notes:
1. These variables are updated by the GPA2 every 20 ms.
2. These variables are updated by the GPA2 every 200 ms.
Appendix F
Recommended Spares
The modules and circuit breaker shown above are interchangeable, allowing
them to be used as spares in any GPA2 electronics system.
Important Note: The main modules that are supplied alone and the ones
contained within the Complete GPA2 System are set up in
terms of functionality and features at the factory as
described in Appendix A. When ordering spares, customer
must identify the specific requirements of the spare using the
model number designators. KELK Form #881 GPA2
Ordering Form is available for this purpose.