APPENDIX 19

ELECTRICALLY HEATED OR GAS FIRED JACKETED


STEAM KETTLES

19-1 SCOPE 19-6 PRESSURE RELIEF


The rules in Appendix 19 provide additional require- The capacity of the safety valve in pounds of steam
ments for electrically heated or gas fired jacketed steam per hour shall be at least equal to the Btu per hour
kettles constructed under the rules of this Division. rating of the burner divided by 1000 or the kilowatt
rating of the electric heating element multiplied by 3.5.

19-7 APPURTENANCES AND


19-2 SERVICE RESTRICTIONS CONTROLS
No steam or water shall be withdrawn from the The jacket shall be furnished with the following
jacket for use external to the vessel and the operating minimum appurtenances and controls [see U-2(a)(4)]:
pressure of the jacket shall not exceed 50 psi. (a) a pressure gage;
(b) a water gage glass; or alternatively, for electrically
heated jacketed steam kettles with immersion type
heating elements, a low level warning light;
19-3 MATERIALS (c) a separate connection, fitted with a stop valve,
for venting air or adding water to the jacket (the water
When in contact with products of combustion, austen-
may be added while the vessel is not under pressure);
itic stainless steel parts shall be of either the low
(d) an electric heater control or automatic gas valve
carbon or stabilized grades. Structural grade carbon
controlled by pressure or temperature to maintain the
steel, SA-36 and SA-283 (Grades A, B, C, and D),
steam pressure in the jacket below the safety valve
shall not be used for any pressure part.
setting;
(e) a low water cutoff that will cut off the fuel to
the burner or power to the electric heating element if
the water in the jacket drops below the lowest permissi-
19-4 DESIGN ble water level established by the manufacturer;
Welded Categories A and B joints in contact with (f) a safety pilot control that will cut off the fuel
products of combustion shall be of Type No. 1 of to both the main burner and the pilot burner in case
Table UW-12. of pilot flame failure.

19-8 DATA REPORTS

19-5 INSPECTION AND STAMPING When all the requirements of this Division and the
supplemental requirements of this Appendix have been
Electrically heated or gas fired jacketed steam kettles met, the following notation shall be entered on the
shall be inspected by an Inspector and shall not be Manufacturer’s Data Report under Remarks, “Con-
marked with the UM Symbol regardless of volume structed in Conformance with Appendix 19, Electrically
[see U-1(j)]. Heated or Gas Fired Jacketed Steam Kettles.”