You are on page 1of 24

Part KR

PRESSURE RELIEF DEVICES


PART KR

Article KR-1 General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175


KR-100 Protection Against Overpressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
KR-110 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
KR-120 Types of Overpressure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
KR-121 Rupture Disk Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
KR-122 Pressure Relief Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
KR-123 Combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
KR-124 Requirements for Pressure Retaining Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
KR-125 Inherent Overpressure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
KR-126 Intensifier Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
KR-130 Size of Openings and Nozzles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
KR-140 Intervening Stop Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
KR-141 Dual Overpressure Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
KR-150 Permissible Overpressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
KR-160 Set Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
KR-161 Single Pressure Relief Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
KR-162 Multiple Pressure Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
KR-163 Pressure Effects to Be Included in the Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178

Article KR-2 Requirements for Rupture Disk Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179


KR-200 Materials for Rupture Disk Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
KR-201 Marking and Stamping Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
KR-202 Burst Testing Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
KR-210 Flow Capacity Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
KR-220 Rupture Disk Devices Used in Combination With Flow Capacity Certified
Pressure Relief Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
KR-221 Rupture Disk Devices Installed Upstream of Flow Capacity Certified Pressure
Relief Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
KR-222 Rupture Disk Devices Installed Downstream of Flow Capacity Certified Pressure
Relief Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180

Article KR-3 Requirements for Pressure Relief Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181


KR-300 General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
KR-310 Design Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
KR-311 Guiding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
KR-312 Spring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
KR-313 Seat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
KR-314 Body and Pressure Retaining Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
KR-315 Bonnet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
KR-316 Inlet Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
KR-317 Sealing of Valve Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181

171
KR-318 Drain Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-320 Material Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-321 Seats and Disks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-322 Guides and Springs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-323 Pressure Retaining Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-324 Nonpressure-Retaining Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-330 Inspection of Manufacturing and/or Assembly of Pressure Relief Valves . . . . . . . . . . 182
KR-331 Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-332 Verification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-340 Production Testing by Manufacturers and Assemblers . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-341 Hydrostatic Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
KR-342 Test Media . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
KR-343 Leak Tightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
KR-344 Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
KR-345 Set Pressure Tolerance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
KR-346 Flow Capacity Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183

Article KR-4 Marking and Stamping Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185


KR-400 Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
KR-401 Marking of Pressure Relief Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
KR-402 Marking of Rupture Disk Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
KR-403 Marking of Pressure Relief Valves in Combination With Rupture Disk Devices . . . 186
KR-410 Use of Code Symbol Stamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186

Article KR-5 Certification of Flow Capacity of Pressure Relief Valves . . . . . . . . . . . . . . . . . . . . . 187


KR-500 Fluid Media and Test Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
KR-501 Fluid Media for Flow Capacity Certification Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
KR-502 Test Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
KR-510 Recertification Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
KR-520 Procedures for Flow Capacity Certification Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
KR-521 Three-Valve Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
KR-522 Slope Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
KR-523 Coefficient of Discharge Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
KR-523.1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
KR-523.2 Number of Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
KR-523.3 Calculation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
KR-523.4 Determining Coefficients . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
KR-523.5 Flow Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
KR-530 Flow Capacity Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
KR-531 Gas and Air Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
KR-532 Nozzle Type Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
KR-532.1 Saturated Water. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
KR-532.2 Other Fluids. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
KR-540 Flow Capacity Certification Testing Requirements for Test Facilities . . . . . . . . . . . . . 190
KR-550 Test Data Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
KR-560 Certification of Flow Capacity of Pressure Relief Valves in Combination With
Rupture Disk Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
KR-561 Test Media and Test Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
KR-562 Sizes of Test Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
KR-563 Testing Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
KR-570 Optional Testing of Rupture Disk Devices and Pressure Relief Valves . . . . . . . . . . . 191

172
KR-571 Larger Sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
KR-572 Higher Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191

Figures
KR-401 Official Symbol for Stamp to Denote the American Society of Mechanical
Engineers’ Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
KR-523.3 Constant C for Gas Versus Specific Heat Ratio k p CP /CV . . . . . . . . . . . . . . . . . . . . 189
KR-532.1 Flow Capacity Curve for Rating a Nozzle Type Relief Valve for Saturated Water
Based on 10% Overpressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190

173
ARTICLE KR-1
GENERAL REQUIREMENTS

KR-100 PROTECTION AGAINST Manufacturer: within the requirements of Part KR, a


OVERPRESSURE Manufacturer is defined as a person or organization
All pressure vessels within the scope of this Division who is completely responsible for design, material
shall be provided with protection against overpressure selection, capacity certification when required, and man-
according to the requirements of this Part. Combination ufacture of all component parts, assembly, testing,
units (such as heat exchangers with shells designed for sealing, and shipping of pressure relief valves certified
lower pressures than the tubes) shall be protected against under this Division of the Code.
overpressure from internal failures. manufacturing design range: a range of pressure within
which a rupture disk will be stamped as agreed upon
between the rupture disk Manufacturer, and the User
KR-110 DEFINITIONS or his Agent. The range shall have a minimum and a
maximum burst pressure specified. If the rupture disk
Unless otherwise defined in this Division, definitions
is used as the primary safety relief device, caution
relating to pressure relief devices in Section 2 of ASME
should be taken in determining the disk manufacturing
PTC 25, Pressure Relief Devices, shall apply.
range so that the stamped bursting pressure of the disk
Assembler: a person or organization who purchases or
will not exceed the design pressure of the vessel.
receives from a Manufacturer the necessary component
parts or valves and who assembles, adjusts, tests, seals, nonreclosing pressure relief device: a pressure relief
and ships pressure relief valves certified under this device designed to remain open after operation.
Division, at a geographical location other than and using overpressure: a pressure increase over the set pressure
facilities other than those used by the Manufacturer. An of a pressure relief valve, usually expressed as a
Assembler may be organizationally independent of a percentage of set pressure.
Manufacturer, or may be wholly or partly owned by pressure relief valve: a passive pressure relief device
a Manufacturer. that is actuated by static inlet pressure. The opening
coincident disk temperature (supplied to the rupture is characterized by a rapid opening (pop action), or
disk manufacturer): the expected temperature of the by opening in proportion to the difference between the
disk when a specified overpressure condition exists, static pressure and the set pressure of the valve, de-
and the disk is expected to rupture. pending on the valve design and the application. A
combination device: one rupture disk in series with pressure relief valve is also designed to reclose to
one pressure relief valve. prevent further discharge of fluid after the inlet pressure
compressibility factor: the ratio of the specific volume decreases below the set pressure of the valve. Also
of a given fluid at a particular temperature and pressure referred to as a safety relief valve, safety valve, relief
to the specific volume of that fluid as calculated by valve, and pop off valve.
ideal gas laws at that temperature and pressure. pressure relief valve set pressure: that pressure which
gas: for the purpose of Part KR, a gas shall be defined causes the valve stem to lift at least 5% of its full
as a fluid that undergoes a significant change in density travel.
as it flows through the pressure relief device. rupture disk: the rupture disk is the pressure retaining
liquid: for the purpose of Part KR, a liquid shall be and pressure sensitive element of a rupture disk device.
defined as a fluid that does not undergo a significant The failure of the rupture disk is the cause of the
change in density through the pressure relief device. opening of the rupture disk device. Rupture disks

175
KR-110 1998 SECTION VIII — DIVISION 3 KR-125

need not be flat round disks, as long as their design KR-123(c) for further discussion about the use of relief
configuration meets the design burst pressure and flow valves in parallel with rupture disks.
capacity requirements.
rupture disk device: a nonreclosing differential pressure
relief device actuated by inlet static pressure and de- KR-123 Combinations
signed to function by the bursting of a pressure retaining A rupture disk device used in combination with a
disk. The rupture disk device includes the rupture disk, pressure relief valve may be advisable on vessels con-
the rupture disk holder, and all other components that taining substances that may render a pressure relief
are required for the device to function in the prescribed valve inoperative by fouling, or where a loss of valuable
manner. The holder is the structure which encloses, material by leakage should be avoided, or where contam-
clamps, and seals the rupture disk in position. ination of the atmosphere by leakage of noxious, flam-
mable, or hazardous fluids must be avoided.
(a) Multiple rupture disk devices in parallel shall
not be used on the inlet side of a pressure relief valve.
(b) When a combination device is used, both the
KR-120 TYPES OF OVERPRESSURE rupture disk device and the pressure relief valve shall
PROTECTION meet the applicable requirements of Part KR. The
rupture disk device shall be installed to prevent frag-
Pressure relief valves, rupture disks, flow paths, or
ments from the rupture disk from interfering with
vents directly or indirectly open to the atmosphere, or
the proper operation of the pressure relief valve. For
inherent overpressure protection in accordance with
additional requirements, see KR-220 and KR-340.
KR-125, may be used for overpressure protection. The
(c) A rupture disk device may be used in parallel
overpressure limits specified in KR-150 shall apply to
with a pressure relief valve whose set pressure is lower
these devices.
than the rupture disk when it is important to limit the
quantity of a release or it is impractical to certify the
flow capacity of the pressure relief valve under the
rules of this Division. The calculated flow capacity of
KR-121 Rupture Disk Devices
the rupture disk device acting alone shall be adequate
Because of the high pressures associated with this to meet the requirements of KR-150, and the rupture
Division, it may be impractical to accomplish full-scale disk device shall meet all the applicable requirements
flow capacity performance testing and certification of of this Part. With the exception of the flow capacity
pressure relieving devices. For this reason, rupture disk certification, the pressure relief valve shall meet all the
devices may be the more commonly used means of requirements of this Part.
overpressure protection for vessels within the scope of
this Division. All rupture disks shall meet the require-
ments of Article KR-2. KR-124 Requirements for Pressure Retaining
The use of rupture disk devices may be advisable Components
when very rapid rates of pressure rise may be encoun- All components subject to the design pressure shall
tered, or where the relief device must have intimate meet the requirements of this Division; requirements
contact with the process stream. Intimate contact may for the pressure relief valve seat, spring, and valve
be required to overcome inlet line fouling problems or stem are given in Article KR-3, and requirements for
to ensure that the temperature of the disk is the same the rupture disk component are given in Article KR-
as the interior temperature of the vessel. 2. Components that are subject to pressures lower than
the design pressure when the pressure relief device
opens shall meet the requirements of this Division or
other Divisions of Section VIII.
KR-122 Pressure Relief Valves
All pressure relief valves shall meet the requirements
KR-125 Inherent Overpressure Protection
of Article KR-3, and shall be flow capacity performance
tested and certified in accordance with Article KR-5, Overpressure protection need not be provided when
except in the case where their opening is not required the source of pressure is external to the vessel and
to satisfy the overpressure limits given in KR-150. See when the source of pressure is under such positive

176
KR-125 PART KR — PRESSURE RELIEF DEVICES KR-162

control that the pressure in the vessel cannot exceed locked or sealed in either the open or closed position
the design conditions except as permitted in KR-150. by an authorized person. Under no condition shall this
valve be closed while the vessel is in operation.

KR-126 Intensifier Systems


KR-141 Dual Overpressure Protection
In the case where a vessel is pressurized by an
Where it is desirable to perform maintenance on
intensifier system whose output pressure to the vessel
relief devices without shutting down the process, a
is a fixed multiple of the supply pressure, the pressure
full-area three-way transfer valve may be installed on
relief device may be located on the low pressure supply
the inlet of the relief device(s). The design of the
side of the intensifier if all the following requirements
transfer valve and relief devices must be such that the
are met.
requirements of KR-150 are met at any position of the
(a) There shall be no intervening stop valves or
transfer valve. Alternatively, the User may elect to
check valves between the driving chamber(s) and the
install stop valves in each branch, but so controlled
relief device(s).
that one branch is open at all times and the requirements
(b) Heating of the discharge fluid shall be controlled
of KR-150 are always met while the process is in
to prevent further pressure increase which would exceed
operation.
vessel design conditions.
(c) The discharge fluid shall be stable and nonreactive
(water, hydraulic fluid, etc.).
(d) The material being processed in downstream KR-150 PERMISSIBLE OVERPRESSURES
equipment is stable and nonreactive, or is provided with
The aggregate capacity of the safety relief devices,
a suitable secondary vent system which will effectively
open flow paths, or vents shall be sufficient to prevent
prevent transfer of secondary energy sufficient to over-
overpressures in excess of 10% above the design pres-
pressure the vessel.
sure of the vessel when the safety relief devices are
The Designer is cautioned to consider the effects of
discharging.
leaking check valves in such systems.
The Designer shall consider the effects of the pressure
drop in the overpressure protection system piping during
venting when specifying the set pressures and flow
capacities of pressure relief valves and rupture disk
KR-130 SIZE OF OPENINGS AND devices. When multiple pressure relief devices can
NOZZLES discharge through a common stack or vent path, the
The flow characteristics of the entire pressure reliev- maximum back pressure that can exist during simultane-
ing system shall be part of the relieving capacity ous releases at the exit of each pressure relief device
calculations. The size of nozzles and openings shall shall not impair its operation.
not adversely affect the proper operation of the pressure
relieving device.
KR-160 SET PRESSURES
KR-161 Single Pressure Relief Device
98 KR-140 INTERVENING STOP VALVES A single safety relief device shall open at a nominal
There shall be no intervening stop valves between the pressure not exceeding the design pressure of the vessel
vessel and any overpressure protection device associated at the operating temperature, except as permitted in
with the vessel, except as permitted in KR-141. KR-162.
A full-area stop valve may be placed on the discharge
side of a pressure relieving device when its discharge
KR-162 Multiple Pressure Relief Devices
is connected to a common header with other discharge
lines from other pressure relief devices on vessels that If the required discharging capacity is supplied by
are in operation, so that this stop valve when closed more than one device, only one need be set to operate
will prevent a discharge from any connected operating at a pressure not exceeding the design pressure of the
vessels from backing up beyond the valve so closed. vessel. The additional device or devices may be set at
Such a stop valve shall be so arranged that it can be a higher pressure but not to exceed 105% of the design

177
KR-162 1998 SECTION VIII — DIVISION 3 KR-163

pressure of the vessel. The requirements of KR-150


shall also apply.

KR-163 Pressure Effects to Be Included in the


Setting
The pressure at which any device is set shall include
the effects of superimposed back pressure through the
pressure relief device and the vent system (see KR-150).

178
ARTICLE KR-2
REQUIREMENTS FOR RUPTURE DISK DEVICES

KR-200 MATERIALS FOR RUPTURE DISK rating of the rupture disk shall be the average of the
DEVICES bursts at specified disk temperature.
Rupture disks may be fabricated from either ductile
or brittle materials. The materials used in the rupture
disk holder shall meet all the requirements of this
Division for pressure boundary components.

KR-210 FLOW CAPACITY RATING


The flow capacity of the rupture disk device shall
KR-201 Marking and Stamping Requirements be demonstrated by either calculations or by certification
Every rupture disk shall have a stamped bursting testing to meet the requirements of KR-150.
pressure within a manufacturing design range at a (a) The calculated capacity rating of a rupture disk
specified disk temperature. It shall be marked with a device shall not exceed a value based on the applicable
lot number, and shall be certified by its Manufacturer theoretical formula for the various media multiplied by
to burst within a tolerance of 65% of its stamped a coefficient of discharge:
bursting pressure at the coincident disk temperature. A
lot of rupture disks shall consist of all disks manufac- KD p 0.62
tured from the same lot of material, made in the same
production run, and having the same size and stamped The area A (square inches) in the theoretical formula
bursting pressure. (See also Article KR-4.) shall be the minimum net area after the rupture disk
burst.
The Designer is cautioned that normal capacity calcu-
lations may not be applicable for supercritical fluids.
Flow through the entire relieving system shall be ana-
lyzed with due consideration for the wide variation of
KR-202 Burst Testing Requirements
physical properties which will occur due to the wide
For a given lot of rupture disks, the stamped bursting range of flowing pressures.
pressure within the manufacturing design range at the (b) In lieu of the method for capacity rating given
coincident disk temperature shall be derived as follows. in (a) above, the Manufacturer may have the capacity
All the tests of disks for a given lot shall be made of a given rupture disk device design certified for the
in a holder of the same form and dimensions as that KD coefficient in general accordance with the applicable
with which the disk is to be used. At least four but procedures of Article KR-5. Rupture disks may be
not less than 10% of the rupture disks from each lot certified as to burst pressure, provided the test stand
shall be burst tested, to verify that the stamped bursting has enough volume to provide a complete burst. The
pressure falls within the manufacturing design range coefficient of discharge KD may be established at a
at the coincident disk temperature of these four tests, lower pressure using a suitable fluid. The Designer is
including a minimum of one burst test at room tempera- cautioned, however, to consider the critical point and
ture and a minimum of two burst tests within 25°F nonlinear thermodynamic properties of the fluid used
(14°C) of the coincident disk temperature. The stamped in service at or near the design pressure.

179
KR-220 1998 SECTION VIII — DIVISION 3 KR-222

KR-220 RUPTURE DISK DEVICES USED IN (g) Fragmenting and shearing plug type disks shall
COMBINATION WITH FLOW be provided with an adequate catcher to retain disk
CAPACITY CERTIFIED PRESSURE parts and prevent interference with proper functioning
RELIEF VALVES of the pressure relief valve.
KR-221 Rupture Disk Devices Installed
Upstream of Flow Capacity Certified KR-222 Rupture Disk Devices Installed
Pressure Relief Valves Downstream of Flow Capacity
Certified Pressure Relief Valves
A rupture disk device may be installed between
a pressure relief valve and the vessel, provided the A rupture disk device may be installed on the outlet
requirements of (a) through (g) are met. side of a pressure relief valve, provided (a) through
(a) The combination of the spring loaded pressure (g) are met.
relief valve and the rupture disk device meets the (a) The pressure relief valve is designed so that the
requirements of KR-150. pressure between the valve outlet and the rupture disk
(b) The stamped capacity of a pressure relief valve does not affect the valve’s set pressure. This volume
is multiplied by a factor of 0.90 of the rated relieving should be vented or drained to prevent accumulation
capacity of the valve alone, or the capacity of the of fluid due to a small amount of leakage from the
combination of the rupture disk device and the pressure valve.
relief valve may be established according to KR-560. (b) The valve and disk combination shall meet the
(c) The volume between the rupture disk device and requirements of KR-150.
the pressure relief valve is provided with a means to (c) The stamped bursting pressure of the rupture
prevent pressure buildup between the rupture disk and disk at the coincident temperature, plus the additional
the pressure relief valve, or the series combination is pressure in the outlet piping that will occur during
venting, shall not exceed the design pressure of the
provided with a second rupture disk device in parallel
outlet portion of the pressure relief device and any
whose burst pressure is 116% of design pressure.
pipe or fitting between the pressure relief valve and
(d) The opening provided through the rupture disk
the rupture disk device. In addition, the stamped bursting
after burst is sufficient to permit a flow equal to the
pressure of the rupture disk at the coincident disk
capacity of the valve [see (b) above], and there is no
temperature plus the pressure developed in the outlet
chance of interference with proper functioning of the
piping during venting shall not exceed the set pressure
pressure relief valve. In addition, the flow area of the
of the pressure relief valve.
burst rupture disk shall not be less than 90% of the
(d) The opening provided through the rupture disk
area of the inlet of the valve unless the capacity and after breakage is sufficient to permit a flow capacity
functioning of the specific combination of rupture disk greater than or equal to the rated capacity of the
and valve have been established by test according to pressure relief valve.
KR-560. (e) Any piping beyond the rupture disk shall be
(e) The use of a rupture disk device in combination designed so that it will not be obstructed by the rupture
with a pressure relief valve should be carefully evaluated disk or its fragments.
to ensure that the media being handled and the valve (f) The contents of the vessel are clean fluids, free
operational characteristics will result in opening action from gumming or clogging matter, so accumulation in
of the valve coincident with the bursting of the rupture the relief system will not interfere with pressure relief
disk, so that the requirements of KR-150 are met. valve function.
(f) The installation shall ensure that solid material (g) The design pressure of the pressure relief valve’s
will not collect in the inlet or outlet of a rupture disk bonnet, bellows if any, and exit connection to the
which could impair the relieving capacity of the vent rupture disk is greater than or equal to the burst pressure
system. of the disk.

180
ARTICLE KR-3
REQUIREMENTS FOR PRESSURE RELIEF VALVES

98 KR-300 GENERAL REQUIREMENTS KR-313 Seat


(a) The requirements of this Article apply to pressure If the seat is not integral with the relief valve, it
relief valves within the scope of this Division, including shall be secured to the valve body so that there is no
those which do not have to be flow capacity tested possibility of the seat lifting or separating.
and certified; see KR-123(c).
(b) Pressure relief valves shall be the direct acting,
spring loaded type. KR-314 Body and Pressure Retaining
(c) The set pressure tolerance of pressure relief valves Components
shall not exceed 63%. In the design of the valve body, consideration shall
(d) Pressure relief valves meeting the requirements be given to minimizing the effects of deposits. See
of ASME Boiler and Pressure Vessel Code Section also KR-124 for requirements for all pressure retaining
VIII, Division 1 or 2, may be used provided all components.
requirements of this Article are met. If the valve is
the primary relief device [see KR-123(c)], the require-
ments of Article KR-5 and Appendix 4 shall be met. KR-315 Bonnet
The bonnet of the pressure relief valve shall be
vented to prevent accumulation of pressure. Sealing /
isolation of the bonnet area from the relieving fluid
KR-310 DESIGN REQUIREMENTS may be required for protection of the spring assembly
KR-311 Guiding from corrosion or solids accumulation.

The design shall incorporate guiding arrangements


necessary to ensure consistent opening at the set pres- KR-316 Inlet Fittings
sure, and reseat when the inlet pressure decreases to
some pressure below the set pressure. Consideration Valves having threaded inlet or outlet connections
shall be given to the effects of galling and friction on in accordance with Article KD-6 shall be provided
the valve operation. with wrenching surfaces as required to allow for normal
installation without damaging operating parts.

KR-312 Spring KR-317 Sealing of Valve Settings


The spring shall be designed so that the spring Means shall be provided in the design of all pressure
compression at full lift of the valve shall not be greater relief valves for use under this Division for sealing all
than 80% of the nominal solid deflection. The permanent adjustments which can be made without disassembling
set of the spring (defined as the difference between the valve before or after installation. Seals shall be
the original free length and the free length measured installed by the Manufacturer at the time of initial
10 min after the spring has been compressed to its shipment and after field adjustment of the valves by
solid height three times after the valve has been preset either the Manufacturer or his authorized representative.
at room temperature) shall not exceed 0.5% of the Seals shall be installed in a manner to prevent changing
original free length. the adjustment without breaking the seal. For valves

181
KR-317 1998 SECTION VIII — DIVISION 3 KR-341

larger than NPS 1⁄2 , the seal shall identify the Manufac- KR-330 INSPECTION OF
turer or Assembler making the adjustment. MANUFACTURING AND /OR
ASSEMBLY OF PRESSURE RELIEF
VALVES
KR-318 Drain Requirements KR-331 Quality
If the design of a pressure relief valve is such that A Manufacturer shall demonstrate to the satisfaction
liquid can collect on the discharge side of the disk, of an ASME designee that manufacturing as applicable;
the valve shall be equipped with a drain at the lowest assembling, production, and testing facilities; and quality
point where liquid can collect. control procedures ensure that the valves produced by
the Manufacturer or Assembler meet the requirements
of this Division. For pressure relief valves requiring
flow capacity certification (see Article KR-5), it shall
KR-320 MATERIAL SELECTION also be demonstrated to the satisfaction of an ASME
designated organization that there will be close
KR-321 Seats and Disks agreement between the performance of random produc-
Cast iron seats and disks are not permitted. The tion samples and the performance of those valves
seats and disks of pressure relief valves shall be of submitted for capacity certification.
suitable material to resist corrosion by the fluid to be
contained (see KG-311.7), and meet the requirements
KR-332 Verification
of KR-324(a), (b), or (c).
(a) Manufacturing, assembly, inspection, and test op-
erations, including capacity testing as appropriate, are
subject to inspection at any time by an ASME designee.
KR-322 Guides and Springs
(b) At the time of the production testing in accordance
The materials used for guides and springs shall meet with KR-340, or the submission of valves for flow
the requirements of KR-324(a), (b), or (c). Adjacent capacity certification testing in accordance with Article
sliding surfaces such as guides and disks or disk holders KR-5, as applicable, the ASME designee and /or its
shall both be of corrosion resistant and galling resistant consultants has the authority to reject or require modifi-
material or shall have a corrosion-resistant coating cation of designs which do not conform with the
applied. Galling resistance shall be demonstrated on a requirements of this Part.
prototype valve by popping a valve to full stem lift
ten times with subsequent disassembly and inspection
showing no indication of galling. KR-340 PRODUCTION TESTING BY
MANUFACTURERS AND
ASSEMBLERS
KR-323 Pressure Retaining Parts All pressure relief valves manufactured in accordance
Materials used in pressure retaining parts shall be with this Division shall be tested as described below.
listed in Part KM. Pressure relief valves may be flow capacity tested in
accordance with this Article and Article KR-5 [see
KR-123(c)].
KR-324 Nonpressure-Retaining Parts
KR-341 Hydrostatic Testing
Materials used in nozzles, disks, and other parts
contained within the external structure of the pressure The primary pressure retaining parts of each pressure
relief valves shall be one of the following categories: relief valve to which the UV3 Code symbol is to be
(a) listed in Section II; applied shall be hydrostatically tested to not less than
(b) listed in ASTM specifications; 1.25 times the design pressure of the parts. These tests
(c) controlled by the Manufacturer of the pressure shall be conducted after all machining operations on
relief valve to a specification ensuring control of chemi- the parts have been completed. There shall be no visible
cal and physical properties and quality at least equivalent signs of leakage. The secondary pressure zone of each
to ASTM standards. closed bonnet valve shall be tested at 1.25 times the

182
KR-341 PART KR — PRESSURE RELIEF DEVICES KR-346

stated design pressure of the secondary pressure zone KR-346 Flow Capacity Testing
but not less than 0.125 times the design pressure of
The following sampling schedule of tests applies to
the primary parts.
production pressure relief valves that are to be flow
capacity certified in accordance with Article KR-5;
produced, assembled, tested, sealed, and shipped by
KR-342 Test Media the Manufacturer or Assembler; and having a normal
Each pressure relief valve to which the Code symbol scope of size and capacity within the capability of
is to be applied shall be tested by the Manufacturer ASME accepted laboratories. Production valves for flow
or Assembler to demonstrate set pressure of the pressure capacity and operational testing shall be selected by
relief valve and the leak tightness. Valves intended for an ASME designee and the testing shall be carried out
compressible fluid service shall be tested with air or in the presence of a representative of the same organiza-
other suitable gas, and valves intended for incompress- tion at an ASME accepted laboratory in accordance
ible fluid service shall be tested with water or other with the following.
suitable incompressible fluid (see KG-311.11). (a) Initial flow capacity certification shall be valid
for 1 year, during which time two production valves
shall be tested for operation, and stamped flow capacity
verified. Should any valve fail to meet performance
KR-343 Leak Tightness requirements, the test shall be repeated at the rate of
A leak tightness test shall be conducted at a maximum two valves for each valve that failed. Initial flow
expected operating pressure, but at a pressure not capacity verification may be extended for 1 year inter-
exceeding the reseating pressure of the valve. When vals until the valve is in production. Valves having an
testing with water, a valve exhibiting no visible signs adjustable blowdown construction shall be adjusted to
of leakage shall be considered leak tight. The leak rate the position recommended by the Manufacturer for use
of the valve tested with a gas shall meet the criteria in service prior to flow testing. This adjustment may
specified in the User’s Design Specification (see KG- be made on the flow test facility.
311.11). (b) Thereafter, two valves shall be tested within each
5 year period of time. The valve Manufacturer shall
be notified of the time of the test and may have a
witness present during the test. Should any valve fail
KR-344 Instrumentation
to relieve at or above its stamped flow capacity, or
A Manufacturer or Assembler shall have a docu- should it fail to meet performance requirements of this
mented program for the application, calibration, and Division after adjustments, the test shall be repeated
maintenance of test gages and instruments. at the rate of two valves for each valve that failed.
Valves having an adjustable blowdown construction
shall be set in accordance with (a) above. These valves
KR-345 Set Pressure Tolerance shall be furnished by the Manufacturer. Failure of
any valve to meet the stamped flow capacity or the
Test fixtures and test drums for pressure relief valves, performance requirements of this Division shall be
where applicable, shall be of adequate size and capacity cause for revocation within 60 days of the authorization
to ensure representative action and response at blow- to use the Code symbol on that particular type of
down ring adjustments intended for installation. Under valve. During this period, the Manufacturer shall demon-
these conditions, the valve action shall be consistent strate the cause of such deficiency and the action taken
with the stamped set pressure within a tolerance of to guard against future occurrence, and the requirements
63%. of (a) shall apply.

183
ARTICLE KR-4
MARKING AND STAMPING REQUIREMENTS

KR-400 MARKING
KR-401 Marking of Pressure Relief Valves
Each pressure relief valve shall be plainly marked
by the Manufacturer or Assembler with the required
data in such a way that the markings will not be
obliterated in service. The markings shall be located
on a plate securely fastened to the valve. Small valves FIG. KR-401 OFFICIAL SYMBOL FOR STAMP TO
(less than NPS 1⁄2 inlet) may have the nameplate DENOTE THE AMERICAN SOCIETY OF
attached with a chain or wire. See KS-130 for methods MECHANICAL ENGINEERS’ STANDARD
of application. The marking shall include:
(a) the name or identifying trademark of the Manufac-
turer and /or Assembler, as appropriate
(b) Manufacturer’s or Assembler’s design or type
number
(c) valve inlet size, in. be obliterated in service and will not interfere with
(d) set pressure, psi the function of the disk. The marking may be placed
(e) flow capacity, SCFM of air (60°F and 14.7 psia) on the flange of the disk or on a metal tab permanently
(16°C and 101 kPa), or gal /min of water at 70°F attached thereto. Alternatively, the marking may be
(21°C), if the pressure relief valve is to be tested to placed on a metal tag packaged with each individual
have a certified flow capacity; see KR-122 and KR- rupture disk, to be attached to the holding fixture at
123(b). If the pressure relief valve is not flow capacity assembly; see KR-201 for additional requirements. The
tested and certified, the flow capacity shall be stamped marking shall include the following:
“NONE.” (a) the name or identifying trademark of the Manufac-
NOTE: In addition, the Manufacturer /Assembler may indicate the turer
flow capacity in other fluids (see KR-530). (b) Manufacturer’s design, type number, or drawing
number
(f) year built or, alternatively, a coding may be
(c) lot number
marked on the valve such that the valve Manufacturer /
Assembler can identify the year built (d) material
(g) ASME Code symbol as shown in Fig. KR-401 (e) size, in.
(h) Use of the Code symbol stamp by an Assembler (f) stamped burst pressure, psig
shall indicate the use of original, unmodified parts in (g) coincident disk temperature, °F
strict accordance with instructions of the Manufacturer Items (a), (b), (d), and (e) shall also be marked on
of the valve. The nameplate marking shall include the the rupture disk holder. See also KR-201.
name of the Manufacturer and the Assembler, and the In lieu of marking all of the listed items on the
Code symbol stamp shall be that of the Assembler. flange or tab of each rupture disk, the marking may
consist of the stamped bursting pressure and a Manufac-
turer’s coding number sufficient to identify each disk
KR-402 Marking of Rupture Disk Devices
with a Certificate which includes the required informa-
Every rupture disk shall be plainly marked by the tion, if such a Certificate is supplied for each lot of
Manufacturer in such a way that the marking will not rupture disks.

185
KR-403 1998 SECTION VIII — DIVISION 3 KR-410

KR-403 Marking of Pressure Relief Valves in specific details of the rupture disk device so that the
Combination With Rupture Disk rupture disk device is uniquely identified and specified.
Devices

Pressure relief valves in combination with rupture KR-410 USE OF CODE SYMBOL STAMP
disk devices shall be marked with the flow capacity Each pressure relief valve to which the Code symbol
established in accordance to KR-220, in addition to is to be applied shall be fabricated by a Manufacturer
the marking of KR-401 and KR-402. The marking may who is in possession of a Code symbol stamp (see
be placed on the valve or on a plate or plates securely Fig. KR-401) and a valid Certificate of Authorization,
fastened to the valve. The marking shall include the obtainable when the conditions of Article KS-2 have
marking required by KR-401(a) through (g) and the been met.

186
ARTICLE KR-5
CERTIFICATION OF FLOW CAPACITY OF
PRESSURE RELIEF VALVES

KR-500 FLUID MEDIA AND TEST valve, new tests shall be performed in accordance with
PRESSURES this Division.
KR-501 Fluid Media for Flow Capacity
Certification Tests
KR-520 PROCEDURES FOR FLOW
Flow capacity certification tests shall be conducted
CAPACITY CERTIFICATION
with liquids, or vapors as appropriate. For fluids which
TESTS
are to be handled near their critical point, or in any
region where their thermodynamic properties are sig- KR-521 Three-Valve Method
nificantly nonlinear, or where a change of phase may
A flow capacity certification test is required on a
occur in the valve (flashing), the flow capacity shall
set of three valves for each combination of size, design
be determined from the vapor and liquid capacity data
and pressure setting. The stamped flow capacity rating
using appropriate correlations and procedures. Saturated
for each combination of design, size, and test pressure
water service is addressed in KR-532.1. Alternatively,
shall not exceed 90% of the average flow capacity of
the flow capacity and design of the overpressure protec-
the three valves tested. Test valves must be installed
tion system may be specified by the User or his Agent,
with an adequate vent system that will not affect the
based on basic data, testing, and demonstration on such
flow capacity of the valves or cause chatter. The flow
actual fluids at expected operating conditions. This
capacity of any one of a set of three valves shall fall
information is stated in the User’s Design Specification;
within a range of 65% of the average flow capacity.
see KG-311.11.
Failure to meet this requirement shall be cause to refuse
certification of a particular safety valve design.
KR-502 Test Pressures
Flow capacity certification tests shall be conducted KR-522 Slope Method
at a pressure not to exceed 110% of the set pressure
of the pressure relief valve. The reseating pressure shall This method may be used if a Manufacturer wishes
be noted and recorded. Valves having an adjustable to certify the flow capacity of a range of pressure
blowdown construction shall be adjusted prior to testing relief valves; four valves of each combination of pipe
so that the blowdown does not exceed 5% of the set size and orifice size shall be tested. These four valves
pressure. Flow tests to certify flow capacity tested at shall be set at pressures which cover the approximate
a given pressure shall not be extrapolated to a higher range of pressures for which the valve will be used.
pressure. In no case shall the set pressure ever exceed the highest
of the four test pressures. The capacities, as determined
by these four tests, shall be calculated as follows.
(a) For compressible fluids, the actual flow capacity
KR-510 RECERTIFICATION TESTING
(mass flow rate through the valve) W and the absolute
When changes are made in the design of a pressure pressure at the valve inlet P shall be measured. The
relief valve that affect the flow path, lift, or may affect slope or the ratio of W /P is calculated for each test
other performance characteristics of the pressure relief valve and the average slope S is calculated.

187
KR-522 1998 SECTION VIII — DIVISION 3 KR-523.5

(1) Each value of slope from the measured data capacity, lift, popping, and blowdown pressures and
shall be within 65% of S for all the measured data. actual flow capacity in terms of the fluid used in the
(2) If one or two values of slope do not fall within test. A coefficient of discharge KD shall be established
the 65% tolerance band, the Authorized Observer shall for each test run as follows:
require that additional valves be tested at a rate of two
additional valves for each valve whose slope is outside actual flow W
KD p p
the tolerance band. Note that only four additional valves theoretical flow WT
can be tested.
(3) The flow capacity W to be stamped on a valve where theoretical flow is determined quantitatively by
shall be determined by: testing, and theoretical flow is calculated by the appro-
priate formula which follows.
W ≤ 0.9S [1.1(set pressure) + 14.7] For tests with air:

(b) For incompressible fluids, the actual flow capacity WT p 356AP (M /ZT)0.5
(mass flow rate through the valve) W and the pressure
drop through the valve (the inlet pressure minus the For tests with other gases:
outlet pressure) P shall be measured. The logarithmic
slope, the ratio of log W /log P, is calculated for each
WT p CAP (M /ZT)0.5
test valve, and the average value of the logarithmic
slope is calculated.
For tests with water or other incompressible fluids:
(1) Each value of logarithmic slope from the mea-
sured data shall be within 65% of the average logarith-
mic slope S calculated for all the measured data. WT p 2406A√r (P − PB)
(2) If one or two values of slope do not fall within
the 65% tolerance band, the Authorized Observer shall where
require that additional valves be tested at a rate of two Ap actual discharge area through the device during
additional valves for each valve whose slope is outside venting, in.2
the tolerance band. Note that only four additional valves Cp constant for gas or vapor based on k, the ratio
can be tested. of specific heats CP /CV (refer to Fig. KR-523.3)
(3) The flow capacity W to be stamped on a valve Mp molecular weight for specific fluid or mixture
shall be determined by: Pp pressure at inlet at full flow conditions, psia
PBp back pressure at discharge from valve /rupture
W ≤ S [1.1(set pressure)] 0.9S disk, psia
Tp absolute temperature at inlet, °R p °F + 460
Wp actual flow, lb /hr
KR-523 Coefficient of Discharge Method WTp theoretical flow, lb /hr
KR-523.1 Procedure. Instead of individual flow Zp compressibility factor for the specific fluid at
capacity certification, as provided in KR-521 and KR- the specified conditions
522, a coefficient of discharge KD may be established r p mass density of fluid, lb /ft3
for a specific pressure relief valve design according to
KR-523.4 Determining Coefficients. The average
the procedure in KR-523.2 and KR-523.3. This proce-
of the coefficients KD of all nine tests required shall
dure will not be applicable to fluids handled near their
be multiplied by 0.90, and this product shall be taken
critical point, or in any region where their thermody-
as the coefficient KD of that design. All experimentally
namic properties are nonlinear. Refer to KR-501.
determined coefficients KD shall fall within a range of
KR-523.2 Number of Valves. For each design, the 65% of the average KD found. Failure to meet this
pressure relief valve Manufacturer shall submit for test requirement shall be cause to refuse certification of
at least three valves for each of three different sizes that particular valve design.
(a total of nine valves) together with detailed drawings
KR-523.5 Flow Capacity. The certified relieving
showing the valve construction. Each valve of a given
flow capacity of all sizes and pressures of a given
size shall be set at a different pressure.
design, for which KD has been established under the
KR-523.3 Calculation Method. Tests shall be made provisions of KR-523.3, that are manufactured subse-
on each pressure relief valve to determine its flow quently shall not exceed the value calculated by the

188
KR-523.5 PART KR — PRESSURE RELIEF DEVICES KR-532

FIG. KR-523.3 CONSTANT C FOR GAS VERSUS SPECIFIC HEAT RATIO k p CP /CV A99

appropriate formula in KR-523.3 multiplied by the where


coefficient KD (see KR-530). In no case shall the set Ap actual discharge area of the relief valve
pressure of the pressure relief valve so certified ever Cp constant for gas which is a function of the ratio
exceed the highest of the test pressures used to deter- of specific heats; see Fig. KR-523.3
mine KD . KDp coefficient of discharge; see KR-523
Mp molecular weight
Pp 110% of set pressure plus atmospheric pressure
KR-530 FLOW CAPACITY CONVERSIONS Tp absolute gas temperature at the inlet, °R p °F
+ 460
KR-531 Gas and Air Service Wp capacity of any gas in lb /hr
For low pressure gases (gases at pressures less than Wap rated capacity, converted to lb /hr of air at 60°F,
two-thirds of their critical pressure), the capacity of inlet temperature
the relief valve in terms of a gas other than that for Zp compressibility factor
which its rating was certified shall be determined as (c) Knowing the certified capacity rating of a relief
follows. valve including the gas and conditions of the gas for
(a) For air: which it certified, it is possible to determine the overall
value of the product of KD A for that given valve by
solving the above equations for KD A. This value of
Wa p CKD AP(M /TZ)0.5
KD A can then be used to solve for W or Wa at a new
set of conditions. For hydrocarbons and other gases
where where the value of k (CP /CV) is not known, assume
Cp 356 a value of k p 1.001 and a corresponding value of
Mp 28.97 C p 315 (see Fig. KR-523.3).
Tp 520 when Wa is the rated capacity
(b) For any gas or vapor with linear thermodynamic
properties through the valve: KR-532 Nozzle Type Valves
Since the flow capacity for supercritical or flashing
W p CKD AP(M /TZ)0.5 service is sensitive to valve configuration, the following

189

ASME B&PVC sec83$u175 05-14-99 16:55:04 pd: sec83 Rev 14.04


KR-532 1998 SECTION VIII — DIVISION 3 KR-563

the tests (Authorized Observer) meet the applicable


requirements of ASME PTC 25 and Appendix 4. The
tests shall be made under the supervision of, and
certified by, an Authorized Observer. The testing facili-
ties, methods, procedures, and qualifications of the
Authorized Observer shall be subject to the acceptance
of the Boiler and Pressure Vessel Committee on recom-
mendation of an ASME designee. Acceptance of the
testing facility is subject to review within each 5 year
period.

KR-550 TEST DATA REPORTS


Flow capacity test Data Reports for each valve model,
type, and size signed by the Manufacturer and the
Authorized Observer witnessing the tests shall be sub-
FIG. KR-532.1 FLOW CAPACITY CURVE FOR mitted to an ASME designee for certification. Where
RATING A NOZZLE TYPE RELIEF VALVE FOR changes are made in the design, flow capacity certifica-
SATURATED WATER BASED ON 10%
tion tests shall be repeated.
OVERPRESSURE

KR-560 CERTIFICATION OF FLOW


applies only to those valves that have a nozzle type CAPACITY OF PRESSURE RELIEF
construction with a throat to inlet diameter ratio of VALVES IN COMBINATION WITH
0.25 to 0.80 with a continuously contoured change and RUPTURE DISK DEVICES
having exhibited a coefficient of discharge greater than
For each combination of pressure relief valve design
0.90. No saturated water or supercritical fluid capacity
and rupture disk device design, the pressure relief valve
conversions shall apply to other types of valve con-
Manufacturer or the rupture disk device Manufacturer
struction.
may have the flow capacity of the combination certified
KR-532.1 Saturated Water. To determine the satu- as prescribed in the following paragraphs.
rated water flow capacity of a nozzle type valve that
meets the criteria described in KR-532 and is rated in
accordance with KR-520, refer to Fig. KR-532.1. For KR-561 Test Media and Test Pressures
a given set pressure, the saturated water curve will The test media and test pressure requirements are
determine the corresponding value of flow capacity the same as those stated in KR-501 and KR-502.
divided by KD A. From the certified flow capacity
stamped on the valve, KD A can be determined and the
flow capacity for any other set pressure can be found. KR-562 Sizes of Test Units
KR-532.2 Other Fluids. For supercritical fluids other The valve Manufacturer or the rupture disk device
than water, the User or his designated Agent is responsi- Manufacturer may submit for tests the smallest rupture
ble for establishing a similar procedure based on the disk device size with the equivalent size of pressure
thermodynamic properties of a particular fluid. relief valve that is intended to be used as a combination
device. The pressure relief valve to be tested shall
have the largest orifice used in that particular pressure
KR-540 FLOW CAPACITY relief valve inlet size.
CERTIFICATION TESTING
REQUIREMENTS FOR TEST
FACILITIES KR-563 Testing Method
Tests shall be conducted at a place where the testing Tests may be performed in accordance with the
facilities, methods, procedures, and person supervising following.

190

ASME B&PVC sec83$u175 05-14-99 16:55:04 pd: sec83 Rev 14.04


KR-563 PART KR — PRESSURE RELIEF DEVICES KR-572

(a) The rupture disk device and pressure relief combi- flow capacity factor shall not be greater than one. The
nation to be tested shall be arranged to duplicate the combination flow capacity factor shall apply only to
combination assembly design. combinations of the same design of pressure relief
(b) The test shall embody the minimum burst pressure valve and the same design of rupture disk device as
of the rupture disk device design which is to be used those tested.
in combination with pressure relief valve design. The (f) The test laboratory shall meet the requirements
stamped bursting pressure shall be between 90% and of KR-540 and shall submit to an ASME designee the
100% of the stamped set pressure of the valve. test results for approval of the combination flow capacity
(c) The pressure relief valve (one valve) shall be factor for certification.
tested for flow capacity as an individual valve, without
the rupture disk device, at a pressure 10% above the
valve set pressure. The rupture disk device shall then KR-570 OPTIONAL TESTING OF
be installed ahead of the pressure relief valve and the RUPTURE DISK DEVICES AND
disk burst to operate the valve. The flow capacity test PRESSURE RELIEF VALVES
shall be performed on the combination at 10% above
KR-571 Larger Sizes
the valve set pressure duplicating the individual pressure
relief valve flow capacity test. If desired, a valve Manufacturer or a rupture disk
(d) Tests shall be repeated with two additional rupture device Manufacturer may conduct tests in the same
disks of the same nominal rating, for a total of three manner as outlined in KR-550 using a rupture disk
rupture disks to be tested with the single valve. The device larger than the inlet of the pressure relief valve
results of the flow capacity tests shall fall within a to determine a combination flow capacity factor applica-
range of 610% of the average flow capacity of the ble to larger sizes. If a greater combination flow capacity
three tests. Failure to meet this requirement shall be factor is established and can be certified by a test
cause to require retest for determination of cause of facility that meets the requirements of KR-540, it may
the discrepancies. be used for all disks larger than the combination tested,
(e) From the results of the tests, a combination flow but shall not be greater than one.
capacity factor shall be determined. The combination
flow capacity factor is the ratio of the average flow
KR-572 Higher Pressures
capacity determined by the combination tests to the
flow capacity determined on the individual valve. The If desired, additional tests may be conducted at higher
combination flow capacity factor shall be used as a pressures in accordance with KR-560 to establish a
multiplier to make appropriate changes in the ASME maximum combination flow capacity factor for all
rated relieving flow capacity of the pressure relief valve pressures higher than the highest tested, but it shall
in all sizes of the design. The value of the combination not be greater than one.

191

You might also like