Professional Documents
Culture Documents
Power Protection
User manual
Digital Energy™ Universal Battery Charger
for use with GEDE UPS
NetPro 3000, LP 11/31T/31
Manufactured by:
Please read these instructions carefully before installation and start-up of the Universal Battery
Charger. Keep this manual in a safe place for future reference.
CONTENTS
2 Introduction ..............................................................................................................................................3
2.1 Introduction
2.2 Intended use
2.3 Transport / storage
3 Installation.................................................................................................................................................4
3.1 Installation rules
3.2 Installation procedures
3.2.1 Connecting the UBC to a NetPro 3000 UPS
3.2.2 Connecting the UBC to an LP 11/31T Series UPS
3.2.3 Connecting two UBC units to an LP 31 Series UPS
3.3 Settings: voltage and current
3.3.1 Setting the charge voltage
3.3.2 Setting the charge current
4 Operation ................................................................................................................................................12
4.1 Start-up and normal operation
4.2 Use: status and alarm Indications
4.2.1 Status indication during normal operation
4.2.2 Alarm indication
4.2.3 Protection
5 Maintenance..........................................................................................................................................13
6 Troubleshooting ...................................................................................................................................13
© General Electric Digital Energy. All rights reserved; reproduction without permission prohibited. This manual may be subject to
change; no liability can be accepted for any error or omission.
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 1 User manual UBC 130-290V 1.0 (GB)
1 - Important safety instructions
All maintenance and service work should be performed by qualified service personnel.
CAUTION
There may be damage to the equipment if procedures and practices are not strictly
observed and followed.
NOTE
Do not attempt to service the UBC unless you have had proper training. Refer all
maintenance and servicing to properly qualified, skilled and competent service
personnel.
Qualified, skilled personnel are persons who (because of their training, experience, and position as
well as their knowledge of appropriate standards, regulations, health and safety requirements and
working conditions) are authorised to be responsible for the safety of the equipment, at all times
whilst carrying out their normal duties and are therefore aware of, and can report, possible hazards
(observe IEC 364, DIN VDE 0105 and national wiring regulations and accident prevention rules).
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 2 User manual UBC 130-290V 1.0 (GB)
2 - Introduction
2.1 Introduction
The GE (General Electric) Digital Energy™ Universal Battery Charger is a compact and modern
battery charging system which incorporates the most advanced power electronics technology to
provide exceptional performance.
The UBC is intended to provide additional battery charging capacity to a UPS (Uninterruptible Power
Supply) equipped with battery extension pack(s). The unit can be applied in those circumstances
where the regular built-in battery charging capacity of the UPS is considered to be insufficient,
given the frequency of power failures and the capacity of the back-up batteries. It is designed to
match the battery characteristics of the following GE Digital Energy UPS models: NetPro 3000 and
LP Series 11 / 31T / 31. Please note that two UBC units are required in a system with an LP 31
UPS. Off factory the UBC is wired for use with a NetPro 3000 UPS.
Mains
Fig. 1 Typical installation with UBC, UPS and battery extension pack(s)
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 3 User manual UBC 130-290V 1.0 (GB)
3 - Installation
The shipping box contains a UBC - Universal Battery Charger, an IEC male-female mains power cord,
a DC cable for use with a Digital Energy LP Series UPS and this manual. Inspect the UPS for damage
after unpacking. If any damage is present please immediately notify the carrier and place of
purchase.
IMPORTANT
Before making any connection and switching on the UBC, please check that your
mains supply is 220 - 240 Volts and 50 Hz
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 4 User manual UBC 130-290V 1.0 (GB)
3.2.1 Connecting the UBC to a NetPro 3000 UPS
5
2
6
3
4
Fig. 2 Connections for NetPro 3000 UPS 3a 3
3. Connect the DC cable plug (1, fig. 2) from the battery pack to the DC socket (2, fig. 2) of the
UBC.
4. Connect the DC cable plug (3, fig. 2) from the UBC to the DC socket (4, fig. 2 and 2a) of the UPS.
You will hear a click when the cable is properly installed. Block the DC connector: install the
small locking plate (3c, fig. 2a) that came with the battery pack, and fasten it with the screw
provided.
5. BEFORE connecting the UBC to mains: Check the dip switch setting at the back side of the UBC
(7, fig. 2) for NetPro 3000 usage, please refer to section 3.3.
6. Use the mains power cord provided with the UBC (6, fig. 2) and connect it to the input socket
(5, fig. 2)
7. Connect the mains power cords of the UBC and UPS to a working, grounded AC wall socket
outlet.
8. Switch on the UPS, refer to the user manual of the UPS for further instructions.
9. The green LED ‘on’ (12, fig. 10) of the UBC illuminates. Depending on the condition of the
batteries LED “charging” (14, fig. 10) may illuminate as well.
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 5 User manual UBC 130-290V 1.0 (GB)
3.2.2 Connecting the UBC to an LP 11 / 31T Series UPS
The UBC is standard wired for use with a NetPro 3000 UPS.
If you want to use the UBC in combination with an LP 11/31T Series UPS you first have to make
some small modifications to the UBC.
1. Make sure that the load protected by the UPS has been switched off.
Switch off the UPS
2. Switch all MCBs (2, fig. 3) to ‘off’ position (down) and open the battery fuse holder (9, fig. 3).
Please refer to the operating manual of the UPS for additional information.
3. Open the battery fuse holder of the battery extension cabinet as well (9a, fig. 3)
4. Read chapter 1.
Prepare the UBC for use with an LP 11/31T Series UPS:
4.1 Remove the screw from the front / bottom side of the UBC cabinet
4.2 Remove the 4 screws at the rear side of the UBC cabinet holding the I/O plate
4.3 Slide out the I/O plate till it is locked
4.4 Disconnect cable 3a from connector J231 and earth stud PE (fig. 5), remove the pull
relief (11, fig. 5) and remove cable 3a.
4.5 A DC cable was delivered with the UBC. Install the red DC+ and black DC- wires of this
cable (3b, fig. 3/6) to connector J231 (fig. 6)
4.6 Connect the yellow-green earth wire of cable 3b to the earth stud “PE”, according to fig.
6 and 7.
4.7 Place the metal pull relief (11, fig. 6) for cable 3b according to fig. 6 and fig. 8.
4.8 Connect the plug of the DC cable coming from the battery extension cabinet (1d, fig.
3/6) to connector 1c inside the UBC (fig. 6).
4.9 Place the metal pull relief for this cable according to fig. 6/8.
4.10 A remote alarm (for details see section 4.2.2) can be installed on the alarm relay
contact (15 on fig. 11). Lead the cable through the hole in the lower middle of the back
panel of the UBC.
4.11 Slide the I/O plate back into the unit and tighten the 4 screws at the backside and 1
screw at the bottom side of the UBC.
4.12 BEFORE connecting the UBC to mains: set the dip switches at the back side of the UBC
(7, fig. 3) for LP Series UPS usage. Please refer to section 3.3.
5. Connect the DC cable plug (3d, fig. 3) from the UBC to the DC socket of the UPS (8, fig. 3).
6. Use the mains power cord provided with the UBC and connect it to the input socket (5, fig.3).
7. Connect the mains power cord of the UBC (6, fig. 3) to a working, grounded AC wall socket
outlet.
8. Switch on the UPS and close the battery fuse holders of UPS (9, fig. 3) and battery cabinet(s)
(9a, fig. 3). Please refer to the operating manual of the UPS for additional information.
9. The green LED ‘on’ (12, fig. 10) of the UBC illuminates. Depending on the condition of the
batteries LED “charging” (14, fig. 10) may illuminate as well.
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 6 User manual UBC 130-290V 1.0 (GB)
LP 5-6 kVA
9
8 7 UBC
3d
6 5
LP 8-10 kVA
3b 1d
1e
LP battery cabinet
9a
9
2 14Ah
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 7 User manual UBC 130-290V 1.0 (GB)
3.2.3 Connecting two UBC units to an LP 31 Series UPS
The UBC is standard wired for use with a NetPro 3000 UPS.
If you want to use the UBC in combination with an LP 31 Series UPS you first have to make some
small modifications to the UBC. Please note that two UBC units are required in a system with an
LP 31 UPS.
1. Make sure that the load protected by the UPS has been switched off. Switch off the UPS.
2. On the UPS, switch all MCBs (2, fig. 4) to ‘off’ position (down).
Open the battery fuse holders (9b, fig. 4).
Please refer to the operating manual of the UPS for additional information.
3. Open the battery fuse holder of the battery extension cabinet (9c, fig. 4)
4. Read chapter 1. Prepare the UBC’s for use with an LP 31 Series UPS (for each UBC unit follow
steps 4.1 through 4.12):
4.1 Remove the screw from the front / bottom side of the UBC cabinet.
4.2 Remove the 4 screws at the rear side of the UBC cabinet holding the I/O plate.
4.3 Slide out the I/O plate till it is locked.
4.4 Disconnect cable 3a from connector J231 and earth stud PE (fig. 5), remove the pull
relief (11, fig. 5) and remove cable 3a.
4.5 Using a 10mm2 3-wire (red - black - yellow/green) DC cable: Install the red DC+ and
black DC- wires of this cable (3b, fig. 4/5/6) to connector J231 (fig. 6). Please note that
this cable 3b has no connector.
4.6 Connect the yellow/green earth wire of cable 3b to the earth stud “PE”, according to fig.
6 and 7.
4.7 Place the metal pull relief (11, fig. 6) for cable 3b according to fig. 6 and fig. 8.
4.8 A DC cable was delivered with the UBC. Connect the plug (1d, fig. 6) of this DC cable (1e,
fig. 4/6) to connector 1c inside the UBC (fig. 6).
4.9 Place the metal pull relief for this cable according to fig. 6/8.
4.10 A remote alarm (for details see section 4.2.2) can be installed on the alarm relay
contact (15, fig. 11). Lead the cable through the hole in the lower middle of the back
panel of the UBC.
4.11 Slide the I/O plate back into the unit and tighten the 4 screws at the backside and 1
screw at the bottom side of the UBC.
4.12 BEFORE connecting the UBC to mains: set the dip switches at the back side of the UBC
(7, fig. 4) for LP Series UPS usage, please refer to section 3.3.
5. Connect the DC cable (3b, fig. 4) from UBC 1&2 to the battery terminals of the UPS (10a, fig. 4).
Please refer to the operating manual of the UPS for additional information.
6. Connect the DC cable (1e, fig. 4 from UBC 1&2 to the battery terminals of the battery
extension cabinet (10b, fig. 4). Please refer to the operating manual of the UPS for additional
information.
7. Use the mains power cord provided with UBC 1&2 and connect it to the input socket (5, fig. 4).
8. Connect the mains power cord of UBC 1&2 (6, fig. 4/5) to a working, grounded AC wall socket
outlet.
9. Switch on the UPS and close the battery fuse holders of the UPS and battery cabinet(s) (9b/c,
fig. 4). Please refer to the operating manual of the UPS for additional information.
10. The green LED ‘on’ (12, fig. 10) of the UBC illuminates. Depending on the condition of the
batteries LED “charging” (14, fig. 10) may illuminate as well.
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 8 User manual UBC 130-290V 1.0 (GB)
UPS
2 battery cabinet
9c
10a 10b
9b
3b-1 3b-2
1e-1 1e-2
7 UBC - 1 7 UBC - 2
5 5
6 6
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 9 User manual UBC 130-290V 1.0 (GB)
battery
1b 1 pack
2
11 1a
PE 3
3a
UPS
battery
1c 1d cabinet
1e
11
PE 3d (LP 11/31T)
3b
UPS
11
3a/b
1e/3a/3b
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 10 User manual UBC 130-290V 1.0 (GB)
3.3 Settings: voltage and current
4 3 2 1 6 5 4 3 2 1
“ON”
position
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 11 User manual UBC 130-290V 1.0 (GB)
4 - Operation
During installation you have properly set the nominal charge voltage and - current, according to
the UPS system. For more information please refer to section 3.3. In the charging mode the UBC
charge voltage will follow the UPS charge voltage. This way the advantages of the superior
battery management features of the UPS are fully used:
temperature compensated battery charging - reduces the battery charge voltage with
increasing temperature. As a result poor charging of the batteries under low temperature
conditions and overcharging of the batteries under high temperature conditions are prevented.
14
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 12 User manual UBC 130-290V 1.0 (GB)
4.2.3 Protection
All electrical circuits are protected against overtemperature or overload by means of protection
circuits for transformer, heatsink, input AC voltage, output DC voltage and short circuit.
5 - Maintenance
The GE Digital Energy Universal Battery Charger is virtually maintenance free: take care of proper
environmental conditions and keep air inlets/outlets free of dust.
6 - Troubleshooting
The following chart is a simple troubleshooting checklist only. If the suggested solution does not
succeed, or if the information is insufficient to solve the problem, please contact your dealer or
consult www.gedigitalenergy.com.
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 13 User manual UBC 130-290V 1.0 (GB)
7 - Technical specifications
Ratings
Input power (W) : 2600
Input fuse (A) : 20
Output power (W) : 2320
Output Fuse (A) : 10
Input converter
AC input voltage : 220 - 240 V
AC input voltage range : 100% load: 187 - 264 V
Minimum start-up AC voltage : 190V
Input current waveform : sinusoidal
conform or better than EN 61000-3-2 (IEC 555-2)
Input current (A) at nom. inp. volt. : 16
Input power factor : 1
Input frequency range (Hz) : 45 - 66
Inrush current (A) : 23
Output converter
DC output voltage : 290V max (dip switch setting 9 – 20 batteries 130.5 – 290V)
DC output voltage tolerance : ± 2%
DC output current : 8A max (dip switch setting 2, 4, 6 or 8 Ampere)
DC output current tolerance : ± 10%
General
Weight (kg) : 5
Dimensions (hxwxd, mm) : 225x185x430
Enclosure / protection : steel-plastic / IP20
Environment
Safety : EN 50091-1-1, EN 60950, IEC 950
Electromagnetic compatibility : EN 50091-2
Ambient temperature : -10 to +40ºC
Audible noise at 1 meter : < 45 dB(A), temperature dependent
Max. relative humidity : 95% (non-condensing)
modifications reserved
OPM_UBC_130_290_XXX_1GB_V010 14 User manual UBC 130-290V 1.0 (GB)