You are on page 1of 1

SAES-Q-010 (Cement-Based, Non-Shrink Grout for Structural and Equipment Grouting)

4. Modification to Process Industry Practice STS03600

> Minimum 28 days compressive strength shall be 34.5 MPa (5,000 psi)

> Cementitious grout minimum 28 days compressive strength shall be 13.8 MPa (2,000 psi) and shall
be used for any of the following:

•Structural Base Plate


•Anchor Bolts
•Columns and Precast Members

> Total Dissolved Solids (TDS) 500 parts per million (ppm)

> Testing
•Two (2) sets of three (3) test cubes in the field
•Curing cubes in the field for 3 days
•Test one (1) cube for 7 days and one (1) cube for 28 days

SAES-Q-011 (Epoxy Grout for Machinery Support)

4. Modification to Process Industry Practice STS03601

> All components, resin, hardener, and aggregate shall be properly labeled, including batch numbers,
shelf life and storage requirements

> Grout shall be applied only when surrounding temperatures are between 15C a n d 32C unless
otherwise specified in the manufacturer's data sheets

> Expansion joints should be placed at approximately 1.2 m to 1.8 m intervals in the grout foundation

> A layered combination of non-shrink cement and epoxy grout may be used, as permitted
by SAES-Q-007 for large baseplates that have structural webs deeper than 230 mm

> If the grout pour is 100 mm or deeper, the grout manufacturer recommendations for installing
reinforcement rebars shall be followed.

> Testing
•Minimum sample frequency is one per shipment or per manufacturing lot of grout.
•Compressive strength and Linear Shrinkage

> Minimum Compressive Strength 80 Mpa (12,000 psi) at 7 days

> Maximum Linear Shrinkage : 0.080 percent

> Minimum Bond Strength of Epoxy Grout to concrete - 2,000 psi (14Mpa)

You might also like