Professional Documents
Culture Documents
Unit 6 - Power Quality - Sem VIII - Pps
Unit 6 - Power Quality - Sem VIII - Pps
A R
B K
A M
K H
UNIT : 6K AL
IJ U
PowerDr.Quality
VA
• As the name implies, DG uses smaller-sized generators than does the typical
central station plant.
• They are distributed throughout the power system closer to the loads.
• The term smaller-sized can apply to a wide range of A Rgenerator sizes i.e
B K
generator sizes less than 10 MW. M
HA
LK
A
• Generators larger than this are typically Kinterconnected at transmission
IJU
voltages where the system is designed to Aaccommodate many generators.
r .V
•
D
Thus, several power quality issues arise when there are multiple sources
• VIDEO:DG
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• The implied message related to power quality is that the DG is small compared
to the grid. This group often has the view that the grid is a massive entity too
large to be affected by their relatively small generator.
• For this reason, many have a difficult time understandingR why utilities limits
A
BK competition.
interconnecting and view the utility requirements and avoid
A M
K H
A L
• DG as improving the reliability of the system (including the grid) and providing
K
better-quality power.
IJ U
A
r .V
• The size of customer owned DG isDmagnified to appear much larger than its
actual size, and it produces power quality issues.
• It is also a little off-center in its design, suggesting that it is not built and
maintained as well as utility equipment.
• Photovoltaic systems
•One of the disadvantages of this technology is high NOx and SOx emissions.
•This severely limits the number of hours the units, particularly diesels, may operate each
year to perhaps as few as 150.
AR backup
•Thus, the main applications will be for peaking generation and emergency
BK
A
•Natural gas–fired engines produce fewer emissions and canHgenerally
M
be operated several
K
thousand hours each year. AL
K
U
IJ cogeneration applications in schools,
A
•Thus, they are popular in combined heat and power
V
government, and commercial buildings where r .they operate at least for the business day.
D
Efficiency:40 % - 45 %
•The turbines commonly turn at speeds of 8000 to 12,000 rpm and geared down to speed
required by the synchronous alternator (typically 1800 or 3600 rpm for 60-Hz systems).
•The alternator output is rectified to direct current immediately and fed into an inverter that
interfaces with the ac electric power system.
•Thus, the characteristic of the microturbine that is of interest to power quality engineers is the
response of the inverter to systemDr.disturbances.
10/27/20
V N Kalkhambkar, Associate Professor,
17
RIT Rajaramnagar
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• Hydrogen and Oxygen from the air and puts out electricity, heat, and water.
• It doesn't use fossil fuels and it doesn't produce greenhouse gases . it should be
the ideal solution to providing distributed or portable electrical power.
• Fuel cells are efficient electricity generators and may be employed in combined
heat and power applications to achieve among the veryAR best possible energy-
B K
conversion efficiencies. M
HA
LK
• Those who see the future energy economy based KA on hydrogen see the fuel cell as
the dominant energy-conversion technology. IJ U
V A
.
Dr
• A fuel cell is basically a battery powered by an electrochemical process based on
the conversion of hydrogen. It produces dc voltage, and an inverter is required
for interfacing to the ac power system.
• The chief drawback to fuel cells at present is cost. Fuel cell technologies are on
the order of 10 times more expensive than reciprocating gensets.
Dr. V N Kalkhambkar, Associate Professor,
10/27/20 20
RIT Rajaramnagar
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• The chief power quality issue associated with wind generation is voltage
regulation. Wind generation tends to be located in sparsely populated areas
where the electrical system is weak relative to the generation capacity.
• The doubly fed induction generator permits a second excitation current input, through slip rings to a
wound rotor permitting greater control over the generator output.
• The DFIG system consists of a 3 phase wound rotor generator with its stator windings fed from the grid
and its rotor windings fed via a back to back converter system in a bidirectional feedback loop taking
power either from the grid to the generator or from the generator to the grid.
• The frequency error is equal to the generator slip frequency and is equivalent to the difference between
Dr. V N Kalkhambkar, Associate Professor,
the synchronous speed and the actual shaft speed
10/27/20 of the machine.
RIT Rajaramnagar
27
Photovoltaic systems
A R
B K
A M
K H
• Several large scale grid connected PV power
AL
K plants have been constructed
U
IJ500 kW capacity but some as high as
throughout the world, mostly of 300 kW to A
300MW or more. r .V
D
• Up to now deployment of large scale plants has been limited to experimental
installations because of the high cost of the solar panels. With typical efficiencies
of around 15%,
• Photovoltaic solar systems generate dc power and are interfaced to the utility system
through inverters. Some systems do not have the capability to operate stand-alone—the
inverters operate only
Dr. V N Kalkhambkar, Associate Professor,
10/27/20 28
RIT Rajaramnagar
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• The energy conversion technology plays some role in the power quality
• However, this type of system should be carefully studied and coordinated with the utility
system protection and voltage regulation equipment.
• Compared to the utility electrical power system, generators sized for typical backup
power purposes have high impedances.
• The subtransient reactance Xd″, which is seen by harmonics, is often about 15 percent of
the machine’s rating. The transient reactance, Xd′, which governs much of the fault
contribution, might be aroundDr.25
10/27/20
V Npercent.
Kalkhambkar,The synchronous
Associate Professor, reactance Xd is generally31
RIT Rajaramnagar
over 100 percent
• Some actual examples of unexpected consequences with synchronous gen
b) There is not enough fault current to trip breakers or blow fuses that were
sized based on the power system contribution.
A R
K
B causes fluorescent
c) The voltage sag when elevator motors are being started
A M
lamps to extinguish. K H
A L
K
• Another aspect that is often overlooked IJ U is that the voltage waveform
A
produced by a synchronous machiner.isVnot perfect. In certain designs, there
D
are considerable third-harmonic currents in the voltage.
•Simple induction generator requires reactive power (vars) to excite the machine
from the power system to which it is connected.
•A common rule of thumb is that if the voltage supplying the induction machine
remains higher than 60 percent, it will continues to feed into the fault as if it were
a synchronous machine.
• To achieve better control and to avoid harmonics problems, the inverter technology has
changed to switched, pulse-width modulated technologies. This has resulted in a more
friendly interface to the electrical power system.
R
Arequirements of IEEE
• The total harmonic distortion limit is 5 percent, based on the K
B limits under specific
Standard 519-1992. Occasionally, some inverters will exceed
A Mthese
conditions. K H
A L
K
• commonly applied inverters basically attempt Ito J U generate a sine-wave current that
V Aproduce power at unity power factor
.
follows the voltage waveform. Thus, they would
Dr
• One of the advantages of such an inverter for DG applications is that it can be switched
off very quickly when a disturbance requiring disconnection is detected
•The bulk of the capacity of this form of DG can be realized simply by transferring the load to
the backup system
•This can allow deferral of major construction expenses for a few years.
•The dependency on this scheme for too many years can ultimately lead to worse reliability.
Dr. V N Kalkhambkar, Associate Professor,
10/27/20 36
RIT Rajaramnagar
Voltage Regulation
• It may initially seem that DG should be able to improve the voltage regulation on a feeder.
• Generator controls are much faster and smoother than conventional tap-changing
transformers and switched capacitor banks.
• With careful consideration, this can be accomplished with sufficiently large DG. However,
there are many problems associated with voltage regulation. AR
BK
• In cases where the DG is located relatively far from the A M
substation, voltage regulation is
H
LK
often the most limiting without changes to the utilityAsystem.
K
U
IJ are unsuitable for regulating
• A
It should first be recognized that some technologies
r . Vmachines and for most utility interactive
voltages. This is the case for simple induction
D
inverters that produce no reactive power.
• Secondly, most utilities do not want the DG to attempt to regulate the voltage because
that would interfere with utility voltage regulation equipment and increase the chances
of supporting an island
• Recently technologies requiring inverters have adopted the switching inverters like the one
described previously in this chapter.
• This has eliminated the bulk of the harmonics problems from these technologies.
R
• One problem that occurs infrequently arises when a switchingAinverter is installed in a
B K
system that is resonant at frequencies produced by the switching
M process
HA
• LKin a system creates resonance at
Problem arises when a switching inverter is installed
K A
frequencies produced by the switching process due
IJ U to capacitors
V A
• The utility power system acts as a short Dr. to zero-sequence triplen harmonics in the
circuit
voltage, which can result in surprisingly high currents.
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• The lowest-level component is the lateral fuse, and the other devices (reclosers and
breakers) are designed to conform to the fuse characteristic.
•There will frequently be two to four feeders off the same substation bus.
• Because there is too much infrastructure in place to consider a totally different distribution
system design to better accommodate DG, the DG must adapt to the way the utility system
works.
• With only one utility device operating to clear a fault, all other DG devices must
R protection system to
independently detect the fault and separate to allow the utility
A
complete the clearing and isolation process. BK
A M
• K
This is not always simple to do from the information that
Hcan be sensed at the generator.
A L
K
U
J the difficulties that occur due to this.
• The section operating conflicts describes someAIof
r .V
D
•Most of the distribution lines are overhead, and it is common to have temporary
faults.
•Once the current is interrupted and the arc dispersed, the line insulation is restored.
A R
•Reclosing enables the power to be restored to most of the B
customers within
K
A M
seconds. K H
A L
K
VIDEO: Reclosing IJ U
r. VA
D
Reclosing presents two special problems with respect to DG:
• DG must disconnect early in the reclose interval to allow time for the arc to
dissipate so that the reclose will be successful.
• The DG relaying must be able to detect the presence of the fault followed by the opening of
the utility fault interrupter so that it can disconnect early in the reclose interval as shown.
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• A greater complicating factor is the use of instantaneous reclosing by many utilities.
• Thus, instantaneous reclose is very likely to be incompatible with DG. It greatly increases
the probability that some DG will still be connected when the reclose occurs or that the
fault did not have enough time to clear, resulting in an unsuccessful reclose.
• Thus, for some distribution systems it will be necessary to compromise one aspect of
power quality to better accommodate significant amounts of DG.
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
Reduction of reach
AR is determined by its
•Each overcurrent relay device has an assigned zone of protectionKthat
minimum pickup value. B
M A
K H
L
•Some refer to this generically as the “reach” of the relay.
KA DG infeed can reduce the current
that the relay sees, thereby shortening its reach. IJU
V A
.
•When the total DG capacity increases toDra certain amount, the infeed into faults can
desensitize the relays and leave remote sections of the feeder unprotected.
•A low-current (high-impedance) fault near the end of the feeder is more likely to go
undetected until it does sufficient damage to develop into a major fault.
•The power quality consequences of this are that voltage sags will be prolonged for some
customers and the additional fault damage will eventually lead to more sustained
interruptions. Dr. V N Kalkhambkar, Associate Professor,
10/27/20 47
RIT Rajaramnagar
A R
B K
A M
K H
K AL
Solutions include: U
IJ
VA
•Decrease the relay minimum pickup currentr.to increase the zone.
D
•Add a line recloser to create another protection zone that extends far past the end of the
feeder.
•Use a transformer connection that minimizes DG contribution to ground faults, since high-
impedance faults are likely to be ground faults.
For example, Figure 1 shows two radial circuits fed from one source. With no DG installed, if
a short circuit occurs on Feeder 2, the short circuit will be completely fed from the utility
source with no short circuit contribution from Feeder 1.
As a result, relay or breaker OC-1 will not respond to the short circuitRat feeder 2. The fault is
cleared by relay or breaker OC-2 as intended. K A
B
A M
K H
K AL
IJ U
. VA
Dr
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
•The desired sequence for the situation depicted in Fig. is for the recloser R to operate
before the lateral fuse has a chance to blow.
• If the fault is temporary, the arc will extinguish and service will be restored upon the
subsequent reclose, which normally takes place within 1 or 2 s. KA
R
B
M
Aand improves the reliability of
•This saves the cost of sending a line crew to change the fuseK H
L
customers served on the fused lateral. KA
IJ U
V A
.
Dr
1.Increase the size of the lateral fuses. All fused cutouts in the zone would have to be
changed, which could be quite expensive.
---This saves the cost of sending a line crew to change the fuse and improves the
reliability of customers served on the fused lateral.
Voltage regulation issues are more likely to occur and cause interconnection problems
Figure 9.15a shows the voltage profile along the feeder prior to the fault occurring. The
intent of the voltage regulation scheme is to keep the voltage magnitude between the two
limits shown. In this case, the DG helps keep the voltage above the minimum and, in fact, is
large enough to give a slight voltage rise toward the end of the feeder.
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• The load is now too great for the feeder and the present settings of the voltage regulation
devices.
• Therefore, the voltage at the end of the feeder sags below the minimum and will remain
low until voltage regulation equipment can react.
A
• This can be the better part of a minute or longer, which increases Rthe risk of damage to
B K
load equipment due to excessively low voltages. M
HA
LK
K A
IJ U
. VA
Dr
• For example, if one were to establish a 5 percent change criterion for the limit, there
would be a curve of generation limit versus distance similar to that shown in Fig.
A R
• If a proposed DG application falls to the left of the curve, it is K
B likely to be acceptable. If
A M
it falls to the right, more engineering study is needed to determine how to accommodate
H
the DG LK
KA
IJ U
. VA
Dr
• The regulator now senses reverse power and attempts to regulate the utility source.
However, the DG is not nearly as strong as the utility source and the regulator will not
succeed.
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• The generation is typically sited several miles from the nearest substation on a
AR a voltage regulator.
feeder that already may have several switched capacitors Kand
B
M
• One typical example based on a wind farm at a Kski HAresort is shown in Fig. The
A L
line is a typical untransposed, horizontal crossarm
K geometry that leads to special
issues. IJ U
V A
Dr.
• As the power output of the generator varies, one outside phase will tend to rise
in voltage while the other tends to drop. Not only is there a magnitude issue but a
balance issue.
• One new distortion problem that arises with the modern inverters is that the switching
frequencies will occasionally excite resonances in the primary distribution system. This
creates nonharmonic frequency signals typically at the 35th harmonic and higher riding
on the voltage waveform.
• This can adversely affect the operation and efficiency of the machine and may result in
the failure of some circuit element.
• In this case, the problem is confined to the generator side of the transformer and does
not
10/27/20
Dr. V N Kalkhambkar,
affect the primary distribution Associate Professor,
system because the triplen harmonics are trapped
61 by
RIT Rajaramnagar
the delta winding. The
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
Islanding is mode where the main grid is cut off and is not supplying power. The main grid
might be turned off due to fault or maintenance purposes
Perhaps the greatest fear of the utility protection engineer is that DG relaying will fail to
detect the fact that the utility breaker has opened and will continue to energize a portion of
the feeder. R A
B K
A
Therefore, much attention has been paid to detecting islands Mor forcing islands to become
K H
unstable so they can be detected. L
KA
U
IJbe subjected to such poor-quality voltage
The reliability concern is that other customers willA
r. V it will be held liable for the damage.
that damage will be sustained. The utility is fearful
D
There is also the safety concern of a generator accidentally energizing the line resulting in
injuries to the public and utility personnel.
• These are typically synchronous and induction generators at present. Small distributed
generators such as inverter based PV systems are connected to the low voltage secondary
feeders (DG3).
• An island situation occurs, for example, when recloser C opens.ARDG1 will feed into the
resultant island in this case. BK
M A
H
K fault in the downstream of the
• The most common cause for a recloser to open is A La
K
IJ U
recloser. A recloser is designed to open and re-close two to three times within a few
seconds. V A
.
Dr
• The intention is to re-connect the downstream system automatically if the fault clears by
itself. In this way, temporary faults will not result in the loss of downstream customers.
• An island situation could also happen when the fuse at point F melts. In this case, the
inverter based DG will feed the local loads, forming a small islanded power system
i)The voltage and frequency provided to the customers in the islanded system can vary
significantly if the distributed generators do not provide regulation of voltage and
frequency and do not have protective relaying to limit voltage and frequency excursions,
R
since the supply utility is no longer controlling the voltage and frequency
A
B K
M public by causing a line to
ii)Islanding may create a hazard for utility line-workers or Athe
K H from all energy sources.
L
remain energized that may be assumed to be disconnected
KA
IJ U
iii)The distributed generators in the island Acould be damaged when the island is
V
reconnected to the supply system. Thisr. is because the generators are likely not in
D
synchronism with the system at the instant of reconnection.
iv)Islanding may interfere with the manual or automatic restoration of normal service for
the neighbouring customers.
The current power industry practice is to disconnect all DGs immediately so that the entire
feeder becomes de-energized. It prevents equipment damage and eliminates safety
hazards. To achieve this goal, each
Dr. V N DG must
Kalkhambkar, have
Associate the capability to detect islanding
Professor,
10/27/20 66
conditions and to automatically disconnect itself from the system.
RIT Rajaramnagar
Ferroresonance
• Ferroresonance is a special kind of resonance in which the inductive element is the
nonlinear characteristic of an iron-core device.
•
Most commonly, ferroresonance occurs when the magnetizing reactance of a transformer
comes in series with cable or power factor capacitance.
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
• The type of ferroresonance shown in Fig. is very sensitive to the amount of load. If
the system can be arranged so that there is always a resistive load attached to the
secondary bus, the resonance can be damped out. The load need not always be large,
but must be significant. Dr. V N Kalkhambkar,
10/27/20
Associate Professor,
RIT Rajaramnagar
68
Shunt capacitor interaction
• These banks are mostly controlled by local intelligence, switching at predetermined times
or at loading levels as measured by either voltage, current, or kvar.
• Some types of DG can also produce reactive power (vars), and this can create control
hunting and other difficulties.
• There can be several capacitor banks on the feeder as illustrated in Fig.
• The capacitors switch independently of the generator control unless special
communications and control have been added to coordinate dispatch R A
B K
A M
K H
K AL
IJ U
. VA
Dr
• If a synchronous generator does not have a 2/3 winding pitch, paralleling to the utility
system provides a very low impedance path for the third harmonics
• the resulting neutral currents may damage generator equipment or simply add unwanted
harmonic currents to the utility A R
• system. BK
A M
K H
• A neutral reactor may be necessary for some wye-connected
A L machines while they are
paralleled to the utility system to – K
IJ U
A
a. Limit the flow of zero-sequence harmonics r .V
(principally, the third)
D
b. Limit the contribution of the generator to ground faults
It would probably be favored for serving loads in nearly all cases if it were not for the
susceptibility of the connection to ferroresonance in cable-fed systems.
Advantages include:
•
There is less infeed into utility-side ground faults.
•
Third harmonics from the DG do not reach the utility system. A R
•
Some isolation from voltage sags due to utility-side SLG faults is
K
Bprovided.
A M
K H
Disadvantages include:
K AL
IJ U
•It is difficult to detect some SLG faults from theV A
secondary side by voltage relaying alone.
.
Dr installations
•It is susceptible to ferroresonance in cable-fed
• Third harmonics in the DG may cause excessive current in the secondary-side neutral.
•If islanded on an SLG fault, utility arresters can be subjected to overvoltages (see Sec. 9.6).
• If arresters are islanded on an SLG fault and there is little load, resonant overvoltages can
result.
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
Advantages include:
■ More economical transformer installation for smaller three-phase service with some
single-phase loads is possible.
■ The load is isolated from ground faults on the utility side. A R
B K
■ DG would not typically feed utility-side ground faults except when
M resonance occurs.
■ Ungrounded interconnection can be provided for inverter-basedHA systems
LK
requiring it. KA
IJ U
Disadvantages include:
r . VA
D
■ Utility-side SLG faults are difficult to detect.
■ Utility arresters are subjected to high steady-state overvoltages if islanded on an SLG fault
(Fig). This is true for delta-wye connections as well.
■ These connections are highly susceptible to ferroresonance in cable fed installations..
Many utility engineers believe this is the best winding connection for interconnecting
generation to the utility system. This is the connection used for nearly all central station
generation. There are many advantages, including:
1.Utility-side faults are easily detected partly because the transformer itself actively
participates in ground faults.
A R
K
Bcause any current to flow
M
2. Triplen harmonic voltages produced by the generator do not
Anearly any generator can be
because it is blocked by the delta winding. Therefore,K H
L
paralleled with this connection. KA
IJ U
V
3. Protection schemes are well understood basedA on many years of experience with utility
.
generation. Dr
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
■ The connection is likely to cause sympathetic tripping of the feeder breaker for faults on
other feeders. The transformer supplies ground current to other feeders connected to the
same substation
■ Ground trip pickup levels must be increased, and more delay must
R
A be used to maintain
K
B(An alternative is to use
M
coordination, which results in less sensitive fault protection.
A
directional overcurrent relaying.) K H
A L
K
■ Sags for ground faults will generally be somewhat
IJ U deeper (the transformer makes the
system appear more solidly grounded). V A
.
Dr
■ If fuse saving is being attempted, the fault infeed, which is likely to be larger than from
the DG itself, makes this much more difficult to achieve.
■ The transformer itself is subject to short-circuit failure when a ground fault occurs. This is
particularly true for smaller transformer banks with impedances less than 4 percent. A
special transformer must generally be ordered.
■ The transformer is also subject to failure thermally because the feeder load is rarely
Dr. V N Kalkhambkar, Associate Professor,
balanced.
10/27/20 Thus, the transformer will act as a sink for zero-sequence load currents.
RIT Rajaramnagar
78
Siting DG
• However, to provide support for distribution feeders, the DG must be sited out
on the feeder away from the substation.
Dr. V N Kalkhambkar, Associate Professor,
10/27/20 79
RIT Rajaramnagar
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
A R
B K
A M
K H
K AL
IJ U
. VA
Dr
A R
B K
A M
K H
K AL
IJ U
. VA
Dr