Professional Documents
Culture Documents
Restriking voltage is the transient voltage appearing across the breaker contacts
immediately after the opening of breaker contacts. It is also called Transient Recovery
Voltage (TRV).
Restriking voltage is associated with high frequency which dies out quickly. Even though
restriking voltage is lasts for very short duration, its importance for breaker fault clearing
cannot be ignored. If the rate of rise of dielectric strength of medium is less than the
restrining voltage, arc quenching will not take place and hence fault will not be interrupted.
This will in turn increase the fault clearing time which is not desirable. In this post we will
focus our attention to the calculation of restriking voltage with the following assumption:
1. The fault does not involve any arcing i.e. the fault is solid one.
2. Effect of corona and saturation is ignored. Corona and saturation of machine
attenuates the voltage surge during breaker contact opening by dissipating energy.
3. The current interruption is assumed to be taking place at natural current zero.
4. The whole system is assumed to be lossless.
The above assumptions are considered to arrive at the maximum restriking voltage after the
removal of fault by breaker contact opening. Figure below shows the simplest model of
system consisting of a source connected to a bus bar. The inductance and capacitance of the
system is lumped together and connected in series and parallel with the source respectively.
A solid fault takes place and in response to the fault, breaker contacts open to isolate the
faulty network from the healthy system. We are now required to find the voltage across the
breaker contacts immediately after the breaker contact opening.
The voltage across the breaker contact will be equal to the multiplication of fault current and
the system impedance as seen from the CB (circuit breaker) contacts with voltage source
shorted (as per thevenins’ theorem). Let us assume this voltage to be v(t). For making
calculations easy, it will be a smart way to consider every parameter in laplace domain.
Therefore,
V(s) = Source Voltage
I(s) = Fault Current
Z(s) = System Impedance as seen from CB contacts
Hence,
V(s) = I(s)Z(s) ………….(1)
But source voltage is VmSinωt, hence source voltage at natural current zero i.e. when breaker
contact open will be Vm. Therefore V(s) = Vm /s and impedance is mainly offered by
inductance, this means Z(s) = Ls
Thus from (1),
Vm/s = I(s)Z(s)
I(s) = Vm / Ls2 ………..(2)
Now let us find the Z(s). Z(s) will be parallel equivalent of inductance L and capacitance C
when viewed from breaker contact. Therefore,
Z(s) = [(Ls)(1 / Cs)] / [Ls + 1/Cs]
= Ls / [Ls + 1/Cs]
= (s / C) / [s2 + 1/LC]
Now from (2),
v(s) = Voltage across breaker contact immediately after opening
= Restriking Voltage
= Transient Recovery Voltage
= I(s)Z(s)
= [(Vm/s)(1/sL) (s / C)] / [s2 + 1/LC]
= Vm [1/s – s / (s2 + 1/LC)]
Taking inverse laplace transform, we get
v(t) = Vm[1 – cosω0t] ………(3)
where ω0 = 1 / √LC and hence f0 = (1/2π√LC) where f0 is the natural frequency of oscillation.
= π √LC
Expression (3) is the restriking or transient recovery voltage. It can be seen from the
expression that TRV is of sustained oscillating nature. But it is not true. The above
expression has been arrived at by assuming some conditions which eliminates the damping
effect. In real scenario, Restriking voltage die out due to damping effect of corona, arc
involved in faults etc.