Relayaux: Auxiliary Relays For Tripping and Control Applications
Relayaux: Auxiliary Relays For Tripping and Control Applications
RelayAux
Comprehensive range of products
Instantaneous trip relays, whose contacts change instantaneously from the rest
position to the working position when the coil is energized. The contacts return to
the rest position when the coil is no longer energized.
This range includes relays with 2 and 4 contacts, with standard operating times (20
ms) or fast operating time (8 ms), depending on the model.
is energized, the contacts will change from one position to the other. The design of
the RelayAux has no consumption in permanence,
and prevents both coils from being energized simultaneously.
This range includes relays with 4 and 8 contacts, with operating times below 10 ms,
depending on the model, and possibility of manual reset.
The position change is made with 2 sets of coils with separated entrances, and
with breaking-flame contacts for each set of coils.
Time-lag relays
PM103518
RelayAux
Comprehensive range of products
For single phase or three phase circuit breakers. Through a small supervision
current the whole circuit is supervised, in both positions of the circuit breaker
(opened or closed).
The correct state of the circuit is showed with a green LED on the front plate of the
relay. The output contacts change its position if the relay detects a failure in the
continuity of the circuit.
Auxiliary relay with four changeover contacts, aimed to supervise the failure of trip
supply.
Connecting the relay across the trip circuit supply, the equipment is normally
energized. Faults will occur when the trip voltage is lost, so the relay drops off
in those cases, providing the related signs and alarms.In order to avoid faulty
alarms due to instantaneous supply voltage dips, the drop off time of the relay is
delayed over 100 ms so those non-permanent failures of trip supply would not be
considered.
Sockets
Front Connection Sockets Flush Mounting Sockets
PM103527
PM103524
PM1103525
PM1103526
MV DISTRIBUTION & GRID AUTOMATION // PROTECTION RELAYS schneider-electric.com | 4
RelayAux
Characteristics
11
3 7
( –) 1 12
4 8
Connections
13
5 9
( +) 2 14
6 10
RelayAux
Characteristics
11
DM105806
3 7
( –) 1 12
4 8
Connections 13
5 9
( +) 2 14
6 10
RelayAux
Characteristics
1 11
20
2 21
30
( –) a
3 31
40
4 41
Connections 50
( +) d 5 51
60
6 61
70
7 71
80
8 81
RelayAux
Characteristics
10 6
Set
14
+ 9 5
- B1 13
Connections 2 + 8 4
1
12
7 3
Reset 11
RelayAux
Characteristics
10
21 2
20
31 3
30
Set
+ - 41 4
b a 40
Connections + - 51 5
d c
50
Reset 61 6
60
71 7
70
81 8
80
RelayAux
Characteristics
Time-lag relay
PM103518
2 1
(-) (+)
A1
( ) B1 ( )
2 1 B1
- + (+)
( )
11
3 7
Connections 12
4 8
13 TIMER
5 9
14
6 10
RelayAux
Characteristics
SUPPLY 1-2
SUPPLY 1-2 t' < t
3-7
4-8 CONTROL B1 - 2
TIMER
5-9
6 - 10
t
3-7
4-8
TIMER
5-9
t
DM105823
DM105826
6 - 10
CONTROL B1 - 2 CONTROL B1 - 2
3-7 3-7
4-8 4-8
TIMER TIMER
5-9
5-9 t t t t
DM105824
DM105827
6 - 10 6 - 10
SUPPLY 1-2
SUPPLY 1-2
CONTROL B1 - 2
CONTROL B1 - 2
3-7
4-8
TIMER
5-9
6 - 10
t t 3-7
t
4-8
TIMER
5-9
DM105825
DM105830
6 - 10 t t
SUPPLY 1-2
SUPPLY 1-2
3-7
CONTROL B1 - 2 4-8
TIMER
3-7 5-9
TIMER
4-8 6 - 10 T1 T1 T1 T1
5-9 t t
6 - 10 T2 T2 T2 T2
DM105828
DM105829
T1 = 12 h T2 = 2 s
RelayAux
Characteristics
DM105804
Connections
RelayAux
Characteristics
DM105805
Connections
RelayAux
Characteristics
DM105822
11
3 7
( –) 1 12
4 8
Connections
13
5 9
( +) 2 14
6 10
RelayAux
Environmental characteristics
Level /
Electromagnetic compatibility Standard Value
Class
Emission tests
Immunity tests
IEC61000-4-3
Radiated radiofrequency fields immunity test III 10 V/m ; 80 to 1000 MHz
ENV 50204
2 kV in common mode
Surge immunity test IEC61000-4-5 III
1 kV in differential mode
In operation
Cold test IEC60068-2-1 - 25 °C All RelayAux relays
Trip and lockout relays; Instataneous Trip
+ 70 °C relays; Instataneous Fast Trip relays; Trip
Dry heat test IEC60068-2-2 Circuit Supervision relays
Time-Lag, Auxiliary Supply Supervision
+ 55 °C
relays
In storage
RelayAux
Environmental characteristics
Certification
Directives and Amendments
• 89/336/EEC Compliance with the European Commission Directive on EMC:
- 92/31/EEC Amendment
CE - 93/68/EEC Amendment
File E322124
UL
GI629039332
MV DISTRIBUTION & GRID AUTOMATION // PROTECTION RELAYS schneider-electric.com | 16
RelayAux
Order Codes and Dimensions
(4 changeover)
PM103524
PM103526
Order Codes
Front Flush
connect. mounting
RelayAux Contacts Pick up Other Auxiliary RelayAux socket socket
Type no. time functions Supply Reference Screw Screw
Reference Reference
24 Vdc REL91200
30 Vdc REL91201
RelayAux
Order Codes and Dimensions
DM105811
DM105820
42,5
50,4
105
72
10,5
RelayAux
Order Codes and Dimensions
PM103525
PM103527
Order Codes
Front Flush
connect. mounting
RelayAux Contacts Pick up Other Auxiliary RelayAux socket socket
Type no. time functions Supply Reference Screw Screw
Reference Reference
24 Vdc REL91240
30 Vdc REL91241
• Diode in paralell
with the coil Low 48 Vdc REL91242
• Front LED Burden 110 Vdc REL91243
Instantaneous 8
< 8 ms • Mechanical 125 Vdc REL91244 REL91351 REL91356
fast trip relay changeover
contact position 220 Vdc REL91245
indicator
110 Vdc REL91253
• Trip flag High
125 Vdc REL91254
Burden
220 Vdc REL91255
• Diode in paralell
with the coil
• Front LED
Instantaneous 8 • Mechanical High
< 8 ms 125 Vdc REL91259 REL91351 REL91356
fast trip relay changeover contact position Burden
indicator
• Trip flag
• Push test button
(1 ) DIN rail according to EN50022, DIN46277/3
(2) Minimum distance between sockets will depend on type of relay and sockets. Please request sockets User Manual for more detailed information
MV DISTRIBUTION & GRID AUTOMATION // PROTECTION RELAYS schneider-electric.com | 19
RelayAux
Order Codes and Dimensions
82,5
DM105816
DM105821
DM105812
50,4
105
72
10,5
RelayAux
Order Codes and Dimensions
PM103524
PM103526
Order Codes
Front Flush
connect. mounting
RelayAux Contacts Pick up Other Auxiliary RelayAux socket socket
Type no. time functions Supply Reference Screw Screw
Reference Reference
24 Vdc REL91260
30 Vdc REL91261
• Diode in paralell Low 48 Vdc REL91262
with the coil Burden 110 Vdc REL91263
Fast trip and 4 • Electrical reset
< 10 ms 125 Vdc REL91264 REL91350 REL91359
lockout relay changeover • Manual reset
• Mechanical 220 Vdc REL91265
contact position 110 Vdc REL91273
High
125 Vdc REL91274
Burden
220 Vdc REL91275
(1 ) DIN rail according to EN50022, DIN46277/3
(2) Minimum distance between sockets will depend on type of relay and sockets. Please request sockets User Manual for more detailed information
MV DISTRIBUTION & GRID AUTOMATION // PROTECTION RELAYS schneider-electric.com | 21
RelayAux
Order Codes and Dimensions
42,5
DM105817
DM105820
DM105813
50,4
105
96,6
10,5
RelayAux
Order Codes and Dimensions
PM103525
PM103527
Order Codes
Front Flush
connect. mounting
RelayAux Contacts Pick up Other Auxiliary RelayAux socket socket
Type no. time functions Supply Reference Screw Screw
Reference Reference
24 Vdc REL91280
30 Vdc REL91281
• Diode in paralell Low 48 Vdc REL91282
with the coil Burden 110 Vdc REL91283
Fast trip and 8 • Electrical reset
< 10 ms 125 Vdc REL91284 REL91351 REL91360
lockout relay changeover • Manual reset
• Mechanical 220 Vdc REL91285
contact position 110 Vdc REL91293
High
125 Vdc REL91294
Burden
220 Vdc REL91295
• Diode in paralell
with the coil
Fast trip and 8 High
< 810ms • Electrical reset 125 Vdc REL91289 REL91351 REL91358
lockout relay changeover Burden
• Mechanical
contact position
(1 ) DIN rail according to EN50022, DIN46277/3
(2) Minimum distance between sockets will depend on type of relay and sockets. Please request sockets User Manual for more detailed information
MV DISTRIBUTION & GRID AUTOMATION // PROTECTION RELAYS schneider-electric.com | 23
RelayAux
Order Codes and Dimensions
82,5
DM105818
DM105821
DM105814
50,4
105
100,5
10,5
RelayAux
Order Codes and Dimensions
PM103524
PM103526
Order Codes
Front Flush
connect. mounting
RelayAux Contacts Pick up Other Auxiliary RelayAux socket socket
Type no. time functions Supply Reference Screw Screw
Reference Reference
42,5
DM105815
DM105820
DM105813
50,4
105
72
10,5
RelayAux
Order Codes and Dimensions
PM103524
PM103526
Order Codes
Front Flush
connect. mounting
RelayAux Contacts Other Auxiliary RelayAux socket socket
Type no. functions Supply Reference Screw Screw
Reference Reference
24 Vdc REL91320
30 Vdc REL91321
Single phase Trip circuit 2 48 Vdc REL91322
• Front LED REL91350 REL91357
supervison relay changeover 110 Vdc REL91323
125 Vdc REL91324
220 Vdc REL91325
(1 ) DIN rail according to EN50022, DIN46277/3
(2) Minimum distance between sockets will depend on type of relay and sockets. Please request sockets User Manual for more detailed information
42,5
DM105817
DM105820
DM105813
50,4
105
96,6
10,5
RelayAux
Order Codes and Dimensions
PM103525
PM103527
Order Codes
Front Flush
connect. mounting
RelayAux Contacts Other Auxiliary RelayAux socket socket
Type no. functions Supply Reference Screw Screw
Reference Reference
24 Vdc REL91330
30 Vdc REL91331
Three phase Trip circuit
2 48 Vdc REL91332
supervison • Front LED REL91351 REL91358
changeover 110 Vdc REL91333
relay
125 Vdc REL91334
220 Vdc REL91335
(1 ) DIN rail according to EN50022, DIN46277/3
(2) Minimum distance between sockets will depend on type of relay and sockets. Please request sockets User Manual for more detailed information
DM105821
DM105814
82,5
50,4
105
96,6
10,5
RelayAux
Order Codes and Dimensions
PM103524
PM103526
Order Codes
Front Flush
connect. mounting
RelayAux Contacts Pick up Other Auxiliary RelayAux socket socket
Type no. time functions Supply Reference Screw Screw
Reference Reference
Auxiliary Supply 4
< 20 ms • Front LED 125 Vdc / Vac REL91344 REL91350 REL91357
Supervision relay changeover
DM105820
DM105813
42,5
50,4
105
72
10,5
RelayAux
Specific applications
GI134468446
(Instantaneous Trip relay and Trip and lockout relays)
Low burden configuration tripping relays are recommended when the initiating
contact is placed close to the tripping relay.
However, and in order to avoid unwanted trip relay operation due to pickup or
transients, particularly if the relay operating coil is connected to extensive wiring,
RelayAux tripping relays could be used with
a high burden configuration, complying with ESI 48-4 international standard, as
EB2 class relays.
These EB2 class relays are suitable for use in high security circuit breaker tripping
circuits, increasing their immunity to capacitance discharge currents.
For relays with rated voltage up to and including the 125 V, the relays will withstand,
without operating, a discharge into their operate circuits of a 10 capacitor
charged to 120% of the higher rated voltage for the relay.
For relays with rated voltage of 220 V, the relays will withstand, without operating,
a discharge into their operate circuits of a 10 capacitor charged to 100% of the
higher rated voltage for the relay, i.e. 242 V.
Specifications:
• ESI 48-4 EB1: 1983 Low Burden
• ESI 48-4 EB2: 1983 High Burden
RelayAux
Different loads configurations
24 Vdc voltage
0 ms 20 ms 40 ms
RelayAux type P(W) I(A) P(W) I(A) P(W) I(A)
1 contact
• Instantaneous Trip relays (REL 91200 to REL 91205)
500 20.83 370 15.42 250 10.42
• Fast Trip and Lockout relays
Vdc
(REL 91260 to REL 91265 a nd REL 91280 to REL 91285)
24
1 contact
• Instantaneous Fast Trip relays
450 18.75 300 12.50 210 8.75
(REL 91220 to REL 91225 a nd REL 91240 to REL 91245)
• Time-Lag relays (REL 91300 to REL 91305)
10 6 10 6
No. operations
No. operations
10 5 10 5
10 4 10 4
0 5 10 15 20 25 0 2 4 6 8 10 12
Current Current
Instantaneous Trip relays (REL 91200 to REL 91205) Instantaneous Fast Trip relays (REL 91220 to REL 91225
Fast Trip and Lockout relays (REL 91260 to REL 91265 and REL 91240 to REL 91245)
and REL 91280 to REL 91285) Time-Lag relays (REL 91300 to REL 91305)
MV DISTRIBUTION & GRID AUTOMATION // PROTECTION RELAYS schneider-electric.com | 30
RelayAux
Different loads configurations
No. operations
No. operations
10 6 10 6
10 5 10 5
10 4 10 4
0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7
Current Current
Instantaneous Trip relays (REL 91200 to REL 91205) Instantaneous Fast Trip relays (REL 91220 to REL 91225
Fast Trip and Lockout relays (REL 91260 to REL 91265 and REL 91240 to REL 91245)
and REL 91280 to REL 91285) Time-Lag relays (REL 91300 to REL 91305)
1 contact 1 contact
2 contacts 2 contacts
MV DISTRIBUTION & GRID AUTOMATION // PROTECTION RELAYS schneider-electric.com | 31
RelayAux
Different loads configurations
No. operations
No. operations
10 6 10 6
10 5 10 5
10 4 10 4
0 1 2 3 4 5 6 7 8 9 10 0 0,5 1 1, 5 2 2, 5 3 3, 5 4
Current Current
Instantaneous Trip relays (REL 91200 to REL 91205) Instantaneous Fast Trip relays (REL 91220 to REL 91225
Fast Trip and Lockout relays (REL 91260 to REL 91265 and and REL 91240 to REL 91245)
REL 91280 to REL 91285) Time-Lag relays (REL 91300 to REL 91305)
1 contact 1 contact
2 contacts 2 contacts
MV DISTRIBUTION & GRID AUTOMATION // PROTECTION RELAYS schneider-electric.com | 32
RelayAux
Different loads configurations
No. operations
No. operations
10 6 10 6
10 5 10 5
10 4 10 4
0,00 0,20 0 ,4 0 0 ,6 0 0,80 1,00 1 ,20 1,40 1,60 0,00 0,10 0 ,2 0 0 ,3 0 0,40 0,50 0 ,60 0,70 0,80
Current Current
Instantaneous Trip relays (REL 91200 to REL 91205) Instantaneous Fast Trip relays (REL 91220 to REL 91225
Fast Trip and Lockout relays (REL 91260 to REL 91265 and REL 91240 to REL 91245)
and REL 91280 to REL 91285) Time-Lag relays (REL 91300 to REL 91305)
1 contact 1 contact
2 contacts 2 contacts
NRJED113433EN-022018 © 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.