0 ratings0% found this document useful (0 votes) 469 views38 pagesGenerator Connections
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
CHAPTER 4
Generator main connections
1 introduction
11 Evolution
2. Principles of isolated phase busbar operation and forces
oncountored
2.1 Principles
22 Forces
23 Votage rise
1 1PB syst
3. Designi
4 Forced cooling
4.1 Forced air coating
42 Liquid cooting
43, Weter cooling
5 System description
5.1 Line end
52. Neutral end
53. Tewotls
54. Deke connections
55. Excitanon busbars
56 Eanh ber
5 Setting out the specifi
7 Component parts of en IPB system
7.1. Conductor and enclosures
12 Equipment enclosures
73 Insulators
73.1, Post mnsulators
73.2. Foot insulators tincluding enclosure supports)
733. Disc bushings
734 Wat eeale
735. Beliows
7.4 Conductor and enclosure expansion joints
7. Floxble comectors
75. Floble laminae connectors
75.2 Biaed lenbie connectors
78. Painting
27 Conditioned aie
18 Voltage tranormers
2.9 Curent transformers
7.10 Environmental conditions
7.11. Ponable earth access covers
7.12 Viewing ports
7.13 Connection of the conductor to plent
7.14 Joints in the conductor
7.15. Onoad temperature measurement
718 VF cubicles
7.17 Access platforms
7.18. Structural stestnors
719 Nevtal earthing equipment
Site instalation
Quality assurance
8 Testing
8.1. Tests on component pars
8.1.1. Insulators and bushings
81.2 Busbar materiel
8.1.3. Transformers
8.1.4 Leading resistors
8.15 Capacitors
8.1.6 Switchgear and earthing switches
8.1.7 Compressed air sysiem
82 Tests on representative sections of IPB
83 Test levels
Ba Tests at site
8 Experience of testing
10 Gonerator voltage switchgear
11 Earthing
12 Esrthing for meintenance purposes
12.1 Primary son
122 Portable drain earns
12 Protection
14 Interlocking
15 Future trends
16 References
1 Introduction
The principal Function of the Main Connections Busbar
System is to connect the generator to its associated
generator transformer and, incidentally, to provide a
convenient means of connecting the Unit electrical
system to the Unit transformer, via a tee-off. It is
resent day practice, for reasons explained later, to use
an aluminium tube for each phase conductor (or
busbar), which is surrounded by a concentric enclosure
of the same material and similar conducting cross-
sectional area; each is effectively isolated from its
neighbour, hence the term isolated phase busbar (IPB).
British practice (1988) uses dry conditioned air at a
pressure slightly above atmospheric as the insulating
medium between the conductor and enclosure.
‘The conductor is supported at the centre of the en-
closure by insulators: these are equispaced and rigidly
287Generator main connections
Chapter 4
fixed around the circumference of the enclosure but
allow limited radial movement of the conductor. The
rating of the main connections installation is es-
tablished on the basis of temperature rise above a
specified ambient at maximum commercial load and
iis ability to withstand both three-phase short-circuit
and earth fault conditions anywhere on the generator
voltage system without damage. These requirements
introduce some complication in the system design in
order to achieve high integrity. Isolated phase busbars
have evolved over a number of years, having originally
been pioneered in the USA and further developed
in France before their introduction in the UK in the
mid-1960s. They represent 34% of the total cost of
the connected generator and transformers. A typical
installation is shown in Fig 4.1,
1.1. Evolution
There has been extensive development of generator
connection designs since their introduction because of
larger generating sets and the consequential increase
in load and fault currents. Clearly a cable connection
to the machine is simplest, but both current and
temperature limit their use to about 120 MW (assuming.
a generator terminal voltage of approximately 23 kV).
Consequently, for larger machines, three bare copper
conductors (one/phase) were introduced, supported
by single insulators at regular intervals and enclosed
within a common duct or enclosure (Fig 4.2 (a)
Aluminium gradually replaced copper for the conduc-
ws
cam SRE ty tuen
excren
cORMECTIONS gan
Pea / \
| SS
ANT INSE
sein
canes
“MDOLE
Fig. 4.1 Generator main connections —
288,
tor, primarily on economic grounds, once aluminium
welding techniques had improved. The duct or en-
closure only excluded gross pollution and prevented
physical contact, giving no protection against phase-
to-phase faults or the electromagnetic forces between
conductors. Strong magnetic fields from this arrange-
ment could cause overheating of external steelwork
adjacent to the busbars, increasing system losses.
As currents increased, phase barriers made of either
a metallic or insulating material were introduced 0
limit the consequences of phase-to-phase Mashover
(Fig 4.2 (b)). Further improvement was achieved by
the use of phase segregation, using a continuous me-
tallic fabricated-aluminium enclosure and barrier, the
barrier being integral with the enclosure (Fig 4.2 (0).
Whilst phase segregation offered an improved design
compared with the original common enclosure, it still
had a number of weaknesses. Phase-to-phase faults
were still possible because adjacent phase conductors
share a common barrier. Complicated circulating cur-
rents in the enclosure produced forces between conduc-
tor and enclosure because no attempt had been made
to isolate the busbars magnetically, and the assembly
generally became large and exacting to construct. Such
designs were used for generators up to S00 MW before
new designs were introduced to deal with the short-
comings of phase segregation. These are insulated by
enclosing each phase in its own conducting metal tube
separate from its neighbours; hence the name ‘isolated
phase busbars'. In an installation of this type, eddy
currents are induced in the enclosure, or sheath, due
TaanSeORNER
sagTuns
vt TRANSFORMER rile
cusica | commétthion
7 cenenaton ENCLESUMES
vg ase TRANSEORER
chencrioa
‘conte
general arrangement of a typical installationPrinciples of isolated phase busbar operation and forces encountered
- [ree
eaten
Zz
Hopedale
Fic, 4.2 Segregated and non-segregated busbars
to the conductor current, and this to some extent shields
the forces between the conductors by modifying the
ficld around the conductor. There are, however, still
substantial magnetic fields outside the enclosure, which
produce forces between phases. These are reduced con-
siderably if the extreme ends of each phase enclosure
are bonded together, thereby allowing a balanced cur-
sent flow in the enclosures of all three phases, This
system is known as an ‘electrically-continuous IPB with
short-circuit’ (see Fig 4.3). Each phase enclosure is
made electrically continuous throughout its length and
all theee are connected together at both ends of the run
This distinguishes it from other systems, namely the
insulated type (where the enclosure is not continuous
but includes non-conducting sections) of the continuous
ype with saturable impedance, where the continuous
Phase enclosures are connected together at the ends of
‘ie run through small saturable reactors which limit
‘he induced longitudinal currents to a design value. The
last-named appears attractive because the reactor limits
the enclosure circulating currents during normal opera-
‘ion, thereby reducing the enclosure losses, and during
————_
fault conditions the reactor saturates, reducing its im.
pedance to circulating currents and allowing greater
enclosure current to flow. As will be explained later,
this enclosure current reduces the forces between con-
ductors during fault conditions. However, in practice,
the reactors tended to burn out, so now only the elec-
trically-continuous IPB with short-circuit is considered
in the UK and elsewhere. These, by virtue of the en-
closure circulating currents, limit forces between phase
‘conductors to approximately 10% of those that would
exist without the enclosure, :
The enclosure system is earthed at one point only
and is insulated from earth along its length by sup-
porting it on insulated foot mountings, thereby giving
control over the path followed by any fault current in
the enclosure. Clearly the main connections have now
become a system in their own right and to control the
circulating currents, as described, the enclosures must
bbe isolated from all iterns of plant to which the conduc-
tors are connected. Enclosures are therefore connected
to auxiliary plant via rubber bellows which maintain
the physical protection of the conductor but isolate
the enclosures electrically from the plant, The bonding
or short-circuiting of the enclosures is done as close
to the end of their run as possible. The external mag:
netic fields produced by the conductor currents can link
with conducting loops in the adjacent steelwork, pro-
ducing circulating currents and heat. This is a problem
to be considered by the designer since excessive heat,
in addition to being an unnecessary system loss, can
‘cause unacceptable expansion and can be a hazard to
personnel if the steelwork is touched.
Machines of 660 MW are now used extensively in
the UK and an IPB installation of the type described
provides an adequate main connections design which
can be naturally cooled and is of manageable size. This
probably represents the limit of naturally cooled de-
signs and any significant inctease in machine rating
will mean that forced-cooled designs will have to be
considered. The components of one phase of such a
system are shown diagrammatically in Fig 4.4
2. Principles of isolated phase busbar
operation and forces encountered
2.1. Principles
Consider, using simple analysis, how the magnetic
fields may be reduced, When a conductor carries an
alternating current, it produces an external concentric
alternating magnetic field, the direction of which is
determined by application of the ‘corkscrew’ rule. If
another conductor runs parallel to it, then an EMF is
induced in it, given by © = ~(d/dt), where @ is that
proportion of the flux linking the two conductors.
‘The negative sign indicates that it tries to oppose the
force which created it.
289Generator main connections
Chapter 4
ono Ean
Fic. 4.3 Phase isolated busbar — continuous sheath
For a length of isolated phase busbar, the voltage
be induced in an elemental section of non-continuous
sheath (say, 5A and 6B in Fig 4,5 (a)) due to the cur-
rent flowing in its associated conductor will be the
same magnitude for all elements on the circumference
of the sheath at any point along its length. It follows,
therefore, that one phase in isolation can have no
current flow in the sheath, since the voltages at all
points are equal.
If next, the condition in Fig 4.5 (b) is considered,
the voltage ¢ induced in an elemental section of non-
continuous sheath due to the current flowing in an ad-
javent conductor will be of different magnitude for
‘cach position around the periphery (say, 5C and 6D),
since each element cuts a different proportion of flux
from that conductor. Therefore, unequal voltages are
available to cause current to flow in the sheath as shown,
in Fig 4,6 (a). This sheath current, which for the ele-
‘mental circuit shown in Fig 4.6 (a) can be considered as
a simple ‘go’ and ‘return’ circuit, will set up an electro-
magnetic field whose direction can be determined by
application of the corkscrew rule. This will give rise 10
a reduction of field within the enclosure but a reinforce-
ment of the field outside as shown in Fig 4.6 (b). Thus
there is a reduction of forces between the conductors
and an increase in forces exerted on the enclosure. The
enclosure will therefore need substantial supports.
‘The currents circulating in each sheath caused by
the proximity effects of adjacent conductor systems
are termed ‘eddy currents’. Formulae for determining
these currents and their associated losses have been
proposed by H. B. Dwight in 1923 and F, W. Carter
290
in 1927. In the paper by Carter [1], the eddy current
was determined by considering the fixed distribution
of conductor currents but taking into account the
magnetic field set up by the induced eddy current in
the sheath itself, This first order eddy current was
then determined for neighbouring sheaths and these
were used as a fixed distribution to obtain second and
further subsidiary eddy currents in the original sheath
The process may be repeated to any degree of approxi-
mation to obtain a total eddy current. In Dr Carter's
day, the problem did not merit meticulous calculation
and the treatment was therefore simplified by consider-
ing only the first order eddy current to produce results
in a convenient form for hand calculation. Working
independently, Dr Dwight tackled a number of proxi-
mity effect problems and in 1923 published a first
order eddy current solution [2] for sheath eddy loss
which is identical to the Carter solution. Later, in 1964,
the analysis was extended to determine the subsidiary
eddy currents for the particular case of a single-phase
circuit and also a three-phase flat grouping.
Since the non-continuous type of IPB is not used
by the CEGB, the theory is not developed here, but
the reader may deduce the necessary formulae from
papers [1 and 2].
Now consider the continuous type of IPB. If the
sheaths of all three phases are electrically connected
at each end of the IPB run, an external path is pro.
vided which allows the sheath currents to flow in the
manner shown in Fig 4.3. The phase conductors and
the enclosures are comparable to the primary and
secondary turns of a short-circuited transformer. ThePrinciples of isolated phase busbar operation and forces encountered
ontisna
aMOsSNMEL,
—
420 1808)
swva wn
UOLONONOD
21¥95 OL NYE ON
‘DNS 510
muomaais
Snrodghs
4004
— | =
wargame |
nna
a
Vs |
avis woxonando
anna Nien
wOLWeaNgo = ]
fi}
AMor NOSSNVeRS L
wOranoNS NWA |
I
YOLVINSM —-3UNSOTONS —_gmMOTIBE
Son
Na worveata9 ona wanuossnves
291Generator main connections
Chapter 4
{a) tna.ced votages an enciosure cue
tos own congue
. e e
.
. ° . ®
. .
-———_:—4
(0) aac voltages in an enclosure ve
foram agjaceat conduct
Fic, 4.5 Induced voltages in an enclosure
[at Enon tay cents a pase ses busbar
magnetic field produced by the primary conductor
induces a current of opposite direction in the secondary
turn, The magnitude of the circulating sheath current
is almost equal to the conductor current, depending
con the resistance and reactance of the enclosure cir
cuit, and is in antiphase to the conductor current. The
sheath current usually amounts to about 90% of the
conductor current.
The circulating sheath current creates its own
surrounding magnetic field which must be in antiphase
to that produced by the conductor, thus the magnetic
field still exists within the enclosure but is cancelled
outside it (see Fig 4.6 (0). Since the enclosure has
resistance, the resultant external magnetic field around
each conductor is about 10% of that which would
occur if there was no metallic sheath
Since the external magnetic field has been reduced,
it follows that the forces between conductors are also
reduced by a similar proportion, as will be the forces
‘between enclosures that exist due to the current flowing
in them,
However, end effects occur where the conductor is
connected to its associated piece of plant and is, for
practical reasons, unshielded. Therefore magnetic fields
at these points are much stronger and forces grcater.
For further analysis, the reader is referred to a paper
by Skeats and Swerdlow [3].
2.2 Forces
The forces caused by short-circuit and earth fault
currents are very complex. Neglecting decrements, a
totally-offset short-circuit current can be represented
Fic, 4.6 Radial current flows due to current in an adjacent conductor
292Principles of isolated phase busbar operation and forces encountered
SPE !}
(ty Patton nus encase fora apy anata’ cru
(Fa cacotatonacomiyous ano arangrent
Fig. 4.6 (cond) Radial current flows due to current in an adjacent conductor
by the expression = I (1 ~ cos at). Consider a
parallel adjacent conductor returning the same cur
rent, The magnetic field emitted therefrom would be
B= By (I~ cos ut)
From Ampere’s Law, the electromagnetic force
between them is
= BI, where fis the length of conductor, therefore,
F = Bolo (1 — cos wt)?
Expansion of the expression (1 — cos ut)? gives
= 2cos wt + Zcos 2ut}, i.e., the force is composed
oF steady, power frequency and second-harmonic com-
ponents. These three components of force are each
reduced by a different shielding factor. For a detailed
explanation of these shielding factors, the reader is
referred to the paper by Wilson and Mankoff [4];
however, the theoretical treatment of these effects is
far from conclusive.
Taking into account current decrement, there is a
reduction with time of each of the electromagnetic
force components, each component having a different
decrement rate. The forces produced differ greatly,
depending on whether the fault is three-phase or single-
phase, the three-phase fault being more onerous,
In principle, the short-cireuit electromagnetic forces
arise from the combined action of the various forces
both between the phases and between the conductor
and sheath of the same phase. However, as previously
explained, for a continuous IPB the external magnetic
fields and the resulting forces between conductors are
293Generator main connections
Chapter 4
substantially reduced, compared with an unbonded
system, Additionally, for a continuous 1PB, the forces
between phases are much smaller than those which
occur between each conductor and its own sheath,
The magnetic field which exists inside the sheath
‘on a continuous IPB system (as shown in Fig 4.6 (€)),
produces a force between the conductor and the en-
closure. The force on the enclosure results in the
vonductor being centralised along a magnetic neutral
ine. In a suitably designed IPB system, the neutral
line is coincident with the axis of the enclosure, thereby
Virtually eliminating bending stresses caused by short-
circuit currents. The conductor supports are designed
{0 allow for this slight movement as the conductor takes
up its position on the neutral line. The force on the
sheath is a repulsion or bursting force which can be
represented as internal pressure on the sheath.
The resultant mechanical stresses developed within
the installation also depend upon the mechanical
frequency response of the structure and will be exacer-
bated by any resonance that may exist
The foregoing text has attempted to show that the
presence of the sheath in fact reduces forces and to
sive an awareness of the factors involved: it has not
attempted a mathematical prediction of the forces
which occur during a short-circuit. Whilst such force
calculations may be attempted for siraight sections
of busbar, they are much more difficult for bends
and tee-offs, At these positions the sheath currents vary
around the periphery and there is not the benefit
of complete mutual compensation of magnetic fields
irom the conductor and enclosure. Thus, immediately
adjacent to bends, very high short-circuit forces exist
which tend to straighten out the conductor. There are
also higher stray fields which may heat up adjacent
sicelwork. The IPB structural support system must
therefore be strengthened at bends and other places
where the configuration changes.
Mathematical analysis of currents, fields and forces
within an IPB system have been attempted, but a main
connections design by calculation is not deemed ac-
ceptable by the CEGB, for no mathematical method
is available that can be used with total confidence.
i should be recognised that whilst during normal
‘operating conditions the magnetic field outside the
enclosure is practically nil; during fault conditions the
field is the difference between the components on the
conductor and enclosure which, since there are different
time elements involved, is very difficult to determine
Consequently, the adequacy of the design is ultimately
demonstrated by testing, a5 discussed further in Section
8 of this chapter
2.3 Voltage rise
Consider the voltage rise of an electrically-discontinuous
IPB enclosure under fault conditions. Since there is
no current flow along the whole length of the sheath
298
installation, large voltages build up across the breaks,
tis, therefore, generally necessary to limit the distance
between the breaks to a less than desirable length in
order to keep these voltages to an acceptable level. With
electrically-continuous enclosures, however, the voltage
is dissipated in IR drop along the enclosure length as
it is generated. Enclosure voltages are consequently
held at completely harmless values, even during maxi-
mum fault conditions. A typical voltage induced per
metre length of continuous enclosure is 3 mV per 1000
A of conductor current.
3 Designing an IPB system
In designing an installation, the factors to be consi:
dered include materials, conductor and enclosure di
mensions required for specified maximum temperature
rises, mechanical strength and structural. steelwork
requirements. Up until now only naturally cooled s
tems have been assumed and the predominating factor
determining the cross-sectional area and configuration
of the conductor for the main connections of a nat
urally air-cooled busbar is the permissible temperature
rise, A tubular conductor has a low skin effect ratio,
described later in this section, which helps keep down
the AC resistance and hence losses. An adequate cross-
sectional area must be provided so as to remain within
temperature confines proven by experience and not
exceeding the temperature limits specified in BS159,
i.e., @ maximum conductor temperature of 90°C. The
largest full-load current in the CEGB at the time of
writing is 20.1 kA, but this will obviously increase as
larger machines are developed. The higher ambient
temperatures overseas give rise to lower temperature
margins for export designs.
Selection of the most suitable material for IPB
construction is generally straightforward, the choice
being between copper and aluminium.
At present an unusual situation exists, whereby cop
per and aluminium are similar in price (usually copper
is much more expensive), but aluminium is still the
cheaper overall. Copper has approximately three times
the weight, but 60% of the resistivity of aluminium,
Since aluminium is the poorer conductor, more ma-
terial is required but, because of skin effect, there
is a practical limit to the advantage gained by increas-
ing material thickness. Consequently it is necessary to
increase the diameter which has the advantage of
increasing the surface area and improving heat dis-
sipation. Aluminium, being much lighter in weight, is
easier to handle than copper: this, together with the
development of modern aluminium-welding techniques,
makes fabrication in aluminium much cheaper than
in copper.
The starting point for the designer is therefore
to determine the dimensions of the conductor and
enclosure appropriate to the specified operating con-
ditions. For the purpose of this exercise, assume the‘normal cylindrical conductor and enclosure configura-
sen Erom experience, an initial conductor diameter
sed thickness is selected. [tis then necessary to check
dhe resultant heat generated in the conductor, which
s given by
Wo = ER. an
“where Wy = heat generated per unit length, W/m
|= rated RMS conductor current, A
Re = AC resistance of the conductor appro-
priate 10 the temperature of the con-
ductor and the supply frequency, 2/m
i. has to take account of skin effect. When AC cur-
rent is passed down @ conductor, the current tends
fo concentrate on the outer surface, The higher the
applied frequency, the thinner is the effective conduc-
ting band. The AC resistance Rac is higher than the
DC resistance Rae? Rae/Rae is termed the skin effect
ratio, a full study of which was made by Dwight [5].
‘An extract of one of the curves produced by Dwight
for a circular tube is shown in Fig 4.7. It is suitable
for aluminum or copper conductors and may be used
for all temperatures found in the operational range
of the main connections.
The DC resistance is relatively straightforward to
waleulate.
‘At 20°C, for a large diameter conductor with a
thin wall section, it may be closely approximated using
the expression
Ra = o/m
7D
42)
where @ = resistivity of the material at 20°C, Om
D = conductor mean diameter, m
1 = conductor wall thickness, m
For a conductor operating at a temperature other than
20°C, the resistance becomes:
Rasa = Racy (1 + a2 @-20) (4.3)
where a2 = temperature resistance coefficient at
20°C
6 = temperature, °C
Having calculated the DC resistance and knowing the
ratio 1/D, the corresponding effective AC resistance
van be determined from Fig 4.7 for the conductor
dimension selected. From this, the loss per unit length
'y calculated, using Equation (4.1),
Next, consider the heat generated in the enclosure
due to the enclosure circulating currents. The loss in
cach phase per metre length is:
Ww, =
IER, watts 44)
Designing an IPB system
Where Ig is the enclosure current, Re is the effective
enclosure AC resistance per metre and is calculated
from the DC resistance in @ method similar to that
above for the conductor
Development of a formula for calculating the enclo-
sure current is complicated by several factors, includ,
ing the impedance of the bonding bars, the skin effect
and the proximity of structural steel or other conduct
and magnetic material, as shown by Niemoller [6]
The reader is referred to the IEFE paper (7} for
the calculation of IPB losses.
Type testing has shown that it is not unreasonable
to assume that the ratio of enclosure current to con-
ductor current (1) to be about 0.95 for an electrically
continuous IPB system, i.e.,
W. = 0.9PR,
In establishing the working temperature, it is assumed
that for a natural air-cooled system, almost all the
losses (We + Wz) have to be dissipated by radiation
and convection from the external surface of the
enclosure. Clearly the heat that must be dissipated is
that quantity which would cause the maximum per-
mitted operating temperature to be exceeded. An ap-
proximate expression for natural convection from the
outside surfaces of a busbar enclosure, indoors but
not in a compartment, at sea level and normal pres-
sure, based on Dwight e¢ al {8} is:
Weon = 1.360!28/D925 W/m?
where Weon = loss dissipated by convection from the
enclosure, W/m?
© = average temperature rise of the hous-
ing, °C
D = diameter of enclosure, m
and the energy lost by radiation is given by the Stefan.
Boltzmann expression:
567 gg
Wreg = —— ke[Th — Ta] Ae W/m?
108
where Wrag = loss dissipated by radiation from
enclosure, W/m?
e coefficient of emissivity of the enclo.
sure surface
Tr = average temperature of enclosure
surface, K
Ty. = ambient temperature, K
Ac cffective radiation surface per metre of
enclosure length, m?
k factor depending on position of phase
as described below
295Generator main connections
Chapter 4
sam errecr nario Se
Fic. 4.7 Skin effect ratio for rods and tubes
Since the radiation from the outer phases will differ
from the cenire phase, the following factors should be
included [9]
360 - da
For the centre phase k = ———— a,
360
360 — 2a
and for the outer phase k = ———— A,
360
where @ = sin~! (R/S)
R = external enclosure
diameter, m
S = phasing spacing, m
‘Total heat loss from the busbar system in W/m run can.
then be established from (Weon + Weaa)®D.
298
Factors not included in the equations which will
affect heat dissipation both by convection and radia-
tion from the enclosure are physical arrangements,
neighbouring structures and surface finish, It must be
borne in mind that hot spots can occur, particularly
at the ends of busbar runs where connections are
made to auxiliary plant. This occurs because of poor
current sharing in unsymmetrical current-carrying con.
nections, as will be discussed later, or from the con
centration of circulating currents, Experience suggests,
that the conduction of heat from associated plant,
namely the generator itself and the transformer bush
ings into the connections, should also be considered
Summarising, (a) the heat generated (W/m run) in
the conductor and enclosure withForced cooling
the dimensions initially selected
from experience can be calculated,
ie, We + We
(0) allowing for specified temperature
rises of conductor above enclosure
and of enclosure above ambient,
the quantity of heat dissipated per
metre length by the selected
installation can be caleulated, i.e.,
(Woon + Wead)rD
Then
‘The values of (a) and (b) are compared and, if they
are not close the dimensions are revised and the pro-
cess repeated.
In the CEGB, the temperatures specified at present
‘# Conductor maximum temperature 90°C.
© Enclosure maximum temperature 65°C.
fe internal air maximum temperature 70°C,
© Ambient temperature 40°C.
Having established the dimensions of the IPB system
from load current thermal conditions, the designer
must then consider fault conditions.
Generally speaking, for 2 main run of IPB, the
busbars are so large for continuous current-carrying
requirements that the thermal requirements for short-
cireuit conditions are more than catered for. How-
exer, for a unit transformer or other tee-off, the
continuous current rating is small but the fault current
rating is very high indeed. Here, the fault current
fied may influence the busbar dimensions that
‘equired because of its thermal effects, therefore
requiring repeat calculations to determine temperature
rises during fault
However, the major design concern arising from
fault considerations is mechanical strength. The de-
sisnee must provide a suitable support arrangement for
the conductor and enclosure to ensure that the final
structure is of adequate strength to withstand the forces
thal are exerted on the system during fault conditions.
The forces have been briefly explained in Section 2
ol this chapter. For the conductor, the designer is
looking 10 provide sufficient support to:
spe
* Prevent deflection between supports due to forces
beiween conductors and between conductor and
enclosures during fault
+ Prevent damage due to ‘straightening out’ forces
hich occur at bends during fault
* Prevent damage due to ‘knife switch’ forces at the
tee-off positions, again due to the conductor at-
fempting to straighten along the line of maximum
fault current,
‘An adequate structural support is required for the
‘enclosure to withstand the resultant static and dynamic
loadings that the system will experience during fault.
The present view of the CEGB is that there is no
mathematical approach to solving these problems that
can be used with confidence. The designer may from his
‘own experience use simple force calculations as a
starting point. Reference [10] is such a suitable starting
point. Ultimately, however, before a design can be
considered acceptable, a full set of short-circuit and
carth Fault type-test evidence is required 10 substantiate
the design, as identified in Section 8 of this chapter.
Finally, the stray magnetic fields surrounding the
main connections, as already described, can give rise
to inductive heating of adjacent steelwork. For an IPB
system, there is unlikely to be any problem with systems
carrying less than 8000 A. However, above this, care
should be exercised. It is not only structural steel-
work which may cause problems, but also piping and
pipe hangers, gas and air ducts as well as stairs and
handrails. Heating of such components could ignite
adjacent flammable material, be a danger to personnel,
cause structural stresses due to restrained expansion,
and of course, incur additional running costs due to
the losses.
‘Analysis of this problem is most difficult and use
is made of existing heat run tests. If the reader wishes
to pursue the problem, an approach is described by
‘Swerdlow and Buchta [11] and there are some guidelines
regarding spacing of adjacent steelwork given in Section
7.18 of this chapter.
Various methods are available to reduce the
temperature rise of structural members, the use of
shielding plates being favoured by the CEGB,
4 Forced cooling
The optimum design of an IPB installation is deter-
mined by considering the capital cost, plus the cost
of generating the associated losses. In order to satisfy
the temperature balance requirements described in
Section 3 of this chapter, naturally-cooled connection
systems greater than 800 MVA, though practical, would
require excessive space and consequently their cost
would be high. For connections rated above 800 MVA,
unless a much higher generator voltage is thought
worthwhile, consideration must be given to forced
cooling of the connections by some method. With
reference to Fig 4.1, which shows a typical natural air
cooled connection installation, it can be seen that the
tee-off connectors from the main busbar carry a
relatively low current, i.e., the high current flow is
from the generator to the generator transformer. In
considering the cross-sectional area of these compo-
nents, it is clear that only the main run can justify
forced cooling, the tee-off design being instead deter-
‘mined by the maximum fault current which could flow
in it, Though it is unlikely that the use of forced
297Generator main connections
Chapter 4
cooling below 8 kA would be economic, the limit for
natural cooting, depending upon generator voltage,
is reached at currents of 25-30 KA and, for currents
in excess of this, the busbars are normally forced-
cooled.
Therefore, if forced cooling is to be considered,
the heat balance approach taken in Section 3 of this
chapter witl have to include a calculation of the heat
removed by forced cooling. Such calculations will de-
pend very much on the design of the installation.
The obvious choice of cooling medium is either air
or water. In considering the economic case for forced
cooling, the saving of material is offset by a possible
inerease in system losses, the additional cost of cool-
ing equipment, routine inspection and maintenance of
motors, fans, pumps, pipework, heat exchangers, etc.
The value assigned to the losses/kW generated will
‘obviously influence whether to force-cool the system
if, in fact, temperature rise has not itself dictated its
Once reliance is placed on forced cooling, any failure
which might occur on the coolant plant would neces-
silate a consequential reduction in generated output,
So it i§ desirable to aim for a high naturally-cooled
current-carrying capacity, i.e., with the cooling plant
‘out of commission, It is also necessary 10 specify the
operating time at full4oad current with the cooling
plant shut down, The more common forced cooling
systems are described below, though work is being
carried out on the use of some of the newer insulating
materials, for example, SF¢ gas.
4.1 Forced air cooling
A typical forced air system would comprise fans, heat
exchangers, dampers and air filters arranged such that
there is one set of equipment for each machine unit.
Cooled air is blown from the heat exchanger, usually
4 finned water-cooled coil, down the busbar run
between the enclosure and the conductor and returned
to the heat exchanger, thereby forming a closed cir-
cuit. Such schemes are used extensively in the USA
and, for a normal installation, air may enter the centre
phase of the connection system, travel along it and
return back through the outer two phases, sufficient
air volume being used to ensure that the final air
temperature does not exceed the maximum allowable
touch-temperature of the enclosure. The cooling equip:
ment may be located at any point along the con-
nections system but the most economical position is
midway between the generator and its transformer
Since the cooling air passes through the entire system,
splitting the total cooling air volume in the centre
phase and forcing it in opposite directions results in
less overall system resistance, therefore requiring less
fan power. The air must be cleaned and dried to reduce
the risk of faults and all the associated equipment
Including the fans, must be duplicated to ensure
availability (2 x 100% or 3 x 50%).
298
In addition, if the cooling air leaves one phase and
enters another, then de-ionisation plant is required
to prevent ionised gases produced by a system fault
entering other phases, thereby extending its severity,
Air has the obvious advantage of being cheap and
plentiful but because it has a relatively low specific
heat and density, large quantities are required to re-
move the heat and the fan requirement is proportional
to the cube of the flow rate. This disadvantage can
be overcome if liquid cooling of the conductor is
considered
The rating for a forced air cooled installation with
cooling plant shut down would probably be in the
region of 1 hour and the naturally cooled rating would
be approximately 60% of full Joad,
4.2. Liquid cooling
It may be considered that the obvious choice is to
extend the transformer cooling oil into the main con-
nections conductor, as oil has low specific heat and
density compared with water. However, the fire risk
associated with oil within the power station buildings
is unacceptable. It is also considered unacceptable 10
risk the integrity of the transformer insulation by
involving any other plant in the oil circuits — even
delia boxes (see Section 5.4 of this chapter), Demin-
eralised water has been used as the cooling medium
in the generator stator for many years and the tech-
niques have been well proven. It would therefore be
possible to extend this system to include the generator
main connections or, alternatively, to install a separate
water cooling system.
4.3 Water cooling
Since water has a better thermal conductivity and
specific heat than air, the temperature rise of a main
connections installation of this type can be more easily
controlled by adjustment of the coolant flow than in
an air cooled system. The material cross-sectional area
provided in these circumstances is then based on con-
sideration of the capitalised cost of the conductor
losses (see Chapter 3, Section 2.1.5) against the ca-
pital cost of the conductor itself, together with the
mechanical strength requirements for fault conditions
Clearly the water in the conductor is at the same
potential as the conductor itself, so some form of
potential dropping device is required between the con-
ductor and remainder of the hydraulic circuit, which
should be at earth potential. This device is a resist-
ance column consisting of a long pliable connector of
non-conducting material having a small cross-sectional
area, thereby providing a high-resistance path to low
currents. The cooling water then flows within a closed-
cycle cooling system with a heat exchanger, itself in-
directly cooled by water. The cooling system may be
incorporated in the stator cooling circuit, if the heatSystem description
venerated in the connections system is small relative
generated eed trom the ator windings. I ill
‘Ren be found most convenient to connect the hy-
‘pete cooling circuits in series. The conductor op-
cring temperature should then be only slightly above
She cooling water temperature
“sins between sections of conductor are welded, the
elds apart trom requiring the necessary mechanical
Mfenath, being watertight, Where conductors are con-
‘ed to the plant, braided flexible connectors are
(aed to allow for expansion and provide vibrati
Jmmunity from chat plant, the terminal palms them-
elves being within the connections, bridged by the
‘water cooling circuit, the bridge bcing of non-conduct-
Jne material. Heat conduction to the conductor helps
keep down the temperature of the flexible connections.
'A water cooled system would have no short-time
full-load rating and a naturally cooled rating in the
event of loss of forced cooling, of approximately 20%.
“The major disadvantages of a water system, there-
fore, are the substantial reduction in unit output if
cooling is lost and the danger of an earth fault develop-
ing if a water leak occurs. The reliability of the water
‘als is therefore very important,
5 System description
A schematic drawing of a typical main connections
system is given in Fig 4.8.
NeviRa uve
‘The generator windings are star-connected. the star
point being formed outside the generator, so there are
two generator terminals for each phase. The output
of the generator is taken from the line end of the
phase windings, the star point being formed at the
neutral end of the windings. It is desirable, for ease
of making connections to the generator, to have these
two ends located as far apart as possible, their relative
positions being dependent on the generator manufac-
turer’s frame design,
The generator transformer is wound in delta/star
configuration, the LV side being the delta winding.
This transformer may consist of one three-phase tank
or three single-phase tanks. The delta connection of
the transformer can either be formed below oil or, as
is now more common, can be made part of the main
connections system to maintain phase isolation. An oil
delta is not nowadays favoured since it allows any
contaminated oil due to a fault in one phase to circulate
into the other phases.
Connections are taken from the main busbar to the
HV terminals of unit auxiliary transformers and the
system voltage three-phase earthing transformer (if
fitted), discussed in Section 11 of this chapter. This
connection, known as a tee-off from the main busbar,
again maintains phase isolation up to the bushings,
the transformers themselves generally being housed in
three-phase tanks.
There is a requirement to monitor voltage conditions
‘on the main connections system for various purposes,
genenaron
cogent Baeanen
okt
‘oENERATOR
PO
canta swoTones.
(1) oct on orprotecron cre
aeangronmen
Fig. 4.8 Generator main connections — simplified schematic
299Generator main connections
Chapter 4
including generator synchronising, tariff metering, in-
strumentation, automatic voltage regulation and protec-
tion schemes. There is also the requirement to monitor
current conditions, for example, for protection pur-
poses. The requirement to monitor voltage is met by
the connection of voltage transformers (see Section 7.8
of this chapter) onto the main connections via a fur-
ther tee-off similar to the auxiliary transformer tee-
Off described earlier. Up to four voltage transformers
per phase may be required, mounted within cubicles
which maintain the phase isolation of the system.
Current transformers (see Section 7.9 of this chapter)
are mounted in the main connections runs, in positions
dependent upon the protection scheme adopted.
Other equipment may be included in the main
connections system, such as connections to generator
excition plant, earthing devices and to the generator
circuit-breaker, These will be discussed later,
‘The various features of the main connections system,
are now described in greater detail,
5.1 Line end
‘The position on the generator of the line terminals de-
pends on the generator manufacturer but the two
obvious locations are either above or below the ma-
chine, Both positions have advantages and disadvan-
tages for the main connections system. In all eases,
consideration should be given to generator rotor re
moval without the necessity to dismantle any of the
main connections installation. Any support given to the
connections should be independent of the machine to
prevent the transmission of vibration.
Where the main connections leave the generator from
above, the overall height of the machine is obviously
increased. This may increase the height of the turbine
hall crane-rails, and hence the turbine hall itself, there-
by creating a cost penalty. Also, connections above
the machine and their support structures ean, if incor-
rectly designed, suffer fatigue due to vibration excited
by the generator.
If, however, the line connections are below the
generator, there are obvious obstructions which require
10 be negotiated, for example, the generator founda-
‘ions, generator/turbine auxiliary equipment, access
ways, ete, Clearance from such obstructions can dictate
‘whether the busbars lie side-by-side or in trefoil con
figuration, Other practical issues to be resolved at the
generator line-end terminals are heat dissipation due to
confined space, access for stator cooling pipework,
Prevention of water ingress and spacing of the line
terminals, which may be arranged on the generator in
an in-line or trefoil configuration. Where space is re-
stricted, it may be necessary to consider the use of
specially designed sections of busbar having reduced
conductor and sheath dimensions, a terminal box ar-
rangement with phase segregation, use of other than
circular cross-section busbars or a short water-cooled
300
section (sce Fig 4.9). In the case of a segregated ter-
minal box the phase barriers should be of the same
material as the box (probably aluminium) and earthed
to ensure that there is an earth plane between phases
which reduces the risk of phase to phase faults. Phase
to earth faults produce fault current which is restricted
by the neutral earthing equipment. However, there
always the possibility of an earth fault developing
into a phase to phase fault which causes much greater
damage; it is therefore preferable to use a phase iso-
lated system if possible.
Early design co-ordination at the interface connec
tion onto the machine is necessary to solve the pro-
blems associated with terminal spacing and ensure that
the specified impulse-withstand level can be achieved.
To allow for possible hydrogen leakage through the
generator terminals, a complete bushing-type seal should
bbe provided in the main connections run to limit the
volume into which hydrogen could possibly enter. This
volume at the generator should then be suitably ven-
tilted to ensure that approximately four air changes
per hour can take place within the enclosure to reduce
the risk of build-up of hydrogen in air, which could
form an explosive mixture.
5.2 Neutral end
The method of generator stator neutral earthing is
described in Section 11 of this chapter. An example of
stator neutral earthing is shown in Fig 4.10.
‘Again, depending on the machine manufacturer, the
generator neutrals can be situated on the top or the
bottom of the generator. It is obviously more straight-
forward if they are positioned below, as all the stator
neutral earthing equipment described can then be housed
within a single module supported on independent steel-
work adjacent to the neutral terminals. If the terminals
are located on the top of the machine, while the stat
connection can be made easily, vibration may be ex-
cessive if the stator neutral earthing transformer is
mounted on the machine frame or support and there-
fore it should be located away from the star bar.
Vibration would certainly prevent the resistor being
mounted on the machine. Either a cable connection
would be required (which is undesirable as it is vul-
nerable to damage) of, alternatively, a short section of
IPB could be used and the transformer located away
from the star bar. Equipment installed on the top of
the machine can raise the height of the turbine hall
with a consequential cost penalty. Due consideration
should be given to preventing ingress of water into
the neutral end equipment, since ventilation must be
provided for the resistor to dissipate the heat produced
during an earth fault.
5.3 Tee-offs
Tee-off connections ate used to connect auxiliary
transformers and voltage transformers to the generatorSystem description
Amcoo.en
wateR cooceo
Fic, 4.9 Specially designed busbar sections for use in space-restricted areas
voltage system. The power requirements of a voltage
transformer are minimal so for these tee-offs, but
not others, a reduction in current-carrying capacity is
acceptable, provided that a suitable fuse is mounted
immediately adjacent to the tee-off connection to deal
with faults. CEGB uses a 10 A fuse at this position.
Downstream of this fuse (a distance generally of the
order of a few metres between the main and the VT
subicle), the tee-off need only be designed to be me.
chanically sound, To ensure that an adequately strong
design is offered, the CEGB specify a continuous rating
of 300 A for this section.
Tee-off enclosures can be bonded into the main run
or isolated and treated as a separate section of IPB,
—_—
the choice being made by the designer and fault tested
as a system.
5.4 Delta connections
The connection of the delta on recent stations, e.g.
Littlebrook D and Heysham 2, is made by using air-
insulated IPB and, since the current flow in each delta
arm is less than the line current by a factor 1/~/3, the
dimensions can be reduced appropriately from that of
the main run, though the system highest voltage is the
same. To ensure that the correct phasor grouping
of the transformer is achieved, correct phase sequence
301Generator main connections
Chapter 4
(1) tocknion oF prorecrion ote
neurmiat caging
Wout
Fic. 4.10 Stator neutral earthing
of the LV and HV phases for the installed trans-
former winding terminals is essential (see Chapter 3,
Transformers}
5.5 Excitation busbars
Some generator designs use rotating excitation equip-
ment, whereas others use separately-located stationary
equipment. In the latter, the electrical connection be-
tween the exciter equipment and the machine is an
IPB system similar to that of the generator voltage
system, though obviously running at the much reduced
design voltage of 3.6 kV and maximum continuous
current rating of 5000 A (AC or DC) (1988), with con-
sequential reduction in size. Typically, the installation
would comprise AC and DC connections forming 2
system as shown in Fig 4.11, with a normal operating
voltage of below 650 V, connecting the main exciter,
he exciter rectifier cubicle, the field suppression switch,
and the generator slipring and brushgear enclosure.
5.6 Earth bar
The earth bar system is quite complicated since all
associated auxiliary equipment must be earthed in a
manner such that no circulating-current paths can
‘occur; a typical system is shown in Fig 4.12. For the
purpose of its design, it is assumed that the neutral
carihing equipment (see Section 11 of this chapter) has
been shorted-out due to a coincident fault and that
the earth fault current is unrestricted. The earth path
must be rated to carry the maximum earth fault cur-
Tent from any part of the connections system where
‘an earth fault could occur back to the generator. For
302
an installation which includes generator voltage switch
gear, an additional earth is incorporated on the system
to provide the earth when the switch is open. The
earth path must be of low resistance to prevent @ rise
in potential on any part of the system (during a fault}
above a level which could cause a danger to personnel
With the system operating normaily, the CEGB specify
this level as 55 V and, during fault conditions, 430 V
is specified as the maximum rise of earth potential
to comply with telecommunication directives within
the UK, However, if faults can be cleared within 200 ms
a voltage rise of 650 V is acceptable.
If no earth path were provided, the return earth
fault current would follow a random path (or paths)
of low resistance back to the machine. These routes
may be tortuous and not adequate to carry such large
currents. The provision of a designed earthing system
directs the flow of earth fault current along a pre
determined route, thereby containing all earth fault
currents within the main connections system. The earth
path comprises an earth bar of adequate cross-sectional
area connected to plant by flexible leads and held at
the potential of the station earth network. Since the
earth bar would provide the lowest resistance path
to earth fault currents, the earth bar redirects the fault
current away from the station earth system which, in
any case, would not normally be rated for such large
currents.
The earth bar is not screened by an enclosure; when
earth fault current flows, large external magnetic fields
are produced, so it is usual to position the bar some
distance from the main busbar installation 10 pre-
vent excessive forces being produced. The earth bar
has to negotiate many obstacles on its route, €.8-,
civil works, auxiliary plant, etc., so that it includesSystem description
ya an
A coeenaron excITER
Eeuaccnone||f | ac CoANEE TONS
eo = excren
sunbieSsion FESrTFER
‘sare | —_____ e088
Fig. 4.11 Exciter busbar arrangement
Neurpas — Gengaaton
TRINSEERIER | socy
‘ean
reatronen
Po 412 Sytem eating
‘many bends, It is essential that sound fixing is provided When testing a main connections design, it is usual
10 prevent the force produced by the fault current from to include the earth bar, thereby testing a complete
Suaightening out these bends. system.
203Generator main connections
Chapter 4
6 Setting out the specification
Having described a typical main connections installa-
tion in the previous sections, consideration is now
given to the design specification of that system, as-
suming natural air cooling. Section 7 of this chapter
will look at the component parts
‘The first consideration is the particular application
— the environment, voltage and current-carrying re-
quirements. AS standerd a design as possible should
be specified, so that testing need not be necessarily
repeated for each application, The parameters that
must be specified are:
‘© The maximum system voltage, frequency and power
factor.
‘¢ The output of the generator, and hence the line
current
© ‘The variation allowed on the above during abnormal
conditions.
© The fault contribution from the generator.
‘The fault contribution from the external grid
network
In a tee-off busbar, there is a combined fault infeed
from the generator and the external grid. This specifies
the maximum fault level of the system for which the
installation must be designed, including the earth bar.
‘The maximum system voltage dictates the impulse
level for which the system must be designed and the
consequential clearances between the conductor and
the enclosure, However, it should be remembered that
the impulse and switching overvoltages entering from
the HV side of the generator transformer are not
transferred according to the winding ratio of the trans-
former but rather to the ratio of the capacitances of
the HV and LV sides. Depending on the steepness
of the incoming wave, the percentage overvoltage on
the generator side may be higher than the HV side.
This overvoltage may be reduced by the capacitance
of the generator and the generator main connections,
Economics and workability dictate the choice of ma-
terial for the conductor and the enclosure; aluminium
's the most probable, bearing in mind that the electrical
resistance should be low but the inherent mechanical
strength adequate to withstand the forces produced
uring fault. The phase configuration, i.e., flat in-line
or trefoil, and probably the spacing, will be determined
by obstructions on the proposed route, The number of
bends should be kep! to a minimum and those selected
should be of a tested design.
The enclosure insulation level from earth must be
specified. This level must be high enough to allow for
degradation caused by dust during the periods between
cleaning. At present the CEGB specifies 3.6 kV.
The temperature rises permitted during maximum
continuous current flow are then specified which, for
304
CEGB installations, are as stated in Section 3 of this
chapter.
7 Component parts of an IPB system
7.1 Conductor and enclosures
‘These items have been dealt with in detail in che
preceding sections.
7.2 Equipment enclosures
At interfaces with plant, for example a transformer,
the physical enclosure of the conductor must include
access for maintenance purposes but still insulate the
enclosure system from the connected plant. Non-con-
ducting bellows, discussed later in this chapter, connect
the enclosure to, say, the transformer, the tank of
which is earthed separately. This equipment enclo-
sure may have viewing ports (see Section 7.12 of this
chapter) in order to inspect the flexible connections
1g up the conductor interface, and an access cover
to allow the application of a portable earth if neces-
sary (see Section 12.2 of this chapter). The enclosure
may be a bolted assembly, removable for maintenance
purposes, and using bonding strips to ensure that all
parts are earthed positively and that no reliance is put
on the bolted construction for earthing. To prevent cir-
culation currents occurring, larger access covers should
be insulated from the rest of the enclosure, except for
a single earth connection on each individual cover.
For the same reason, hinges should be bridged, using
a flexible connector. Designs should offer the facility
of taking a transformer out for maintenance, while
allowing the main connections to be re-energised safe-
ly. This latter requirement may be achieved by the
removal of links or a short section of conductor, and
the fitting of caps over the busbar ends in a manner
which maintains the insulation of the system.
7.3 Insulators
7:
These support the conductor within the enclosure to
‘maintain the air clearance needed for the highest sys-
tem voltage. They are made either of epoxy resin or of,
porcelain; if porcelain, it must be thoroughly vitrified,
so that the glaze is not depended upon for insulation.
The strength of the insulators should be such that
when they are supporting the maximum. short-circuit
loads, the factor of safety is not less than 2.5. The
number of supporting insulators at each point and the
spacing between them is confirmed by short-circuit
testing. Typical arrangements are shown in Fig 4.13.
Stresses due to expansion and contraction in any
part of the insulator and its fixings must not lead to
1 Post insulatorsComponent parts of an IPB sys.em
Fic. 4.13 Typical insulaior support arrangements
the development of defects. The fixings, which should
be non-magnetic, should be such as to allow movernent
of the conductor when centralising forces occur during
short-circuit. The post insilator is usually mounted on
plate which bolts externally onto a flange fitted to the
tnclosure, as shown in Fig 4.14, thereby permitting easy
removal of the insulator.
7.32. Foot insulators (including enclosure
supports)
‘These are plate-type insulators which insulate the
support side of the enclosure from the structural
steelwork. An insulation level of 3.6 kV is general-
ly specified for this device, which allows for some
dust build-up during the operation of the plant. The
support structure itself should allow relative movement
Yy INSULATOR BAS Pare
Fo, ASA typical
sulator support assembly
between it and the enclosure 10 accommodate thermal
expansion. Where supporting structures suffer exces-
sive vibration, installations may require anti-vibration
pads to be incorporated in the design, although the
CEGB does not generally use them. The design of the
connections mountings should be such that the natural
frequency of any part of the busbar structure and its
supporting metalwork does not fie between 130% of
the frequency of the applied electro-magnetic force,
.¢., static and dynamic loadings for the power fre-
‘quency specified should be taken into consideration.
7.3.3 Disc bushings
Disc bushing seals are fitted at the end of busbar runs
adjacent to plant housings to provide an airtight seal,
thereby preventing hydrogen from the generator, or
oil from the transformers, passing along the isolated
phase-runs in the event of leakage. The isolated phase-
tun is then fed with conditioned air, as discussed later
A bushing seal must also be provided in the VT tee-
off, allowing the on-load maintenance of the VTs
without affecting the conditioning air system. Careful
attention is given to the bushing profile 1o ensure that
moisture, which would reduce the creepage path of
the bushing, cannot be trapped in it
7.3.4 Wall seals
Wall seals are provided where the enclosure passes
through a wall (see Fig 4.15). The individual enclo-
sures are connected to the wall seal using the bellows
arrangement described in the next section. A similar
seal is fitted where the installation passes through a
floor
Also, to prevent transformer noise causing annoy-
ance in residential areas, the generator transformer
may be fitted with a noise enclosure. A wall seal will
then be required for the busbar to pass through that
enclosure,
7.38 Bellows
The bellows maintain the insulation of the main con-
nection enclosures from the connected plant (see Fig
305Generator main connections
Chapter 4
Fic. 4.15 An example of 2 wall seal
4.16). They allow relative movement due to expansion
and vibration, and cater, 10 a limited extent, for any
installation misfit due to the worst combination of
allowable tolerances. When bellows are installed on a
length of busbar at, for example, a conductor expansion
point, they must be bridged using flexible aluminium
BeLLows ASseUsLy
laminae, Alternatively, aluminium bellows may be used.
‘The bellows are usually of synthetic rubber, completely
weatherproof and airtight and must withstand at least
twice the design working pressure of the conditioning
air system within the enclosure. When bellows are
located outside buildings in direct sunlight, the material
must be chosen to ensure that degradation does not
occur.
7.4 Conductor and enclosure expansion
joints
Allowance for the expansion and contraction of the
conductor (Fig 4.17) and enclosure (Fig 4.18) is pro-
vided on the longer busbar runs. This typically com-
prises a ‘cage’ arrangement, where the expansion gap
is bridged by aluminium laminae, The connection must
have adequate current-carrying capacity and correct
current-sharing among the laminae is ensured by using
a symmetrical array of laminae.
7.5 Flexible connectors
Flexible connectors can be laminae or braid, the choice
depending on the type of relative movement of the parts
being connected. When removed, they provide isolation
of plant. The significant difference between them is
that laminae only allow relative movement in two
dimensions, whereas braid gives full three-dimensional
‘movement.
excxosuRe
Laeptinnaprene!
ee
eonsapeed eet
Fic, 4.16 A bellows assembly
306Component parts of an IPB system
Fic. 4.17 Main conductor expansion joint
Lauare assevaues
ra
UNE ESSEC
Fic. 4.18 Enclosure expansion joint — typical arrangement
7.8.1 Flexible laminae connectors
These are constructed from thin strips of aluminium
‘tid one above the other, with aluminium palms welded
on cach end (Fig 4.19), Suitable holes in the palm
allow the connector to be bolted to the conductor
palm. Their applications are limited to sections of
‘rain runs (for example, to allow the insertion of
CTs) at expansion joints, connections to generator
voltage switchgear, and earth connections to some
items of plant.
7.5.2 Braided flexible connectors
‘These are made up of tinned-copper braid or braids
(Fig 4.20) with ferrules fitted at each end which are
307Generator main connections
Chapter 4
Fic. 4.19 Construction of a Nexible laminae connector
imines Wa cases
Une SUPRSSE
SBE FE mnegest
couemessen
cowetessco
confacr Pinnie
Soneee
‘each
coupfesceo
Fen
voces
Fic. 4.20 Construction of a braided flexible connector
drilled to allow a bolted connection onto the termi-
nat palms of external plant. It is essential that the
ferrules are crimped omto the braid, since sweated
assemblies have been found to suffer from mechanical
creep problems, with failure resulting after a period
of time. Clearly, whilst the braids overcome the pro-
biem of relative movement of component parts of the
system, they introduced a dissimilar metal interface
when connected to the aluminium conductor palm.
308,
Ik has been found preferable to remove tinning from
the ferrule at the joint interface surface. Methods
of overcoming problems associated with dissimilar
metals are discussed later. Careful selection of the
braids is necessary to ensure that there is adequate
current-carrying capacity and that they are capable
of operating continuously at the maximum specified
temperature.
Consideration should be given to:fh of braid compared with the gap, to en-
The lenst!
Should be 28-35 mm free play).
number, size and position of the fixing holes
he Te crimped ferrule (which affects the clamping
on feare on the joint and hence its current-carrying
capability)
‘The ambient air temperature within the enclosure
7.6 Painting
‘The outside of the conductors and the inside of the
is geures are normally painted with matt black heat-
vraistant paint 0 improve heat transfer
7.7 Conditioned air
Bolted inspection covers, portable earth access covers
and the insulator base fixing-plates are provided with
oskets, and the ends of busbar runs incorporate a
ise bushing. These measures prevent the leakage of
inoist or polluted air into the enclosure. It is usual
to pressurise the enclosure so that leakage is outwards
to atmosphere. The leakage rates are approximately
10% by volume of the busbar enclosure per hour.
This airflow, though quite small, purges any ionised
gases which may have accumulated inside the enclosure
and prevents condensation forming, particularly during
periods of shutdown. The cooling effect of this air
is not taken into account in the design of the busbar
and therefore failure of the associated equipment does
not necessitate shutdown of the unit
All the main connections within the confines of
the bushing seals are fed with dry conditioned ait at
12.5 mbar(gauge). To prevent condensation, the design
S based on a dewpoint of —25°C. A typical system
comprises one air compressor and its associated receiver
and drying equipment per unit. Alternatively, if avail-
able, air supplies can be obtained from the Station
Instrument Air System. Either source is acceptable,
though sizing and rating problems can occur with
nstrument air sources. It is usually preferable to
provide an independent compressor. Some air is fed
around the disc bushings to vent to atmosphere after
passing through the equipment housings.
7.8 Voltage transformers
Voltage transformers (VTs) are mounted within a
cubicle (see Section 7.16 of this chapter) which is de-
signed so that the transformer can be safely removed
for maintenance without requiring access to live parts,
should that be required during operation. A typical
VT weighs in the region of 100 kg. It is generally
4 single-phase cast-resin transformer connected in a
star arrangement with a ratio of 22 KW/110 V, the
Component parts of an IPB system
nearest preferred ratio to the present generator voltage
with accuracy maintained for 0-100% rated output
The primary sides of the VTs are earthed at one end
to a common earth, which is then connected to the
generator stator earth. They are fed from the voltage
transformer tee-off busbar via fuses rated to discri-
rminate against the fuse located at the tee-off from
the main busbar. In the secondary circuits, any earth
connections are made to the Station earth, as that is
the earth which is used in instrumentation circuits
Some manufacturers have traditionally provided ter-
tiery windings on their voltage transformers connected
in delta and used to prevent the occurrence of neutral
inversion and voltage transformer ferro-resonance, The
delta winding is closed solidly or through a loading
resistor, depending on the X/R ratio needed to prevent
ferro-resonance. Neutral inversion is the displacement
of the neutral due to abnormal system conditions,
such as open-circuits in one or more phases of systems
possessing inductance and capacitance. Ferro-resonance
can occur when the magnitude of the inductance of
the VT compared to the capacitance of the circuit t0
which it is connected is equal and opposite. When not
required, the tertiary windings are left open-circvited
with one open-end earthed; this is usual with neutral
earthing methods now used. The reader is referred to
Chapter 3 (Transformers) and Chapter 11 (Protection),
for a more detailed discussion of these issues and the
problems they cause.
7.9 Current transformers
Current transformers (CTs) are located in various parts
of the installation, depending upon the protection
scheme employed. Typically, for the scheme shown in
Fig 4.1, CTs would be installed in the following lo-
cations (shown in Fig 4.8)
At the neutral end of the stator winding, between
the terminal plate and the star-bar, for the following
Purposes:
© Tariff metering.
Efficiency testing.
© Unit instrumentation and turbine-generator
automatic control input signals.
© Low forward power protection.
© Negative phase sequence and loss of excitation
protection
‘© Generator differential protection
Within the generator neutral earthing module on the
secondary side of the neutral earthing transformer for
stator earth fault protection (see Fig 4.10).
309Generator main connections
Chapter 4
AL the unit transformer for:
© Generator differential protection,
© Unit transformer differential protection.
On the HV bushing of the generator transformer fot
generator differential protection
The design of the CTs must be such that they do not
reduce the electrical impulse-withstand level or the
power frequency withstand level of the installation. The
CTs positioned in the main connections busbar are of
the ‘slipover’ type, mounted within a housing, for ease
of erection. They include an earthed screen to shield
the secondary winding from the electric field of the
conductor, thereby allowing the secondary insulation
level to be a nominal 2 kV. This assembly is held at
earth potential by connecting the CT core-shield as-
sembly to an independent earth cable at one point only,
to prevent any circulating current paths. All secondary
cabling should be glanded on an insulated glandplate,
thereby maintaining the 3.6 kV insulation level of the
enclosure. Adequate support and bracing of the CTs
is required as a typical assembly is heavy; a neutral
CT assembly may weigh 600 kg and a line CT assembly
350 kg. Sufficient ventilation must be provided to
ensure that the heat produced in the windings does
ot cause unacceptable temperature rises. Any forces
exerted on the CTs during fault conditions will be
limited to those attempting to centralise them around
the neutral line of the enclosure, These are not signi-
ficant if the CTs are mounted concentrically. There
will be little, if any, axial force exerted on the CTs
and this is easily contained by the mountings. The
generator has an impulse-withstand level of 85 kV,
consequently a similar figure can be allowed for the
neutral-end equipment.
CTs should be clearly tabelled with details of their
duty and their orientation within the system must be
identified to ensure the correct polarity of secondary
signals.
7.10 Environmental conditions
For design purposes, the relative humidity should be
taken as 100% and any equipment mounted out-of-
doors should be completely weatherproof and capable
of withstanding inclement weather conditions, includ-
ing wind and snow loading, and solar heating. Tae
entire installation should be drip proof, dust proof
and vermin proof, with an enclosure rating to at least
IP4s of BSS490.
7.11 Portable earth access covers
The philosophy of portable earthing is discussed in
Section 11 of this chapter. The mechanism by which
310
it is applied is covered here. The design of the access
covers must allow reinstatement of the air conditioning
system when portable earths are applied to prevent
condensation and dampness forming within the main
connections system during periods of prolonged out-
ages. The access cover to the enclosure must allow
00d access to the conductor and earthing device withi
the enelosure, but be securely bolted and hinged when
not in use, The earthing connection onto the conductor
is made by a clamp and is applied using an insulated
pole. A flexible cable then connects this via another
clamp onto the main connections earth system. The
access cover must also allow the application of a
voltage testing device. CEGB safety rules require the
cover to be lockable,
7.12 Viewing ports
Viewing ports, comprising clear glass or Perspex view:
ing windows, are provided in the enclosure at positions
where there is a need to check the condition of flexible
connectors and other equipment regularly. These also
permit the use of infra-red heat measuring devices for
checking the temperature of the connectors.
7.13 Connection of the conductor to piant
As detailed earlier in Section 7.5.2 of this chapter,
braided flexible connectors are used to continue the
conducting path to the connected plant. At the gen
erator, a ‘candelabra’ assembly (see Fig 4.21) has been
developed which forms a circular terminal arrangement
fitted to the machine terminals. Braids then bridge the
gap between the main connections conductor and the
generator terminals forming, in effect, a short cylinder
that assists equal current-sharing among the braids.
Care must be taken in the design to ensure that there
is adequate clearance from stator water cooling pipe-
work,
Connections onto the generator transformer, which
may be either a three-phase tank or three single-phase
tanks, are by braided flexible connectors onto six ter
minal bushings. A typical arrangement in isolated phase
busbar is shown in Fig 4.22.
To give a good current distribution, the connections
conto the bushings should be arranged in as near cit-
cular configuration as possible, typically cight palms
arranged in an octagonal formation (see Fig 4.23). A
single palm connection would not give good current
distribution and should be avoided. However, since the
generator transformer connections carry phase current
rather than line current, there is no need for the ela
borate candelabra arrangement used at the generator
Connections to auxiliary transformers, ¢.g., the unit
transformer, are simpler than the generator transformer
since the load currents are much lower.
‘The temperature rise due to losses in the connec-
tions system must be reduced in areas where significantComponent parts of an IPB system
GENERATOR TERMINAL
FSi
ereLosune
INSULATOR SUPPORT ASSEMBLY
Fic, 4.21 Generator terminal ‘candelabra’ connection
he
may be conducted from plant, for example, at the
senerator and the generator transformer via its bush-
ing. The specifications for these items permit higher
lemperatures than are permitted for generator main
sonnections,
Access {0 terminals should be as easy as possible,
ith the removal of a minimum of enclosure compo-
hhents {0 gain access to the terminations.
7.14 Joints in the conductor
\lthough apparently simple, joints have given serious
Problems in the past, due to the unequal current-shar-
‘ng in braids and poor pointing procedures. One cause
sometimes aggravates the other and leads to the even-
tual failure of the joint, often with catastrophic results,
A joint (which really consists of many joints in parallel)
can be so badly burnt-out that the original cause of
the fault is impossible to determine. Consequently, ex-
tensive experimental work on joints has been performed
by the CEGB to establish the most suitable joint surface
preparation assembly and fixing procedures.
There are several influencing factors to consider
when making a joint:
¢ The material of the mating surfaces to be joined.
© The preparation of the mating surfaces.
© The bolt size.
© The bolt material
3Generator main connections
Chapter 4
22
MAIN PHASE
‘connections
BR SIncte PHASE
GENERATOR TRANSFORMER
_-HVBUSHING
REMOVABLE,
ina
Fubaite CONNECTIONS
’AND LV BUSHING
Fic, 4.22 Air delta arrangement in isolated phase busbars
The size of spreading washer to give necessary clamp-
ing load.
@ The necessary torque,
The method of locking the nut
‘The materials making up the joint are normally either
aluminium or copper; the joints are therefore copper
to copper, aluninium to aluminium or copper 10 alu-
minium, in order of increasing difficulty in making the
joint. It is recommended in the CEGB that where
surfaces are coated or plated this should be removed
a the interface by finishing, so that one of these three
joint interfaces is created. Without going into the
science of jointing, the most satisfactory method will
be described. The jointing surfaces are first cleaned
‘sith a wire brush, a separate wire brush being used for
each material. A liberal coating of petroleum jelly is
then applied to prevent further oxidation. High-tensile
steel bolts, washers and nuts are then torqued-up and
locked, the number of bolts depending on the size of
the ferrule being bolted. Recommended sizes of these
components are shown in Table 4.1.
32
cevenaron
cme apinoniar
Tame 4
Recommended dimensions for bls and wasters wed
washer
Tie dia Oui dia Thiskocs
Me ou 2 1
Me aoe ee eae
mio [| ws om ae | 3s
mo foe 30 | 0
mis | oes wa |
7.15 On-load temperature measurement
‘As can be appreciated, temperature measurement of
‘an IPB system is not easy, but it is necessary during
commissioning to ensure that the design requirements
have been met, and during operation to ensure that
there has been no degradation of joints, flexible con-
ectors, ete. During commissioning, there are variousscousre
Bere =
sion,
Ge
scc#ss COVER. access coven.
a
Component parts of an IPE system
an
org
‘at SECTION
conovevor
ewe. 08URE /COXDUCIOR MSULATOR
exoansion
~ Ba tows
SECTON sroMnG
NOUSNG INTERIOR
Fic, 4.23 Generator transformer connections
‘stick-on’ tapes available to record the maximum
temperature attained at a spot, They have the obvious
disadvantage that they can only be read after the sys-
tem has been de-energised but they are a useful way
of doing a temperature survey. Temperature-sensitive
paints are also available which change colour at a set
temperature, For both these methods, it is essential
to ensure that, once the sensor has been ‘triggered’,
it remains stable until an opportunity to check it is
available, Thermocouples and contact thermometers
also exist, but they are generally only of use on the
star-bar because of the high voltages involved. An
alternative method is an infra-red camera, which ob-
iously requires line-of-sight vision to the spot to be
‘measured. Painting the surface of the joint can improve
the efficiency of emission of infra-red. Since magnetic
flelds can influence an infra-red camera, caution must
he exercised when using it.
Because of the difficulty of temperature measure
‘nent, indirect methods of monitoring can be consi-
dered, Checks of joint resistance, using a micro-ohm
meter, can be made during plant shutdown, and all
Joints checked for obvious signs of discoloration due
to high cemperature.
1 viewing ports are provided, both the infra-red
camera and visual checks for discoloration are possi-
ble. Hot spots only occur at jointed areas; the general
busbar temperature is not a problem, provided that the
busbars have been correctly designed.
7.16 VT cubicles
Each phase may require up to five VTs arranged in
isolated phase compartments. When isolating a VT, it
is usual to break the primary side before the secondary
side, so that isolating contacts compatible with the
secondary voltage can be used. Each VT is separately
protected by a primary fuse, typically 3 A, which
discriminates with the 10 A fuse fitted at the tee-off,
already described. The VT secondary wiring, suitably
fused, is wired to a combined CT and VT secondary
marshalling cubicle and then into its associated pro-
tection or instrumentation scheme. When the VT is
isolated, before access can be gained to it, earths must
be applied by the VT isolating mechanism to both
sides of the 3 A fuse, and the primary and the se-
condary terminals of the transformer. To ensure that
this procedure is followed, the VT cubicle door is
interlocked.
7.17 Access platforms
Since the main connections route is complicated by
proximity to other plant, some access covers are un-
avoidably located at awkward places; access platforms
are therefore necessary to facilitate quick inspection
of joints and connection of portable earthing equip-
‘ment. Sufficient room must be available for an operator
to manoeuvre voltage sensing probes, earth application
313Generator main connections
Chapter 4
poles, etc. Care must be taken to ensure that ladders
and handrails do not bridge insulated joints elect
cally at plant interfaces and thus render them inef-
fective. Also, such structures in the vicinity of the
connections are designed so that they are not heated
by stray magnetic fields during continuous operation
of the plant
The continuicy of any current-condueting path in
the steelwork should be interrupted by the inclusion
of insulating pads, bushes and washers, ete. Attention
should be given t0 the need to sectionalise or insulate
cladding or screens
7.18 Structural steelwork
Structural steelwork running parallel 10 main con
hneetions enclosures must be spaced at least 300 mm
distant. Steelwork running at right angles to. main
connections enclosures must be spaced at least 150 mm,
distant. The supporting structure for the whole of the
main connections, including the tee-off connections,
is designed to give a rigid structure for the static and
dynamic loads imposed with a typical safety factor
of LS. Supports must be completely independent of
the equipment to which the busbars are connected
and separate from main building steelwork. They are
floor-mounted and designed to prevent heating of
the structure by magnetic leakage fields.
7.19 Neutral earthing equipment
This equipment has developed in the manner described
in Section 11 of this chapter and, for a 660 MW gen-
erator, typically comprises a solid insulation (SNAW)
462 KVA cast-resin transformer with a suitably-sized
load resistor and anticondensation heater_mounted
within a free-standing module, one per unit. The trans-
former is normally unenergised, so particular attention
must be given to ensuring that the complete encap-
sulation performed under vacuum is free from voids,
cracks and other defects, and accurate location of the
winding is essential. The resistor is likely to be of
the metallic type and have a value which limits the
earth fault current to 10-15 A in each neutral. Tt will
be air cooled, non-deteriorating, non-corrodible and
fireproof, non-inductive and capable of carrying the
carth fault current for five minutes without mechani-
val damage: the total resulting temperature rise should
not exceed 200°C.
7.20. Site installation
Clearly itis advantageous to do as much factory
labrication as possible, subject to transportation limits.
Equipment housings and sections including bends re-
quire more complicated fabrication techniques and
are best done at the works, leaving the relatively easy
welding of siraight joints to be done on site. The sec-
314
tions are transported complete, i¢., they include
conductor, enclosure, insulaiors and all fittings.
7.21 Quality assurance
Notwithstanding the quality checks required for each
individual component, careful final assembly and weld.
ing of the busbar sections is most important. Welding
must be in accordance with a specified standard, e.g.
BS3S71 Part | for metal are welding or BS3019 Part 1
for cungsten arc welding (both inert gas}, and all welds
must be clearly identified in the design, including their
type, weld process, weld preparation, with samples of
‘each weld type made available for examination. Welds
can be grouped as electrical circuit welds or structural/
mechanical welds and detailed welding procedures are
prepared. Testing of welds by radiography and dye-
penetrant techniques is carried out on a percentage of
all welds produced, with clear acceptance levels agreed
before work starts,
8 Testing
This section covers tests for
© Component parts of the main connections
installation. 7
# Manufacture of a test piece 10 ensure adequate
design.
© Testing on site.
© Type tests
© Routine tests.
© Sample tests.
8.1. Tests on component parts
a41
At the time of writing, these components are made
of an epoxy material. Type fests are carried out on
samples of complete insulators representative of each
type used in the installation; they will already have
passed the specified Rowtine tesis. Each insulator type
needs a different jig in order to subject it to realistic
testing. The necessary corrections for temperature, ba-
rometric pressure and humidity are applied. Typical
type tests are:
Insulators and bushings
© Lightning-impuise voltage withsiand This is the
standard 1.2/30 ys impulse test with the test con-
ditions given in BS3297 Part 1 1974 or BS223 1985,
as appropriate, the test value being that for the
highest system yoltage of the installation.
© Dry power frequency withstand To BS3297 at the
appropriate test value for one minute.:
Testing
+ aver power frequency withstand To BS3297 at the
propriate rest value for one minute.
partial discharge West Carried out in accordance
cidy BSA828, the purtial discharge being measured
wMlerins of apparent charge; the level should not
exceed $0 picacoulombs.
Cantilever mechanical (ype-test This is applied to
Complete insulator secured by its normal means of
Faing, with the load applied at right angles to the
duis of the insulator, This test would not be applied
to a dise bushing.
‘jhe following Routine fests should be carried out on
all individual insulators and bushings:
‘« Visual examination.
Electrical routine vest A V-minute withstand test at
the appropriate voltage.
‘e Mechanical routine test A cantilever test at 70% of
the failing load of the insulator in this mode.
In addition to these Type and Routine tests, the fol-
lowing Sample tests should be performed; the method
cof selection is discussed in BS3297 Part 1, 1974:
« Verification of dimensions This involves checking
that the dimensions are in accordance with the re-
evant drawings, with due regard for tolerances and
other details which may affect interchangeability.
+ Temperature cycle sample test Several cycles of
immersion in hot and cold water, the sample being
held at each temperature for one hour to ensure
hat a uniform temperature has been attained. The
difletence in hot and cold temperatures should not
be less than 70°C. This test would be followed by a
routine electrical test to ensure that no degradation
of the insulator has occurred.
© Oseillatory-load sample test This simulates mechani:
cal shocks onto the main connection installation
caused by, for example, operation of a circuit.
breaker, The number of oscillations selected is left
lo the judgement of the engineer specifying the
installation (of the order of four million), but is
ot applicable to dise bushings.
* Tension sample test Each sample insulator is
subjected to 70% of its ultimate tensile failure load
for one minute without failure to it or its fixings.
{i is not applicable to disc bushings.
* Torsional sample test A torsional load is applied
to each threaded insert or stud of an insulator or
bushing to demonstrate that no permanent distortion
or loosening of fittings occurs. For thread sizes up
(0 Mi2, a load of $0 Nm is used.
© Puncture sample test For this, the insulator is
inmersed in switchgear oil and a voltage of approxi-
mately 50% of the specified puncture voltage applied
across the unit. This voltage is then inereased gradually
to 1.3 times the actual dry flashover voltage of the
unit without causing puncture,
© Ukimate cantilever-load sample test Finally, a unit
should be loaded up in the cantilever mode umtil
failure occurs. For this sample test, failure should
not occur below 80° of the failure load obtained
from the Type testing.
8.1.2 Busbar material
Checks are made to ensure that the material is to
specification and that different material types are clear-
ly identified, so that the incorrect material or thick-
ness cannot be inadvertently used in any part of the
installation
8.1.3 Transformers
The various VTs and CTs throughout the system require
Type and Routine tests, as described in Chapter 3
8.1.4 Loading resistors
‘The neutral earthing system loading-resistor must be
tested in accordance with BS587: 1957, as follows
Type testing
© High voltage.
'* Ohmic value of resistor.
‘© Temperature rise.
Routine testing
© High voliage.
© Ohmic value of resistor,
8.1.5 Capacitors
Capacitors may be installed in the main connections
for the reasons explained in Section 10 of this chapter.
‘They should be tested in accordance with BS1650.
8.1.6 Switchgear and earthing switches
Testing requirements for switchgear are discussed in
Chapter 5,
Type and routine testing of earthing switches is in
accordance with BS5253, the test arrangement simu-
lating the service condition as far as practical, i.e., the
switches should be mounted in their service enclosures,
together with a section of busbar. The short-circuit
test is made on a three-phase group of switches, but all
‘other tests may be performed single-phase.
Control and electrical interlocking circuits, if appli-
cable, should be tested for correct operation.
315Generator main connections
Chapter 4
8.1.7 Compressed air system
All compressors, pipework, valves and ancillary ap-
paratus are tested to appropriate standards, i.e., the
Pressure of their associated safety valves, with air
receivers being pressure tested to one and a half times
their safety valve operation pressure.
8.2 Tests on representative sections of IPB
It has been explained earlier that calculation of the
forces that exist upon @ main connections installation
during short-circuit is very difficult and at the time of
writing there is no reliable calculation method avail-
able. Any computational method later developed will
Tequire validation by testing. Consequently the CEGB’s
normal practice is to test the capability of a main con.
nections design by subjecting it to the worst Fault
urrents which might occur in service. There are limited
facilities worldwide where tests of this kind can be
carried out, and such testing is very expensive. It may
be advantageous for the manufacturer to offer a main
connections installation of higher current rating than
is necessary simply in order to use a tested design,
thereby making repeat tests unnecessary.
1c is normal to offer two test pieces; a section of
main and tce-off busbar, including the tee-off itself
and the delta section. The former requires representa.
tion of all three phases and the earth bar whereas for
the latter a ‘go and return’ section plus earth bar suf.
fices. An example of a test piece comprising aluminium
busbar in an aluminium enclosure representative of
@ unit transformer tee-off connection is shown in
Fig 4.24
Consideration should be given to incorporating ad-
ditional equipment into the test piece, for example CT
chambers, expansion joints, flexible connections, ete.
The following design aspects of the test piece should
be considered. In addition to the selected test piece,
it is advisable to add a short interface section where
connections are made to the incoming unscreened
section of the test station busbar. This reduces the
end effects of non-representative connections on the
test piece. The connection to the test station supply is
by flexible connections, as used in normal service
The short-circuit is by means of a shorting bar of
construction generally similar to part of the main con-
nections installation. It is connected to the test piece
by joints similar to a normal ee-off but strengthened,
typically by welded webs, in order to withstand the
high knife-switch forces in this area, those forces being
higher than those in practice at a rigint-angle bend
In a single-phase-to-earth fault, connection to the test
Piece is in a section of earth bar returning 10 the test
Fic, 4.24 Test piece for generator main connections
316sonnections by unscreened conductor, this being
resentative of @ normal earth bar arrangement in a
epal design. Laminated flexible sections should be
wprded at cach end of the screened conductor and
re conductor held down in the manner proposed i
the earth bar design. Bonding bars should be incor-
varated in the test piece at the test supply end, though
pera teireut bar enclosure will provide the bonding
honween individual phase enclosures at the remote
vette te piece
ae eae ihpoa- ese
station ¢
are recorded:
e Input ‘The applied current (and voltages) are re-
corded on UV oscillographs. It is advisable to take
additional current measurements using Rogowski-
coil type current transducers in various parts of the
test piece, these being particularly useful for di
gnostic purposes should some failure occur. (If any
CTs are fitted in the test piece, they should have
heir secondary windings shorted unless some mea-
surement of their output is required.)
@ Force Piezoelectric force transducers should be
positioned to measure load on the earth bar. If a
correlation is being made between the test results
and predictions by calculation, as many transducers
as possible should be applied to the earth bar to give
greater confidence in the calculation method.
‘@ Voltage rise The voltage rise in various parts of
the test piece should be measured relative to one
point on the test piece.
© Temperature Maximum-indicating temperature de-
vices of the stick-on type should be liberally applied
to the test piece in order to record the maximum.
temperature reached. These should be examined
after the one-second test (see Section 7.15 of this
chapter) to ensure that the final conductor tempera-
lure does not exceed specification. Clearly, initial
temperature prior to short-circuit must be recorded
to determine temperature rise. The thermal short-
cireuit capacity of the main busbar is far in excess
of the actual values due to the high continuous
current and large conductor and enclosure cross-
sections. For the unit transformer tee-off, the tem-
perature rise has less margin due 10 its relatively
smaller cross-section,
83° Test levels
The fault conditions normally quoted in a specification
‘We synthetic insofar as the actual fault currents that
ould flow on a given power station installation cannot
be predicted precisely. The test values are therefore
dletived from real plant parameters, assuming that all
the variables combine at their worst. The test philo-
Sophy is based on the presumption that any real fault
will be less severe than the test condition.
Testing
The values of fault conditions are the sum of the
contributions from the generator side and the genera:
tor transformer side of the system, The design values
should be applied throughout the system, including the
associated earth bar system, to ensure a high integrity.
For a 660 MW installation, the test levels quoted
would be as follows:
(2) Equivalent RMS short-circuit three-phase 200 kA.
fault current for I second
(b) Calculated first loop peak of (a) 630 kA
168 kA
(©) RMS short-circuit single-phase equiva
Jent to each fault current for 1 second
(ie., this represents the heating effect
equivalent to that fault current which
actually flows, taking into account cur-
rent decrement)
(4) Calculated first loop peak of (c) 435 kA
The earth fault values assume that the generator neu-
tral earthing transformer primary is short-circuited. (a)
and (c) are thermal tests, whereas the peak tests (b)
and (d) are mechanical.
Representative parts of the design are also tested 10
demonstrate:
© Lightning impulse-voltage withstand, using the stand-
ard 1.2/50 us impulse, i.e., that there is adequate
air clearance between conductor and enclosure. At
resent generator voltages, a test level of 170 kV peak
full-wave is used, applicable to a system highest
voltage of 36 kV.
‘© Power frequency one-minute dry withstand corre-
sponding to the above figure, in this case 70 kV RMS
at 50 Hz.
Due to the less-onerous service conditions, the tests on
cexciter systems (see Section 5.5 of this chapter) can be
confined to:
‘# Power frequency dry withstand, 10 kV RMS for one
minute at 50 Hz,
¢ Full wave lightning-impulse withstand, 5 positive
and $ negative discharges, at 40 kV.
© A heat run of $000 A RMS for 8 hours, including
adequate instrumentation to survey the whole system.
8.4 Tests at site
The complete installation, including compressed ait
pipework if fitted, for a 660 MW Generator would
be subjected to either a dry one-minute power fre
‘quency voltage-withstand test at 68 kV RMS or a dry
fifteen-minute DC voltage test at a test level of 66 kV
DC. The insulation resistance is measured before and
after this HV test. The connections to the generator
307Generator main connections
Chapter 4
and transformer windings are disconnected during the
test
{In addition to the above, a heat rum is carried out
on che complete installation, using the generator as the
power Source to ensure that the main connections
design is satisfactory for the rated overload current
and temperature condition. This test is performed by
short-circuiting the main connections on the grid side
ot the generator transformer, closing the HV earthing
witches in the grid connection to form a three-phase
short-circuit and adjusting the generator voltage to
give the maximum continuous rated current of the con-
neetions, A liberal number of temperatures should be
recorded and the installation run for sufficient time
to become thermally stable.
Finally, the enclosure installation should be subject
to an insulation-to-earth test appropriate to @ 3.6 kV
insulation level
Similar tests are performed on the exciter connection,
though at a reduced level
9 Experience of testing
In the event of an unrestricted fault at or in the unit
transformer, the main connection system cannot pre-
vent damage at the point of the fault. It is therefore
considered that a specification for the main connections
should ensure that:
‘¢ They are not the source of any faults.
‘# The connections will not compound @ fault occur-
ring outside the main connections terminal points.
Their design must be such as to allow a return to
operation with the minimum possible refurbishment.
‘The test results of a main connections design are
therefore analysed with the above criteria in mind.
‘The short-circuit testing of designs undertaken by the
CEGB has not been without incident and has shown
that the designer eannot rely fully on calculations. This
is true both of the thermal and the mechanical short-
circuit tests. The distortion of the test sections caused
by mechanical forces has been considerable. In addi-
tion, the rise in potential of enclosures and earth bars
ss been higher than predicted. Experience has shown,
that as many measurements as possible, of all the
parameters, should be taken so that all the results of
the test can be fully interpreted. An adequate supply of
measuring devices is also essential, since some can be
camaged during the test, Since test laboratory time
is expensive, detailed preparation work is essential to
ensure a trouble-free test session. This requires a com-
plete understanding of the requirements among con-
actors, laboratory staff and customer.
Ivis essential to ensure that the test connections from
Ute test station are arranged such that no unrepresenta-
bse stress is put on the test piece due to their presence,
318
The results of all short-circuit tests that have been
performed to date by the CEGB allow some general
comments to be made concerning the arcas of the
design which are most critical
Faults in the past have generally been associated
with small-section conductors, sharp changes of direc
tion in small-section conductors, welds in small-section
conductors and end effects at bonding bars. Generally,
the main conductor cross-section required for con.
tinuous maximum rating is such that it has ample
short-circuit withstand capability. The same is true of
the main enclosure except, for example, where extra
local loading is placed upon it by poorly supported
bonding bars, Nevertheless, itis still essential to include
a section of main busbar in the test piece in order
to steady the unit transformer tee-off and other small
‘or complex section conductors, e.g., in line laminae,
bolted joints, earth bar fittings, etc.
Details of some typical problems reveated in testing
are:
# Enclosure bonding bars, if not sufficiently robust,
will be distorted at the test piece ends during the
mechanical test. Bonding bar movement can pass.
the stress down to the enclosure support Feet, causing
them to distort.
© The additional forces that exist due to end effects
are revealed by general relative movement and dis-
tortion of the conductors at the test piece ends,
though elsewhere the conductor and enclosure must
remain straight and undistorted. The forces in this
end area can damage laminae or braided flexible
connectors.
‘© Inadequate earth bar cross-section and insufficient
holding down points can allow the earth bar to dis.
tort severely: this is probably one of the most
common problems revealed by testing. This demon-
strates the effect of lack of shielding since the earth
bar is not provided with a sheath. It also illustrates
that a system of this mass, when subjected to forces,
produced by the fault current, will suffer distortion
and possible damage whilst absorbing the energy
present. The conductor is a large, very rigid structure
supported by a strong insulator system in a braced
enclosure itself supported on strong insulated feet.
This assembly has litte flexibility and a large mass
(very high inertia). The earth bar, whilst supported
at many points and of large cross-section, is rela-
tively less massive as a system and in the event of
reaction between it and the conductor system it is
the earth bar that suffers most damage.
© Because of the centralising force exerted on the
conductor by the enclosure, damage can result to the
feet supporting the conductor by spreading or crack-
ing, and the design must cater for this force.
© Testing has shown that during short-circuit con:
ditions, diametrically opposite laminaes or braidsGenerator voltage switchgear
‘vill be attracted Jogether when forming part of the
Nonductor and repelled when part of the enclosure.
sondian cause movement of the conductor and
damage to the support insulator Feet, or indeed the
solator itself
‘The forces produced during the mechanical test
provide a coinprehensive check of the adequacy of
the welding specification,
During the testing it is common for extensive arcing
and smoke to be produced, generally caused by
paint in joints of the test piece frame burning out
fine to circulating current. If such arcing is to be
tliminated, sound electrical joints in the frame are
required.
ne other significant factors have arisen concerning
ystrumentation of short-circuit tests
The principal object of the tests is to short-circuit
pproof-test a busbar specimen. The instrumentation pro-
‘ded is intended to provide supplementary information
for comparative records as well as data that might
help in the ensuing fault analysis, Taking the instru-
mentation normally applied in turn:
|a) Voltage measurement Measurement of enclosure
voltages does prove useful, but care should be taken
when interpreting the results. The intention is to
measure the voltage drop along the enclosure when
fault current flows in the conductor. The actual
enclosure currents are the sum of many complex
and interacting phenomena. For example, the prin-
cipal enclosure current flows on the inner surface
but currents induced by other conductors flow on
the outer surface.
‘The current flow in the enclosures is not
homogenous, but is subject both to concentrations
and eddies. As a result, placing a set of potential
measuring points along the outside of a relatively
short test piece of complex geometry will not yield
a smooth potential gradient along the test piece.
However, experience has demonstrated that en-
closure monitoring points can show when arcs or
‘conducting metal touch the enclosure. Additionally,
providing that the correct measuring method is
chosen, useful information can be derived concern-
ing the earth bar and the voltage drops along it
iy
Surain gauges Strain gauges are very sensitive to
electrical interference and, furthermore, unless great
care is taken when positioning them, they can be
affected by thermal expansion of the test piece
Converting the results obtained into meaningful
loading figures is unreliable because of the diffi-
wulty of defining exactly how the loadings are
Produced
Temperature The stick-on maximum temperature
indicating devices are a perfectly adequate means
of recording temperatures during these tests.
(0) Film record The basic concept of a film record
is sound and such a record should be specified.
Some shortcomings have been highlighted in recent
tests which should be dealt with.
The designer's assumption at the outset of test-
ing is that no major problems will be encountered
Thus filming is carried out in a fairly standard
fashion, using a frame speed in the region of S000
frames/s at the instant of the fault. If a fault
occurs in which the camera sees an electrical arc
then the film record from this point onwards is
Virtually useless. On other tests where an arcing
fault has been intentionally provoked, filming has
been performed through a high sensitivity neutral
filter. The illumination of the arc is sufficient to
penetrate this filter and give @ rough outline of the
surrounding equipment but, prior to the arc, the
film is totally blank and unexposed.
One possible solution, on a test where it is
not known whether arcing will occur, is to run both
normal and filtered cameras simultaneously, al-
though this is wasicful of film should a fault not
occur, It is also complicated and expensive in terms
of the initial equipment to be provided
Another potential solution currently being in-
vestigated, centres around a product marketed for
military use. A chemically-treated plastic, trans-
parent under normal illumination, becomes almost
‘opaque when subject to intense ultra-violet radia-
tion. The time taken to change from clear to opaque
is very short indeed, and a fier of this material
applied to the lens of the camera might offer a
cheap and ready insurance against unexpected arc-
ing faults with the possibility of recording evidence
during the are.
10 Generator voltage switchgear
Only a brief mention of this equipment is made here:
the actual switchgear is described in Chapter $ and
the factors to be considered regarding its use are dis-
cussed in Chapter 1. However, if such equipment is
incorporated in the main connections installation, this
affects the layout of the busbar and calls for additional
equipment to be installed, ¢.g., pneumatic equipment,
cooling equipment and, possibly, system capacitors.
‘The switchgear is located in the horizontal cun of bus-
bar and an area, preferably enclosed, must be provided
to house it. Due to the physical size of the switchgear,
increased centres between phases will be required in
that area. The switchgear comprises an independent
‘interrupting device’ per phase, thereby maintaining
complete phase isolation throughout the system. Con-
sideration must be given to the foundation requirements
for mounting the switchgear.
The switchgear itself may be either water ot air
cooled, the option being selected after consideration of
the continuous current-carrying capacity and therefore
319Generator main connections
Chapter 4
the quantity of heat to be extracted, air cooling having
obvious limitations.
To minimise transmission of shock to the main
busbars due to the operation of the switchgear, flexible
connections are made between the switch and busbar,
normally using aluminium laminae. Caution should be
exercised if aluminium laminae are used, as this may
reduce electrical clearances to an unacceptable degree
if the switchgear was designed to be connected by
copper laminae. Since a continuous circuit for circu
lating current within the main connection enclosure
is required, loop connections to the body of the switch-
gear must be provided, the most suitable being alu-
‘minim laminae.
Another significant factor affecting the main con.
nections is whether the switchgear is fault-rated oF
iower-rated as isa switch disconnector; the implications
of this decision are discussed fully in Chapter 1 of this
volume. However, depending on the characteristics of
the switchgear selected, and in particular the value of
the transient recovery voltage (TRV), capacitors may
have to be added to the system, fitted between the
conductor and the earth, to cater for the satisfactory
operation of the generator switchgear under all op-
erating conditions. The most suitable position for these
capacitors is generally in a specially designed compart-
ment within a VT cubicle, a three-phase bank of single-
phase capacitors being connected between phase and
earth. These are used to decrease the steepness of the
switching or fault clearance voltage wavefront in order
not to exceed the maximum allowable voltage stress
on the insulation of the equipment. They reduce the
rate-of-rise of recovery voltage at the interruption of
short-cireuits and load currents. Capacitors can also
reduce overvoltages caused by single-phase faults on
the LV side of the generator transformer, The capa-
citors themselves comply with BS1650 or equivalent
specilication, and are preferably of the steel-tank oil-
filled type, having insulation and impulse voltage ca-
pabilities equivalent to those specified for the remainder
of the main connections installation. The capacitors
should incorporate discharge resistors to ensure that
they are safely discharged to earth potential, following
the shut down and isolation of the plant. When the
capacitors are installed in the VT cubicle and the tee-
off cubicle is fed through fuses (Section 5.3 of this
chapter), then those fuses must be capable of handling
the capacitor inrush current without failure,
The design of the generator stator neutral earthing
is described in Section 11 of this chapter. If generator
switchgear is installed, main connections system
between the switchgear and the generator transformer
is unearthed when that switchgear is open, To cater
for this, a system neutral earthing transformer must
be installed between the switch and the transformer
which will form @ neutral point on the LV side of the
generator transformer, This neutral earthing trans-
former has an interstar primary with its neutral point
earthed via a transformer and resistor, these last (wo
320
components being similar to those used for the gen-
erator stator neutral earthing, already described.
Consideration must be given to the additional syn-
chronising requirements when generator switchgear is
employed. The normal measuring VTs, already de-
scribed, are installed between the switchgear and the
generator (see Fig 4.8), To monitor the ‘system’ side
of the switchgear either a supply can be taken from the
system neutral earthing transformer, by incorporating
@ tertiary winding within it, or an additional tee-off
and VT provided instead. If system capacitérs are
needed, the latter is the better solution and the VT
cubicle would then house both the additional synchro
1g VTs and the system capacitors.
‘The methods of earthing for maintenance purposes
are different for installations with and without gen
erator switchgear.
11 Earthing
‘The methods of earthing the main connections, namely
stator neutral earthing and systems neutral earthing,
have already been discussed, together with the earthing
tequirements for the enclosure system and fot con-
nected equipment, for example, transformer tanks. This
section briefly explains the philosophy of earthing the
generator and its connections.
Prior to 1950, the normally established earthing
practice for the neutral of a main generator connected
to the system by transformers, was to use @ voltage
transformer, the secondary of which generally operated
an alarm in preference to tripping the generator. A
number of serious breakdowns in the early 1950s caused
this practice to be abandoned, Instead, the neutral
was earthed via a low resistance, namely a liquid earth-
ing resistor. The resistance was typically 22 ohms for
30 MW and 60 MW generators operating at 11.8 kV,
so that the maximum line-to-earth current would be
about 300 A. The time rating of the resistor was 30 5,
This method continued until the 1960s when, instead,
earthing was effected by a low resistance connected
to the LY winding of a distribution-type matching
transformer, the HY winding of which was connected
in the neutral lead (see Fig 4.10). This has worked
satisfactorily and costs no more than earthing through
2 liquid earthing resistor. The high effective resistance
to earth fault current limits the damage at the point
of fault and there is the advantage that the resistor
can be designed for low voltage with attendant robust-
ness and reliability. The surge-reflection characteristics
Of this system have been found to be satisfactory. This
scheme has the additional advantage that, because the
maximum earth fault current is very low, in the order
of 10-15 A, a sensitive setting of the protection relay,
as shown in Fig 4.8, can be used in the unit protection
scheme, Clearly, the fault current flows in the trans-
former primary winding, so the curreni-limiting resistor
‘on the secondary side of the matching transformercurrent, During normal conditions with
aries a ggrents balanced, no current flows in the
‘re pal carting transformer.
seinthen this scheme was developed, the trans-
Maly resistor wete situated some distance away
vores anc Uf point, sometimes outside the turbine
trom Jee the ‘ansformer was il filed, This neces:
hall guhe use of Tong length of cable, an earth fault
~iste th could only be detected during outage times
vee yStuch a fault on this eable would, ducing an
Cin ac a the ate, cause oMenced
arepsalt current to Flow. Consequently, a cast-resin
wah ansformer was developed which is located ad
(oe tothe star-bar together with its loading resistor,
Jeeer sanereasing the integrity ofthe system by having
eon a connection tO the star-bar as possible.
a eietaiso Section 10 of this chapter for details of
sgouin nevtcal eatthing when a generator switch is
carries a higher
Initial
installed.
12. Earthing for maintenance purposes
before any maintenance work can be performed on a
tain connections installation, the system must be ef-
rively isolated by lockable means, and fully earthed
The methods used and the extent to which this is
achieved depend on the Safety Rules of the operating
lity
Ac the time of writing, the CEGB uses @ National
Code of Practice for earthing high voltage apparatus
whieh (simply put) calls for a ‘Primary earth’ to be ap-
plied within the isolated zone on which work is to be
performed. This Primary earth must be of adequate
«ross-seetional area to discharge safely any fault current
which may flow as the result of inadvertent energisa-
tion. A citcuit-breaker or a specially provided earth
switeh or fixed earthing device must be used to make
the fist Primary earth connection. After application of
this earth, the system then has a number of ‘portable
drain earths’ added in accordance with an agreed ‘Earth-
ing schedule’ in positions such that, wherever work is to
be carried ous, the person performing the maintenance
work can See at all times that the portable drain earth
iy in position, The CEGB requires that a visible drain
sarin must be positioned within 19 m of the place of
11 generator switchgear is installed, the Primary earth
switch must be located between the generator and the
eenerator switehgcat. This earth then covers the section
in whieh itis fitted and also the remainder of the instal-
lation when the generator switchgear is closed. There-
lore earthing procedures and sequences are different,
epending on whether a generator switch is installed.
12.1. Primary earth
or a 660 MW installation without generator voltage
Switchgear, it is considered that inadvertent re-ener-
Earthing for maintenance purposes
gisation via the HV breaker in the substation is not
credible due to the fact that it would be open and
locked, as would the HV isolator, and the HV earth
switches would be closed and locked
Any back-feed is then limited to:
TA for 2s
Residual magnetism at barring speed 1 kA continuous
Unit auxiliary system
1 KA continuous
25 KA for 2s
Residual magnetism at full speed
Full excitation at full speed
It is therefore deemed adequate that, for installations
without generator voltage switchgear, the primary earth
should be rated at 25 KA for 2s.
For installations with generator voltage switchgear,
the section between the switch and the generator could
be re-energised, since the switch is the point of isolation.
Here, the Primary earth is applied by fully-rated
motorised earth switches, complying with BS5253, on
the basis of one per phase for each generator unit
For a 660 MW generator installation, the following
minimum earth switch specification would be expected
for a terminal voltage of 23.5 kV, 50 Hz.
© Impulse voltage withstand 170 kV peak
© Power frequency voltage withstand 75 KV RMS.
to earth
© Continuous rated current 1000 A
@ Rated short time current 160 kA
© Permissible duration of short-circuit 1 s
@ Rated peak current 440 kA peak
‘© Operating time 10s
‘@ Rated short-circuit making current 750 A peak
at rated voltage
A typical earth switch arrangement is shown in Fig
4,25, one switch would be installed in each phase.
‘The switch is mounted integrally with the main
connections enclosure and penetrates to the conductor
via a drive housing. The actual earth connection is
made by a motor-driven lead-screw system operating
a drum-type contact. A position indicator must be
provided on the outside of the switch: a window in
the busbar enclosure allows the position of the contact
to be checked visually, It is usual to provide a handle
for manual operation of the earthing switch, should
that be necessary.
12.2 Portable drain earths
These devices are applied after the Primary earth, as
explained earlier in this section, and are rated to handle
the maximum fault current, For a 660 MW generator
321Generator main connections
fonve oro
Fic. 4.28 Single-phase earth switsh
operating at 23.5 kV, the portable earthing equipment
is rated at 17.5 kA for 2 s or, alternatively, 23.5 kA
for one second,
‘The portable carth is applied to the conductor after
gaining access to it via a portable earth access cover.
E ne cum
“conpucton
anna
(ohn DST;
(OPERATING Foxe OETA
Chapter 4
A typical method of application is the fitting of a
clamping device on the portable earth connection to
2 ‘ball’ fitted permanently to the conductor, the com.
ponent parts being shown in Fig 4.26,
The earthing clamp is applied to the ball, using an
HV insulated pole of approved design, The pole is
about two metres long so that the person applying the
earth is never in any danger if, for some extremely
unlikely reason, the equipment were alive. Similar de.
vices are used to apply earths to substation equipment
but a longer pole, typically four metres long, is used
because of the higher voltages in those arcas. Design
Of the clamping devices must be such that it is not
Possible to apply an earth with a two-metre pole, when
@ four-metre pole should be used.
After application of the clamp onto the conductor,
the portable earth access caver should be closed.
At the other end of the portable earthing cable, an-
other clamp is fitted, suitable for connection co the
system main earth bar. For this purpose, secondary
earth bar loops from the main earth bar tun are pro.
vided adjacent to each portable earth access point,
though the main earth bar run must be continuous and
independent of such loops. Typical points to which it
should be possibie to connect portable drain earths are:
* Generator transformer LV bushings.
© Unit transformer HY bushings,
EARTH END CLAN?
Fia, 4.26 Ponable earthing device
322
SsFuture trends
System earthing transformer HV bushings.
‘Teansformer side of unit transformer tee-off CTs.
Unit transformer tee-off.
oth sides of generator switchgear,
off.
VT cubicle te
\T cubicle side of tee-off Tuse,
‘¢ Generator terminals,
‘¢ Sestem capacitor terminals and tanks,
portable earthing equipment must obviously be ex-
vpined regularly to ensure that it is undamaged and
the results of such examinations must be recorded
{i must also be examined immediately before use by the
person responsible for the application of such earths.
Carelul recording of the number of portable earths
Spnlied and of their locations is essential to ensure
‘hat all are removed prior to re-energisation of the
Sistem, This can be performed either by a mechanical
jnverlock method (which can become very involved
‘and time consuming on extensive systems), or by strict
administrative controls.
‘The locations of some of the portable earth access
covers may be several metres above ground, Access
platiorms are provided, the design of which takes into
count the difficulty of applying the portable earth
lamp. Careful consideration must be given to avoiding
induced circulating current in this steelwork.
13 Protection
Ih is not intended to explain the protection systems
employed to cover the main connections; these are
hilly described in Chapter 11. However, the designer
the main connections installation must be fully
aware of the requirements for protection devices, such
‘current transformers, within the equipment and
heir accommodation within the design. He must also
bbe aware of the operation time of the protection and
his equipment to carry fault current safely for
shat period. Present figures are quoted in Section 8.3
oF this chapter,
The design of accommodation must take into ac-
‘ouint ease of assembly, access for testing and ease of
withdrawal if @ device becomes faulty. During com-
‘missioning and reinstatement of the main connections,
primary and secondary injection tests must be per-
Yormed 10 check the protection schemes. Also, con-
sideration should be given to incorporating primary
loop through a CT for primary injection purposes
‘shen that CT is located in an inaccessible position,
‘or example, in @ transformer bushing
Marshalling cubicles accommodating interposing cur
iransformers and terminals for secondary wiring
Nill be required.
14. Interlocking
Operational and maintenance interlocking schemes are
discussed in detail in Chapter 1 but the designer of
the main connections should be aware of the possible
requirements for such schemes. The method of inter-
locking may be electrical on circuit-breakers and earth
switches, but may be of the mechanical key-interlock
type on other equipment. If minimal interlocking is
used, then very strict administrative controls are re-
quired to ensure that the operator cannot gain access
to live equipment and that a safe sequence of events
has to be performed before access can be achieved.
15 Future trends
660 MW generators are now the standard size used
by the CEGB, though the industry is considering an
increase from that figure for both fossil-fired and nu-
clear (PWR) stations. There are two possible future
steps in the short term: the choice will probably depend
on the type of steam raising plant. If the PWR con
cept is pursued, it may be decided to drive only one
generator from each reactor, thereby requiring a tur
bine-generator rated at about 1300 MW.
Future coal-fired plant may incorporate turbine.
generators rated at about 900 MW.
Whichever option is selected, a move to some form
of forced-cooling of generator main connections will
be required, with a probable increase in voltage and
higher line current; in this way, large dimensional in-
creases can be avoided. A forced-air cooled system is
the more likely since this would be a relatively simple
extension of current designs.
It may become possible, if adequate research work
is performed, to increase the operating temperature
of main connections. If so, itis likely that silver plating
will be required to avoid oxidation.
Since the cost of testing main connections designs
is so high, some development work would be desirable
to reduce testing costs. This could involve cither cal-
culation methods or small-scale comparisons. In the
former, a design would be completely modelled and the
forces due to shori-circuit calculated. Some physical
testing would initially be required to validate the cal
culation method. As an alternative, it may be possible
to model the installation or a representative part of
it and to fault-test at higher than normal frequency.
This reduces the size of the test piece required and
consequently the cost. It also means that the test could
be performed in smaller test stations rather than hav-
ing to use the very limited facilities available for full
scale testing.
Clearly IPB systems will continue to be required
and the basic technology of this subject will apply for
the foreseeable future. Only a rapid improvement in
superconductivity techniques would cause @ dramatic
rethink of the materials and conditions used in the main
connections installations of tomorrow.
323.Generator main connections
Sees eee EEE
16
a
py
by
18)
15)
324
References
Carter, F. W. Note on losses in cable sheaths: Proceed-
ings of Cambridge Philosophical Society No. 24, pp 68-73:
1
Duvight, H. B.: Theory for proximity effects in wites, thin tubes
and sheaths: ALEE Trans 42: 1923,
Skeats, W. F. and Swerdiow; N.: Minimising the magnetic field
surrounding isolated phace bus by eletrcally-continuous en:
closures: AIEE Trans. No 62: 1962
Wilson, W. R, and Mankof!, L. Li: Short eltewit forces in
Isolated phase buses: AIEE Trans: 1954
Daight, H. Bu: Electrical coils and conductors: MeGraw Hi
sss
Chapter 4
[6] Niemotler, A. B.: Isolated phase bus enclosure curcents: Trans,
IEEE: August 1968
7] IEEE: Guide ror calculating loses in isolated phase bus: IEEE
Paper 298: June 1969
8) Dwight, H. B., Andrews, G. W. and Tileston Jnr, W.: Ter
perature ise of busbars: General Electric Review: May 194
9] Albright, R. H., Conasla, A., Bates, A.C. and Owens, J. 8
Iolated phase ‘metal-enclosed conductors for large eect
generators,
Ashdowa, K.T- and Swerdlow, N.: Cantilever-loaded insula.
tors for isolated phase bus: AIEE Paper: Apel 1953
Swerdlow, N, and Buchta, M. A.: Practical solutions of in
ductive heating problems resulting from high current buses
Trans, AIEE 1960
19)
ua