Professional Documents
Culture Documents
net/publication/3918459
Conference Paper in Conference Record - IAS Annual Meeting (IEEE Industry Applications Society) · January 2001
DOI: 10.1109/IAS.2001.955643 · Source: IEEE Xplore
CITATIONS READS
27 1,356
1 author:
Mohamed Saied
Independent Researcher
231 PUBLICATIONS 1,086 CITATIONS
SEE PROFILE
All content following this page was uploaded by Mohamed Saied on 12 October 2014.
I. INTRODUCTION
The available literature includes numerous Fig. 1: The sample transformer substation
investigations on the inrush current phenomena in power
transformers and its impact on the design and operation of II. METHOD OF ANALYSIS
their protection schemes [1-6]. Procedures such as voltage-
or harmonic-current-restraints are being used to The starting point for analyzing the transients is the
distinguish between large fault currents (for which fast accurate representation of the transformers’ magnetic
disconnection of the transformers is necessary) and cores. There are several models suggested in the literature
eventually excessive magnetizing inrush currents (for for emulating the strongly nonlinear and multi-valued
which the transformer protection should not operate) [5,6]. function relating the core fluxes to the corresponding
Little work is available in the literature, such as [2,3], on exciting currents [1-4]. For this investigation, the relation
the inrush current in a transformer within a substation, between the flux φ(t) and the magnetizing current i(t) of
such as that indicated in Fig.1. It is expected that there will each transformer is expressed by the following equation ,
be a mutual , sometimes called “sympathetic”, interaction as proposed in [1].
between the different transformers. This is primarily due
to the common supply impedance represented in the i = c. tan[( ϕ /a) – b.i] (1)
equivalent circuit shown in Fig. 2 by its inductance and
resistance Rs . Other symbols are defined as: which is equivalent to
1181
Fig. 6: The hyteresis loop for a single transformer
Fig. 3: Simulation results for a single transformer switching at the zero switching at the voltage peak
crossing of the supply voltage, i.e. α =0
of several multiples of the expected steady state
magnetization current. Moreover, the high harmonic
content of the current in both cases is evident. The
hysteresis loops of the transformer are illustrated in Figs. 5
and 6 for α =0 and α =90, respectively. Fig. 5 indicates a
strongly unsymmetrical loop, as compared to the almost
symmetrical case of α =90,depicted in Fig. 6.
1182
It is further noticed that the total current needs less than two
cycles to reach its symmetrical shape. It will then oscillate
between about ± 6A.
Fig. 7: The current in the already connected transformer T 1 , α =0. Fig. 10: The waveforms of the fluxes in both transformers after
energizing T 2 , α =0.
T 1 (top) T 2 (bottom)
1183
since both transformers are in parallel, the difference between
the two fluxes will be constant. Hence, their time derivatives
(i.e. the induced EMF’s) will be equal.
T 1 is loaded by 30 Ω.
1184
Fig. 16: The current in the already connected transformer T 1 , α =0.
Fig. 15: The supply current i s (t) and bus voltage v(t) following
energizing T 2 , α =0.
T 1 is loaded by 30 Ω.
The supply current is shown in Fig. 15. After just one half
cycle, the DC offset practically disappeared and the current
is almost sinusoidal. The supply voltage and supply current
waves are almost in phase. This diagram should be compared
with the corresponding one in Fig. 9 for the unloaded case.
More important, the peak values in Fig. 15 are generally
smaller than the corresponding (much sharper) peaks in
Fig. 9.
Fig. 17: The energizing current transient in transformer T 2 , α =0.
Case IV: Effect of The Source Impedance:
1185
Case II but after adding a shunt capacitor of C=50 µ F to the
bus-bar. The switching of T 2 occurs with α =0. Fig. 19
IV. CONCLUSIONS
shows the waveforms of the 3 currents iT 1 (dotted curve),
1. This paper deals with simulating the inrush current
iT 2 (thin continuous curve) and the supply current i s (bold
phenomena in substations including parallel-connected
curve).The presence of C will increase the peak magnetizing transformers. The analysis and computer program are based
current in the already connected transformer T 1 from 5A in on analytical expressions for the transformers’ nonlinear
Fig. 7 to slightly more than 6A. This is also valid for the magnetization curves and the numerical solution of the
governing equations.
inrush current in T 2 . Its first peak exceeds 8A, which is the
corresponding value in Fig. 8. More important, however, is 2. The results of single transformer switching were first
the strongly distorted supply current. presented. The inrush current is most dangerous if switching
occurs at the supply voltage zero crossing. The transformer
exhibits a strongly unsymmetrical magnetization loop, as
compared to the almost symmetrical case of switching at the
voltage peak. The high harmonic content of the current is
evident for any switching time point.
Fig. 19: The individual transformer currents iT 1 (t), 4. Both transformers will need much longer time in order to
reach their steady state condition of symmetrical no-load
iT 2 (t) and the supply current i s (t)
current. The total current needs less than two cycles to reach
following the energization of T 2 , α =0. its symmetrical shape.
1186
9. An increased source parameters will also lead to an
increased interaction between the transformers due to the
common voltage drop across the source internal impedance.
12. Shunt capacitors will also raise the peak value and
increase the harmonic content in the bus voltage. The
distortion is much more pronounced in the capacitor current.
REFERENCES
1187