You are on page 1of 4

GIPAM-10

Features
� Easy installation and simple parameter setting.
� Reliable, high-quality response for your network protection applications.
� Carefully designed and robustly manufactured to work in a severe

environment providing the essential protection functions


� In addition to its protection function, GIPAM-10 Series provide accurate

measurement and monitoring information necessary for efficient


maintenance and post-fault analysis.

● Digital protective relay with the function of protection, monitoring, analyzing,


communication and user interface.
● Fault recording
- Setting relay elements and analyzing fault records are convenient.
- Event records : saving max. 32events
- Fault records : recording the quantity of electricity and the relay elements activated at the
moment of fault
- Wave records : recording 30Cycle, 32Sample/Cycle with DIO operation status

● PC Manager is easy to analyze various faults.


- CU Type : 50/51, 50N/51N, 46 - VO Type : 27, 59, 47P, 64
- CR Type : 50/51, 50N/51N, 46, 79 - NZ Type : 67N, 67G, 64

■ Ratings

Type Specification

Voltage PT: 110V(Max. 0.5VA) GPT: 190, 190/ 3V


Input
Current CT: 1A, 5A(Max. 10VA), ZCT: 1.5mA
Control voltage AC/DC 110/220V(Max. 30W)
Digital input Digital Input, AC/DC 110V
Output
For power AC250V 16A/ DC30V 16A, Resistive Load
For alarm AC250V 5A/ DC30V 5A, Resistive Load
Insulation Resistance Over DC 500V 100
Insulation Voltage AC 2kV (1kV)/for 1 min
Impulse Voltage AC 5kV (3kV) Over 1.2
Overload withstand 2 In for 3 hours, 20 In for 2 seconds
Fast Transient Disturbance Power Input 4kV, Other Input 2kV
Electrostatic Discharge Air 8kV, Contact 6kV
Operation / Storage temperature -10 ~55 (14 F~131 F)/-25 ~70 (-13 F~158 F)
Humidity 30% ~ 80%
Others 1000m and below, Non-impact place Non-air pollution place
Standard IEC 60255, KEMC 1120
Weight 3 kg
■ Protection Functions Overview
Type Function Device No. GIPAM-10CU GIPAM-10CR GIPAM-10VO GIPAM-10NZ
OCR 50/51 ● ● - -
OCGR 50/51N ● ● - -
NSOCR 46 ● ● - -
Reclosing 79 - ● - -
Protection OVR 59 - - ● -
UVR 27 - - ● -
POR 47P - - ● -
OVGR 64 - - ● ●
SGR 67G - - - ●
DGR 67N - - - ●
Latching 86 ● ● ● ●
Trip Indication ● ● ● ●
Control & Supervision Event Recording 32 EA
Fault Recording 32 EA
Wave Recording 4 EA (32 Samples/Cycle × 30 Cycle)
Communication Modbus ● ● ● ●
Binary Input 5 EA
Inputs/Outputs
Binary Output 4 EA (2: Power, 2: Alarm)
PC Interface USB mini B ● ● ● ●

■ Measurement

Measurement Display range Accuracy Applicable models


±0.5(%) at Vn
Phase voltage (V) 0.000V ~ 999.999kV GIPAM-10VO
±0.5(%) or ±1(V) at Other Voltagerange
The entire range of measurement
Line voltage (V) 0.000V ~ 999.999kV GIPAM-10VO
±0.5(%) or ±1(V)
The entire range of measurement
Zero Phase voltage (Vo) 0.000V ~ 999.999kV GIPAM-10VO/10NZ
±0.5(%) or ±1(V)
±0.5(%) at In.
Phase current (A) 0.000A ~ 999.999kA GIPAM-10CU/10CR
±0.5(%) or ±0.05(V) (5A rating), ±0.001A(1A rating) at Other Currentrange
±0.5(%) at In.
Zero Phase current (In / lo) 0.000A ~ 999.999kA GIPAM-10NZ
±0.5(%) or ±0.05(V) (5A rating), ±0.001A(1A rating)
±0.5(%) at In.
Reverse Phase voltage (V2) 0.000V ~ 999.999kV ±0.5(%) or ±0.05(V) (5A rating), ±0.001A(1A rating) GIPAM-10VO

■ Operating
Protective Function Setting Range Operating Time (sec) Curves
CT 5A : OFF, 5~100/1A
Inst. OCR (50) 0.04~60.0/0.01s
CT 1A : OFF, 1~20/1A
CT 5A : OFF, 1~12/0.1A
Time OCR (51) 0.05~1.2/0.1s (SI, VI, EI, LI), 0.10~60.0/0.01s (DT) DT, SI, VI, EI, LI
CT 1A : OFF, 0.2~2.4/0.1A
CT 5A : OFF, 2.5~40/0.1A
Inst. OCGR (50N) 0.04~60.0/0.01s (Block Time : 0.1~60.0sec/0.1)
CT 1A : OFF, 0.5~8/0.1A
CT 5A : OFF, 0.5~5/0.1A
Time OCGR (51N) 0.10~60.0/0.01s DT, SI, VI, EI, LI
CT 1A : OFF, 0.1~1.0/0.1A
CT 5A : OFF, 0.5~5/0.1A
NSOCR (46) 0.10~60.0/0.02s
CT 1A : OFF, 0.1~1.0/0.1A
Number of auto-reclosures : Up to 4
Auto-reclosure (79) 1st~4th Shot Delay : OFF, 0.1~200/0.01s
Reclaim Time, Prepare Time : 0.1~200/0.01
Operating Mode : 3Phases OR 3Phases AND
UVR (27) 0.10~60.0/0.01s
Pickup : 10~110/1V
OVR (59) Pickup : 60~160/1V 0.10~60.0/0.01s
OVGR (64) Pickup : 10~110/1V 0.10~60.0/0.01s
Overvoltage (47P) Pickup : 5%~100%/1% 0.10~60.0/0.01s
Pickup (Io) : 0.9~6.0/0.1mA
SGR (67G) Pickup (Vo) : 10~80/1V 0.10~60 0/0 01s
Angle : 0~90/1。
Pickup (In)
CT 5A : 0.5~5.0/0.1A
DGR (67N) CT 1A : 0.1~1.0/0.1A 0.10~60.0/0.01s
Pickup (Vo) : 10~80/1V
Angle : 0~9。/1。
Dimension (mm)

1∞
35 37.5
Terminal (GIPAM-10 Series)

(81.82)
27.5

<Top view>
90
100 15 177 25 80 80
M5
4-
240

195

220

220
213
8
14.5

<Front view> <Side view> <Back view> <Cut size>

Characteristic Curves

SI curves for OCR, OCGR VI curves for OCR and OCGR


100 1000

100
10
Operation time, sec
Operation time, sec

1.2 10

0.6
1 0.4
0.3
0.2
1
1.2
0.1
0.6
0.4
0.05 0.3
0.1
0.2
0.1
0.1

0.05

0.01 0.01
1 10 20 1 10 20
Current in multiples of set current, I / Is Current in multiples of set current, I / Is

EI curves for OCR and OCGR LI curves for OCR and OCGR
1000 10000

100
1000

10
Operation time, sec

Operation time, sec

100

1.2 10
0.6 1.2
0.1 0.4 0.6
0.3 0.4
0.2 0.3
0.1 0.2
1
0.01 0.05 0.1

0.05

0.001 0.1
1 10 20 1 10 20
Current in multiples of set current, I / Is Current in multiples of set current, I / Is
Wiring

A B C A B C A B C
GIPAM-10CU GIPAM-10VO GIPAM-10NZ
VA1

VA2 VA IN1

IA1 VB1 IN2 IN


VB1 VB
IA2 IA
VC1
IB1
VC IO1
IB2 VC2
IB
IC1 VO2 IO2 IO
ZCT
IC2 IC VO1 VO
IN1
IN2 IN VO2
CLA VO1 VO

50 51 50 51 27 59 67N 67G

50N 51N 50N 51N 47P 64 64

46 46 79

GIPAM-10CU GIPAM-10CR GIPAM-10VO GIPAM-10NZ

Odering

GIPAM-10 CU RS M 5A 60Hz AC/DC88~264V DI_AC/DC110V

Protection Element Communication Frequency Control Power Digital Input


CU 50/51,50N/51N,46 Media 50Hz AC/DC 88~264V AC/DC 110V
RS RS-485
CR 50/51,50N/51N,46,79 60Hz
VO 27,59,47P,64
NZ 67N,67G,64 Protocol Rated CT
M MODBUS 1A
5A

LS constantly endeavor to improve our products so that information in this HEAD OFFICE
catalog is subject to change without notice. LS Tower 1026-6, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do
431-848, Korea
Tel. (82-2)2034-4901, 4376, 4645 Fax. (82-2)2034-4648
GIPAM-10 (E) 2012.10 (01) 2012.10 Printed in korea STAFF