WARNING, CAUTION, DANGER

BEFORE OBTAINING ACCESS TO TERMINALS, ALL SUPPLY CIRCUITS MUST BE


DISCONNECTED.
 THIS APPLIANCE IS NOT FOR USE BY PERSONS (INCLUDING CHILDREN) WITH REDUCED
PHYSICAL, SENSORS OR MENTAL CAPABILITIES, OR LACK OF EXPERIENCE AND Power LED
KNOWLEDGE, UNLESS THEY HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION
CONCERNING USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR HEIR SAFETY. Alarm LED
 CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE
APPLIANCE. Pre-Alarm LED
Technical Specification:
Voltage……………………………………... Either 230VAC ± 10% 50/60Hz at 1.5VA.
Reset Button
Fusing…………………………………… Mains input is fused at 3A with 20mn cartridge fuse,
supply voltage is cut off in the event of over voltage. Manually reset.
Relay Rating……………………………….. 6A 250VAC—5A 30VDC resistive
Sensor……………………………………… Catalytic
Pre-Alarm Level…………………………... 10% L.E.L. adjustable from main panel
Alarm Level………………………………... 15% L.L.L. adjustable from main panel.
Monitoring………………………………….. Pre-Alarm, Alarm
Local or remote operation of Relays ……. Local from sensor or remote.
Operating Temperature…………………….. -15 to 45ºC within 0 to 90% RH non condensing QR Code Indicates:
Terminal cable size……………………….. 1.5mm GAS LEAK SENSOR:
Approvals……………………………………. EN601010 & IEC60335-1 Device Type
 Catalytic Gas Sensor
Mooting……………………………………... Surface Serial No. ****
Size………………………………………….. 98 x 98 x 49mm deep Production Date ****  230V AC—power supply
ABS housing IP Rating…………………… IP32 www.EDS-ESL.com
 Internal Sounder and relay
Info@EDS-ESL.com
 Both Industrial and domestic use

*To Test detector Set-up hold Rest button for two seconds,
until sounder operates.
Installation:
The sensors should not be installed:
A. Where it can be splashed with water.
B. In direct air from a fan.
C. Near an open window.
D. Above Cooking Stove.
E. Where water can drip on it.
F. With any obstacle in front of it.
G. In direct sun light.
*Sensors should not be installed more than 300mm from the ceiling in the
case of methane or 300mm from the floor.
*Sensor should not be installed closer than 1.4M from a door or a 100mm
from a Gas stove.
*Kitchen ventilation should be taking into account in the siting of the sensor
to avoid any gas leak from the stove being sucked out through the
ventilator.