WARNING, CAUTION, DANGER

BEFORE OBTAINING ACCESS TO TERMINALS, ALL SUPPLY CIRCUITS MUST BE


DISCONNECTED.
 THIS APPLIANCE IS NOT FOR USE BY PERSONS (INCLUDING CHILDREN) WITH REDUCED Power LED
PHYSICAL, SENSORS OR MENTAL CAPABILITIES, OR LACK OF EXPERIENCE AND
KNOWLEDGE, UNLESS THEY HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION Alarm LED
CONCERNING USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR HEIR SAFETY.
 CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE
Reset Button
APPLIANCE.
Technical Specification:
Voltage……………………………………... Either 230VAC ± 10% 50/60Hz at 1.5VA.
Fusing…………………………………… Mains input is fused at 3A with 20mn cartridge fuse,
supply voltage is cut off in the event of over voltage. Manually reset.
Relay Rating……………………………….. 6A 250VAC—5A 30VDC resistive
Sensor……………………………………… Catalytic GAS LEAK SENSOR:
Alarm Level………………………………... 15% L.L.L. adjustable from main panel. QR Code Indicates:
Monitoring………………………………….. Alarm.
Local or remote operation of Relays ……. Local from sensor or remote. Device Type
Operating Temperature…………………….. -15 to 45ºC within 0 to 90% RH non condensing  Catalytic Gas Sensor
Serial No. ****
Terminal cable size……………………….. 1.5mm
Production Date ****  230V AC—power supply
Approvals……………………………………. EN601010 & IEC60335-1
Mounting……………………………………... Surface www.EDS-ESL.com
 Internal Sounder and relay
Size………………………………………….. 98 x 98 x 49mm deep
Info@EDS-ESL.com
ABS housing IP Rating…………………… IP32  Both Industrial and domestic use
*To Test detector Set-up hold Rest button for two
seconds,
until sounder operates.

Installation:
The sensors should not be installed:
A. Where it can be splashed with water.
B. In direct air from a fan.
C. Near an open window.
D. Above Cooking Stove.
E. Where water can drip on it.
F. With any obstacle in front of it.
G. In direct sun light.

*Sensors should not be installed more than 300mm from the ceiling in the
case of methane or 300mm from the floor.
*Sensor should not be installed closer than 1.4M from a door or a 100mm
from a Gas stove.
*Kitchen ventilation should be taking into account in the siting of the sensor
to avoid any gas leak from the stove being sucked out through the
ventilator.