40
12.60
1.70 1.10 1.60 1.00
CONSTRUCTION NOTES: 1.20 10.10 1.20
LADDER
SEE DETAIL E
*VERIFY SPECIFICATION
a
A. GENERAL
1.20
1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS
OTHERWISE SHOWN OR NOTED, MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL
3.00
CONDITIONS.
2. SHOP DRAWINGS WITH ERECTION & PLACING DIAGRAMS OF ALL STRUCTURAL STEEL,
5.40
5.40
MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC. SHALL BE SUBMITTED FOR ENGINEER'S
4.20
APPROVAL BEFORE FABRICATION.
4.40
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN, CHECK
5.40
2.40
WITH MECHANICAL OR ELECTRICAL CONTRACTORS FOR CONDUITS, PIPE SLEEVES, ETC, TO
BE EMBEDDED IN CONCRETE.
SHORING & BRACINGS OF THE STRUCTURE FOR ALL LOADS THAT MAYBE IMPOSED DURING
CONSTRACTION.
1.00
B. CONCRTE AND REINFORCEMENT
a
1. ALL MATERIALS & WORKMANSHIP SHALL CONFIRM WITH THE LATEST BUILDING CODE OF
CHLORINE REACTION TANK (CONCRETE)
AMERICAN CONCRETE INSTITUTE (ACI - 318)
CHLORINE REACTION TANK (CONCRETE)
SECTION AT A
S C A L E 1 : 1 0 0 M T S
2. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT THE END OF
TWENTY EIGHT (28) DAYS WITH CORRESPONDING MAXIMUM SIZE AGGREGATE AND SLUMP
L A Y O U T
S C A L E 1 : 1 0 0 M T S
AS FOLLOWS:
FOUNDATION AND 3
3000 PSI IN. (19MM) 4 IN. (100MM)
RETAINING WALL 4
C1F1 C1F1 C1F1 C1F1 C1F1
ALL OTHERS
INCLUDING BEAMS, 3000 PSI 3
IN. (19MM) 4 IN. (100MM)
4
SUSPENDED SLABS &
COLUMNS
SLAB ON GRADE
3. ALL REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 40 FOR DIA.20MM & 16mmØ- G40 TOP BAR SPACED AT
4.40
SMALLER BARS & GRADE 60 FOR DAI. 25MM & LARGER BARS. COLUMN HOOPS ARE ALL 200mm ON CENTER BOTHWAYS
GRADE 40 BARS. 20mmØ - G40 BOTTOM BAR SPACED AT
200mm ON CENTER BOTHWAYS 1.25
4. IN GENERAL, THE LATEST EDITION OF ACI - 315, MANUAL OF STANDARD PRACTICE C1F1 C1F1 C1F1 C1F1 C1F1
DETAILING REINFORCED CONCRETE STRUCTURES SHALL BE ADHERED TO UNLESS 0.25 1.00
OTHERWISE SHOWN OR NOTED.
12mm Ø REBAR SPACED
5. MAINTAIN MINIMUM CONCRTE COVER FOR REINFORCING STEEL AS FOLLOWS: AT 200mm ON CENTER
0.45
WHERE CONCRETE IS DEPOSITED
DIRECTLY AGAINST EARTH.............................................2 IN. (50MM.)
1.00
AT 200mm ON CENTER
OTHERWISE SHOWN ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE. HORIZONTAL BAR
3.00 3.00 3.00 3.30 16mmØ - G40 REBAR SPACED
AT 200mm ON CENTER
D. FOUNDATION
VERTICAL BAR
20mmØ - G40 REBAR SPACED
1. FOUNDATION IS DESIGNED FOR ASSUMED ALLOWABLE SOIL BEARING CAPACITY OF : AT 200mm ON CENTER
BU - 5,000 PSI; BA - 2,000 PSI B2 B2 B2 B2
2. FOUNDATION SHALL REST ON NATURAL SOIL. UNLESS OTHERWISE NOTED BY THE
ENGINEER, NO PART OF THE FOUNDATION SHALL REST ON FILL.
3.THE CONTRACTOR SHALL NOTIFY THE ENGINEER AFTER FOOTING EXCAVATION HAVE
4.40
B2 S1 B2 S1 B2 S1 B2 S1
BEEN COMPLETED & PRIOR TO CONCRETING TO CONFIRM THE DESIGN SOIL BEARING 0.20
CAPACITY. B2 DETAIL- E
S C A L E 1 : 1 5 M T S
B2 B2 B2 B2
CONTRACTOR: DESIGNER: CHECKED AND APPROVED BY: PROJECT TITLE : PHASE: SHEET CONTENTS: SHEET NO.:
0.25
WALLS:
PROVIDE HOOK EVERY 1.00 METERS; BOTHWAYS
BEAM DESIGN
SUPPORT MIDSPAN
BEAM NO. NUMBER OF TIES
0.25
REINFORCEMENTS REINFORCEMENTS
B2 3 - 20MMØ 2 - 20MMØ
1.30
USE 10MM Ø STIRRUPS SPACED 1 @ 0.025M., 5 @ 0.05M.,
2 - 20MMØ 3 - 20MMØ 5 @ 0.10M., REST AT 0.15M., ON CENTER
0.25 X 0.45
1 = SPAN
S
2 1
2 2
1
C:\Users\rachelS'leyson\Desktop\Baring.jpg
= SPAN'
E = WIDTH OF ROOF EAVES
LATERAL TIES
5- 10mm Ø AT 0.05M ON CENTER
5- 10mm Ø AT 0.10M ON CENTER
REST AT 0.15M ON CENTER
HEIGHT IN METERS
0.20
COLUMN REBARS
8 - 20mm Ø REBARS
TOP SLAB DETAIL
S C A L E 1 : 2 0 M T S
HORIZONTAL BAR
16mmØ - G40 REBAR SPACED
AT 200mm ON CENTER
VERTICAL BAR
20mmØ - G40 REBAR SPACED NGL
0.90
C1 USE 10MM Ø TIES (2 SETS) SPACED 5 @ 0.05M.,
8 - 20MMØ
1.20
5 @ 0.10M., REST AT 0.15M., ON CENTER
0.25 X 0.40
0.25
COLUMN FOOTING DESIGN
0.30
MIDSPAN
BEAM NO. REINFORCEMENTS NUMBER OF TIES
WALL DETAIL
CHLORINE REACTION TANK (CONCRETE)
S C A L E 1 : 2 0 M T S
MEMBRANE TANK (CONCRETE)
COLUMN-FOOTING DETAIL
S C A L E 1 : 2 0 M T S
CONTRACTOR: DESIGNER: CHECKED AND APPROVED BY: PROJECT TITLE : PHASE: SHEET CONTENTS: SHEET NO.: