The Expert of Heat Pump Water Heater And Cooling System

Air Source Heat Pump


(Cold Water+Hot Water)

User Manual
Do not install by users, installation should be
done by dealer or the authorized Installation
Company, or it will affect machine
Warning performance.

We reserve the rights for our products improvement without prior notice! Before using, please read the user manual carefully and keep it for future reference!
WIRE DIAGRAM

Catalogue

Circulation water pump

Water flow switch


Water flow switch
Terminal-2
N
Introduction of Products........................................................1

*** For circulation type heat pump,no need connect water pressure switch,thermostat and water output temperature meter
User Guide...........................................................................2

Installation............................................................................5

High pressure switch

Low pressure switch

Cover
Introduction Diagram...........................................................10

Water output temperature

*** All power output can not connect to big machine,electric heater needs add A/C connector
Error Code Table.................................................................11

Public point
High pressure

Water flow switch

Anti frozen switch

High water level

Low water level


Compressor

Low pressure

*** The public point between water level and high-low pressure is forbidden to connect.
Public point
Crank heater

Function Description............................................................12 Water supply pump

To wire controller
Thermostat
Electric heater

Electronic expansion valve 1


Introduction For Display Board............................................15
Anti frozen

Anti cold air

4-way valve

Introduction For Parameter.................................................18 Water pump


Output water temperature

Fan Discharge temperature 1

Output 2(Blue)
Wire Diagram......................................................................19

4-way valve
Defrosting temperature

Output 1(Blue)
White
Suction temperature

Blue
Return water temperature

Input(Red)

TR
Ambient temperature

Current
N

NC
NC
A1
A2

Compressor
White

L3
Red

L3
C

L2
L2

L1
Blue
S

L1

Yellow/Green
AC Connector R
(220V/50Hz coil)

Fan
Capacitor
Black White

M
Yellow/Green
Terminal-1

Yellow/Green
GND
N
L

220V/50-60HZ ~

21
WIRE DIAGRAM INTRODUCTION OF PRODUCTS

Air-source pump water heater apply the air source pump theory, The refrigerant absorb the

Circulation water pump

Water flow switch


Water flow switch
For double system

Terminal-2
heat from air ,and compress into the gas with a high pressure and temperature by

N
compressor, then transmit the heat to water by heating exchanger, it is a effective way to heat

For circulation type heat pump,no need connect water pressure switch,thermostat and water output temperature meter
ⅠThe advantages of recycle commercial HPWH

1-Temperature of water is easy to adjust ,and have a wider apply even in all kinds of projects
2-Having a high stability in water yield.
High pressure switch 1

Low pressure switch 1

Low water level

High water level


Water flow switch
High pressure switch 2

Low pressure switch 2


Public point

Public point
Anti frozen switch

All power output can not connect to big machine,electric heater needs add A/C connector
To wire controller
Fan 2 3-The heating exchange system have a constant water recycle ,it will make a adequate water

The public point between water level and high-low pressure is forbidden to connect.
Fan 1
Electronic expansion valve 2
exchange.

4-It is faster and more convenient for user.


Current 2

Crank heater

Output water temperature


Electronic expansion valve 1

Compressor 2
Discharge temperature 2
Water output

Compressor 1
Discharge temperature 1
ⅡThe Applicable scope
Defrosting temperature 2

Anti frozen
Suction temperature 2
This product can work in all reasons all-day, without the effect of weather, using in the
temperature of -7~43(-25~43 is available), applied in residential area, villa, public bathing room,
Thermostat

Anti cold air Defrosting temperature 1


Current 1

Suction temperature 1 swimming pool, hotel, school, hospital ,factory ,and so on.
4-way valve

Return water temperature

Water supply pump


Ambient temperature
Output 1(Blue)
CN1

CN3
CN2

Output 2(Blue)

Water pump
Input(Red)

2#AWY

1#AWY
ⅢThe feature of products
Electric heater
B phase
Three

C check

TR

1-Energy saving:The energy consumption is only 25% of same capacity electricity heater
A

2-Security:The heat of air-source pump water heater come from air ,not the electricity or other
fuel, avoid a danger from electricity leakage ,dry-burning explosion, poisoning.
Brown

Blue
Red

Fan 2
Black White

Capacitor
M

3-Environment protection: There are no polluted gas for using the air sources heating, belong to
Yellow/Green

green environmental products


Fan 1
Black White

Capacitor
M
Yellow/Green

4-High Tech: adapt the microcomputer control system ,melt the frost intelligently, with a strong
To low pressure switch 1

To high pressure switch 2

2
Compressor 1 Yellow/Green Compressor

adaptability
NC
NC
A2
A1

White
T3 T1

Red Red
T2

Brown Brown

Blue Blue
To low pressure switch 1
Relay
AC Connector

To high pressure switch 1


NC
NC
A2
A1

T3 T1

Red Red
M
T2

Brown Brown

Blue
Blue
AC Connector

Relay

Yellow/Green
Yellow/Green
(2)Double system

Terminal-1

380-440V/50-60Hz~

20 1
USER GUIDE WIRE DIAGRAM

Notice:

Terminal-2

Circulation water pump

Water flow switch


Water flow switch
N
1-Do not put hands or other things in fan exit ,or high speed fan will endanger your safety
2-Avoid the moisture from electricity control system, or it will cause short circuit
3-After washing filter, fix it as the former, forbid running without filter, or it will affect the effect.

4-Tthe flashlight and other electromagnetic radiation source will affect the machine, if it occurs

High pressure switch

Low pressure switch

Cover

For circulation type heat pump,no need connect water pressure switch,thermostat and water output temperature meter
, pls cut off the power,and restart it when the phenomenon disappears.

5-Do not stock or cover the exhaust exit or the space of machine.

Water output temperature


High pressure

Anti frozen switch


Low pressure

Water flow switch

High water level


Low water level
Compressor

Public point
Public point
Crank heater

Safety Notices
Water supply pump

All power output can not connect to big machine,electric heater needs add A/C connector
Please make sure you have read this guidance before using, pls operate it according this

Thermostat

To wire controller
Electric heater

Electronic expansion valve 1


guidance.

The public point between water level and high-low pressure is forbidden to connect.
Water input valve

Water return valve

Warning: 4-way valve

Water pump
Output water temperature
Wrong to operate this machine will cause the accident of death, injure, harmfulness
Fan Discharge temperature 1

4-way valve

Output 2(Blue)
Defrosting temperature

Output 1(Blue)
Notices Suction temperature

White
Improper to use machine will result accident, the harm of machine ,and degrade the

Blue
Return water temperature

performance of machine ,please read the label of mainframe . any abnormal condition ,l ike

Input(Red)

TR
Ambient temperature

phase
Three

check
abnormal noisy, oder,smog ,rising temperature, electricity leakage, visible fire, please cut off

C
A
B

Current
N
the electricity ,call the dealer or provider ,if need ,please call the apparatus ,

Brown
Red

Blue
Warnings

NC
NC
A1
A2
1-Do not install by user himself, installation should be done by dealer or the authorized White

Compressor
T1
Red Red

M
Installation Company, or it will affect machine performance.

T2
Brown Brown

T3
Blue Blue
2-Except the professional direction, any unprofessional persons are not allow to open the

Yellow/Green
Relay
AC Connector
machine, or which will damage the machine. If the electricity wire is broken ,please call the
appointed maintenance center or professional engineer to change.\

Capacitor
Black White

Fan 1
3-Do not use the flammable substance, like oil, alcohol, paint, petrol, which can cause fire.
4- Put the main power switch in the place out of touch of child in case of any danger.
(1)Single system

Yellow/Green
5-Do not sprinkle any water or liquid on machine in case of the electric shock

GND

Yellow/Green
R

N
S
T
6-Do not touch machine with wed hand in case electric shock
7- Switch off in stormy weather in case flashlight shock
8-Please cut it off when stopping using . 380-440V/50-60Hz~

2 19
INTRODUCTION FOR PARAMETER USER GUIDE

9-Do not cut it off when machine is running


A0 Environment temperature b0 Environment temperature 10-The machine need a separated electricity source switch and a special power line as well,
A1 Return water temperature b1 Return water temperature and use appointed line for power supply, which should equipped with circuit breaker(with
A2 Compressor 1 suction temperature b2 Compressor 2 suction temperature power leakage breaker)
A3 Compressor 1 defrosting temperature b3 Compressor 2 defrosting temperature
11-Using a regulated wire, connect the ground safely, and avoid touching of the water pipe,
A4 Compressor 1 discharge temperature b4 Compressor 2 discharge temperature
gas pipe , telephone line, lightning conductor.
A5 b5 Return water temperature
Output water temperature Output water temperature 12-The machine must keep a proper distance with building in a reasonable line arrangement:
A6 b6
Compressor 1current Compressor 2 current the mix distance is 800mm.
A7 b7
A8 13-As for the firm line's equipment , please use a international standard switch (The safety
Electronic expansion valve 1 open Electronic expansion valve 2 open international standard 24.3),or install a all-pole disconnection switch which can be closed or
A9 percentage /4 b9 percentage /4 cut by user, and contact to electricity source ,more detail , please refer the picture of circuit
line.
14-The equipment should connect the all-pole disconnection switch with at least 3mm gap in
touching point.
15-The equipment should be installed according to national wiring rule.
16-The electricity wire extending from electricity box ,should attach a leakage circuit breaker.
and the rate current should be equal or more 1.5-3 times than the machine one

Using notice
1- Do not open or cut off the machine frequently to avoiding any harmfulness to machine
2-The machine' operating parameter and the settings of protection device is ready after
factory, please do not change it casually, and protect the protection units from short circuit ,
or it will damage the machine
3-The refrigerant used in the machine non-poisonous and non-flammable, due to it is heavier
than air, the refrigerant will cover on floor when leakage. so please keep a good air fluency to
avoid choke.
4- When cleaning the machine, to wipe it with neutral water, do not using acidic material or
alkaline material which can cause a color-fade and malfunction the button
5-If having the leakage of refrigerant, please contact with the maintenance center, and notice,
do not have any visible fire in working site ,because the refrigerant will decompose the
poisonous gas when meeting the fire
6-Stop the machine and keep the connection with electricity under the 0℃ weather for
protecting the water system pipe from frost freezing, if customer will stop using for a long
time ,please cut off the power source and exhaust the water.

18 3
安装说明书
USER GUIDE INTRODUCTION FOR DISPLAY BOARD

7 -The water switch have a great protect importance to the cooling water system ,so the Timer setting:
machine should attach a standardized switch and import the protection signal into output Touch this key to enter to set main unit Timer ON/Timer OFF. At the beginning, adjust
block of water switch, as for the exterior connection system of water pump, please input the
the first phase Timer ON, press to adjust Hour, Touch timer key again, press to
signal into corresponding terminals, and should keep the electric-control board a good
adjust Minute. Touch timer key again, adjust the first phase Timer OFF, press to adjust
sensibility to water pump
Hour, Touch timer key again, press to adjust Minute.
8-Do not start the compressor frequently for extending the longevity of machine (no more
Touch timer key again to enter to, second phase Timer ON/Timer OFF.
than 5 times in one hour),
All Timer ON/OFF finish to quit, the marks will show on the display.
9- DO not pull or distort the electricity wire for avoiding any shock case
10 In case of any accidents, please do not touch any electricity units or buttons when Show it is the timer for first phase

machine is working COLD/HEAT CMP ON

Set Out
11 If there are any problems about machine , please do not mend it by yourself ,and call the
serviceman or sales center , any unprofessional mend will arouse the damage of machine or
even people safety events
Timer on for first phase ON

12- please maintain the machine according to the direction book for keeping a good state of
machine

Other safety knowledge Timer Function

1- please read all safety cautions before using the machine


2-please obey the rules of safety cautions strictly during using
3-The machine should need a unique electricity source separating from other machine , and
please using standardized wire when connecting , as well as a corresponding specified GCB
Timer cancel:Touch Timer for 3S,all timer will be cancelled
4- when wiring ,please obey the rule of separation of force electricity and weak electricity..
Time setting:On condition of no timer, touch Timer for 8S,enter to time set when
5- Please strictly using the regular fuse ,iron wire or copper wire is unavailable.
there is a sound from bullze. First adjust Hour, touch Timer again, adjust Minute. Quit
6-The machine should using specified earth wire, and do not contact with gas and water pipe
automatically if no touch for 5S
,or lightning conductor , also the electricity shock will be aroused for an unreasonable or
infirmed connect.
Manual defrosting: When unit is working, touch for 8S,enter to defrosting.
7-The machine should remove the fire danger , when it happens : firstly, to cut off the
electricity source and eliminate the fire Quit when coil temperature properly or reaches defrosting time

8- Cut off before mending the machine.


9- Do not touch the tubes of exhaust with hand , it will scald you with more than 100 degree
temperature
10-Avoid touching the sharp wing and edge ,there are harmful
11-DO not move the machine without the guidance of professional person, it will damage the
machine ,even cause the people hurting
12- Forbidding to touch the revolving fan blade ,, it will cause the damage or hurt 13- DO not
put any things on machine, avoid the drop when machine run ,it will hurt worker or people

4 17
INTRODUCTION FOR DISPLAY BOARD INSTALLATION

COLD/HEAT d0 real parameter CMP ON


Installation Direction of Air source Pump Water Heater
Set Out
Ⅰ-The making of equipment base.
1-The cement concrete base, demands:
1)-the surface should be solid ,firm and leveling ,and bear the weight as large again as the
equipment
2)-During building the base ,please have these handle : put in helical binding with a 9.5 mm
diameter, bundled them in two layers ,keep a 10cm width between two steels.
3)-When build a cement base on floor, please keep the surface coarse and construct after
cleaning and keeping an adequate water.
Check d0 parameter 4)-The cement base should be mixed at the rate 1: 2: 4 for a solid according to the size
and embed numbers of specific Anchor Bolt, after construction, should keep the level of
surface.
Timer Function
5)-Tthe surface should have the water-proof handle, around it , there are reasonably trench
drain leading to the entrance with a certain slope (>0.5°)
To check parameter directly 6)-To install the machine after the base has dried
7)-Keep the equipment balance and add a anti-vibration pad between the bottom of
Setting parameter equipment and base , these measures are to keep the machine running in a less noise and a
good state
Press the key of ″set ″ over 10 seconds, move finger enter into parameter setting when there 8)-Take the measure of location, to avoid the distort and crack of machine causing from
is a sound from ″beep ″. Then press the key of ″set″again, to enter the next parameter
displacement because of a long-term using.
setting. The parameter will change by press the key   .It automatically exit after 10 seconds
without operation . Remarks:
P0 parameter setting
Parameter description: COLD/HEAT CMP ON a, the base should be higher than ground at 100mm;
1. Current protection value: Unit is Set
b, the height of base should reach more than 200mm,
Out
ampere, when the parameter is set to c , keep a level base (the slope <0.1%)
0, the current protection function is 2-welding a bearing with channel ,I-beam, angle iron ,the bearing should be firm
cancelled.
2. Dis water temperature difference: Remarks: and can stand the weight whether the machine is quiet or running , it is done to
the difference temperature between reduce the effect to around.
the dis and the water tank, only the
electronic expansion valve use. Ⅱ The conditions of installation place
1-keep a enough space for machine and installation,
3. Mode selection: press the key ″+″
for 10 seconds, to select cooling / 2 - A strong wind is unavailable, and has no obstruction in air entrance and exit
Check P0 parameter
heating mode. 3- Keep the surroundings dry;
4-The bearing should be firm and can stand the weight, with a flat surface ,reduce the shake
Timer Function and noisy
5- Keep the noisy and exhausted wind away from people
Press the button for around 10S to set parameter 6- Keep away from fuel gas, and easy to connect the pipe and other attached machine

16 5
INSTALLATION INTRODUCTION FOR DISPLAY BOARD

1.Drawing of display board


Ⅲ Open machine and examination

Remarks: before installation, please check the components, and make sure everything is
ready, Setting Temp. Water Temp.

1-Check the surface of equipment, it should be completed, without moisture, Error


COLD/HEAT CMP ON
2-Check whether the name ,specification ,size is right ,the using direction and qualified
Set Out
certificates are completed , as well ,keep the attachment same as the loading list
3-Check the equipment about the below contents:

Check items Check details Check items Check details ON OFF

1 whether the Sheet metal is Timer


1 whether the machine
distorted or impacted by other reach insulated standard
The total
things; ; 2-whether the earth wire
machine the fan Time
2 Whether the tubing kits is and motor electricity wire
motor
completed; are firm Timer Function
ON/OFF
3 Whether the accessories is
completed; Setting timer
4 Whether the refrigerant disclose Up/Down
Setting and check parameter
1-whether the circuit and contactor
are completed ,as well ; 1-whether the fan blade
2. Operation
Electricity 2-whether the electricity wire of become deformed;
controller the fan a.Unlock: Press any key ( except on/off key ) over 3 second, move finger for unlock when
contactor and earth wire is firm; 2-whether the motor is
ina good state there is a sound from ″beep″.
3-Whether the joint of plug-ins on
circuit are firm b.ON/OFF: Press the key of ″on/off″, Under Off, press the key to enter ON; under ON,
press the key to enter OFF; OFF mode can not see water temperature and set temperature.

4 Take the records of inspection c.Water temperature set:Under ON, press the COLD/HEAT CMP ON

key      to adjust water temperature. At the Set Out

Accessories name
processing, the symbols of ″set temperature″
1-outside packing will flash and the set water temperature will
Machines examination
2-whole unit examination change.
ON
3- PCB examination
4-fan and motors examination d.Parameter check: Under On, press the key of
5-others
Function to check running parameter.
1-User Manual
Technical Docs
2-Warranty Card
examination
3-Others Timer Function

Problems and treatments


Checked by

6 15
FUNCTION DESCRIPTION INSTALLATION

d. Return water sensor fault: The machine is stop.


e. Suction sensor fault: Stop and the display board shows error code. The machine is running
5 -The space of installation : please leave enough space during
properly after recover. installation
7.Lose/ incorrect phase protection: All the parts of machine are not allowed to work. The display
board shows error code.
When the discharge temperature > 110 ℃, the machine will stop and alarm. When the default
recover after the temperature dropped below 90 ℃. Only within one hour more than 3 times, the
controller will lock this default.
The compressor can not re-start whether or not pressure switch reset. The display board shows
error code.
When the discharge temperature have failed, the compressor continue to run, but all the function
of discharge has been cancelled.
When there is communication fault, the control shows code ( E9 ). If the accident (such as
disconnection, etc.) lead to communication fault, after the failure of the repair, it automatically
eliminate the display of fault code.
10.In/out water temperature difference protection: After the water pump running 1 minute, if the in
and out water temperature difference > P8℃, the compressor immediately stop. The display
board shows ″15 code ″. Within one hour, if appears 3 times, it will lock and can not reset. Remarks: Do not cover on air outlet of machine. Please keep the distance more than 200mm
11.Out put water temperature protection: After the compressor running 220 seconds, if the out when the barriers above the unit. Please keep the distance less than 400mm between the
put water temperature keep 3 seconds > 70℃ or <5℃,the compressor immediately stop. The head of unit when its surroundings are full of the stacked objects..
display board shows ″18 ( too high) and 20 ( too low ) ″.It automatically reset after 3 minutes,
6-Lifting and Packing.
but lock within one hour for 3 times.
Each unit is tested and inspected strictly when ex-works to make sure its function and quality,
12.Current protection: It will detect current after the compressor running 20 seconds. When the
current of compressor > the current protection values or when the current is 0,the machine will so it must be carefully when installation, especially can not damage the control system and
stop and alarm. It automatically reset after 10 minutes, but lock within one hour for 3 times, and pipeline. It should be make the transporting scheme before the lifting, which include entering
it is no longer run. date, packing size, weight, transport routing, obligate hole and lifting equipment. Please see
13.Return air temperature protection: After the compressor running 1 minute, if return air the following form:
temperature <7℃, the machine will stop and alarm. It automatically reset after 3 minutes, but
lock within one hour for 3 times.
The reference form for the unit lifting
Content Key Checking

1. Corridor, the door of stair and transport routing checking.


transport Routing
2. Roof, underground and lifting routing checking.

1. equipment weight checking


Discharge 2. discharge equipment preparing
3. Temporarily place checking, keep unit cleaning

Adjust the distance of obligate hole and wall when necessary


enable the transport of unit easily.
Others manpower and equipment preparation personnel and
equipment safety

14 7
INSTALLATION FUNCTION DESCRIPTION

Ⅳ the inspection of power source After 60 seconds ,if return water temperature < 5℃, the compressor will be working. The
machine will be off when the temperature of water tank reaches 15℃, otherwise, it is off until 60
1 Before installation ,please check the capacity ,wire, switch of power source ,and maek sure seconds after enter first anti-frozen.
they can support the running of machine. 5.Four-way valves: When cooling power off, heating power on. The compressor is working for 20
2-The power source of machine should extend the electricity wire from power switch , and seconds at the beginning , the four-way valves will power off after 10 seconds. 
make sure the power source and voltage reach the standards 6.Crankshaft heating: If environment temperature < 8℃ and compressor was off over 1 minute,
then crankshaft heating will working. Before 1 minute of the compressor reaches the starting
condition and environment temperature > 10℃,crankshaft heating off. And it off when
Ⅴ- Important notices environment sensor default.
1-safety notices : 7.Auxiliary Electric heater: When environment temperature ≤ 10℃, it starts. When
environment temperature ≥ 12℃, it off.
It will cause safety problem in below install situation
A-The installation site with mineral oil ,like the oil of cutting machine 8.Water pump mode: Normal mode: the return water temperature reaches the set temperature
not stopping. Special mode: the return water temperature reaches the set temperature stopping.
B-The installation site with a lot of salts in the air ,like seaside
C-The installation site with erosion gas ,like the sulfur in spring 9.Defrosting electric heating control: On only defrosting.
D-The installation site with a heavy fluctuation in voltage and current ,like the factory 10.Safety valve control: When environment temperature > 5℃ and discharge temperature >
E-The car or cabin ,some place similarly 105℃, it starts. When environment temperature < 5℃ and discharge temperature >5 ℃ return
F-The kitchen with a lot of oil gas water temperature, it starts. When discharge temperature < 2 ℃ return water temperature, it
closes.
G-The installation site with a strong fluctuation of electromagnetic wave
H-The installation site with flammable gas and material 11.Anti cold wind relay: On cooling starts. On heating, if return water temperature ≤35℃ ,it
closes. But > 37℃, it starts.
I-The installation site with the existence of acidic gas or alkaline gas.
J-The installation site with other special conditions Protection function
2-The cautions before installation 1. The compressor have 3 minutes delay protection, the shortest operation time of same
compressor is 90 seconds, the interval for start/ stop of different compressor is 10 seconds.
A-Choose the right carrying way
2. When the circulating water pump running, if the water flow switch off for 10 seconds, the
B-Carry machine at the original package
compressor and water pump will power off. After 3 minutes automatically reset and unlock.
C-If the machine will be installed on metal base , insulate issue must be considered ,and
3. Anti-frozen switch: When anti-frozen switch continued to off for 2 seconds, the compressor
obey the corresponding standards immediately stop. After the anti-frozen switch on, it will automatically resume operation.
4. High pressure protection:( high pressure switch power off ) In 3 times/hour, the display board is
Ⅵ-The key-point of installation not shows ″pressure protection″. After pressure recovery, the compressor re-start after 3
minutes; Over 3 times/hour, the controller will lock this default. The compressor can not re-start
1-Installation Confirm the model ,serial number ,name before installation whether or not pressure switch reset. The display board shows error code.
2- Electricity lines allocation: 5. Low pressure protection: In defrosting not detect the low pressure switch. It will be detect on
A-The power capacity and the route of electricity wire should heating and cooling working after 3 minutes. Then ( high pressure switch power off ) in 3
times/hour,the display board is not shows ″pressure protection ″. After pressure recovery, the
be chose according to design manual ,the diameter of compressor re-start after 3 minutes; Over 3 times/hour, the controller will lock this default. The
machine electricity wire should be larger than the ordinary one compressor can not re-start whether or not pressure switch reset. The display board shows error
B-And make sure whether the earth wire is effective code.

3-Trial running: Only the machine connect the power more 6. Sensor fault:
than 12 h ,can user take a test run a. Environment sensor fault: Stop and the display board shows error code. The machine is
running properly after recover.
4-The connection and installation of machine pipe : when
b. Coil sensor fault: Stop and the display board shows error code. The machine is running
connecting the water inlet pipe and water outlet pipe of properly after recover.
machine , please use two pliers on these two joints ,and
c. Out put water sensor fault: The machine is stop.
make sure the pipes no moving .(refer to following picture)

8 13
FUNCTION DESCRIPTION INSTALLATION

1.Cooling operation: When the mode set cooling, the display board shows ″cooling″.
Operation methods:after turn on the machine, press the + button for 5 seconds to enter. Lifting &Packing Instruction.
Symbols explain: Tw - Return water temperature . Ts - user set temperature.
(1), It should be consider the weight of unit when lifting, the lifting rope load must be more
Compressor ON condition: when Tw = Ts+3℃,turn on two compressors.
2.5 times than the unit weight, the protection pad and wooden bearing should be put on the
Compressor OFF condition: when Tw = Ts-2℃,turn off two compressors.
surface of unit to avoid the scratch and deformation of metal plate surface.
Cooling on process : Turn on → water pump on→ water flow switch detect → fan on →
(2).Keep level position when the units are moved and lifted; heeling more than 20 degree is
compressor 1 on →compressor 2 on
prohibited.
Cooling off process: compressors off → fan off → water pump off( according to the specific
parameter set ) (3).The lifting should be handled with care; the unit must be bear the force equally. It should
be meet the safety regulations of local construction plant when lifting and transportation, it
2.Heating operation: When the mode set heating ,the display board shows″heating″.
Operation methods:after turn on the machine, press the + button for 5 seconds to enter. should be operated by qualified workers with precautionary measures to guarantee the safety
a. Compressor ON condition: when Tw = Ts+3℃,turn on two compressors. of people and equipment.

Compressor OFF condition: when Tw = Ts-2℃,turn off two compressors.


b. Cooling on process : Turn on→ water pump on→ water flow switch detect → four-way valves VII- Water System Installation
on → electric heating on →fan on →compressor 1 on→ compressor 2 on
c. Cooling off process: compressors off →fan off → water pump off ( according to the specific 1-The water pump should be installed indoor of water flowing heat exchanger, the flexible
parameter set ) connection must be used for pipeline and water pump which means the flexible connection
3.Defrosting operation - Heating mode only must be used for inlet and outlet of water pump, Dirt-remover instrument must be installed at
a. Defrosting ON condition: the entrance of unit to guarantee the water quality and prevent the equipment from scaling;
the check valve should be installed on outlet of water pump; 60 item above Y-style filter
1.When the compressor is under the heating or hot water working mode, it starts to clock
when the detect to the outer coil of the temperature is ≤ the low temperature timing of should be installed on inlet of water pump and the block valve should be installed in front of
temperature value ( CO parameter ) . But time cancelled, when the outer coil of temperature is filter.
> the low temperature timing of temperature value. Until 5 minutes, the temperature of outer 2-BY the side of water inlet and water outlet, thermometer and pressure gauge should be
coil is recorded start value. The machine will enter defrost ,when time ≥40 min and coil
installed, so that it will be check easily during the operation.
temperature ≤ 0℃ .
2.If the compressor accumulate to 4 hours, detect the environment temperature is in -5 to 5
℃.It will be enter defrosting but never do it.
VIII. The connection of unit pipeline.
b. Defrosting on process: During the defrosting, the display board shows ″defrosting ″. When
defrosting is working, the compressor is stopping, in put water valve is closing, and until 55
seconds the four-way valves will power off, then the water circulating pump and the compressor 1-Instructions:
will working and the evaporator fan will stopping.
A. It should be avoid that air, dust and other impurities invaded in the pipeline system
c .Exit defrosting condition:
during the installation of connecting pipeline.
1.If outside coil temperature ≥ 15℃ or defrosting time ≥6 ,min, the defrosting is working
but will exit when there is high pressure default. B. The inlet and outlet water pipeline can be installed after the heat pump water heater is
2.Exit defrosting → compressor off → after 55 seconds → four-way valves power on → fixed.
after 50 seconds →fan and compressor on → enter heating.
4.Automatic anti-frozen: In order to prevent plate type heat exchanger, water pipe and water 2-Heat Insulation
pump break in winter, when the machine requires the following conditions to be satisfied, it will
be automatically entered into anti-frozen. When environment temperature < 5℃ and the water The outlet of pipeline must be covered by heat insulated materials
circulating pump is power off over 30 minutes, the machine will be start first anti-frozen.

12 9
INSTALLATION DIAGRAM ERROR CODE TABLE

A: For hot water

Error code Problem


Water supply valve Cold water inlet
00 Water flow off
Water level switch Stop Valve
01 Water temperature sensor fault
Return water temperature sensor
03 Password protection
Water return valve
High water level S1 Water return pipe
04 Lose/ incorrect phase fault protection

Expansion water tank 05 Environment temperature sensor fault


Booster pump 06 Out put water temperature sensor fault
Low water level S2
Heat Pump 07 In put water temperature sensor fault
Main Unit Stop Valve
Public terminal
09 Compressor 1 over current protection
Water temperature sensor Manual stop valve
Circulation Pump Y type filter 10 Defrosting sensor 1 fault
11 System 1 high pressure switch fault
12 System 1 low pressure switch fault
Hot water to user 13 Coil 1suction temperature fault
14 Compressor 1 discharge temperature over 110℃
15 In-out water temperature difference too high
16 Compressor 1 discharge temperature sensor fault
B: For heating Anti-frozen switch open percentage
17
18 Out put water temperature too high
19 Compressor 2 over current protection
20 out put water temperature too low
21 System 2 high pressure switch fault
22 System 2 low pressure switch fault
23 Suction 1 temperature too low protection
24 Compressor 2 discharge temperature over 110℃
25 Suction 2 temperature too low protection
26 Compressor 2 discharge temperature sensor fault
27 Defrosting sensor 2 fault
28 Suction temperature sensor 2 fault
31 communication fault

Warm notice:If fault happens, the display shows error code and flashes.

10 11