You are on page 1of 7

900 43 Kalinkovo 146

Slovak Republic
Tel.: 00421 / 2 / 40203111
40203112
Fax: 00421 / 2 / 45989179
Email: imos@imos.sk
http://www.imos.sk

DIFFUSION GRILLES
IMOS-VDQ
TECHNICAL CONDITIONS

IMOS - VDQ - 4 IMOS - VDQ - 2

TPI 23-07
The present technical specifications determine sizes, properties, scope of application an final manu-
facture of PKI series fire dampers manufactured by IMOS-ASEK spol. s.r.o. The specifications apply to
design, ordering, production, delivery, acceptance and use of these products as of March 1, 2007.
These technical conditions substitute TPI 23- 94.

I. GENERAL
Diffusion grilles IMOS- VDQ are used as terminal air conditioning elements for inlet and outlet of modified air. Tight profile
blades form effluent place of the grille. Diffusion grilles VDQ are manufactured in versions with an alignment to one side
(VDQ-1), to two sides (VDQ-2), to three sides (VDQ-3) and to four sides (VDQ-4).

Construction Features:

Fig.1 Main functional parts IMOS-VDQ

IMOS- VDQ consists of aluminum tangential frame 1, filling, formed of quarter arched tight aluminum leaves 2. In stan-
dard version is IMOS-VDQ delivered in natural elox with 20 µm thickness surface finishing.

Regulation R1 consists of frame 3 and set of contra moving adjustable leaves 4, which are made of zinc plated sheet.

Fixative frame UR 5 is made of zinc plated sheet.

Fig. 2 Manufacture of IMOS- VDQ

1 TPI 23-07
II. TECHNICAL CONDITIONS
Main parameters are stated in figures. Dimensional rank and effective places are stated in tables.

VDQ

VDQ - UR

VDQ - R1

Fig. 3 Main dimensions and manufactures of IMOS-VDQ

Tab.1 Main dimensional rank, free cross section


Design VDQ-1 VDQ-2 VDQ-3 VDQ-4
a b VDQ-1 VDQ-2 VDQ-3 VDQ-4
according to Sc Sc1=Sc2 Sc1=Sc2 Sc3 Sc1=Sc2 Sc3=Sc4
mm diagram no. m2 kg
448 0,0353 0,0176 0,0155 0,0133 1,38 1,38 1,49 I.51
3
548 0,0443 0,0221 0,0200 0,0178 1,72 1,72 1,81 1,89
648 0,0533 0,0266 0,0245 0,0223 2,07 2,07 2,17 2,27
248 0,0043 0,0043
848 0,0712 0,0356 0,0335 0,0313 2,76 2,76 2,89 3,03
2
1048 0,0892 0,0446 0,0425 0,0403 3,45 3,45 3,62 3,79
1248 0,1072 0,0536 0,0515 0,0493 4,14 4,14 4,34 4,18
548 0,0620 0,0310 0,0264 0,0218 2,06 2,06 2,16 2,27
3
648 0,0740 0,0370 0,0324 0,0278 2,41 2,41 2,54 2,65
848 348 0,0999 0,0500 0,0454 0,0092 0,0408 0,0092 3,1 3,1 3,25 3,41
1048 2 0,1249 0,0625 0,0579 0,0533 3,79 3,79 3,93 4,13
1248 0,1509 0,0755 0,0709 0,0663 4,48 4,48 4,7 4,93
648 0,0927 0,0464 0,0381 0,0298 2,75 2,75 2,88 3,03
3
848 0,1237 0,0618 0,0535 0,0452 3,44 3,44 3,61 3,79
448 0,0166 0,0166
1048 0,1547 0,0773 0,0690 0,0607 4,13 4,13 4,33 4,5
2
1248 0,1867 0,0933 0,0850 0,0767 4,82 4,82 5,06 5,31
848 0,1554 0,0777 0,0640 0,0503 3,78 3,78 3,96 4,15
3
1048 548 0,1943 0,0972 0,0835 0,0274 0,0698 0,0274 4,47 4,47 4,69 4,92
1248 2 0,2343 0,1172 0,1035 0,0898 5,16 5,16 5,41 5,68
Sc - overall free cross section
Sc1-4 - partial free cross section ( as noted in fig.2)

2 TPI 23-07
Product ordering
In an order, it is necessary to indicate the following information:

Designation: IMOS - XXX - X - XX - XxX


Diffusion grille VDQ
Flow direction (see fig.2) 1
2
3
4
With air regulation R1
With fixative frame UR
Sizes axb

Example: IMOS - VDQ - 1 - R1 - 448x248 12 pieces TPI 23-07


IMOS - VDQ - 4 -UR - 648x448 3 pieces TPI 23-07
IMOS - VDQ - 3 - 1048x548 3 pieces TPI 23-07

III. DIFFUSION GRILLES DESIGNING

Fig.4 Parameters for calculation

Diagram 1 Pressure loss and nosiness indications for VDQ-R1

3 TPI 23-07
Diagram 2 Stating air parameters for VDQ-1 (according to table1) and for VDQ-2, VDQ-3, VDQ-4, for
place Sc1 and Sc2

Diagram 3 Stating air parameters for VDQ-1 (according to table1) and for VDQ-3, VDQ-4, for place Sc3
and Sc4

4 TPI 23-07
Diagram 4 Stating amount of air for places Sc1 to Sc4 for VDQ-3 and VDQ-4

Example 1
Stated indications: Type VDQ-2
Distance from the diffusion grille L= 7 m
Total volume overflow qv0= 1000 m3h-1
Air velocity vL=0,5 ms-1
Temperature difference ∆t0=6 K

Calculated indications:
Partial volume overflow qvc= 500 m3h-1
From diagram no.2 Sc=0,044 m2
From tab.no.1 ve¾kos VDQ-2-648x448
From diagram no.2 Sc1=0,0464 m2
i=18
∆tL/∆t0=0,14
∆tL=0,14x6=0,84 K

Example 2
Stated indications: Type VDQ-4
Size 648x348
Total volume overflow qv0= 1800 m3h-1

Calculated indications:
From tab.no.2 Sc=0,099 m2 from diagram no.4
From tab.no.2 Sc1=0,048 m2 partial volume overflow qvc1= qvc2 = 720 m3h-1
Sc3=0,0092 m2 qvc3= qvc4 = 180 m3h-1

5 TPI 23-07
Explanatory notes:
LW, LWA [dB] - level of acoustic output
∆pt [Pa] - pressure loss
∆t0 [K] - difference in temperatures- between the temperature in the room and temperature of supplied air ∆t0 = t-t0
∆t [K] - difference in temperatures- between the temperature in the room and the temperature in distance H1
A [m] - distance between two diffusion grilles
H1 [m] - distance between stay zone and the ceiling
vH1 [m.s-1] - medium speed of airflow between two diffusion grilles in the distance H1
v0 [m.s-1] - speed of air in the free cross section of the diffusion grille
qV0 [m3.h-1] - volume overflow of supplied air provided by the diffusion grille
qVC [m3.h-1] - partial volume overflow of supplied air (in one direction)
S0 [m2] - free cross section of diffusion grille
SC [m2] - partial free cross section- noted in fig. No.2
i - induction

About The Product


A manufacturer's label is attached to every IMOS-VDQ, indicating the following data:
a.) Manufacturer's name and address
b.) Product indication, type, dimensions

IV. CHECKING, ACCEPTANCE AND WARRANTY


The manufacturer attaches a quality and completeness certificate and warranty certificate.
The manufacturer grants 24 months´ guarantee from the dispatch date of diffusion grille. Acceptance is due to valid
instructions in the company IMOS-ASEK spol.s.r.o.

V. MOUNTING AND MAINTENANCE

Fig.4 Mounting of IMOS-VDQ

VI. PACKAGING, TRANSPORTATION AND STORAGE


IMOS- VDQ products are packed to a plastic foil. The customer is required to deliver such cover to a waste disposal or
recycling facility at his expense. Transportation to the customer is organized with the use of ordinary means of transport
and the cost is also to be borne by the customer. Products must be kept in a closed and dry place with the temperature
to 50 °C.

VII. APPENDIX
Any deviations from the present technical specifications are subject to agreement with the manufacturer. The manufac-
turer hereby reserves the right to technical innovations without prior notice to customers and holders of this TPI.
Related standards: STN EN 12792 (12 001) Ventilation of buildings. Terminology
STN EN 1505 Ventilation of buildings. Metal sheet pipes and shaped pieces of square cross section.
Dimensions.

6 TPI 23-07

You might also like