Professional Documents
Culture Documents
WC 7-1992
ICEA Publication No. S-66-524
CßQSS-LINKED-THERMOSET7-lNG-PQLYETHYLENE-INSULATED
WIRE ANDCABLE FOR THE TRANSMISSION AND DISTRIBUTION
OF ELECTRICAL ENERGY
Approved by
Insulated Cable Engineers Association, Inc.
Publish& by:
National Electrical ManufacturersAssociation
2101 L Street, N.W.
Washington, DC 20037-1526
March I, 1 9 9 3
TO: All known h o l d e r s of WC 7-1988
FROM: S t a n d a r dPs u b l i c a t i o En d i t o r '
E n c l o s e dp l e a s ef i n d WC 7 - 1 9 8 8R e v i s i o n 3 . P l e a s e follow t h e
d i r e c t i o n sb e l o wt ob r i n gy o u r c o p y o f WC 7-1988up t o date. the
r e v i s i o n was a p p r o v e do nJ u l y 16, 1 9 9 2 .
REMOVE REPLACE
Title page T i t l e page
Table of C o n t e n t s Table o f C o n t e n t s
pages 11-14 pages 1 1 - 1 4
page 3 5 / 3 6 page 35/36
p a g e s4 7 / 4 8 pages 4 7 / 4 8
p a g e s 81-84 pages 81-84
p a g e s 99-102 pages 99-102
WC 7
CROSS-LINKE#-THERMOSE7TlNG-POLYETHYLENE-INSULATED
WIRE AN# CABLEFOR THE TRANSMISSION AN# DISTRIBUTION
OF ELECTRICAL ENERGY
Published by:
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 2101 L STREET, N.W., WASHINGTON, D.C. 20037
INSULATED
CABLE
ENGINEERS
ASSOCIATION W PO BOX P, SOUTH YARMOUTH, MA 02664
COPYRIGHT National Electrical Manufacturers Association
Licensed by Information Handling Services
TABLE OF CONTENTS
-9.
FOREWORD ......................................... i
Section 1 GENERAL
. Sc0pe .............................................. 1
General
Information ...................................... 1
Informationto be Suppiied by the Purchaser . . . . . . . . . . . . . . . . . . . . . . . . . 1
Characteristicsof System on WhichCable is to be Used . . . . . . . . . . . . . . . . . . 1
QuantitiesandDescription of Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Section 2 CONDUCTORS
Wires.Physicaland Electrical Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Copperwires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Aluminum Wms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Conductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Solid 2
Conductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stranded 3
Conductor Size Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Conductor DC ResistancePerUnit of Length . . . . . . . . . . . . . . . . . . . . . . . . . 3
DirectMeasurement of DC ResistancePer Unit Length . . . . . . . . . . . . . . . . . . 3
Calculation of DC ResistancePer Unit Length . . . . . . . . . . . . . . . . . . . . . . . 3
Conductor
Diameter ...................................... 3
Layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stress Control 4
Section 3 INSULATION
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Insulation Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Three-phax Systemswith 100 or 133 PercentInsulationLevel ............ 11
Delta Systems Rated Where One LegMay Be Grounded
for Periods over 1 Hour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Single-andTwo-phaseSystemswith100and 133 Percent Insulation Level . . . . . . 11
DirectCurrent
Systems .................................. 11
InsulationThickness for SubmarinePowerCable . . . . . . . . . . . . . . . . . . . . . . . 11
Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Insulation CIasses andRequirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
VoltageTests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Insulation Resistance
Constants ............................... 14
Insulation for Cables R ad O through 2000 W t s . . . . . . . . . . . . . . . . . . . . . . . 14
Physical and
AgingRequirements ............................. 14
Elecaical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
VoltageTests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
InsulationResistanceTest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
AcceleratedWaterAbsorptionRequirements ........................ 14
Insulation for Cables Rated 2001 Volts and Above . . . . . . . . . . . . . . . . . . . . . . 14
Physical and AgingRequirements ............................. 14
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
k l u g e Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
InsulationResistance Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Partial-dischargeExtinction Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
AdditionalRequirements .................................. 15
U-BendDischarge .................................... 15
"
"
hg.
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
BoreholeCable(SuspendedatOne End Only) . . . . . . . . . . . . . . . . . . . . . . . 32
Annor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
S i z e of Armor Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Lay ............................................ 32
Dredgecable ........................................ 32
Armor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
SizeofArmorWire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PitchRatio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Shaftcable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
VerticalRiserCable(Suspendedat One EndOnly) . . . . . . . . . . . . . . . . . . . . 33
NonsheathedCable for 1n:Wation v.ithin Buildings . . . . . . . . . . . . . . . . . . 33
Amor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Size of Armor Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Size of Armor Wm for Sheathed Vemcal Riser Cable . . . . . . . . . . . . . . . . . . 33
Wie BandServing ..................................... 33
DIWSIOH III-ROUSD WIREARMOR FOR BURIED CABLE. . . . . . . . . . . . . . . . . 34
scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Armor Wire and Jute (Sheathed and Nonsheathed Cables) . . . . . . . . . . . . . . . . . 34
P.O.
Calculation of Area of TestSpecimens . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
PhysicalTest
Procedures .................................. 40
Test
Temperature ..................................... 40
Type of TestingMachine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
TensileStrength
Test ................................... 40
SetTest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Elongation
Test ...................................... 41
Tensile Suess Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
AgingTests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Aging Test
Specimens .................................. 41
OxygenPressureTest ................................... 41
Air Oven Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
OilImmersionTest for Cross-linked ~ e r m o s e t Jacket
) ................ 41
OilImmersionTest for Po;yvinyl Chhide Jacket . . . . . . . . . . . . . . . . . . . . 42
HotCreepTest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
SolventExtraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
PhysicalTests for SemiconductingMaterialIntended for Extrusion . . . . . . . . . . . . 42
Sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test 42
Test
Specimens ...................................... 42
Elongation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Britlleness
Test ...................................... 42
Retests for Physicaland Aging PropertiesandThickness . . . . . . . . . . . . . . . . . 42
CapacityandPowerFactorTests ............................... 42
AcceleratedWaterAbsorptionTests .............................. 43
Test
Sample ......................................... 43
Melhod (EM-60) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 43
ThicknessofTapes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Compound-Filled Tape ................................... 43
Metallic Shielding Tape or Sm1 Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Thickness of Metallic Sheaths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Thickness of JuteBeddings and Servings . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Tests forThermoplasticJackets ................................ 44
Heatshock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Heat
Distortion ....................................... 44
Specimen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test 44
TestProcedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Cold
Bend .......................................... 44
EnvironmentalCracking .................................. 44
Specimen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test 44
Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
AbsorptionCoefficientTest for Jackets . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Tests for DischargeResistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
General ........................................... 45
SpecificSurfaceResistivity ................................. 45
Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
U-Bend 45
Track Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
MethodA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
MethodB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
WumeResistivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Test
Sample ......................................... 46
Conductor Sm= Control .................................. 46
InsulationShield. ...................................... 46
SmppingTest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Rame Test (Deleted) .................................... 47
....
hg.
ConductorStressControlLayer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Insulation 83
Covering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Armor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
. Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Section a APPENDICES
Appendix A MBREVIA~ONS AND SYMBOU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Appendix B RepresentativeTensileStrength and Elongation of NonmagneticMetals . . . . . . . . . . 86
Appendix C Definitions for Maximum Temperatureof Conductors in Insuiated Wire and Cable . . . . . 87
Maximum Conductor Temperature-Opeaamg . . . . . . . . . . . . . . . . . . . . . . . . 87
hAaximum ConductorTemperature-Emeqency Overload . . . . . . . . . . . . . . . . . . 87
Maximum ConductorTemperature-ShortCircuit . . . . . . . . . . . . . . . . . . . . . . . 87
Appendix D ECWGENCY OVERLOADS ................................... 88
Appenlx E NEMA. ICEA. AND ASTMSTANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . 89
NEMA Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
ICEA Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
ASTM Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Appendix F AWACITIES FOR ?\VO-CONDUCTOR CONCEN-IRIC-NEUTRAL SINGLE-PHASE
PRIMARY UNDERGROUND RESIDEhTAL DISTRIBLTON CAELES . . . . . . . . . . 91
Appendix F-1
h P A C I T l E S FOR THREE-PHASE UNDERGROUND DISTRIBUIION CABLES . . . . . . . . . . . 91
Appendix G SHIELDING ........................................... 92
Definition of Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Functions of Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Use of Insulation Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Grounding of the Insulation Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Shield
Materials ........................................ 92
SplicesandTerminations ................................... 93
Appendix H RECOMMESDED BENDINGRXDII FOR CABLES. . . . . . . . . . . . . . . . . . . . . . . . . 94
Sc0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pe ........ 94
Shielding
Metallic
Without
Cables
Power or Armor . . . . . . . . . . . . . . . . . . . . . 94
PowerCablesWithMetallicShielding or Armor . . . . . . . . . . . . . . . . . . . . . . . 94
Interlocked Armored Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
FlatTapeandWireArmoredCables ............................ 94
Shielded Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Tape Shielded Cables ................................... 94
Wm Shielded Cablcs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Portable Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Drum Diameter of Reels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Appendix I AMPACITIES FOR THREE-coNDu~R MINE WER CABLES . . . . . . . . . . . . . . . . . 96
Appendix J AMPACITIES AND VOLTAGE RATINGS OF PORTAELE CABLES . . . . . . . . . . . . . . . . . 97
Ampacities(Current-Carrymg Ampacity in Amperes) . . . . . . . . . . . . . . . . . . . . 97
tbltage Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Appenhx K Deleted
Appendix L ADDITIONALC O N D U ~ INFORMATION
R ........................... 103
i
COPYRIGHT National Electrical Manufacturers Association
Licensed by Information Handling Services
STD.NEMA WC 7-ENGL 1988 647024
0753376
T49 7
CROSS-LINKED-THERMOSETTING-POLYETHYLENE-INSULATED WIRE
AND CABLE FOR THE TRANSMISSION AND DISTRIBUTION OF
ELECTRICAL ENERGY
Section 1
GENERAL
1.1
SCOPE 5. Cable insulation level (see 3.2).
These standards apply to materials,constructions, 6. Minimum temperature at which cable will be in-
and testing of cross-linked-thermosetting-polyethylene- staIIed.
insulated wires and cables that are used for the trans- 7. Description of installation.
mission and distribution of electrical energy for normal a.Inbuildings.
conditions of installation and service, either indoors, b. Inundergroundducts.
aerial, underground, or submarine. c. Aerial.
1. On messenger in metal rings.
1.2 GENERAL INFORMATION 2. On messenger with marlin ties.
These standards cover the requirements for conduc- 3. Preassembled.
tors,theinsulationsand protective coverings, and 4. Fieldspun.
general constructional and dimensional details common d. Direct burial in ground.
to most standard types of wires and cables. Construc- e. Submarine.
tions of specific typesare covered in Section7. Where a f. Descriptions other than the foregoing.
conflict exists between the requirements of Section 7 8. Conditions of installations.
and those of Sections 1to 6, inclusive, therequirements a. Ambient temperature.
of Section 7 shall apply. See Appendix E for complete b. Number of loadedcablesin duct bank or
titles and dates of ICEA publications and ASTM Stand- conduit. If in conduit, give type of conduit
ards towhich reference ismade in this publication. (metallic or nonmetallic),number of loaded
Insulation thicknessesare designated in terms of cable conduits, enclosed or exposed, and spacing
insulation levels (see 3.2). between conduits.
In classifying jackets and sheaths in these standards, c. Load factor.
the term “jacket” refers to a continuous nonmetallic d. Method of bonding and grounding of metallic
covering and “sheath” to a continuous metallic covering. coverings (including shields).
In these standards, units are expressed in the English e. Wet or drylocation.
system. For information only, their approximate metric f. Thermal resistivity (rho) ofsoil.
equivalents are included. 1.3.2 Quantities and Description of Cable
1.3INFORMATION TO BE SUPPLIED BY 1. Total number of feet, including test lengths, and
PURCHASER lengths if specific lengths are required.
When requesting proposals from cable manufac- 2. Type of cable. Describe as single conductor, two-
turers, theprospectivepurchasershouldfurnish the conductor flat, two-conductorround, etc.
followinginformation:(Thisparagraphapproved by 3. Rated circuit voltage,phase-to-phase.
NEMA as Authorized Engineering Information.) 4. Type of conductor - copper or aluminum.
5. Size of conductor - AWG or circular mils. If con-
1.3.1 Characteristics of System on Which Cable ditions require other than standard stranding, a
is to be Used complete description should be given.
1. Current - alternating or direct. 6. Insulation.
2. Frequency-hertz 7. Thickness of insulation in mils.
3. Normal operating voltagebetweenphases or, if 8. Type of outer covering.
direct current, between conductors. 9. Maximumallowableoveralldiameterininches.
4. Number of phases and conductors. If series light- When duct space is not limited, it is desirable not
ing, give open-circuit voltage and state whether to restrict the overall diameter.
system isoperating with or without protectors. 10. Method of conductor identification.
Section 2
CONDUCTORS
2.0 Requirements of a referenced ASTM standard shall apply only to non-compressed and non-compact
shall be determinedin accordance with the procedure conductors. The requirements of 2.1.2.2 or 2.1.23 shall
or method designated in the referenced ASTM stand- not apply if the requirements of 2.3.1 or 2.3.2 are met.
ard unless otherwise specifiedin the standard.
The following technical information on typical con- 2.1.2.1 Aluminum UM wires shaIl meet the chemical
ductors may be foundin Appendix L requirements ofASTM B 233.Aluminum alloy wiresshall
a. Approximate diameters of individualwires in contain a minimum of 97 percent aluminumby weight.
stranded conductors.
2.1.2.2 Aluminum 1350 and aluminum alloy wires in-
I b. Approximate diameters
listed in Table 2-7.
of conductors
c. Approximateconductor weights.
not
tended for a stranded conductor shall meet one of the
foliowing:
1. Hard-drawn wire shall meet the tensile, elongation,
2 1 WIRES, PHYSICALANDELECTRICAL of ASTM B 230.
finish and brittleness requirements
PROPERTIES 2. Annealed or intermediate temper wire shall meet
of ASTM B 609.
the tensile and finish requirements
The wires usedin conductors shall be copper in accord-
ance with 21.1 or aluminumin accordance with 2.1.2. 2.1.2.3 Aluminum 1350 and aluminumalloywires
removed froma concentric lay stranded conductorshall
21.1 Copper Wires
meet the tensile requirements and bendingproperties
Copper wires shall meet the requirements of 21.1.1 and of ASTM B 231, Sections 8.5 and 8.6 or 9.2 and 9.4.
either 2.1.12 or 2.1.13. The 2.1.13 option shall apply only
to non-compressed and non-compact conductors. 2 2 SOLIDCONDUCTORS
Solid conductors shall meet the requirements of 2.2.1
2.1.1.1 Copper wires shall meetthe chemical require-
ments of ASTM B 5. or 2.2.2.
2.2.1 A solid copper conductorshall consistof a single
2.1.1.2 Soft or annealed copper wires intended for a
round wire meeting the requirements given in 2.1.1.1
stranded conductor shall meet the elongation, finish,
and 2.1.1.2.
and coating continuity requirements of one of the fol-
lowing: 2.2.2 A solid aluminum U50 or aluminum alloy con-
1. ASTM B 3 for uncoated wires. ductor shall consist of a single round wire meeting the
2. ASTM B 33 for tin-coated wires. requirements given in 2.1.2.1,2.2.2.1, and Table 2-1 and
3. ASTM B 189 for lead or lead-alloy-coated wires. the finish requirements of M T M B230.Tensile strength
of aluminum 1350 and aluminum alloy conductors and
2.1.1.3 Copper wires removed from a concentric lay
elongation of aluminum alloyconductors shaIl be deter-
strandedconductor,annealed after stranding, shall
meet the elongation requirements of ASTM B 8, Sec- mined according to ASTM B 230.
tions 7.4,75, and 7.6. 2.2.2.1 Size 12 to 8 AmericanWtre Gauge (AWG)
2.1.2AluminumWires solid aluminum conductors shall be an aluminum alloy
with an elongation atrupture of not less than 10 percent
Aluminum wires shall meettherequirements of in 10 inches.
2.1.2.1 and either 2.1.2.2 or 2.1.2.3. The 2.1.2.3 option
Table 2-1
Solid Aluminum 1350 and Aluminum Alloy Conductors
Tcnsik Strength
Conductor Sim Aluminum 1350 Aluminum Alloy
AWG psi MPa psi MPa
diameter 0.750 inch (19 mm) or larger shall be measured reduce the non-compressedoutside diameter, the com-
in accordance with 63.3.1 or 6.33.2. The diametershall pression shall not exceed3 percent.
not differ fromthe nominal values shown in Table 2-7 by
more than 2 5 percent. 27 STRESS CONTROL LAYER
Conductors to be insulated for a rated circuit voltage
2.6.1 The 5 percent diameter tolerance for solid and above 2OOO volts shallbe covered witha separate stress
stranded conductors is provided to enable a designer of controlling material compatible with the conductor and
connectors to determine the range of conductor sizes the insulation. The material shall have allowable
operat-
that will fit a particular connector; however, aconductor ing temperatures at least equal to those given for the
meeting the minimum diameter requirement does not insulation.
necessarily meetthe requirement for maximum dc resis-
tance given in 2.5. 2.7.1 The stress control layershall be a polymeric
covering consisting of a conducting tape, extruded
2.6.2 If one or more layers of any concentric lay- material or extruded material over conducting tape.
stranded Class B,C, or D conductor is compressed to The layer shall have a minimum thickness of 2.5 mils
(0.06mm).
Table 2-2
Weight Increment Factors*, K
Solid Conductors 1
Concentric-lq Strand, Class B,C, and D
up to 2000 kcmil 1.02
- ..,
1.03
37 1.05
61 1.05
7 x 7 bunch stranded members 1.06
19x7 1.07
37x7 1.07
61x7 1.07
'Bascd on the methcd specified in either AST" B 8, ASIM B 496, ASIM B400,A S M B 231, A S I M B 172, ASIM B 173, or A S I N B 174 as
applicable.
W C 7-88 6470247 0 0 0 7 0 6 . 7 ~ ~
WC 7-1988
ICEA S-66-524 Page 5
Table 2-3
Schedule for Establishing MaximumDC Resistance Per Unit Lengthof Completed Cable
I
NomPortable Cables
Type Cable Maximum Dc Resistance
d
Single Conductor Cable and Flat Parallel Cable Table
2-4a
Value Plus 2%
(R max = Rx1.02)
Multiple Conductor Cables and Table 2-4a Value
Plus 2% Plus One of the Following:
%sted Assemblies of Single Conductor Cables
2% -One Layer of Conductors
(R rnax = R x 1.02x 1.02)
3%-More than One Layer ofConductors
(R max = R x l . 0 2 ~1.03)
4%-Ppairs or other PrecabledUnits
(Rmax = R x 1 . 0 2 ~1.04)
Portable Cablesand Flexible Cords
Cable Type Maximum DC Resistance
d
Single Conductor Cable and Flat Parallel Cable
(R max = RX 1.02)
_____
R =10-~v~
Where-
t
R = Conductor resistance in 52/1OOO ft
F = Factor from Table 2-8
A = Cross-sectional area of conductor in kcmil
See 25.2 for cross-sectionalarea determination
bFor 20AWG and 18 AWG Class K conductors specified inTable 2-6 this value shall
be 3 percent.
Table 2-4
Nominal DC Resistance in Ohms Per 1000 Feett at 25% (77°F)
of Solid and Concentric Lay-Stranded Conductor
Concentric Lay-Siranded’
Aluminum Copper
AWG or Uncoated Coated
k c d Uncoated Coated Class B,C,D
Class B,C,D Class B Class c Class D
22
20
27.1
16.9
16.5
10.3
17.2
10.7
27.4
17.3
16.7
105
17.9
11.1
... ...
a..
.I. ...
18
17
10.7
8.45
651
5.15
6.76
5.35
10.9
8.54
6.67
5.21
7.07
5.52
...
... e..
e..
16 6.72 4.10 4.26 6.85 4.18 4.43 e.. e..
... S..
...
.a. 0.00715
0.00596
0.00436
0.00363
0.00448
0.00374
**.
...
...
3500 ... ... ... 0.00515 0.00314 0.00323 ... *..
m..
..a
...
e..
e..
WC 7-1988
ICEA S-66-524 Page 7
Table 2-5
Nominal DC Resistance in Ohms Per 1000 Feet* At 25OC (7PF) For Flexible Aluminum Conductors
Conductor Size
AWGClass
or kcmil G Class H Class I
8 ... ... 1.07
7 0.858 ... 0.850
6 0.681 ... 0.687
5 0.540 ... 0.545
4 0.428 a.. 0.432
3 0.340 a.. 0.343
2 0.269 0.272 0.272
1 0.216 ... 0.216
V0 0.171 0.172 O. 172
U0 0.136 0.136 0.137
310 0.107 0.108 0.109
410 0.0852 0.0857 0.0861
250 0.0725 0.0728 0.0735
300 0.0604 0.0607 0.0613
350 0.0518 0.0520 0.0525
400 0.0453 0.0455 0.0460
450 0.0403 0.0405 0.0409
500 0.0363 0.0364 0.0368
550 0.0331 0.0334 0.0334
600 0.0304 0.0306 0.0306
650 0,0280 0.0283 0.0286
700 0.0260 0.0263 0.0265
750 0.0243 0.0245 0.0247
800 0.0228 0.0230 0.0232
900 0.0202 0.0204 0.0206
lo00 0.0182 0.0184 0.0186
1100 0.0166 0.0167 0.0169
1200 0.0152 O.Ol53 0.0155
1250 0.0146 0.0147 0.0148
1300 0.0140 0.0141 0.0143
1400 0.0130 0.0131 0.0133
1500 0.0121 0.0123 0.0124
1600 0.0115 0.0115 0.0116
1700 0.0108 0.0108 0.0109
1750 0.0105 0.0105 0.0106
1800 0.0102 0.0102 0.0103
1900 0.00968 0.00968 0.00977
m 0.00919 0.00919 0.00928
*Resistancevalues in miltiohms per meter shall be obtainedby multiplyingthe above valuesby 3.28.
WC 7-BA .B 64702470007070 L r
WC 7-1988
Page 8 ICEA S-66-524
Table 2-6
Nominal DC Resistance inOhms Per 1000 Feet* At 25°C (77OF)
For Flexible Annealed Copper Conductors
Conductor S h Uncoated Coated
AWGorkcmil ClassG
ClassH
Class1
ClassK
ClassM ClassG CIassH Class1
ClassK
ClassM
20
18
...
... ... ...
..
10.6
6.66
10.6
6.66
...
...
... ...
... 11.4
7.15
11.4
7.15
16 ... ...
S..
...
t
..*
e.. 2.82
1.77
2.82
1.81
10 1.05 ...
e.. S..
1800 0.00623 0.00623 0.00629 ... ... 0.00648 0.00648 0.00654 ... ...
1900 0.00590
0.00561
0.00590 0.00596
0.00566
...
...
1..
...
0.00614
0.00583
0.00614
0.00583
0.00619
0.00588
.*.
...
S..
...
*Resistancevalues in milliohms
per metershall be obtainedby multiplying the above valuesby 3.28.
Table 2-7
Nominal Diameters for Copperand Aluminum Conductors
Nominal Diameters.
Conccnlric Lay-Stranded
Conductor Sim Solid Compressed
Compact Class B Class c class D
~~ ~
AWG
Inch Inch
kcmil Inch Inch Inch Inch
22 0.812 0.0253 ... ... f . . ... ...
20 1.02 0.0320 ... ... ... ... ...
19 1.29 0.0359 ... ... ... ... ...
18 1.62 0.0403 ... ... ... ... ...
17 2.05 0.0453 ... ... ... ... ...
16 2.58 0.0508 ... ... ... ... ...
15
-~ 3.26 0.0571 ... 0.0629 0.0648
14 4.11 0.0641 ... 0.0704 0.0727 O.Öj35 o.ö;35
13 5.18 0.0720 ... 0.0792 0.0816 0.083 0.0826
12 653 0.0808 ... 0.0888 0.0915 0.0925 0.0931
11 8.23 0.0907 ... 0.0998 0.103 0.104 0.104
10 10.38 0.1019 ... 0.112 0.116 0.117 0.117
9 13.09 0.1 144 0.126 0.130 0.131 0.132
8 16.51 0.1285 o.ï& 0.141 0.146 0.148 0.148
20.82 7 0.1443 ... 0.158 0.164 0.166 0.166
6 26.24 0.1620 0.169 0.178 0.18.1 0.186 0.186
5 33.09 0.1819 0.200 0.206 0.208 0.209
41.74 4 0.2043 053 0.225 0.232 0.234 0.235
3 52.62 0.2294 0.238 0.252 0.260 0.263 0.264
2 66.36 0.2576 0.268 0.283 0.292 0.296 0.297
1 83.69 0.2893 0.299 0.322 0.332 0.333 0.333
110 105.6 0.3249 0.336 0.361 0.372 0.374 0.374
U0 133.1 0.3648 0.376 0.406 0.418 0.420 0.420
M 167.8 0.4096 0.423 0.456 0.470 0.471 0.472
410 211.6 0.4600 0.475 0512 0528 0.529 0530
250 05000 0520 0558 0575 0576 0576
300 osn 0570 0.611 0.630 0.631 0.631
350 05916 0.616 0.661 0.681 0.681 0.682
400 0.6325 0.659 0.706 0.728 0.729 0.729
450 0.6708 0.700 0.749 0.772 0.773 0.773
500 0.7071 0.736 0.789 0.813 0.814 0.815
550 ... 0.775 0.829 0.855 0.855 0.855
600 ... 0.813 0.866 0.893 0.893 0.893
650 ... 0.845 0.901 0.929 0.930 0.930
700 ... 0.877 0.935 0.964 0.965 0.965
750 ... 0.908 0.968 0.998 0.999 0.998
800 *.. 0.938 Loo0 1.o30 1.032 1.032
900 ... 0.999 1.061 1.o94 1.093 1.095
lo00 ... 1.060 1.117 1.152 1.153 1.153
1100 ... ... 1.173 1.209 1.210 1.211
1200 ... ... 1.225 1.263 1.264 1.264
1250 ... ... 1251 1.289 1.290 1.290
1300 ... ... 1.275 1.314 1.316 1.316
1400 ... ... 1.323 1.365 1.365 1.365
1500 ... ... 1.370 1.412 1.413 1.413
1600 ... ... 1.415 1.459 1.460 1.460
1700 ... ... 1.459 1.504 1504 1504
1750 ... ... 1.480 1526 1527 1527
1800 ... ... 1502 1.548 1.548 1549
1900 ... ... 1542 1590 1590 1.591
~ ~
2000 ... ... 1583 1.632 1.632
*Diametersin millimetersshall be obtained by multiplying the above values in inches by 25.4.
Table 2-8'
Factors' for Determining Nominal Resistanceof Stranded Conductors Per1000 Feet
Diameter of Individual Coated Copper Wires in Inches
for
Stranded Conductors
- Under Under Under Under
0,460 to 0.290 to 0.103 to 0.0201 to 0.0111 to
AI1 Sizes. Uncoated 0.290, 0.103, 0.0201, 0.0111, 0.0010,
Aluminum Copper Inclusive Inclusive Inclusive Inclusive Indusive
I Percent
Conductivity, 61 100 97.66 97.16 96.16 94.16 93.15
25OC25OC 25'C 25°C25°C 25°C 25OC
Rope Stranded
49 strands 17865 10892 11153 11210 1l327 11568 ...
133 strands 18038 10998 11261 11319 11437 11681 ...
259 strands 18125 11051 11315 11374 11492 11737 ...
427 strands 18212 11104 11370 1142.8 11547 11793 ...
More than 427 strands 18385 11209 11478 11537 11657 11905 ...
Bunch Stranded
AU sizes 17691 10786 ... ... 11217 11579
Rope-stranded Bunches
7 ropes of bunched strand 18038 10998 ... ... 11437 11681 11806
19,37,or 61 ropes of bunched strand 18212 11104 ... ... 11547 11793 11920
7 X 7 ropes of bunched strand 18385 llrn ... ... 11657 11905 12033
19.37, or 61 X 7 ropes of bunched strand 18559 11315 ". ... 11767 12018 12147
Concerttric Stranded
Up to 2ooo kcmil 17692 10786 11045 11102 11217 11456 11580
> 2"3CNM kcmil 17865 10892 11153 11211 11327 11568 11694
> 30004MO kcmil 18309 10998 11261 11319 11437 11680 11807
>4000-5000 kcmil 18212 11104 11369 11428 1W7 11792 11921
'The factors givcn in Table 2-8 shall be based on the following:
k Resistivity
1. A volume resistivity of 10575 Q * CmiUft. (100 pcrccnt conductivity) at 25°C for uncoated (bare) capper.
2. A 25°C volume mistivity converted from the 20°C values specified in B 33 or A m B 189 for coated copper.
3. A volume resistivity of 17.345 R CmiWft. (61.0 percent conductivity)at 25°C for aluminum.
B. Increase in Resistance Due to Stranding
1. The value of K (weight increment factor) givcn in Table 2-2.
t See Table 2-3 for Use of Facton.
MATERIAL
3.1 3.2.2 Delta Systems Where 0- Leg M a y Be
The insulation shall be a filled or unfdled cross-linked- Grounded forPeriods over 1 Hwr.
thermosetting polyethylene meeting the dimensional, elec- See 173 percent level in foomote *followingTable 3-1B.
trical and physical requirements specifiedin Section 3. A 3.2.3 Singk and -Phase Systems with 100
filed cross-linked-polyethylene insulation is one which and 133 Percent Insulation Level
conrains 1O percent or more of carbon and/ = mineral
black
filers byweight. An unfilled cross-linked polyethylene For nonshielded cables, multiply the voltage to ground
insulation is one which contains less than 10 p e r c e n t of by 1.73 and use the resulting voltage value to select the
carbon black and/or mineral fillers.Insulation for cables axresponding insulation bickness from Column A cm
rated 2001 V up to and including 5 kV may contain a Column B of Table $IA, as applicabk.
maximum of2-11'2 percent carbon black. Insulation for For shielded cables, multiply tht voltage to ground by
cables =led above 5 kV shall not containcarbon black. 1.73
from
and
the
select
100
the
percent
CMItSpanding
insulation level
insulation thickness
or 133percent insu-
This insulationis suitable for use on power cables in wet
or dry locations at conductor temperaturesnot exceeding lation level Column in Table 3-1B.as applicable.
90°C (194°F) fornormaloperation,130°C (266°F)for 3.2.4Direct Current Systems
emergencyoverloadconditions (see Appendix E), and Up to and including 2OOO volts, consider the Same as
250°C (482°F) for short circuit conditions. three-phase ac systems in accordance with3.2.1. Ova
The insulation on the conductor shall be free from any 2000 volts, consult themanufacam.
contaminants or porosity visibleto the eye with not more 3.3INSULATIONTHICKNESS FOR
than five times magnification. Thereshall be no water in SUBMARINE POWER CABLE
the stranded conductor of the finished cable.
The insulation thicknessshall be as given in Table 3-1A
3.2INSULATIONTHICKNESS and Table 3-1B exceptthe average thickness shall not be
The insulation thicknesses given in Table 3-1AandTable less than 60 mils for cables withouta jacket 01 sheath far
3- 1B are based on the rated circuit voltage,phase-tuphase, voltage classificationsup to and including 2 kV,
and on the cable insulation level. 3.4 REPAIRS
The thicknesses of insulation given in Table 3-1A and
Table 3-1B shall apply to single-conductor cables andto Repairs or joints in the insulation shall conformto the
the individual conductors of multiple-conductor cables, limitations on insulationthicknessgiven in 32. Each
except nonsheathed submarine cables and portable power length of insulated conductor containingrepairs or pints
cables. For nonsheathed submarine cables, see 3.3. For shall meet the electrical requirements of 3.6 or 3.7, as
portable power cables, see 7.4. applicable.
The average thicknessof the insulationshall be not less 3.5 INSUIATlON CLASSESAND
than that given in Table 3-1A and Table 3-1B. The mini- REQUIREMENTS
mum thickness shall be not less than 90 percent of the 3.5.1 Classes
values givenin Table 3-1A and Table 3-1B.(See 6.4.3 for
method of measurement.) The classes of insulation shall be as follows:
The thickness of insulation for various systems shall be a. 2ooo volts or less (sec3.6).
determined as follows: b. 2001 volts and above(see3.7).
3.2.1 Three-Phase Systems with 1W or 133 3.52 Voltags Tests
Percent Insulation Level Compktedcableshallbetestcdinaccardanccwiththe
Use the thickness values given in the respective columns paragraphs mfid in W k 32. The cable shall with-
of Table 3- 1A or Table 3- 1B as applicable. srand,without failur~,
tktest v~ltagagimin 'IBblt 3-1A
and Table 3-1Bas -kable.
Thetestvoltagesshallbcbasedontheratedvoltageof
thecableandthesizeoftheconductorandnotonthe
apparent thicknessof the insulation.
ICEA $66-524
WC 7-1988
Revision 2
Page 13
+
D ::t t
COPYRIGHT National Electrical Manufacturers Association
Licensed by Information Handling Services
WC 7-1988 ICEA S-66-524
Revision2
Page 14
3.5.3 InsulationResistance Constants Ekirical Method
The insulation resistance constants of insulations shall Dielectric constant aftex 1 &y, maximum 6.0
be in accordance with 3.6 or 3.7, as applicable (see 6.15
for test method). Increase in capacitance. maximum. pacent
3.6 INSULATION FOR CABLES RATED O 1-14 &YS 3.0
THROUGH 2000 VOLTS 7-14 &v 1.5
3.6.1Physical and Aging Requirements Stability factor after 14 days, maximum* 1.0
When rested in accordance with Section6, the insulation
shaII meet the following requirements:
Alunliue to stability faCt0r"stabiiity factor"
fexence, 1 UD 14 days, maximum* 0.5
Wysical Requirements ~ancoftbaetworsq~aa&dbc~naboth.
3.7 INSULATION FOR CABLES RATED M o 1
Tensile strength, minimum VOLTS AND ABOVE
psi 1800 3.7.1 Phydcal and Aging Requlreme~~ts
MPa 125 When tested in accordance with Section 6,the insulation
Uongation at rupture, minimum, percent 250 shall meet the following nqur
iements.
Aging Requirements Wysical Requirements
After air oven test at 121'Cf1 'C for 168 Tensile strength, minimum
hours-Tensile strength and elongation at rup
t u e , minimum, percentage of unaged value Psi 1800
75 MPa 12.5
After hot creep test at 1SO"CB"C Unwed Fiud Elongation at rupture,
minimum, percent 250
*Hot creep elongation, maximum, per- Aging Requirements
cent 175 100
After air oven test at 121 'C for 168
*Cf1
*Hot aeep set, maximum,
percent 10 5 hours-msile soength and elongation at rup
*U h i s value IS exceeded. the Solvau Exu~cuonTut may be F r - cure, minimum, percentage of unaged value 75
formed and will serve as I referee method U) duermmc c o m p l ~ a n c c
(nuximumpcrccm a f e r 20 hours drying time-30). After hot creep test at 15O'Cfl'C UnflUed FOkd
3.6.2 Electrical Requirements
+Hacreep elongation, maximum,per-
3.6.2.1 VOLTAGE TESTS CMt 100 175
See 3.5.2. +Hot creep set,maximum. p e m t 10 5
3.6.2.2 INSULATION RESISTANCE TEST *If this V ~ U CI S Uthc S&a* Eanctian T+ m y bc PI-
f~andmllscweurduœmabodtodacrmacomplmce
Each insulatedconductor in the completedcable shall be (mrxlmum pranr &r M bapr dryin8 time"3Q.
tested in accordance with 6.15and shall havean insulation 3.7.2 Ekctrictrl Requimments
resistance not less than that corresponding to a constant of
10,ooO at 15.6'C (WF) . insulationresistance test is
The 3.7.21VOLTAGE TESTS
notrequiredwhenthedcsparkttstorrheacspasktestis See 3.5.2
performed (see35.2). 3.7.2.2 INSULATION RESISTANCETEST
3.6.3AcceleratedWater Absorption Eachinsnlam!d~inrhccompletbdcabkshallbe
Requirements ttstcdinaccordancewith6.15andshallhavtminsuIation
(Sec 6.6.)The insuiation shall meet the following re- resisaurcenotlessthanthatcaqmdingtoacrnstantof
quinments when tested in accordance with the electrical 20
O
,O O at 15.6'C (WF).
(Ehldo) method as specifled in 6.6.2.
3.7.2.3 PARTIAL-DISCHARGE
EXTINCTION
LEVEL 3.7.3.3 ACCELERATED
WATERABSORPTION
REQUIREMENTS
(See ICEA T-24-380.) Each length of completed
I power cable rated for service at 2001 volts and above
with insulation shielding on the individual conductors
The insulation
shall
meet
following
the
requirements when tested in accordance withthe
shall comply with the following table: Accelerated
Water
Absorption Test, E M 4 0 as
specified inIGEA T-27-581MMA WC 53 at the
Rated Circuit Minimum Partial-dischargeExtinction temperature specifiedin the table below:
Voltage, ~ Level, kV
Phase-to-Phase
~~~ ~ . 100 Percent 133 Percent ~~ ~~~~ ~
Volts Insulation Level Insulation Level Electrical Method (60 Hz) at 75 f 1°C
2001-5000 4 5'
5001-8000 6 8
Dielectric constant after 24 hours, maximum 3.5
8001-15000 11 15 Increase in caDacitance, maximum, Dercent
15001-25000 19 26 1 to 14 days 3.0
25001-28000
28001-35000
1 .o
Alternate to stability factor-stability
3.7.3 Additional Requirements factor difference,
3.7.3.1 U-BENDDISCHARGE 1 to 14 days, maximum* 0.5
* Only one of these two requirements needbe satisfied, not both.
(See 6.11.) Single-conductor nonshielded cables
rated at 2001-5000 volts shall not fail or show any
3.7.3.4 CAPACITY A N D POWER FACTOR
cracks, when tested in accordancewith 6.11.
(See 6.5). The insulation on cables rated at 5001
3.7.3.2 SURFACE
RESIST~VITY voltsand above shallhave a specific inductive
capacity not exceeding 3.5 and a power factor not
(See 6.1 1.) Single-conductor nonshielded cables
exceeding 2.0 percent.
rated at 2001-5000 volts shall have a specific surface
resistivity ofnot less than 200,000 megohms when
3.7.3.5 INSPECTION FOR EVIDENCE
OF WATER
tested in accordance with 6.1 1.
Each length of Completed shielded cable 2001
volts and above shall be inspected for evidence of
water in accordance with 6.19. If evidence of water
is present, the affected cable length shall be dried by
a suitable method.
Section 4
SHIELDING AND COVERINGS
Al SHIELDING OF INSULATEDCABLE of at least 5OOO circular mils per inch (0.1 mm2/mm) of
Shielding of insulated cables shall consist of conduc- insulated conductor diameter, or of other nonmagnetic
tor shielding and insulation shielding. For conductor metals havingequivalent conductance.
shielding, see 2.7. Metal tapes, wires, straps, and sheaths may be usedin
combination providing they are compatible and meet
4.1.1 InsulationShield System the requirements of the preceding paragraph.
The insulation shield system shall consist of a non- Metal components embedded in a conducting non-
metallic covering directly over the insulation and a non- metallic covering shall notbe exposed nor become ex-
magnetic metal component directly over or embedded posed during normal installation bending (see
in the nonmetallic covering. The nonmetallic covering Appendix H).
shall comply with 4.1.1.1. The metal component shall NOTE-Additional conductance may be required in the metal com-
comply with 4.1.1.2.The insulation shield system shall ponent depending upon installation andelectricalsystemcharac-
teristics,particularlyinregard to thefunctioning of overcumnt
be resistant to or protected against chemicalaction from
protective devices, available fault current, and the manner in which
other cable components. the systemmay be grounded.
000q07q ar
WC 7-1988
ICEA S-66-524 Page 17
9 Table 4-1
Requirements for Nonmetallic Conducting Coverings Using Nonembedded
Metal Components
Thermoplastic Thermoset
Aging Requirements (see 6.4.15)
After air oven test at 10O0C+1"Cfor 48 hours - elongation at rupture, minimum, percent 10O* ...
After air oven test atl2loC+1"C for 168 hours- elongation at rupture,
minimum, percent ...
~~~~
loo*
~
psi 1200
MPa 8.27
Elongation at rupture, minimum, percent 100
Aging Requirements (see 6.4) - after air oven test at 121"C+- 1°C
for 168 hours
Tensile strength, mn
im
i um,percentage
valueof unaged 85
Elongation at rupture, minimum, percent 100
Brittleness Temperature
6.4.l5), (see not warmer than -10°C
Volume Resistivity, maximumat room temperature and at rated temperature 21°C (see 6.12), ohm-meters 500
Table 4-3
Operating Voltage Limits, kV, above which Insulation ShieldingIs Required
Power Cable-100 and 133 Percent InsulationLevel
1. Single conductor (including assemblies
of single conductors)
With a.
b. AU others 2kV
2. Multiple conductor with common covering
a. 5kV
~~ ~~
1 1.73 0.866
*Where it is not definitely specifiedthat a line operatesas an isolated single-or two-phase system,it shall be consideredas a branch of a 100
percent insulation level three-phase circuit, and the rating shall be the line-to-line of this
voltage
100 percent insulation level three-phase circuit.
JACKETS
4.3
GENERAL Physical Requirements
Jackets shall be one of the types covered in 4.4 except Rnsile Strength, minimum
that, for cable with an embedded metal component, the
jacket shallbe a nonmetallic conducting covering meet- psi 150
ing the requirements ofTable4-2.For jackets over MPa 1
metallic coverings,see 4.5.
Elongationatrupture,minimum,percent100
4.4THERMOPLASTICJACKETS Aging Requirements
These jackets consist of a moisture-resisting ther-
moplastic compound for use as the coveringonor jacket After air oven test atlOO"C& 1°Cfor 5 days
insulatedwiresorcables.Theyshallmeet the ap- Tensile strength, minimum, percentage of
plicable requirementsof 4.4.1 through 4.4.7. The tests
value unaged 85
shall be made only on jackets having a nominal wall
thickness of 30 mils (0.76 mm)or greater. Elongation at rupture, minimum, percent-
age
value
of unaged 6 0 .
This jacket shall consist of a polyvinyl chloride com- Tensile strength, minimum,percentage of
pound suitable for a minimum installing
value temperature
of unaged 80
-10°C (14°F). When tested in accordance with 6.4 and
6.10, the jacket shall meet the following requirements Elongation at rupture, minimum, percent-
and, when applicable,the requirements given in 4.4.6. age of
value
unaged . 60
Heat distortion, 12loC+-1"C,
maximum
percent 50
121"Ckl"C
shock,
Heat No Cracks
-35"Ck
1°C
bend,
Cold No Cracks
Method B Method C
Chlorinated Polyethylene Polyvinyl Chloride (4.4.1)
Thermoplastic (4.4.3)
6470247 """- TT
WC 7-1988
ICEA S-66-524 Page 21
O Table 4-5
Jacket Thicknesses for Single-Conductor Metallic Shielded Cables
(For All Uses: Conduit, Trays, Troughs, Underground Duct, Aerial, and Direct Burial)
2001-5Ooo Volk 5001-8oooVolk 8001-L5oO0 Volk
Size,or
AwG LOO and 133Percent LOO133
Percent Percent LOO Percent 133 Percent
kcmil InsulationLevel Insulation Level Insulation Level Insulation Level Insulation Level
mils mm mils mm mils mm mils mm mils mm
8 45 1.14 ... ... ... ... ... ... ... ...
6 60 1.52 60 1.52 60 1.52 ... ... ... ...
4 60 1.52 60 1.52 60 1.52 ... ... ... ...
C
2 60 1.52 1.52
60 1.52 60 80 2.03 ... ...
1 60 1.52 60 1.52 80 2.03 80 2.03 80 2.03
110 60 1.52 60 1.52 80 2.03 80 2.03 80 2.03
210 60 1.52 80 2.03 80 2.03 80 2.03 80 2.03
310 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
410 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
250 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
300 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
350 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
400 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
450 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
500 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
600 80 2.03 80 2.03 80 2.03 80 2.03 80 2.03
750 80 2.03 80 2.03 80 2.03 80 2.03 110 2.79
lo00 80 2.03 80 2.03 110 2.79 110 2.79 110 2.79
For all other sizes and voltages not tabulated above see Table 4-8, Column (2).
Table 4-6
Individual Conductorsof Multiple-Conductor
Table 4-7
Common Overall Jacketof Multiple-Conductor
O
Cables Undera Common Covering Cables (For All Voltages andAll Uses)
Calculated Diameter of Individual Calculated Diameter of Cable Under Jacket Jacket Thickness
Conductor Under Jacket Jacket Thickness
inches mm mils mm
Jnches mm mils* mm
0.425 or less 10.80 or less1.14 45
0.250 or less 6.35 or less 15 0.38
0.426-0.700 10.82-17.78 60 1.52
0.251-0.425 6.38-10.80 25 0.64
0.701-1.500 17.81-38.10 80 2.03
0.426-0.700 10.82-17.78 30 0.76
1.501-2.500 38.13-63.50 2.79110
0.701-1.500 17.81-38.10 50 1.27 x
2.501 and
larger 63.53 and larger
140 3.56
1.501-2.500 38.13-63.50 80 2.03
NOTE 1-Table 4-7 applies to all round multiple-conductorcables
r
*These thicknesses applyto jackets only and do not apply to colored having a common overall jacket.
coatings on the individualconductors of multiple-conductor cables.
NOTE2-For flat twin cable, usethe calculated major core diameter
under the jacket to determine the jacket thickness.
Table 4-8
Single- and Multiple-Conductor Wires and Cables
(All Uses Except Communication and Portable Cables*)
Jacket Thickness
Single-conductorCabks Multiplesonductor Cables*
Calculated Diameter of Cable Under Jacket (1) (2) (3) Individual (4)
Nonshielded Shielded** Conductorst Overall
inches mm mils mm mils mm mils mm mils mm
0.250 or less 6.35 or less 15 0.38 45 1.14 15 0.38 45 1.14
0.251-0.425 6.38-10.80 30 0.76 45 1.14 25 0.64 45 1.14
0.426-0.700 10.82-17.78 45 1.14 60 1.52 30 0.76 60 1.52
0.701-1.500 17.81-38.10 65 1.65 80 2.03 50 1.27 80 2.03
1.501-2.500 38.13-63.50 95 2.41 110 2.79 80 2.03 110 2.79
2,501and larger 63.53
larger
125
and 3.56
140
3.18 ... ... 3.56
140 ,
I
WC 7-1988
Page 24 K E A S-66-524
proved by NEMA as Authorized EngineeringInforma- and applied with opposite directions of lay, The inner
tion.) serving shallbe an impregnated jute yarn that shall be
Table 4-10 run through hot asphalt or tar compound before the
Thickness of Smooth Aluminum Sheath application of the outer serving which shall be No. 16/3
calculated Diameter of Core* Thickness of Sheath impregnated jute yarn or plied jute of equivalent thick-
mils mm
ness.
Inches mm
For.either one or two servings, the outer serving shall
0-0.400 0-10.16 35 0.89 be run through hot asphalt or tar compound and coated
0.401-0.740 1.14
10.19-18.80 45 with some suitable material that will prevent sticking of
0.741-1.050 18.82-26.67 55 1.40 adjacent turns of the cable when woundon a reel.
1.051-1.300 26.70-33.02 65 1.65 4.5.6 Flat Metal Tape Armor
1.301-1.550 1.90
33.05-39.37 75
1.551-1.800 2.16
39.40-45.72 85 4.5.6.1 SCOPE
1.801-2.050 45.75-52.07 95 2.41 This section covers plain and zinc-coated flat steel
2.051-2.300 52.10-58.422.67 105 strip-in coils for use as flat armor for electrical cables.
2.301-2.550 58.4544.77 115 2.92 The zinc coating shall be applied by either hot-dip or the
electro-galvanizingprocess such that all surfaces of the
2.551-2.800 64.80-71.123.18 125
finished tape width are coated, including edges.
2.801-3.050 71.15-77.47 3.43 135
3.051-3.300 77.50-83.823.68 145 4.5.6.2 TENSILE STRENGTH AND ELONGATION
3.301-3.550 83.85-90.173.94 155 The plain and zinc-coated strip shall have a tensile
3.551-3.800 90.20-96.524.19 165 strength of not lessthan 40000 psi (276 MPa) normore
4.453.801-4.050
96.55-102.9
175 than 7oooO psi (482 MPa).The tensile strength shall be
__.
determined on longitudinal specimens consisting of the
*The thickness of the aluminum sheath for flat twin cable shall be
based on the calculated major core diameter. full width of the strip when practical or on a straight
specimen slit from the center of the strip. The strip shall
4.5.5 Jute Serving over Metallic Sheath without have an elongation of not less than 10 percent in 10
Metallic Armor inches (254 mm). The elongation shallbe thepermanent
increase in length of a marked section of the strip,
4.5.5.1 JUTESERVINGS originally 10 inches (254 mm) in length, and shall be
The thickness of one serving (ortwo servings) of jute determined after the specimen has fractured. All tests
applied over metallic sheathed cable for mechanical shall be made prior to application of the strip to the
protection shall be as given in Table 4-11. cable.
Table 4-11
4.5.6.3GALVANIZINGTEST
Thickness of Jute Servings Over Metallic
Sheath (Without Metallic Armor) 4.5.6.3.1WEIGHT OF ZINCCOATING
Average Thickness of Jute The weight ofzinc coating shall be determined before
Calculated
Diameter of Cable
Serving
Under Jute Serving*
application of the strip to the cable. The strip shall have
One Serving Two Servings a minimum weightof coating of 0.35 ounce per square
inches
1.ooOor less
mm
25.40 or less
ruils
65
mm
1.65
mils
95
-
mm
2.41
foot (106.8 grams/meter2) of exposed surface. The
weight of coating specified isthe total amount on both
1.001-2500 25.43-63.50 65 1.65 110 2.79
surfaces and edges and shall be determined in accord-
ance with the method described in ASTMA90.
2501 &larger 63.52 &larger 65 1.65 125 3.18
*Thethickness of juteservings over metallic sheath for twin
flatcable 4.5.6.3.2 ADHERENCEOF COATING
shall be based on the calculated major core diameter. The zinc coating shall
remain adherent without flaking
4.5.5.2
APPLICATION or spalling whenthe strip is subjected to a 180-degree
bend over amandrel Vi inch (3.18 mm) in diameter. The
When jute servingsarerequired, themetallicsheathed zinc coating shall
be considered as meeting thisrequire-
cable shall be run through hot asphalt or tar compound ment if, when the strip is bent around the specified
and served with a closely wound of layNo. 16/3 impreg- mandrel, the coating does not flake or none of it can be
nated jute yarn or plied jute of equivalent thickness.If removed fromthe strip by rubbing withthe fingers.
two servings are required, they shallbe closely wound
~ 7 0 2 4 70 0 0 7 0 8 7
WC 7-1988
ICEA S-66-524 Page 25
Loosening or detachment duringthe adherence test of the tape or 0.200 inch (5.08 mm), whichever is the
of zinc formed bymechani- greater.
of superficial, small particals
calpolishing of the surface of the zinc-coated strip shall During or prior to application, the tapes shall be
not constitute failure. flushed with a suitable compounddeter to corrosion.
Table 4-13
4.5.6.4
WIDTH Thickness of Metal Tape for Flat Armor
The nominal widthof metal tapes shall be not greater (Plain or Zinc-Coated)
than that specified in Table 4-12. Calculated
Diameter of Cable Nominal
Thick-
For nominal widths 1.000 inch (25.4 mm) or less, the Under
Jute
Bedding* ness of Metal Tape
tolerance in width shallbe f31mils. For nominal widths
inches mm mils mm
greater than1O.OOinch (25.4mm), the toleranceinwidth - =
shall be 247 mils. 1.00025.40
less
or 20 0.51
Table 4-12 1.001
and larger 25.43 and larger 30 0.76
Width of Metal Tape for Flat Armor
(Plain or Zinc Coated) *For flat twin cable, the nominal thickness shall be based on the
calculated majorcore diameter.
Calculated Diameter
of Cable Nominal Widthof
Under Jute Bedding* Metal Tape
4.5.7 Interlocked Metal Tape Armor
inches mm inches mm
4.5.7.1 SCOPE
0.450 or less
11.43
less
or
0.750
19.0
This section covers flat metallic strip-in coils for use
0.451-1.000 11.46-25.40 1.000 25.4 as interlocking armor for electrical cables. All tests shall
1.001-1.400 25.43-35.56 1.250 31.8 be made prior to the application of the the strip
cable.
to
1.401-2.000 35.59-50.80 1.500 38.1 4.5.7.2STEELTAPE
2.001-3.500 50.83-88.90 2.000 50.8 Steel tape (except stainless) without a protective
3.501 andlarger 88.93 andlarger 3.000
76.2 covering shallbe zinc-coated. The zinc coating shall be
applieC hv either the hot-dip or the electro-galvanizing
*For flat twin cable, the nominal width shallbe based on the calcu- process such that all surfaces of the finishedtape width
lated major core diameter. are coated, includingthe edges. If an outerjute or other
protective covering is furnished, plaintape steel
may be
4.5.6.5
THICKNESS used. The quality of the steel tape and the requirements
The nominal thicknessof metal tape shall be not less for the galvanizing shallbe those specifiedin 4.5.6.2 and
than that given in Table 4-13. See 6.7.2 for method of 4.5.6.3 for flat steel tape.
measuring metaltape thickness.
The tolerance in the nominal thickness of the tape 4.5.7.3
WIDTH
shall be. +.3 mils. The nominal widthof metal tape may be less than but
The zinc-coated tape shall not at any placebe more shall notbe greater than that specified
in Table 4-14.
than 20 percent thicker thanthe stripped tape thickness, Table 4-14
which should the be specified nominal thicknessbare for Width of Metal Tape for InterlockedArmor
metal. The tolerance for nominal thicknessof bare metal
should apply tothe stripped tape. Calculated Diameterof Cable Nominal Width of
Under Armor Metal Tape Armor
4.5.6.6 APPLICATION,LAY, AND SPACING inches mm inches mm
'&o metal tapes shall be applied helically in
the same 0.500 or less 12.70 or less 12.7
0.500
direction over the jute bedding except that they may be
applied in opposite directions where the total areaof 0.501-1.000 12.73-25.40 19.0
0.750
the conductors is less than 50000 circular mils (25.34 1.001-2.000 25.43-50.80 22.2
0.875
mm2). The direction of lay of the inner tape shall be
2.001 and larger 50.83 and larger 25.4
1.000
opposite to thatof the jute bedding. When applied in
the same direction as the inner tape, the outer
tape shall
be approximately centered over the spaces betweenthe For any width of metal tape used, the tolerance in
convolutions of the inner tape. The maximum space width shallbe + 10 mils or -5 mils, except for aluminum,
between turns shall not exceed 20 percent of the width which shall be+-lomils.
4.5.7.4
THICKNESS
The nominal thicknessof metal tape shall be not less
gitudinallyfoldedaroundthecablecore,seamwelded,
and corrugated or by applying over the cable core a
e
than that given in lible 4-15. See 6.7.2 for method of seamless sheath or tube, which is then corrugated.
measuring metaltape thickness. 4.5.7a.2 TYPE OF METAL
The tolerance in nominal thickness of the tape shall
be "3 mils, The zinc-coated tape shall not atany place 4.5.7a.2.1 When metal armor is formed by a flat
be more than20 percent thicker than. the stripped tape metal tape, the tapes used shallbe aluminum, copper,
thickness, which should be the specified nominal thick- steel, or alloys thereof.
ness forbare metal. The tolerance for nominal thickness
of bare metal should apply to the stripped tape. 4.5.7a.2.2 When metal armor is formed by applying
Table 4-15 a seamless sheath or tube, the metal be shall
aluminum
Thickness ofMetal Tape for Interlocked Armor or an aluminum alloy.
Nominal Thickness 4.5.7a.2.3 The minimum thickness oftape or of the
Ambrac, Brass, sheath or tube before corrugation shall
be as shown in
Steel, Stainless 'Ihble 4-14a. .
Calculated Diameterof Cable
Under Armor and Monel Aluminum and 4.5.7a.3 FLEXIBIL~
Taw Zinc Taw
inches mm mils mm mils mm The armored cable shall be capable of being bent
around a mandrel having a diameter of 14 times the
0-1500 0-38.10 20 o51 25 0.64 cable diameter. The armor shall show no evidence of
1.501&larger 38.13 &larger 25 0.64 30 0.76 fracture visible to the unaided eye. The test shall be
conducted in accordance with the procedure given in
4.5.7.5 NONMAGNETICTAPE
Section 6.
When nonmagnetic tapes, such as aluminum, brass,
bronze, zinc, or stainless steel tapes
are used, the widths 4.5.7a.4CORROSIONPROTECTION
shall be in accordancewith 4.5.7.3 and the thicknesses
in accordance with4.5.7.4.
When required
corrosion
a protective
be applied over the armor.
covering
shall 0
Representative valuesof tensile strength and elonga-
tion for the nonmagnetic metals are given in Appen- 4.5.8 Galvanized Steel Wire Armor
dix B.
4.5.8.1 SCOPE
4.5.7aContinuouslyCorrugatedMetal Armor This section covers zinc-coated low-carbon-steel wire
for usein the armoringof borehole, vertical riser, sub-
4.5.7a.1
SCOPE
marine, and underground cables used for power, con-
This section covers the requirements applicable to trol, and lighting circuits for normal use. For wire armor
continuously corrugated metal armored cable. The for special usessee Division II and III (4.5.17 through
metal armor is formed by a flat metal tape thatis lon-
Table 4-14a
Minimum Thickness ofMetal for Corrugated Armor
Diameter
Calculated
SteelCopper
Aluminum
Armor of Cable
Under
inches mm mils mm mils mm mils mm
0-2.180
0.56 22 0- 55.37 ... a.. ... e..
WC 7-1988
ICEA S-66-524 Page 27
Table 4-19
Size of Galvanized Steel Armor Wire for Submarine
Cable
1.001-1.700
1.701-2.500
tence has been approved by NFMA as Authorized En- before it is run through the first application of com-
gineering Information.) pound.
The tolerance in diameter for galvanized steel wire
shall be as shown in Table 4-20. 4.5.9.2DIRECTION OF LAY
Table 4-20 The direction of lay ofthe jutebedding or serving shall
Tolerances of Diameter be opposite to that of the armor directly in contact with
Nominal Diameter of CoatedWire Tolerances,inches
it, except as allowed in 4.5.8.6. Adjacent layers of jute
shall be applied with opposite directions of lay.
mils mm
238-166 6.054.22 a0.005 4.5.9.3
THICKNESS
The thickness of jute bedding under the armor in the
165-109 4.20-2.77 kO.004
finished cable shall be not less than that specified in
108-65 2.74-1.65 zkO.003 Table 4-21.The thickness shallbe determined by the use
of a diameter tape and shall be considered as one-half
4.5.8.5 LAY of the difference in measurement under and over the
The length of lay of the armor wires shallbe not less bedding.
than seven nor more than twelve times their pitch 4.5.10 Jute Serving Overall for Armored Cable
diameter for all constructions except for dredge cable.
For dredge cable, see 4.5.20. See 4.5.11 for Interlocked Armored Cable.
“Lay” is defined as follows. “The lay of any helical
4.5.10.1
APPLICATION
element of a cable is the axial length of a turn of the helix
of that element.” When an outer jute serving isrequired, the armored
cable shall be run first through hot asphalt or tar com-
4.5.8.6DIRECTION OF h Y pound, then served with a layer of number sixteen three-
Successive layers of jute and armor shall be laid in ply(No.l6/3)impregnatedjuteyarnappliedwithashort
opposite directions, The direction of lay of the armor close lay, againrun through hot asphalt or tar compound
wires shall be so chosen that birdcaging of the cable and finished by running through some suitable material
being armored shall be reduced to a minimum. that will prevent stickingof adjacent turns of the cable
when wound in a reel.
4.5.9 Jute Bedding for Armored Cable
4.5.10.2DIRECTION OF h Y
See 4.5.11 for Interlocked Armored Cable.
The direction of lay of the jute serving shall be op-
4.5.9.1 APPLICATION posite to that of the armor in contact with it.
Metallic-sheathed cable to be armored shall be run 4.5.11 Jute for Interlocked Armored Cable
through hot asphalt or tar compound before being
served with a bedding of impregnated jute yarn or 4.5.11.1JUTEBEDDING
roving, each layer of which shall be run through hot If jute bedding is required, the application and direc-
asphalt or tar compound. If the cable is without metallic tion of lay shallbe in accordance with 4.5.9.1and 4.5.9.2.
sheath, the core shall be covered as specified in4.5.12.1 The thickness shallbe as specified for metal taped cable
in Table 4-21.
WC 7-1988
ICEA S-66-524 Page 29
Table 4-21
Thickness of Jute Beddinsfor Armored Cable
Minimum Thicknessof Jute Bedding
Calculated Diameter
of Cable Under Jute Bedding*
Round Wire Armored Cable
Mehl Taped
Sheathed or Jacketed
Nonsheathed or Noqjacketed
inches mm mils mm mils mm
4.5.16.1THERMOPLASTICm E S
Thermoplastic jackets,when used, shallbe extruded
over the metallic armor and shall fit tightly thereto.
They shallbe either:
e
Table 4-26
Thickness of Jacket Over Metallic Armor
= Thickness
Diameter of Cable
Calculated Under
Jacket All Cables
(Excepl
Interlocked or Cables
With
Interlocked
or
Corrugated
Corrugated
Armored) Armor
inches mm mils mm mils mm
less or 19.05
0.750 or less 50 1.27 50 1.27
0.751-1.500 19.08-38.10
1.65 65 50 1.27
1.501-2.250 38.13-57.15 80 2.03 60 1.52
2.251-3.000 57.18-76.20
2.41 95 1.90 75
a
0 larger and 76.23larger
3.001 and 85 2.16
WC 7-1988
Page 32 ICEA S-66-524
DIVISION II 4.5.20DredgeCable
Round Wire Armor for Borehole, Dredge, Shaft,
and Vertical Riser Cable 4.5.20.1
ARMOR
Galvanized round steel wire shall be used for dredge
4.5.17
Scope cable and shall be applied with ashort lay.
Division II gives details of construction of armor ap-
plicable particularly to borehole, dredge, shaft, and ver- 4.5.20.2 SIZE OF ARMORWIRE
tical riser cables. The size of the armor wires shallbe as given in Table
4-28.
4.5.18
General Table 4-28
The requirements of Division I pertaining to quality Size of Galvanized SteelArmor Wire
of materials, design, and construction, apply also to for Dredge Cable
borehole, dredge, shaft, and vertical riser cable (which Calculated
Diameter of Cable
Nominal
Size of
are designed forspecial uses), exceptas tothe particular Under Juie Bedding
Armor
Wire
details expressly set forth in the following sections for inches mm BWG mils mm
2
0-1.000 0-5.40 12
2.77 109
1.001-1.700 25.43-43.18 13410 3.40 4.5.22.2 SIZE OF ARMORWIRE FOR SHEATHED
VERTICAL RISERCABLE
1.701-2.500 43.21-63.50 8 165 4.19
The size of armor wire for sheathedvertical riser cable
* 2.501 andlarger 63.53 andlarger 6 5.16
203 for indoor installation shall be in accordance with
4.5.19.2 for borehole cable, but with a tensile safety
4.5.22 Vertical Riser Cable (Suspended at One factor of not less than four.
End Only)
4.5.23WireBandSem'ng
4.5.22.1NONSHEATHEDCABLE FOR lNSTALlATlON
WITHIN BUILDINGS
Where wire band servings directly overthe armor are
required for cable suspended vertically from one end,
4.5.22.1.1 ARMOR No. 12 BWG (109 mils) (2.77 mm) wire shall be used.
Galvanized roundsteel wire shallbe used for vertical The length of the serving band andthe spacing of the
riser cable. band throughout the length of the cable shall be in
accordance with Table 4-31.
The wire bands shall be applied sufficiently tight to
prevent their movement along the cable as a result of
handling the cable during installation.
Table 4-31
Spacing and Lengthof Band Servings
Calculated
Diameter
Over lhe Armor
Wire Maximum
Band
Spacing
Band
Length
of
inches mm feel meters inches mm
P I_
6 Table 4-32
Thickness o f Jute Bedding and Sizeof Armor Wire
CalculatedDiameter of CableUnderJuteBedding Minimum Thickness of JuteBedding Nominal She of ArmorWire
c
inches nun mils mm BWG mils mm
WC 7-1988
Page 34 K E A S-66-524
DIVISION 111
Round Wire Armor for Buried Cable
exceptastoparticulardetailsexpresslyset forth in the
following sections or as otherwise modified.
O
4.5.24 Scope 4.5.26 Armor wire and Jute Servings (Sheathed
and Nonsheathed Cables)
Division III gives details of construction of armor for
buried land cables where greater longitudinal strength The size of armor wire and thicknessof jute bedding
than that provided by flat tape armor is required, but not shall be in accordancewith Table4-32.
the strength of the regular armor required for sub- The lengthof lay of the armor wires shall be not less
marine service. than three nor more than twelve times their pitch
diameter. This lay shall the armor will
be used such that
4.5.25 General be applied closely without appreciable space between
The requirements of Division I (4.5.3 through 4.5.16) wires. P
pertaining to quality of materials, design, and construc- A jute serving as specified in 4.5.10 shall be applied
tion apply also to buried round wire armored cables, over the armor.
Q
WC 7-1988
Page 36 ICEA S-66-524
Section 6
TESTING AND TEST METHODS
components, shallbe made only witha microscope. The For determination of unaged properties
micrometer and microscope shallbe capable of making Tensile strength and ultimate elongation 3t
measurements accurate to at least 0.001 inch.
Permanent set 3t
6.4.3.1 MICROMETERMEASUREMENTS
For accelerated aging tests 3t
When a micrometer is used, the average thicknessof
immersion
the insulation shallbe taken as one-half oil
of the difference For 3t
between the mean of the maximum and minimum Heat shock 1*
diameters over the insulationat one point and the
average diameter over the conductor or any separator Heat distortion 3t
measured at the same point. The minimum thicknessof Cold bend 1*
the insulation shallbe taken as the difference between a
measurement made overthe conductor or any separator Environmental
cracking see 6.10.4
plus the thinnest insulationwall, and the diameter over Absorption coefficient see 6.10.5
the conductor or any separator. The first measurement
shall be made after slicing off the thicker side of the
Striming 1*
~~
insulation. The thickness of any separator shall not be 'For the heat-shock,cold-bend, and stripping tests, only one
included in the thickness of insulation. specimen shall be tested.
If the wire or cable has a jacket, the jacket shall be t o n e test specimen out of three shall be tested and the other two
removed and the minimum and maximum thickness of specimens held in rcsewe, exceptthatwhen only one sample is
the jacket determined dircctly with a micrometer. The selected in accordance with 6.4.4 and 6.43,all three test specimens
average of these determinations shall be taken as the shall be tested, and the averageof the results reported.
average thicknessof the jacket.
Table 6-4
Number and Lengthof Samples
Quantity of Completed
Ordered
Cable Conductor
SizeNumber
of Minimum Length of
of Each Sample
Samples
14 meters kcmil mm2 conductor conductor
feeî meters
Less
than 2OOO Less
than 610 than
Less 250 Less
than 127 none a.. ...
1000
than
Less 305 250 and larger 127 and larger
none ... ...
zooo-a,000 610-15,240 Less than250 Less than 127 1 6 1.8
F 1OOO-25O
, OO 305-7620 250 and larger 127 and larger 1 3 0.9
More than 25,000 More than 7620
v First 25,000 First 7620 250 and larger 127 and larger 1 3 0.9
Each additional Each additional 250larger
127
and and larger 1 3 0.9
7620 25,000
More than 50,000 More than 15,240
First 50,000 First 15,240 than
Less 250 127than
Less 1 6 1.8
Each additional Each additional
than
Less 250 127
than
Less 1 6 1.8
15,240 50,000
Table &5
Number and Lengthof Samples
Quantity
Completed
of Cable Ordered Nominal
Overall
Diameter
Cable
of Number " m u m Length
of
Each of Sample
Samples
feet meters inches cable mm feet cable
meters
Less than 2OOO Less than610 Less than1.0 Less than25.4 none ... ...
Less than 1000 Less than 305 1.0 and larger 25.4 and larger none a.. ...
2000-50,000 610-15,240 Less than1.0 Less than25.4 1 6 1.8
1O00-25,000 305-7620 1.0 and larger but 25.4 and larger but
less than2.0 less than50.8 1 3 0.9
2.0 and larger 50.8 and larger 1 2 0.6
D More than 50,000 More than 15,240
First 50,000 First 15,240 Less than1.0 Less than25.4 1 6 1.8
Each additional Each additional Less than1.0 Less than25.4 1 6 1.8
50,000 15,240
More than 25,000 More than 7,620
First 25,000 First 7620 1.0 and larger but 25.4 and larger but 1 3 0.9
less than2.0 less than50.8
Each additional Each additional 1.0 and larger but 25.4 and largerbut 1 3 0.9
25,000 7620 less than2.0 less than50.8
More than 25,000 More than 7620
First 25,000 First 7620 2.0 and larger 50.8 and larger 1 2 0.6
Each additional Each additional 2.0 and larger 50.8 and larger 1 2 0.6
25,m 7620
6.4.7 Size of Specimens insulation. The height of the segment is the wall of
The test specimens shall be prepared using either insulation on theside from which the slice is taken.
ASTM D412 Die B or E with specimenlength not less When the cross-section of the slice is not a segmentof
than 6 inches (152 mm) or ASTM D412 Die C or D with a circle,the area shall be calculated from a direct meas-
specimen length not less than 4.5 inches (114 mm). urement of the volume or from the specific gravity and
In the case of wire and cable smaller thansize 6 AWG the weight of a known length of the specimen having a
having an insulation thicknessof 90mils (2.29 mm) or less, uniform cross-section.
thetestspecimenshallbepermittedtobetheentiresection The values may be obtained from a table giving the
of the insulation. Whenthe full cross-section is used, the areas of segments of a unit circle for the ratio of the
specimensshallnotbecutlongitudinally.1nthecaseofwire height of the segment to the diameter of the circle. (This
and cable size6AWG and larger, or in the case of wire and paragraph is approved by NEMA as Authorized En-
cable smaller than size 6 AWG havingan insulation thick- gineering Information,) ).
nessgreaterthan90mils(2.Bmm),specimensrectangular
6.4.10.3 When the conductor is large and the insula-
in sectionwithcross-section
a not greater than0.025 square
tion thin and when a portion of a sector of a circle has
inch (16 mm2) shallbe cut from the insulation.In extreme
to betaken, the areashall be calculated as thethickness
cases, it may be necessary to use a segmental specimen.
times the width.
(This sentenceis approved by NFMA as Authorized En-
gineering Information.) This applies either to a straight test piece or to one
stamped out with a die and assumes that corrugations
Specimensfor test onjacket compoundsshallbe taken
from the completed wire or cable and cut parallel to the have been removed. (This paragraph is approved by
NEMA as Authorized Engineering Information,)
axis of the wire or cable. The test specimen shall be a
segment cut with asharp knife or a shaped specimencut 6.4.10.4 When the conductor is large and the insula-
out with adie and shall have a cross-sectional area not tion thickand when aportion of a sector of a circle has
greater than 0.025 square inch (16 mm2) after ir- to betaken, the areashall be calculated as thepropor-
regularities, corrugations, and reinforcing cords or tional part of the area of the total cross-section.
wires havebeen removed.
6.4.8 Preparation of Specimens of Insulation
6.4.10.5 The dimensions of specimensto beaged shall
be determined before the aging test.
0
and Jacket
The test specimen shall haveno surface incisions and 6.4.11PhysicalTestProcedures
shall be as free as possible from other imperfections. See 6.4 for 'Est Samples and Specimens.
Where necessary, surface irregularitiessuch as corruga-
tions due to stranding, and such, shall be removed so 6.4.1 1.I TEST TEMPERATURE
that the test specimen will be smooth and of uniform Physical tests shall be made at a room temperature not
thickness. less than 20°C (68°F)nor more than 28°C (82.4"F).The
test specimens shall be kept at room temperature for not
6.4.9 Specimen for Accelerated Aging Test less than 30 minutes prior to thetest.
Specimens shallnot be heated, immersed in water, nor I
subjected to any mechanicalor chemical treatment not 6.4.1 1.2 m P E OF TESTING MACHINE
specifically described in this standard. The testing machine shall
be in accordance with 6.1 of
ASTM D412.
6.4.10 Calculation of Area of Test Specimens
6.4.1 1.3 TENSILE STRENGTH TEST
6.4.10.1 Where the total cross-section of the insula-
tion is used, the area shall be taken as the difference The tensile strength test shall be made with specimens
between the area of the circle whose diameter is the prepared in accordance with 6.4.6 and 6.4.7.The length
average outside diameter of the insulation and the area of all of the specimens for the test shall be equal. Gauge
of the conductor. The areaof a stranded conductor shall marks shall be 2 inches (50.8 mm) when using 6 inch
be calculated from its maximum diameter. (152.4mm) specimens and 1 inch (25.4mm) apart when
using 4.5 inch (114.3mm) specimens exceptthat 1 inch
6.4.10.2 Where a slice cut from the insulation by a (25.4 mm) gauge marks shallbe used for polyethylene
knife held tangent to the wire is used and when the regardless of specimen length. Specimens shall be
cross-section of the slice of the cross-section of a seg- placed in the jaws of the testing machine with amaxi-
ment of a circle, the area shall be calculated as that of mum distance between jaws of 4 inches (101.6 mm)
the segment of a circle whose diameter is that of the except 2.5 inches (63.5 mm) for polyethylene. The
~~ ~
6.9 THICKNESS OF JUTE BEDDINGS AND the endof this period, the thickness, T2, shall be read on
SERVINGS the dial of the gauge. The distortion shall becalculated
The thickness of jute bedding under the armor shall as
be determined by the use of a diameter tape and shall Distortion,percent - T1-T2 x
be considered as Yi of the difference in the measure- T1
ments under and over the serving. The measurement in
each case shall be the average offive readings taken at 6.10*3 COM Bend
different points along the serving. The test specimen shall be subjected to the specified
temperature for 1 hour and then bent 180 degrees
6.10 TESTS FOR THERMOPLASTIC JACKETS around a mandrel having a diameter in accordance with
Table 6-9 immediately upon its removal from the cooling
6.10.1Heat Shock chamber. The bend shall be made at a uniform rate, and
S a P l e s (see 6e4.5) of Polyvinyl-chloride-jacketed the time required shall net exceed 1minute.
wire or cable shall be wound tightlyaround a mandrel Table 6-9
having a diameter in accordance with Table 6-8, held
firml;in place, and subjected to a temperature of Outside Diameter of Wire orCable Diameter or Mandrel as a
Multiple of the Outside
12l0C21"Cfor 1hour. inches mm Diameter of Cable
A sample of the completed cable shall be bent, in theNOTE-For further information, see IEEETransactions on Power
form of a U, 180 degrees around a mandrelhaving a Apparatus and Systems, Volume 84,1965, p. 815 (paper 31 TP6),
diameter in accordance with Table6-10. Discharge Resistant Characteristics of Polyethylenes for Wire and
Cable by E. K. Duffy, S. Jovanovitch, and I.J. Marwick. (For the
purposes of N E M A , this note is approved as Authorized Engineering
Information).
its immersed length. This procedure shall be may be made with only two electrodes spaced at least 2
repeated four times per minute for a minimum of inches (50.8 mm) apart.
ten cycles and a maximum of fifty cyclesor until The power of the test circuit shall not exceed 100
failure occurs, Failure occurs when arc isanmain- milliwatts. The test shall be made at the specified
tained for two successive cycles between the temperature with either ac or dc voltage.
electrode and solution across 1inch ofspecimen. The voltage resistivity shall
be calculated as follows:
4. A 60 Hz test potential shall be applied to the 2R(D2-d2)
P=
electrode attached to the specimen. The tracking 100L
voltage isthe voltage at which no failures occur Where -
on
five consecutive test specimens. P = Volume resistivity in ohm-meters.
NOTE-For further information, see IEEETransactions on Electri- R = Measured resistance inohms.
cal Insulation, December 1967, Vol. EI-2, No.3, p. 137 (Paper 31 D = Diameterover the insulationshieldlayerin
TP66-360)Dip-TrackTest
, byC.F. Wallaceand C.A. Bailey.(Forthe inches.
purposes of NEMA, this noteis approvedas Authorized Engineering d = Diameter over the insulation in inches,
Information).
L = Distance between potential electrodes in inches.
6.12 VOLUME RESlSTlMTY
6.12.4StrippingTest
6.12.1TestSample Test samples and specimens shallbe selected in ac-
One sample shall be taken from each lot or from eachcordance with lhbles 6-5 and 6-6. The test specimen
25,000 feet of completed cable, whichever is less. shall be approximately 15inches (381 mm) long, and all
coverings over the extruded insulation shield shall be
6.12.2ConductorStressControl removed.
The samples shallbe cut in half longitudinally theand Starting at one end, two parallel longitudinal cutsM
conductor removed.Foursilver-painted electrodes inch (12.7 mm) apart and not less than12 inches (305
shall be applied to the conductor stress control layer. mm) long shall be made throughthe insulation shield.
The two potential electrodes shallbe at least 2 inches The specimen shall be rotated 180 degrees and two
(50.8 mm) apart. A current electrode shall be placed atidentical cuts shall be made starting from the same end.
least 1inch (25.4mm) beyond each potential electrode. Each M inch (12.7mm) strip shall be peeled back from
When a high degree of accuracy is not required, this the test cut end for a distance of 2 inches(50.8 mm),
may be made with only twoelectrodes spaced at least 2 The specimen shall be mounted horizontally in a test-
inches (50.8 mm) apart. ing machine and secured at each end. The 2 inch(50.8
The powerof the test circuit shall not exceed 100 mm) end of the peeled strip shall be gripped in the
milliwatts. The test shall be made at the specified testing machine in sucha manner that it can be pulled
temperature with either ac or dc voltage. at an angle of 90 degrees tothe cable axis.
The volume resistivity shallbe calculated as follows: Each strip shall be peeled the from
cable at a constant
speed not exceedingM inch (12.7 mm) per second for a
R(D2-d2) distance of not less than 10 inches mm).
(254
P= The angle of pull shall be maintained as close as
l00L
possible to90 degrees throughoutthe test.
Rwr, 6 1
TEST SPECIMEN FOR TEAR TEST
R = KlOglO
D
-
d
Where-
conductor cableswith nonshielded individual conductors R = Insulation resistancein megohms-1000 feet.
having a metallic sheath, shield,or armor over the cable K = Constant for the grade of insulation.
assembly, the test voltage shall be applied between each (See Part 3)
insulated conductorand all other conductorsand ground D = Diameter-over the insulation.
6.14.8 Vottage Jests after lnstalbtion d = Diameter under the insulation.
If voltage tests are made after installation, they shall If thetemperatureatthetime of measurement
be made immediately. The test voltage shall be a dc
differs from 15.6"C (60°F),theinsulationresistance
voltage as given in Table 6-11 and shall be applied in
shall
be
corrected
to
that
at 15.6"C (60°F) by
accordance with 6.14.1 and 6.143.
multiplying
the
measuredvaIue
the
by
proper
Table 6 1 1 correctionfactorgiven in Table 6-13, using the
DC Test Voltages After installation, kV coefficient(see 6.12.3) fortheparticulargradeof
Rated Circuit T e l Voltage, kV insulation and temperature in question. The temperature
Vollrrst, Conductor ofthewatershall be notlessthan 10°C (50°F)nor
100 Percent 133 Perccnl
PhaSt-to-Phw SIZC,
Voll5 AwG or kcmil Insulation InsulaLion more than 29.4OC (85°F).
Lcvcl Lcvel
~- ~~ ~- ~ ~
6.15.3 Determination of Temperature Correction
2001- 5000 &lo00 25 25 Factors for Insulation Resistance
5001- 8000 b
W
l O 35. 35 Three samples, preferably of 14 AWG solid wire with
a 45 mil (1.14 mm) wall of insulation, shall be selected
8001-15000 2-1000 55 65 as representative of the insulation under consideration.
15001-25OOo 1-lo00 80 100 The samples shall be of sufficient length to yield insula-
tion resistance values under 25OOo megohmsat the
25001-28OOo 1-lo00 85 ... lowest waterbath temperature.
28001-35000 1/0-1o00 100 ... The threesamples shall be immersed in a water bath
equipped with heating, cooling,and circulating facilities
6.15INSULATIONRESISTANCE with the ends of the samples extended at least 2 feet (0.6
meter) above the surface of the water and properly
6.15.1TestApparatus prepared for minimum leakage. The samples shall be
The test apparatus shall consistof a source of constant left in the water atroom temperature for 16hours before
potential of 100 to 500volts and such other apparatusas adjusting the bath temperature to10°C or beforetrans-
is listed in ASTM D257. ferring the samples to a 10°C test temperaturebath.
The resistance of the conductor shall be measured at
6.1 5.2 Test Procedure suitable intervals until itremains unchanged for at least
5 minutes. The insulation will then beat the temperature
Single conductor cables shallbe tested between the of the bath as read on the baththermometer. Insulation
conductorand
metallic
sheathor
water.
Multiple resistance shall then be measured in accordance with
conductor cables with nonshielded conductors shall be 6.152.
tested between each conductor andall other conductors Each of the three samples shall be exposed to succes-
andsheathorwater.Multiple-conductorcables with sive watertemperatures of 10,16,22,28, and 35°C and
shielded
conductors shall be
tested
between
the returning 28,22,16 and 10°C. Insulation resistance read-
conductor and shield. ings shall be taken ateach temperature after equilibrium
The conductor under test shall be connected to the has been established.
negativeterminalofthetestequipment and readings The two sets of readings taken at the same tempera-
shall be taken after an electrification of 1 minute. ture shall be averaged and, together with the reading at
Each coil, reel or lengthof wire or cable shall have 35"C, plotted on semi-log paper. The insulation resis-
aninsulationresistanceinmegohms-1000feetat a tance valce at 156°C (60°F)shall be readfrom the plot.
temperature of 156°C (6OOF)of not less than the value The 055°C (1°F) coefficient shall be calculated by
of R calculated as follows: dividing the insulation resistance at 156°C (60°F)by that
at 16.1"C (61°F).
6.16 Deleted
Table 6-12
Temperature Correction Factors for Insulation Resistance
to 15.6"C (6OOF)
Temperature Coefficient for lop
op oc 1.03 1.04 1.0s 1.06 1.07
1.09 1.08 1.10 1.11 1.12
50 10.0 0.75 0.68 0.62 0.56 0.51 0.46 0.42 0.38 0.35 0.32
51 10.6 0.77 0.70 0.65 0.59 0.54 0.50 0.46 0.42 0.39 0.36
52 11.1 0.79 0.73 0.68 0.63 0.58 0.54 0.50 0.47 0.43 0.40
53 11.7 0.82 0.76 0.71 0.67 0.62 0.58 0.55 0.51 0.48 0.45
54 12.2 0.84 0.79 0.75 0.70 0.67 0.63 0.60 0.56 0.54 0.51
55 12.8 0.87 0.82 0.78 0.75 0.71 0.68 0.65 0.62 0.60 0.57
a
56 13.3 0.89 0.86 0.82 0.76 0.76 0.74 0.71 0.69 0.66 0.64
57 13.9 0.92 0.89 0.87 0.84 0.82 0.80 0.78 0.76 0.73 0.71
58 14.4 0.94 0.93 0.91 0.90 0.88 0.86 0.85 0.83 0.82 0.80
59 15.0 0.97 O.% 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89
60 15.6 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
61 16.1 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12
62 16.7 1.06 1.08 1.10 1.13 1.15 1.17 1.19 1.21 1.24 1.27
63 17.2 1.09 1.13 1.16 1.19 1.23 1.26 1.30 1.34 1.38 1.42
64 17.8 1.13 1.17 1.22 1.26 1.31 1.36 1.41 1.47 1.53 1.58
65 18.3 1.16 1.22 1.28 1.34 1.40 1.47 1.54 1.62 1.70 1.78
66 18.9 1.20 1.27 1.35 1.42 1.50 1.59 1.69 1.78 1.88 1.98
67 19.4 1.23 1.32 1.41 1.51 1.62 1.72 1.84 1.96 2.09 2.21
68
~~ 20.0 1.27 1.37 1.48 1.60 1.72 1.85 1.99 2.15 2.31 2.48
69 20.6 1.31 1.43 1.55 1.69 1.84 2.00 2.18 2.36 2.57 2.77
70 21.1 1.35 1.48 1.63 1.79 1.97 2.17 2.38 2.60 2.85 3.10
71 21.7 1.39 1.54 1.72 1.90 2.11 2.34 2.59 2.87 3.17 3.46
72 22.2 1.43 1.60 1.80 2.02 2.26 2.53 2.82 3.15 3.52 3.90
73 22.8 1.47 1.67 1.89 2.14 2.42 2.72 3.08 3.46 3.90 4.37
74 23.3 1.52 1.74 1.98 2.27 2.58 2.94 3.35 3.81 4.31 4.88
75 23.9 1.56 1.80 2.08 2.40 2.76 3.18 3.65 4.19 4.78 5.47
76 24.4 1.61 1.87 2.19 2.54 2.96 3.43 3.98 4.61 5.30 6.12
77 25.0 1.66 1.95 2.30 2.70 3.17 3.70 4.34 5.08 5.88 6.85
78 25.6 1.71 2.02 2.41 2.86 3.39 4.00 4.73 5.59 6.51 7.68
79 26.1 1.76 2.11 2.53 3.03 3.62 4.33 5.16 6.14 7.27 8.59
80 26.7 1.81 2.19 2.66 3.21 3.87 4.67 5.61 6.72 8.07 9.65
81 27.2 1.87 2.28 2.80 3.40 4.15 5.04 6.12 7.43 8.98 10.8
82 27.8 1.92 2.37 2.94 3.60 4.43 5.45 6.69 8.18 9.92 12.1
83 28.3 1.98 2.47 3.08 3.82 4.72 5.89 7.28 9.00 11.0 13.6
84 28.9 2.04 2.57 3.23 4.05 5.04 6.35 7.92 9.90 12.2 15.2
85 29.4 2.10 2.67 3.40 4.30 5.42 6.84 8.67 10.8 13.5 17.0
JANUARY 1991
WC 7-1988
ICEA s-66-524 Page 53
Section 7
CONSTRUCTIONS OF SPECIFIC TYPES
1 through 6 shall be met exceptas otherwise modified in Section 7.)
(The requirements of Sections
7.1 CONCENTRIGNEUTRALUNDERGROUND 100 percent insulation level. The minimum thickness Shan
DISTRIBUTION CABLES benotlessthan90percentofthevaluesgiveninthetable.
7.1.1 Scope 7.1.4 Insulation Shielding and Protective
This section covers twoconductor concentric-neutral Covering H
power cables consisting of one cross-linked-thermoset- A layer of conducting nonmetallic material meeting the
ting-polyethylene-insulatedcentralconductorandone requirements of 4.1.1 shall be extruded directly over the
copperconcentricconductorappliedhelicallyoverall. insulationto~easbothanelectrostaticshieldandapro-
These cables are intended for use on singlephase and tective covering. The thickness of the e x W insulation
threephase primary undergrounddistributionsystems op shieldingat any location when measured on completed cable
emting at 2001 through 35000 volts phasemphase at 100 shall be in accordancewith Table 7-2.
ampxities, see Appendix F.
percent insulation level. For The conducting layer shall be compatible withthe insula-
tim and shall be legibly identifiedas beiig conducting.
7.1.2CentralConductor Tmpentms lower than 130'C (2°F)may be required
Central conductorsshall be annealed copper,or alumi- for emergency m l o a d conditions because of the type of
num. The minimum conductorsize shall be in accordance materialused in thecable, joints, andterminations or because
with Table7-1. of
cable
environmentalconditions.
paragraph is ap
Table 7-1 provedbyNEMAasAuthorizedEngin&gInfomation.)
Minimum ConductorSize Table 7-2rn
Rated CirmitVoltage, Minimum ConductorSbz, AWC ForCableWithorWithoutan Overall Jacket
P h p s e - t o - m Vdts Caldated Insulation Diameter Insulation Shleld
2001-15000 4 ThickneaP
Inche3 "mum Maxmum
Maxmum
15001-28000 1 Point Poht Poht
28001-35000 1K) Inch Inch Inch
1.OOO or less .O30 .O70 .O15
7.1.21 C
O- 1.001-1.500 .O40 .O85 .O15
'Tlreconductashalbeannealed"aannealed
coatedcoppereitherCkssBaCssandeda,forunooated 1.501-2.000 .o55 .loo .mo
~,cQm~shandedinaccardancewi~sectioa2 largerand
2.001 .O55 .115 .O20
Note: The minimum point does not apply to locations under the metallic
7.1.22 ALUWUM shield indent.
Theconductor shall be aluminum 1350, eithersolid
(through 4/0 AWG) Class B or C stranded or compact 7.1.5ConcentricConductor
stranded in accordancewith Section 2. The overall concentric conductor shall consist of num-
a
ber of copper wires meeting the chemical requirements of
7.1.2.3 CONDUCTORSTRESSCONTROL LAYER ASTM B5 and the resistivity, tensile, and elongationre-
The conductor shall be covered with a smss control quirements of ASTMB3 for uncoated wires, ASTM B33
layer in accordance with Section 2. for tincoated wr ies,or ASTM B 189 for lead-alloy-coated
wires. The number wiresof of a specifiedsize shall be not
7.1.3
Insulation less than that given in Table7-3 for cables usedin single-
Theshieldedcentralconductorshallbeinsulatedwitha phase systems and in either Table 7-5 or Table 7-6 for
cross-linked-thermosetting-polyethylenecompoundthat three-phase systems.
meets the requinments of 3.7. The average thickness of the The nominal diameters and circular mil
areas of the wires
insulationshallbenotlessthanthatgivenin~le3-1forthe in Tables 7-3,7-5,and 7-6 shall be BS follows:
R e v i d 1-30-1991.
AWC S h "
W Aren, kcmil Table 7-4
14 0.064 1 4.11 Level
Discharge
Partial
RatdCWVdtnge, " m u m Partlal-dLschPrge
0.0808 12 6.53 Phssc"P~Vdts Extinction Level,LV
0.1019 10 10.38 m1-5m 5
9 o.1144 13.09 5 0 0 1 ~ 7
8 0.1285 16.51 8001-15000 13
Thein~~~wirescomprisingagivenconcentriccon- 15001-25000 22
ductormayvaryf5percentindiametexfmmtheappropri- wx)~-28ooo 25
ate nominal value given above, butthe total circular mil
area
the of specitïed concentric
conductor shall be as 28001-35000 31
follows:
1. For single-phase systems,at least 98 percent of the 7.1.6 Optional Jackets Applied over a
product ofthe appropiate number ofwires given in Concentric Conductor
Table 7-3times theappropriate nominal circular mil The jacketsshall be either nonconductingor conducting
arta tabulated above. &pending upon installation requirements.If nonconduct-
2 For threephase systems at least 98 percent of the ing compoundis used, it shall meet the physical and aging
product of the
number of wires given
in requirements of4.4.1 through 4.4.3 as applicable.
Tables 7-5œ 7-6 times the appropriate nominal If conducting compoundis used, it shall be eitherType
circular mil 8 1 ~ tabulated
8 above. I or II compound meetingthe physical and aging require-
NOTE: This is for a one-third neutral. ments of Table 7-6A.
The wires of the concentric conductorshall be applied A 'I)pe II jacket provides m m heat and deformation
directly over the conductor material given7.1in.4with a resistance than lslpe I.
lay not less than six nor more than ten times the diameter CAUTION-Cable users should be aware that some
over the concentric wires. typesof jackets may alter the physical and electrical char-
Table 7-3 acteristicsofcablecomponents.('Thissentence is ap-
Full Neutral Concentric Conductor proved by NEMA asAuthorizedEngineering
Inanlated Conductor ConcentricConductor Information.)
SbAWCorkcd MlnlmumNumberdWires
7.1.6.1EXTRUDEDTC~FILL JACKET
C Q V ~Aluminum l4AWG l2AWC 10 AWC 9 AWG
The jacket materhl shall cover the concentric conductor
... 4 6 ... ... ... and íillthe spaces between wires. The jacket materialshall
4 2 10 ... ... ... be in Contact with the insulation shielding, butshall strip
3 1 13 ... ... ... W.
2 1/0 10* 16 ... ... When measured over the wires, the average jacket thick-
1 2/0 U)* 13 ... ... ness shall be not less than the appropriate value given in
1/0 10*
25* 16 ... Table 7.4A.
2/0 3/0
4/0 32* U)* 13 10*
3/0 250 ... 25* 16 13*
350
4K) ... 32* 20* 16
+Altemrtc cmstmchm.
Table 7.4A
Jacket Thickness and Test Voltage
AC SparkTestVdtage@V)for
Cnldated Diameter Conductor Average JrLetThickmss Nonconducting
CFoss-unLed Thermoplastic
Inche Jackets Ineh Jackets
0-1.500 .O50 2.0 4.5
Over 1.500 .O80 3.0 7.0
wc7-1988
iCEA S-66-524 Page 55
Table 7 6
One-third Neutral Concentrk Conductor for Copper Central Conductor
"
Table 74A rn
Properties of Thermopiastk Conducting Jackets
r n I lppeII
Physical Requirements
Tensile strength, minimum
Psi 1200 1500
Elongationpercent
at rupture,minimum 100 150
Aging Requirements
Afier air oven agingat lOO'C&l'C for 48 hours
Tensile strength, minimum pemntage of unaged value 75
Elongation
at rupture,minimum percentage of unaged value 100
After air oven agingat 121'Cfl'C for 168 hours
percentage
minimum
strength,
Tensile valueof unaged 75
at Elongation
percentage
rupture,minimum 75
Heat Distortion,Maximum, Percent
Air oven at 90'Ckl'C 25
Air oven at 121'Cfl'C 25
Wume resistivity at m m iernpemm (23'CS.C) and 90'Cfl 'C, max, meter-duns 100 100
Brittleness Temperature,'C, not wanner than -15 -10
Revised 1-30-91.
7.2.2.2.1
COPPER 7.2.3 insulation
Conductors shallbe hard drawn uncoated copper and 7.2.3.1PHYSICAL AND AGINGREQUIREMENTS
shall meetthe requirementsof ASTMB1 andB8. Sizes
2 AWG and smaller shallbe solid or shall be Class B The insulation shall be black and, when tested in
stranded in accordancewith Table 2-7. Sizes
larger than accordance with Section 6, shall meet the following
2 AWG shall be Class B stranded in accordancewith requirements:
Table 2-7. Physical Requirements
7.2.2.2.2
ALUMINUM Tensile strength, minimum
Conductors shallbe hard drawnaluminum1350. The psi
stranding shall be in accordancewith ClassA Table 2 or
MPa
I:
ASTM B231 for sizes up through 210AWG and in
accordancewith Class B Table 3of ASTM B231for sizes Elongation
at
rupture, mn
im
i um,percent 150
310 AWG and larger. The direction of lay of the outer Aging Requirements
layer shall be right hand.
After air oven test at 121"Crt1°C for 168 hours
7.2.2.2.3 COPPER AND COPPER-COVERED-STEEL
COMPOSITE Tensile strength, minimum, percentage
of
75 value unaged
Conductors shall be concentric-lay-stranded-copper
andcopper-covered-steel-compositeconductorsand Elongation at rupture,minimum, percent-
shall meet the requirements givenin the applicable 65 age
value
of unaged
sections of ASTM B229. After hot creep test at 150°C&2"C
7.2.2.2.4 ALUMINUMCONDUCTORS-STEEL Unfilled Filled
REINFORCED *Hot creep elongation, maximum,
7.2.2.2.6 ALUMINUMALLOYCONDUCTORS
250-500 80 2.03
-6201-T81 The minimum thickness shallbe not less than90 per-
Conductors shall meet the requirements of ASTM cent of these values.
B399. The stranding shall be 7-wire strand for sizes
246.9 kcmil and smaller and 19-wire strand for sizes 7.2.4
Assembly
larger than246.9 kcmil. 7.2.4.1 WISTED ASSEMBLIES
One or more insulated conductors shall be twisted
around the neutral conductor without fillers witha lay
of 25 to 60 times the diameter of one of the insulated
conductors.The directionof layshall be the same as that
of the outer layerof wires ofthe neutral conductor.
7.3.2.2GROUNDINGCONDUCTORS 7.3.4InsulationShielding
Grounding conductors shall
be Class B or C stranded Each power conductor shall be shielded in accord-
annealed coated copper wire and shall meet
the require- ance with4.1.
ments given in Section 2. The size of each grounding
conductor shallbe in accordancewith Table7-9. 7.3.5
Identification
Power conductors shallbe identified as black, white,
7.3.2.3GROUNDCHECKCONDUCTORS and red.
The ground check conductor shall be Class B or C The ground check conductor shall be covered with a
stranded annealed coated or uncoated copper of the closely woven cotton or rayon braid which is colored
minimum size shown in Table 7-9 and shall meet the yellow or witha yellow colored insulation.
requirementsgiven in Section2.
7.3.6ConductorAssembly
7.3.3
Insulation The conductor assembly shall have a left-hand A lay.
c
Insulation shall meetthe requirements given in Sec- grounding conductor shall be placed in continuous con-
tion 3. tact withthe metallic shields in each intersticeof 'Qpe
The average thickness ofthe insulation on the power MP cables and two in intersticesof 'Qpe M€-GCcables.
conductors shallbe not less than that given inTables7-10The ground check conductor of %e MP-GC cables
and 7-11. The average thickness of the insulation on shall be placed between the black and white conductors.
ground check conductors shall be not less than45 mils Fillers of suitable material shallbe used to produce an
(1.14 mm) for 8 AWG and not less than30 mils (0.76 essentially round cross-section inthe completed cable.
mm) for 10 AWG. The minimum thickness shallbe not When required, a binder tape andlor threads shall be
less than90 percent of these values. used overthe conductor assembly.
Table 7-8
Neutral Conductors for Use with Aluminum Power Conductors
Aluminum Insulated Neutral ConductorSizes, AWG
Power Conductor
Copper Covered
Copper Aluminum 1350 ACSR Aluminum Alloy
Sizes AWG or kcmil
Steel* 5005-Hl96201-T81
6 8 8C 6 6 6
4 6 6C 4 4 4
4 8 8C ... 6 6
2 4 4A 2 2 2
2 6 6C ... 4 4
V0 2 2F V0 110 110
110 4 4A ... 2 2
U0 1 210 1F 210 210
U0 3 3A ... 1 1
310
dl0 110 310 110 F 310
310 2 2F ... 110 110
410 410 U0 410210 F 410
410 1 1F ... 210 210
266.8 312.8 ... 266.8 ... 266.8
... ... 195.7 ... 167.8
336.4 394.5 ... 336.4 ... 336.4
... ... 246.9 ... 211.6
397.5 465.4 ... 397.5 ... 397.5
... ... 312.8 a.. 266.8
477.0 559.5 ... 477.0 ... 477.0
... ... 394.5 e.. 336.4
*SeeAST" B229 (see Appendix E) for letter designations and construction.
Table 7-9
Conductor Sizes
Size of Power
Conductors, AWG or kcmil Copper
Grounding
Conductors
Copper
Ground
Check
Conductor, Minimum Size,
Type MP Cables, Size in Type MP-GC Cables, Size in
AWG
Copper Aluminum Each,
Interstice, AWG Each of Two Interstices, AWG
10 6 4 10
4 2 8 8 8
2 110 8 6 8
1 210 7 5 8
110 6 4 8
210 5 3 8
310 4 2 8
410 350 3 1 8
250 400 2 U0 8
m. 450 1 110 8
350 500 1 210 8
400 ... 110 310 8
450 a.. Il0 310 8
500 e.. 210 410 8
Table 7-10
Insulation Thicknesses and Outside Diameters-
2001 to 5000 Volts*- 100 and 133 Percent Insulation Level
Minimum Partial-discharge
Extinction Level., kVf
.
AC Tesì
Conductor size’
AWG or kcmil Insulation Thickness Outside Diameter
kV Voltage,
Insulation Level
mm mils inches mm 100 percent 133 percent
P
Table 7-1 1
Insulation Thicknesses and Outside Diameters
Con- 100 Percent Insulation Level 133 Percent Insulation Level
ductor
:z
or
Insulation
Thickness
mils mm
Outside
Diameter
inches mm
Test Voltage,
AC
kV
DC
Minimum
Partialdis-
charge&-
Insulation
Thickness
mils mm
Outside
Diameter
inches mm
Test Voltage,
AC
kV
DC
Minimum
Partialdis-
charge
Ex(inction
tinction
kcmil Level, kV Level, kV
WC 7-1988
Page 62 ICEA S-66-524
Table 7-13
Nominal DC Resistanceof Medium Hard-Drawn Coated
and Uncoated Copper Conductors Concentric Stranded, Class
B and C
Conductor
@I"
25OC-lui 2O0C 250c 20%
AWG or Class of
kcmil
Sîranding ohmsper ohms per ohms per ohms per ohmsper ohmsper ohmsper ohmsper
lo00 feet km lo00 feet km lo00 feet km lo00 feeî km
6 B andC 0.436 1.43 0.444 1.46 0.417 1.37 0.425 1.40
4 B andC 0.274 0.899 0.279 0.917 0.262 0.860 0.267 0.877
2 B andC 0.172 0.565 0.176 0.577 0.165 0.541 0.168 0.552
1 B andC 0.137 0.448 0.139 0.457 0.131 0.429 0.133 0.437
110 0.108
B andC 0.355 0.110 0.362 0.104 0.340 0.106 0.347
210 B and C
0.0859 0.282 0.0876 0.287 0.0822 0.270 0.0838 0.275
310 BandC0.0681 0.224 0,0695 0.228 0.0652 0.214 0.0665 0.218
410 B 0.0536 O. 176 0.0547 0.179 0.0517 0.170 0.0527 0.173
410 C 0.0540 0.177 0.551 0.181 0.0517 0.170 0.0527 0.173
250 B andC 0.0457 0.150 0.0466 0.153 0.0438 0.144 0.0446 0,146
300 B and C 0,0381 0.125 0.0389 0.128 0.0365 0.120 0.0372 0.122
350 B and C 0.0327 O.iO7 0.0333 0.109 0.0313 0.103 0.0319 0.105
400 B 0.0284 0.0931 0.0289 0.0949 0.0274 0.0898 0.0279 0.0915
400 C 0.0286 0.0938 0.0292 0.0956 0.0274 0.0898 0.0279 0.0915
450 B 0.0252 0.0827 0.0257 0.0844 0.0243 0.0798 0.0248 0.0813
450 C 0.0254 0.0834 0.0259 0.0850 0.0243 0.0798 0.0248 0.0813
500 B 0.0227 0.0745 0,0231 0.0759 0.0219 0.0718 0.0223 0.0732
500 C 0.0229 0.0750 0.0233 0.0765 0.0219 0.0718 0.0223 0.0732
7.3.7
Jacket
-
kgflmm' 0.35
A thermosetting jacket that meets the requirements of Elongation
at
rupture,
minimum,
percent 300
7.3.7.1,7.3.7.2,7.3.7.3,or 7.3.7.4 or a thermoplasticjack-
et that meetsthe requirements of 4.4.1 or 4.4.3 shall be Set, maximum, percent 20
applied over the conductor assembly. The average Aging requirements
thickness of the jacket shallbe not less than that given
in Table 7-12 and the minimum thickness ofthe jacket After air oven testat 10OoC+1"Cfor 168
shall be not less than80 percent of these values. hours- tensile strength and elongationrup-
at
ture, minimum, percentage of unagedvalue 50
7.3.7.1NEOPRENE, HEAWD m ,BLACK
After oil immersion test at12l0C+.loCfor 18
This jacket shall consist of a vulcanized black hours-
tensile
strength
elongation,
andmini- e
neoprene compound. When testedin accordance with mum, percentage
unaged
value
of 60
6.4, the jacket shall meetthe following requirements,
and when applicable, the requirements given4.4.5in 7.3.7.2 N~TRILE-BUTADIENE/POLWINYL-CHLORIDE,
Physical requirements HEAWDUTY
Tensile strength, minimum This jacket shall consist
of a vulcanized acrylonitrile-
butadienelpolyvinyl-chloridecompound suitable for a
psi 1800 minimum installing temperature of -25°C (-13°F). It
kgf/mm2 1.27 shall be based on a fluxed blend of acrylonitrile-
butadiene synthetic rubber and polyvinyl-chloride resin.
Tensile stress at200 percent elongation, minimum When tested in accordance with 6.4, the jacket shall
psi 500 meet the following requirements and, when applicable,
the requirements given in4.4.6:
Table 7-15
o to 2000 Volts
Single-Conductor Portable Power Cable
Power Diameter Outside
Conductor
size,
AwG or Insulation Thickness Normal Service Hard
Voltage,
Test
Service kV
kcmilt Inus mm inches mm inches mm AC Dc
cables shall be in accordance with Table7-17, and four- between the black and white power conductors. These
conductor cables shall be in accordance with Table7-18. cables shall be in accordance with Table7-19.
-E 7.4.4.3 lYPE G-GC, THREE-CONDUCTOR ROUND, 7.4.5 Type W and G, Five- and Six-Conductor,
WITH GROUNDING CONDUCTORS AND 0-2000 Volt Cables
GROUND CHECK CONDUCTOR Five-conductor cables shall be of one of two types:(1)
s
These cables shall consist of three power conductors V p e W, without agrounding conductor and (2) Type G,
that are separately covered with insulation, twoground- with agrounding conductor. Six-conductor cables shall
ing conductors (see 7.4.12), and one ground check con- be we W only.
ductor (see 7.4.11). Each power and ground check
conductor shall be separately covered with a colored 7.4.5.1 m E W, WITHOUT GROUNDINGCONDUCTOR
tape orbraid which maybe omitted if colored insulation These cables shall consist of five or six conductors
is used (see 7.4.15). All power, grounding,and ground which are separately covered with insulation.Each con-
check conductors and anynecessaryfillersshall be ductor shall be separately covered with colored tape or
cabled with aleft-hand lay inaccordance with Table 7-14 braid, which may be omitted if colored insulation is used
and covered with ajacket that meets the requirements (see 7.4.15). The conductors, together with any neces-
of 7.4.18. The ground check conductor shall be laid sary fillers, shall
be cabled with aleft-hand lay inaccord-
ance with Table 7-14 and covered with a jacket that
Table 7-16
O to 2000 Volts-Type W and G Two-Conductor Round Portable Power Cables
Conductor
Power Thickness
Insulation Oulside Diameter TekV
st Voltage,
Slu, AWG or kcmilt
mils mm inches mm AC Dc
8 60 1.52 0.81 20.5 7.0 21.0
6 60 1.52 0.93 23.6 7.0 21.0
4 60 1.52 1.08 27.4 7.0 21.0
3 60 1.52 1.17 29.7 7.0 21.0
2 60 L52 1.27 32.3 7.0 21.0
1 80 2.03 1.44 36.6 8.0 24.0
110 80 2.03 1.52 38.6 8.0 24.0
U0 80 2.03 1.65 41.9 8.0 24.0
310 80 2.03 1.77 45.0 8.0 24.0
410 80 2.03 1.92 48.8 8.0 24.0
250 95 2.41 2.10* 53.3* 9.5 28.5
300 95 2.41 2.22* 56.3* 9.5 28.5
350 95 2.41 2.36* 59.9* 9,5 28.5
400 95 2.41 2.47* 62.7* 9.5 28.5
450 95 2.41 2.60* 66.0* 9.5 28.5
500 95 2.41 2.70* 683* 9.5 28.5
*These cables require extra-heavy-duty jackets(see 75.1).
tSee Table 7-28.
Table 7-17
O to 2000 Volts-Type W and G Three-Conductor Round Portable Power Cables
Conductor
Power Thickness
Insulation Vollage,
Test
Oulside Diameter kV
Size, AWG or kcmilt
mils mm inches mm AC Dc
8 60 1.52 0.91 23.1 7.0 21.0
6 60 1.52 1.01 25.7 7.0 21.0
4 60 1.52 1.17 29.7 7.0 21.0
3 60 1.52 1.24 31.5 7.0 21.0
2 60 1.52 1.34 34.3 7.0 21.0
1 80 2.03 1.51 38.4 8.0 24.0
110 80 2.03 1.65 42.0 8.0 24.0
WO 80 2.03 1.75 44.0 8.0 24.0
310 80 2.03 1.89 48.0 8.0 24.0
410 80 2.03 2.04* 51.8* 8.0 24.0
250 95 2.41 2.39* 60.7* 9s 28,5
300 95 2.41 2.56* 65.0* 9.5 28.5
350 95 2.41 2.68* 68.1* 9.5 28.5
400 95 2.41 2.82* 71.6* 9.5 28.5
450 95 2.41 2.94* 74.7* 9.5 28.5
95 2.41 3.03* 77.7* 9.5 28.5
*These cables require extra-heavy-duty jackets
(see 75.1).
tSee Table 7-28,
e
COPYRIGHT National Electrical Manufacturers Association
Licensed by Information Handling Services
WC 7-1988
ICEA 5-66-524 Page 67
Table 7-18
o to 2000 volts
Type W and G Four-Conductor Portable Power Cables
Power Conducfor Insulation
Diameter
Outside
Thickness Test Voltage,
kV
Siu, AWG or kcmilt
mils mm inches mm AC Dc
8 60 1.52 0.99 25.1 7.0 21.0
6 60 1.52 1.10 27.9 7.0 21.0
4 60 1.52 1.27 32.3 7.0 21.0
3 60 1.52 1.34 34.0 7.0 21.0
2 60 1.52 1.48 37.6 7.0 21.0
1 80 2.03 1.68 42.7 8.0 24.0
V0 80 2.03 1.79 45.5 8.0 24.0
U0 80 2.03 1.93 49.0 8.0 24.0
310 80 2.03 2.07* 52.6* 8.0 24.0
410 80 2.03 2.26* 57.4* 8.0 24.0
250 95 2.41 2.66* 67.6* 9.5 28.5
300 95 2.41 2.84* 72.1* 9.5 28.5
350 95 2.41 2.98* 75.7* 9.5 28.5
400 95 2.41 3.14* 79.8* 9.5 28.5
450 95 2.41 3.26* 82.8* 9.5 28.5
500 95 2.41 3.40* 86.4* 9.5 28.5
*These cables require extra-heavy-duty jackets
(see 75.1).
t h Table 7-28.
Table 7-19
o to 2000 volts
Type G-GC Three-Conductor Round Portable Power Cables
with Two Grounding Conductors and One Ground Check Conductor
Conductor
Power Esch Grounding
Ground
Check
Conductor Insulation Thickness Conducfor
Conductor
Diameter
Outside
Test Voltage,
kV
s 4 Size,
Number of Minimum Insulation
AWGor mils
mm AWGThickness,
Size,
WIresper inches mm AC Dc
kcmilt
Conducfor AWG mils
~~
10
8 49 60 10 1.52 21.0 7.030 24.6 0.97
106 49 60 10 1.52 21.0 7.0 30 26.6 1.05
4 60 1.52 8 49 2110
.0 7.0 30 30.2 1.19
3 60 1.52 8 10 49 21.0 7.0 30 31.7 1.25
b
2 60 1.52 7 10 49 21.0 7.0 30 34.3 1.34
1 80 2.03 6 133 8 45 1.51 38.4 8.0 24.0
V0 80 2.03 5 133 8 45 1.65 42.0 8.0 24.0
U0 80 2.03 4 133 8 45 1.75 44.0 8.0 24.0
310 80 2.03 3 133 8 45 1.89 48.0 8.0 24.0
410 80 2.03 2 133 8 45 2.04* 51.8* 8.0 24.0
2502.41 95 2 133 8 45 2.39* 60.7* 9.5 28.5
3002.41 95 1 133 8 45 2.56" 65.0* .9.5 28.5
350 2.41 95 110 259 8 45 2.68* 68.1* 9.5 28.5
400 2.41 95 110 259 8 45 2.82* 71.6* 9.5 28.5
450 2.41 95 210 259 8 45 2.94" 74.7* 9.5 28.5
500 2.41 95 210 259 8 45 3.03" 77.7* 9.5 28.5
*These cables require extra-heavy-duty jackets 75.1).
(see
$See Table 7-28.
WC 7-1988
Page 68 ICEA S-66-524
meets the requirements of 7.4.18.These cables shall be conductor, The assembly shall be covered with a jacket
in accordance with Table 7-20. These cables shall be that meetsthe requirements of 7.4.18.These cables shall
used forthe internal wiring of equipment only. be in accordance with Table7-22.
7.4.6 Type PG, Two- and Threepower 7.4.8 Type G,Three-conductor Round with
Conductors with Single Grounding Grounding Conductors, 2001-5000Volts
Conductor, 0-2000 Volts These cables shall consist of three power conductors
These cables shall consistof two or three power con- that are separately covered with insulation. Each power
ductors that are separately covered with insulation. conductor shall be separately coveredwith a colored
Each power conductor shall be separately covered with tape (see 7.4.15). The power conductors, together with
a coloredtape or braid,which maybe omitted if colored the grounding conductors (see7.4.12), and any neces-
insulation is used (see 7.4.15). The power conductors, sary fillers, shallbe cabled with a left-hand lay in accord-
together with a single grounding conductor 7.4.12) (see ance with Table 7-14 and covered with a jacket that
and any necessary fillers, be shall
cabled with a left-hand meets the requirements of 7.4.18.The cables shallbe in
lay in accordance with lhble 7-14 and covered with a accordance with Table 7-23.
jacket that meets the requirements of 7.4.18. These
cables shallbe in accordance with Table 7-21. 7.4.9 Type SH, SHC-GC, SHD, and SHD-GC
Shielded Cables, O-25,000Volts
7.4.7 Type PCG, Two- and Three- Power
Conductors with Control Conductors and 7.4.9.1 n P E SHSINGLE-CONDUCTORCABLES,
Single Grounding Conductor, 0-2000Volts 2001-25000 VOLTS
These cables shall consistof two or three power con- These cables shall consistof an insulated conductor
ductors andtwo No. 10 AWG control conductors all of covered with a tape, a shield that meets the require-
which are separately covered withinsulation.Each ments of 7.4.16 with or without a tape over the shield,
power and control conductor shall be separately and a jacket that meets the requirements of 7.4.18.The
covered with a tape or braid, except that on power cables shall be in accordance with Table
7-24.
conductors thistape or braidmay be omittedif colored
7.4.9.2 TVPE SHC-GC THREE-CONDUCTOR CABLES
insulation is used (see7.4.15). The power conductors, 2000 VOLTS OR LESS
together with two control conductors and a single
grounding conductor, shall be cabled together with a These cables shall consist of three power conductors
left-hand lay in accordance with Table 7-14. Each con- that are separately covered with insulation. Each power
trol conductor shall be inseparate
a interstice between conductor shall be separately covered with a colored
the power conductors:the black control conductor shall tape or braid, which may be omitted if colored insulation
be betweenthe black and white power conductors, and is used (see 7.4.15). The power conductors, together
the white control conductor adjacent to the white power with two groundingconductors (see7.4.12), one ground
Table 7-20
o to 2000 Volts
Type W and G, Five- and Six-conductor Portable Power.Cables
ounding Power
Conductor Crype G ) Oulside Diameter
S b Mininlunl Five-conductor
AwGi Insulation Thickness Size, Number of Type W and G Six-conductorTypeW Test Voltage, kV
mlls mm
AWG strands
inches m inches mm AC M!
8 60 1.52 8 49 1.07 27.2 1.18 30.0 7.0 21.0
6 60 1.52 7 49 1.21 30.7 1.31 33.3 7.0 21.0
4 60 1.52 5 133 1.40 35.6 1.52 38.6 7.0 21.0
3 60 133
1.52 4 1.48 37.6 1.61 40.9 7.0 21.0
2 60 133
1.52 3 1.61 40.9 1.75 44.4 7.0 21.0
1 80 2.03 2 133 1.88 47.8 2.05* 52.1* 8.0 24.0
T
'h
es
ecables require extra-heavy-duty jackets (see 7.5.1).
tSee Table 7-28.
Table 7-21
O to 2000 Volts, Type PG Two- and Three-Conductor PowerCables
Conductor-
Power
Power
Grounding
Conductor
Outside Diameter
Conductor Insulation Thickness
Strands, Minimum Two-conductor
Cables
Three-conductor
Cables Test Voltage, kV
Size, AWG
AWG Number
or kcmilt mils mm mm inches mm AC Dc
of Strands inches
a Size, AWG
or kcmilt m mmils
8 60
mm
1.52
AWG
8
Number
of Strands
49 0.94 23.9
inches
1.03
mm
26.2
AC
7.0
Dc
21.0
6 60 1.52 8 49 0.98 24.9 1.18 30.0 7.0 21.0
4 60 1.52 6 49 1.10 27.9 1.29 32.8 7.0 21.0
3 60 1.52 6 49 1.20 30.5 1.31 33.3 7.0 21.0
2 60 1.52 5 133 1.29 32.8 1.39 35.3 7.0 21.0
1 80 2.03 4 133 1.44 36.6 1.52 38.6 8.0 24.0
U0 80 2.03 3 133 1.52 38.6 1.68 42.7 8.0 24.0
210 80 2.03 2 133 1.65 41.9 1.79 45.5 8.0 24.0
80 2.03 1 133 1.77 45.0 1.93 49.0 8.0 24.0
310
410 80 259
2.03 110 1.92 48.8 2.13* 54.1*
24.0 8.0
P 250 95 2.41 210 259 2.16 54.9* 2.39* 60.7* 9.5 28.5
*These cables require extra-heavy-dutyjackets (see 75.1).
Table 7-23
2001 to5000 Volts Type G Three-conductor Portable Power Cables
Power Con- InsulationThickness
Thickness
Jacket Oulside Diameter
Test Volhe, kV ~
ductor Size,
AWG or
mils mm mils mm . inches mm AC Dc
kcmilt
check conductor (see7.4.11), and any necessary fillers ments of 7.4.18. The ground check conductor shallbe
shall be cabled with a left-hand lay
in accordance with laid between the black and white power conductors.
llble 7-14. The ground check conductor shall be laid These cables shall be in accordance llblewith 7-26.
between the black and white power conductors. The
assembly shallbe covered with a shield that meetsthe 7.4.10PowerConductors
requirements of 7.4.16 and a jacket that meets the re-
7.4.1 O. 1 Power conductors shall be madeof annealed
quirements of 7.4.18. The cables shall
be in accordance
coated or uncoated copper wires in accordance with
with Table7-25.
Section 2. A separator may be used.
7.4.9.3 TYPE SHD THREE-CONDUCTOR CABLES,
25,000 VOLTS OR LESS 7.4.10.2 The sizes, strandings, and nominal diameters
of the conductors shallinbe accordancewith Table7-28.
These cables shall consist of three power conductors
that are separately covered with insulation, a colored 7.4.10.3 Conductor stress control shall bein accord-
tape (see 7.4.15), and a shield that meets the require- ance with2.7.
ments of 7.4.16, and three grounding conductors (see
Table 7-28), one in each interstice. 7.4.1 1 Control and Ground Check Conductors
All power and grounding conductors and any neces- The control conductors for m e PCG shall be no
sary fillers shall
be cabled with a left-hand lay in accord- smaller thanNo. 10AWG. The ground check conductor
ance with llble 7-14 and covered with a jacket that for m e s G-GC, SHC-GC, and SHD-GCshall be given
meets the requirementsof 7.4.18. These cables shall be in Tables 7-19,7-25, and 7-26.
in accordancewith Table7-26. A minimum of 49 strands of annealed coated or un-
coated copper wire shall be used.A separator may be
7.4.9.4 TVPE SHD-GCTHREE-CONDUCTORCASUS, used. In all other characteristics,the conductors shall
25,000 VOLTS OR LESS meet the requirements of 7.4.10.
These cables shall consistof three power conductors
that are separately coveredwith insulation, a colored 7.4.12GroundingConductors
tape (see 7.4.15) and a shield that meets the require-
ments of 7.4.16, and two grounding conductors (see 7.4.12.1 The grounding conductors for two-, three-
Table 7-28) and onegroundcheckconductor(see and four-conductor round Vpe G, SHC-GC, SHD, and
7.4.11). SHD-GC shall be annealed copperof not less thanthe
All powerconductors,groundingconductors,the size and number of wires in Table 7-28 for the cor-
ground check conductor, and any necessary fillers shall responding power conductor sizes. In all other charac-
be cabled with a left-hand lay in accordance with Table teristics they shall meet
the requirements of 7.4.10.
7-14 and covered with a jacket that meets the require-
WC 7-1988
ICEA S-66-524 Page 71
Table 7-24
Type SH Single-conductor Portable Power Cables for100 Percent Insulation Level Only
Power Con- InsulationThickness Thickness
Jacket
Outside
Diameter+
Test Vollage, kV
duclor She,
AWG or
mils mm mils mm inches mm AC M:
kcmilt
2001 to 5000 Volts
110 2.79
2.79 110
.~ o."m
0.7 195 13.0
...
~ ~ S..
f
110 2.79 140 356 1.04 26.4 13.0 ...
110 2.79 140 3.56 1.07 27.1 13.0 ...
110 23.94
.79 155 1.18 29.9 13.0 ...
110 23.94
.79 155 1.24 315 13.0 ...
120 3.94
3.05 155 1.32 335 13.0 ...
120 3.05 170 4.32 1.37 34.8 13.0 ...
120 3.05 1.47
170 4.32 37.3 13.0 ...
120 34.83
.05 190 1.62 41.1 13.0 ...
5001 to 8000 Volts
150 3.81 125 3.18 0.97 24.6 18.0 45.0
150 3.81 140 356 1.03 26.1 18.0 45.0
150 3.81 140 3.56 1.O7 27.1 18.0 45.0
150 3.81 140 . 356 1.12 28.4 18.0 45.0
1.19
150 3 .94
3.81 155 ~~ 30.2 18.0 45.0
150 3.81 155 3.94 1.24 315 18.0 45.0
150 3.81 155 3.94 1.30 33.0 18.0 45.0
150 3.81 155 3.94 1.37 34.8 18.0 45.0
150 3.81 170
1.45 4.32 36.8 18.0 45.0
150 3.81 170 4.32 152 38.6 18.0 45.0
150 3.81 170 4.32 1.57 39.9 18.0 45.0
150 34.83
.81 190 1.76 44.7 18.0 45.0
8001 to 15,000 Volts
210 5.33 155
1.22 3.94 30.9 27.0 70.0
210 5.33 155 3.94 1.26 32.0 27.0 70.0
1.31
210 3.94
5.33 155 ~ ~~ 33.2 27.0 70.0
210 5.33 155 3.94 1.36 345 27.0 70.0
210 5.33 170 4.32 1.46 37.0 27.0 70.0
210 5.33 170 4.32 152 38.6 27.0 70.0
210 5.33
4.32 170 157 39.9 27.0 70.0
210 5.33 170
1.64 4.32 41.6 27.0 70.0
210 5.33 190 ' 4.83 1.73 43.9 27.0 70.0
210 5.33
4.83 190 1.88 47.7 27.0 70.0
15001 to 25,000 Volts
295 7.49 170 4.32 1.49 37.8 38.0 100.0
295 7.49 170 4.32 154 39.1 38.0 100.0
295i59 7.49
4.32 170 40.4 38.0 100.0
295 7.49 170 4.32 1.64 41.6 38.0 100.0
295 7.49 190 4.83 1.74 44.2 38.0 100.0
295
1.79 1.49
4.83 190 45.5 38.0 100.0
295 7.49 190
1.86 4.83 47.2 38.0 100.0
350 " -
29s 7.49
4.83 190 1.91 48.5 "._
wn 100.0
500 537.. ._
.349 2.10 5.21 38.0 100.0
*These cables require extra-heavydutyjackets (see 7.5.1).
$SeeTable 7-28.
Table 7-25
2000Volts o to
Type SHC-GC Threeconductor Portable Power Cable for100 Percent Insulation Level Only
Power Con- Power
Conductor Insulation Ground
Jacket Thickness Outside
Diameter* AC Test
ductor Size, Thickness Con-Check Voltage, kV
AWG or ductor Size,
mils mm mils mm inches mm
kcmilt AWG
6 70 155
1.78 10 3.94 1.27
7.0 32.2
4 70 155
1.78 10 3.94 1.39
7.0 35.3
3 70 170
1.78 10 4.32 7.0
1.49 37.8
2 70 170
1.78 10 4.32 1.57
7.0 39.9
1 80 1.78 8 190 4.83 1.75
8.0 44.4
110 80 2.03 8 190 4.83 1.85
8.0 47.0
WO 80 2.03 8 205 5.21 1.99 50.5 8.0
310 80 2.03 8 205 5.21 2.11
8.0 53.6
410 80 2.03 8 220 5.59 2.29
8.0 58.2
2.41
250 95 8 220 5.59 2.46
9.5 62.5
300 95 2.41 8 235 5.97 2.63
9.5 66.8
350 95 2.41 8 235 5.97 2.75
9.5 69.8
500
2.41 95 8 265 6.73 3.14
9.5 79.8
These cables require extra-heavy-duty jackets
(see 75.1).
t&e Table 7-28.
Table 7-26
for 100 Percent Insulation LevelOnly
Type SHD and SHD-GC Three-conductor Portable Power Cables
Power Con- Power
Conductor
Ground
Jacket Thickness Oulside Diameter*
Voltage,
Test kV
ductor Size, Insulation Thickness Check
Con-
AWG or ductor Size,
kcmilt mils mm mils mm inches mm AC Dc
AWG (Type
SEID-GC)
o to 2000 Volts
70 1.78 3.94
10 155 1.29 32.8 7.0 ...
70 1.78 3.94
10 155 1.40 35.6 7.0 ...
70 1.78 10 170 4.32 1.51 38.3 7.0 ...
70 1.78 8 170 4.32 1.59 40.4 7.0 ...
80 2.03 4.83
8 190 1.76 44.7 8.0 ...
80 2.03 8 1% 4.83 1.86 47.2 8.0
...
1..
7.4.15.1POWERCONDUCTORS
'Avo-conductor cables
All types black,
Three-conductor cables
~~~
m eG
~
m eG-GC,
sPG,
PCG, SHD*, SHD-GC*,
SHC-GC
and
black,
white,
red
greenVPeW white, black,
Four-conductor cables
orange VPeG red, white, black,
m e w white, black, red, green
Five-conductor cables
l)lpe blue red, orange,
orange VPeW green, red, white, black,
Six-conductor cables
m e w white,
blue black,
orange, red, green,
*When conducting nonmetallic
tapes are used, identificationmay be by means of stripes or printing in a contrasting
color.
ductors, PCG
Control 'Zfipe
conductor,
Ground
check
G-GC, m e SHD-GC,
and m e SHC-GC
yellow
7.4.16
Shielding P = Picks per inch
7.4.1 6.1 The shielding for?$pes SH, SHD, SHC-GC 7.4.16.3METALWIRESHIELDS
and SHD-GC cables shall consist of non-magnetic Where the shielding is applied the form
in of a serving
wires. or wrap,the coverage shallbe not less than60 percent
Where copper or copper alloy wires are used, they as determinedby the following formula:
shall be coated in accordancewith 2.1.1.
Nd
Percentcoverage = - X 100
7.4.16.2METALBRAIDSHIELDS W
When shielding is applied thein
form of a metal braid, Where -
the coverage shall
be not less than84 percent as deter- N = Number of parallel wires
mined bythe following formula: d = Diameter of individual wiresin inches
Percent coverage = 100 (2F-9) W=nDcosa
D = Diameter under shield in inches
Where- a = Angle between serving wires and axis of cable
NPd D
F= - Tana=n-
sin a C
- of braid withaxis of cable
a = Angle C = Pitch of serving in inches
2zDP
Tana= -
C 7.4.17Conductor Assembly
d = Diameter of individual braid wires in inches For round cables,the insulated conductors, together
C = Number of carriers with grounding conductors and ground check conduc-
D = Diameter under shieldin inches tor when required and any necessary fillers, shall be
N = Number of wiresper carrier
WC 7-1988
ICEA S-66-524 Page 75
Table 7-27
Jacket Thicknesses for Types and Sizes of Portable Cables Not Covered by Tables 7-15 through 7-26
Table 7-28
Conductors
Power Conductors T Grounding Conductors(Round Cables)
Threesonductor
Diameter of Conductor Two-conductor Type SHD-GC and Threesonductor Four-conductor
Each Wire Diameter Type G Cables Type SHC-GC Type G Cables "pe G Cables
Mini- Cables
mum Sizeof Mini-
Size of Mini- Size of Mini- Size of Mini-
Conduc- Number
Ground- mum Ground- mum Ground- mum Ground- mum
tor Size, of Wires h g Con- Number ing Con- Number ing Con- Number ing Con- Number
AWG or per Con-
kcmil ductor ductors, of Wires ductors, of Wires ductors, of Wires ductors, of Wires
mlls mm inches mm AWG per Con- AWG per Con- AWC per Con- AWG per Con-
ductor ductor ductor ductor
cabled with a left-hand lay. For w e s SHD and SHD- 7.4.18.1.2 HEAVY-DUTY NEOPRENE JACKET
GC cables,the grounding conductors shall be in contact Physical requirements
with the metallic shields. Suitable fillersbeshall
used to
produce an essentially round cross-sectionin the com- %mile strength, minimum
pleted cable. When required, a binder tape and/or psi 180
threads shall be usedover the conductor assembly. 2
kgflmm 1.27
7.4.18 Jackets
Tensile stress at200 percent elongation,minimum
7.4.18.1 GENERAL psi 500
The jacket shall be applied in one or two layers. If kgf/mm2
applied in two layers,the outer jacket shall constitute at
least 50 percent of the total thickness of jacket. The Elongation
at
rupture,
minimum,
percent 300
single-layer jacket and the outer layer of a two-layer Set, maximum, percent 20
jacket shall meet the applicable requirements of
7.4.18.1.1,7.4.18.1.2,7.4.18.1.3,7.4.18.1.4,7.4.18.1.5, Aging requirements
7.4.18.1.6,7.4.18.1.7, or 7.4.18.1.8. After air oven test at
100"Cfl"C for 168
Single- or two-layer jackets be shall
reinforced by two hours - tensile strength and elongation at
servings or a braid of a suitable natural or synthetic rupture, minimum percentage of unaged value 50
material. The diameter of the reinforcing material shall
be not greater than35 mils (0.89 mm). If two servings After oil immersion test at 121"Cf1"C for 18
are used, they shall be applied in opposite directions of hours -tensile strength and elongation, mini-
lay. The reinforcing shall be under the single-layer jack- mum, percentage of unaged
value 60
et and under or between the layers of the two-layer
construction. 7.4.18.1.3EXTRA-HEAVY-DUTYNITRILE-
BUTADIENE/POLWINYL-CHLORIDE
7.4.18.1.1EXTRA-HEAVY-DUTY-NEOPRENEJACKET JACKET*
Physical requirements Physical requirements
Tensile strength, minimum Tensile strength, minimum
psi psi 2400 2400
kgf/mm2 kgf/mm2 1.69 1.69
~
Tensile stress at200 percent elongation, minimum Tensile stress at200 percent elongation, minimum
psi psi 700 700
kgf/mm2 kgf/mm2 0.49
Elongation
at rupture, minimum,
percent 300 Elongation
at
rupture,
minimum,
percent
300
Set, maximum, percent 20 Set, maximum, percent 30
Tear, minimum Tear, minimum
per pounds inch 40per pounds 40
kgflmm kgflmm 0.71 0.71
Aging requirements Aging requirements
After air oven test at
100"C+l°Cfor 168 After air oven test at
100"Cfl"C for 168
hours - tensile strength and elongation at hours - tensile strength and elongation at
rupture, minimum percentage of unaged value 50 rupture, minimum percentage of unaged value 50
After oil immersion test at l21"C+ 1°C for 18 After oil immersion test at 121"C+l"C18for
hours- tensile strength and elongation, mini- hours -tensile strength and elongation,
mini-
mum, percentage of unaged
value 60 mum, percentage of unaged
value
60
*Suitable fora minimum temperature of -1O'C (14°F).
~~ ~~ ~~ ~~~ ~ Elongation
at
rupture, minimum, percent 300
Elongation at
rupture, minimum, percent 300
- ~~ 30
Set, maximum, percent 30
Tear, minimum
Aging requirements
per pounds inch 40
After air oven test at 10OoC~1"C for 168
KN/m 7.01
hours - tensile strength and elongation at
rupture, minimum percentage of unaged value 50 Aging requirements
-~ ~
After oil immersion test at 121°C+1"C for 18 After air oven test at 10OoC~1"C
for 168 hours
hours - tensile strength and elongation, mini- Tensile strength, minimum, percentage of un-
mum, percentage of unaged value 60
aged value 70
'Suitable for a minimum temperatureof-10"C (14°F). Elongation at rupture, minimum, percentage
of unaged value 60
7.4.18.1.5 HEAW-DunCHLOROSULFONATED
POLYETHYLENE After oil immersion test at 121"CItl"Cfor 18
Physical requirements hours- tensile strength and elongation, mini-
mum, percentage of unaged value 60
Tensile strength, minimum
psi 1800 7.4.18.1.7CHLORINATEDPOLYETHYLENE,
HEAVY
~~ ~ ~~ ~~ ~
Dun, CROSSL~NKED
kgflmm2- 1.27
Physical requirements
Tensile stress at200 percent elongation, minimum ~~ ~ - ~~
psi 1800
kgflmm2 035
MPa 12.41
Elongation at
rupture, minimum, percent 300
Tensile stress at 200 percent elongation, minimum
Set, maximum, percent 30
psi
Aging requirements
MPa 3.45
After air oven test at 10OoC~1"Cfor 168
hours - tensile strength, minimum, percent- Elongation
at
rupture, minimum, percent 300
age of unaged value 85 Set, maximum, percent 30
Elongation at rupture, minimum, percentage Aging requirements
of unaged value 65
After air oven test at 100"C-Cl"Cfor 168 hours
After oil immersion test at 121"Ck1°C for 18
hours- tensile strength and elongation, mini- Tensile strength, minimum, percentage of un-
mum, percentage of unaged value 60 aged value 85
7.4.18.1.8-7.4.2.1
Text deleted.
7.5 NONSHIELDED
SINGLE-CONDUCTOR
POWER CABLE
7.5.1 Scope
This section covers
nonshielded singleconductor
nonjacketed and jacketed power cable with mss-linked-
thermosetting-polyethylene insulation intended foruse at
2001 to SOO0 volts at 100 percent insulation level and
2001 to 3000 volts at 133 percent insulation level under
conditions where shields cannot be adequately grounded
or where spaceis inadequate for proper terminationof the
shielding, as follows (see4.2 and AppendixG):
1. Single Conductors
Unspliced
a. cables in random lay in
groundedmetal conduit indoors above
grade in dry location.
b. Mounted on insulators in free air.
2. Triplexed Single Conductors (Factory
Assembled)-In conduit or cable trays
indoors above grade in dry locations.
3. Single and Triplexed Conductors-Aerially,
field spun to a grounded messenger.
WC 7-1988
Page 80 KEA S-66-524
Table 7-31
Insulation Thicknessfor Series Lighting Cable
Circuit Voltage, Conductor Size, Insulation Thicknesst Test Voltage, kV
Volk* AWG
mils mm AC Dc DC Spark
O-lo00 12-4 60 1.52 21.05.0 15.0
1001-2000 1.918-4 26.5 75 22.5 7.5
2001-5000 2.798-4 110 35.0 13.0 ...
at each step represents the maximum operating voltage recommendedfor the thickness of insulation.
*The highest circuit voltage
?If protectors are employed, the thickness shallbe determined by the full-load voltage. If the circuit is to be operated without protectors, the
thickness shallbe determined by the open-circuit voltage.
The following tabulation of series lighting transformer ratings is representative of those in common use.*
Secondary
6.6 Ampere 20 Ampere Secondary
Ratings, kW Full-load Voltage, Volk, Open-circuit Voltage, Volk, Full-load Voltage, Volk,
open-circuit
Volhge, Volk,
With Protectors Without Protectors With Protectors Without Protectors
10 2090 500 690
15 2272 1020 3090 750
20 3030 4115 lo00 1360
25 1250 5110 1685
30 1500 4545 6130
40 2000 6060 8180
*This paragraph is approved by NEMA as Authorized EngineeringInformation.
62
1-U0
310 AWG-250 kcmil
300400
450-600
750-1000
lay shall be in accordance with Section 5 and shall be based 7.8.9 Tests
on the calculated diameter of the individual powerconduc- ThecableshallbetestedinaccordancewithSection6and
tor. A suitable binder shall be applied over the assembly. m e t req-en~ setion 7.8.
7.8.8 Amor
An interlocked metal tape armor meeting the require-
ments of4.5.7 shall be applied over the assembly.
Section 8
APPENDICES
Appendix A
ABBREVIATIONS AND SYMBOLS
Appendix B
OF NONMAGNETIC METALS
REPRESENTATIVE TENSILE STRENGTH AND ELONGATION
Slrenglh
Tensile Elongation 2 inch (50.8 mm)
Lenglh, Percent
Metal ') psi MPa
5 Aluminum 90-310 13,00045,000
Ambrac 50,000-70,000 345-482 20-40
Low40-50
Brass 276-345 40,000-50,000
Bronze Commercial 241-289 35,00042,000 40
Copper 241-345 35,000-50,000
517Monel 75,000 45
Stainless
50 565-620 82,000-90,OOO
Zinc 138 60
Appendix C
OF CONDUCTORS IN INSULATED WIRE AND CABLE
DEFINITIONS FOR MAXIMUM TEMPERATURE
WC 7-1988
Page 88 ICEA S-66-524
Appendix D
EMERGENCY OVERLOADS
Operation at the emergency overload temperature of 130°C (%OF) shall not exceed 100 hours in any twelve
consecutive monthsnor more than500 hours during the lifetime of the cable.
Lower temperatures for emergency overload conditions may be required becauseof the type of material used in
the cable, joints,
and terminations orbecause of cableenvironmental conditions.
Appendix E
REFERENCED PUBLICATIONS AND STANDARDS
El NEMA PUBLICATIONS
I NEMA26-1984*
WC Wire and Cable Packaging
E2 ICEA PUBLICATIONS
T-24-380, rev. i2JSO Guide for Partiaì-Discharge Test Proceduret
T-27-581PJEM.A
WC 53-1983 Standard Test
Methods for Extruded Dielectric Power,
Control, Instrumentationand Portable Cables
P-46-426EEE
Ampacities**
Cable
Power
#S-135
(SH007096)
P-53-426, 2nd Ed./NEm WC 50-1976 Ampacities, Including Effect of Shield Losses for Single-
(R1982,1988) Conductor
Solid-Dielectric Power Cable, 15 kV through
69 kV*
E3 ASTM STANDARDS$
E3.1 .i ASTM Standards to which referenceis made in this standard, but not in all of the other three: S-19-81, WC
3; S-61-402, WC 5 ; and S-68-516,WC 8.
B 232-86 Concentric-Lay-Stranded AluminumConductors, Coated Steel-
Reinforced (ACSR), Specification for
B 233-85 Aluminum-Alloy 1350 Drawing Stock for Electrical Purposes,
Specifications for
B 246-88 Tinned Hard-Drawn and Medium-Hard Drawn Copper Wirefor
Elecfrical Purposes, Specifications for
B 397-85 Concentric-Lay-Stranded Aluminum-Alloy5005-HI9 Conductors,
Specification for
B 557-84 Tension Testing Wrought and Cast Aluminum-and Magnesium-Alloy
Products
D 1248-84 (R 1989) Polyethylene PlasticsMolding and Extrusion Materials, Specification
for
D 2132-85 Dust-and-Fog Tracking and Erosion Resistance of Electrical Insulating
Materials, Testfor
D 2765-84 Degree of Crosslinking in Crosslinked Ethylene Plastics as Determined
by Solvent Extraction Tests for
E3.1.2 ASTM Standards to which reference is made in each of the following four standards: S-19-81, WC3; S-61-
402, WC 5, S-66-524, WC 7; and S-68-516, WC 8.
A 90-81 (R 1987) Weight of Coating Zinc
on Coating (Galvanized)Iron or Steel Articles,
Test Method for
B 1-85 Hard-Drawn Copper Wire, Specification for
B 2-88 Medium-Hard Drawn Copper Wire, Specification for
B 3-74 (R 1980, 1985) Soft or Annealed Copper Wire, Specificationfor
B 5-89 Tough-Pitch Electrolytic Copper Refinery Shapes, Specification for
B 8-86 Concentric-Lay Stranded Copper Conductors, Hard, Medium-Hard, or
Soft,Specification for
WC 7-1988
KEA S-66-524 Page 91
Appendix F
AMPACITIES FOR TWO-CONDUCTOR CONCENTRIC-NEUTRAL SINGLE-PHASE PRIMARY
UNDERGROUND RESIDENTIAL DISTRIBUTION CABLES (SEE7.1.)
Conductor Copper Aluminum
Size, AWG or
kcmil
Direct In Buried In Airt In Duct In -Direct InBuried In Ai* InDuct In
Buried* Duct* Airt Buried* Duct* W
Cables Rated5 kV 90°C
4 132169 97
111 114 88 90 76
3 193 128 132 111 ...... ... ...
174
1 126 2 152
219 144 100
115 120
1 249
174 116
165 139 132
144 199
V0 284 188 200 163 226 150 160 131
WO 324 217 233 189 256 172 186 149
310 368 247 268 215 291 195 211 170
410 425 288 316 250 335 226 247 197
250 ... ... ...
278 ...
252 370 . 219
300 ... 250 ... 319 ... 287 ... 418
Cables Rated15 kV 90°C
4 162 . 116 128
120 100 79
91 95
132
3 186 138 114 ... ... a.. ...
2 210158 150 131 168 119 125 103
119
1 145
240 137
171 193
181 148
110 273 194 208 169 218 155 166 135
210 313 224 240 1% 248 177 190 154
310 358 255 278 222 284 201 218 176
410 410 293 324 257 324 230 253 201
250 ... ...... ... 360 257 285 225
300 ... a.. ... ...
291 403 254 324
* Ambient temperature of 20°C; 100 percent load factor; thermal resistivityRHO-90
The multiplyingcorrection factors for load factors of 75 and 50 percent shall be:
Correction Factors
75 Percent Load Factor 50 Percent Load Factor
Appendix F-1
AMPACITIES FOR THREE-PHASE UNDERGROUND DISTRIBUTION CABLES
For ampacitiessee theICEA/NEMA Standards Publication No. WC 50,AmpacitiesIncluding Effectof Shield Losses
Appendix G
SHIELDING
G2.1.1 A conductor stress control layer is employed to 63.1.4 Where nonshielded cables are used in under-
preclude excessive voltagestress on voids between con- ground ducts containing several circuits that must be P
ductor and insulation. To be effective, it mustadhere to worked on independently, the external field, if suffi-
or remain in intimate contact with the insulation under ciently intense, can cause shocks to those who handle or
all conditions. contact energized cable. In cases of this kind, itmay be
advisableto use shielded cable. Shielding used to reduce
G2.1.2 An insulation shieldhas a numberof functions: hazards of shock should have a resistance low enough
1. To confine the dielectric field within the cable. to operateprotectiveequipment in case of fault. In some
2. To obtain symmetrical radial distribution of volt- cases, the efficiency of protective equipment may re-
age stress within the dielectric, thereby minimiz- quire proper size ground wires as a supplement to
ing the possibility of surface discharges by shielding. The same considerations apply to exposed
precluding excessive tangential and longitudinal installations where cables may be handled by personnel
stresses. who maynot be acquainted with the hazards involved.
3. To protect cable connected to overhead lines or
otherwise subject to induced potentials. 64.1 GROUNDING OF THE INSULATION SHIELD
4. To limit radio interference.
5. To reduce thehazard of shock. This advantage is G 4 1.I The insulation shield must be grounded at least
obtained only if the shield is grounded. If not at one end and preferably to two or more locations. It
grounded, the hazard of shock may be increased. is recommended that the shield be grounded at cable
terminationsand at splices and taps. Stress cones should
G3.1USE OF INSULATIONSHIELDING be made at all shield terminations.
G3.1.I The use of shielding involvesconsideration of G4.1.2 The shield should operate at or near ground
installation and operating conditions. Definite rules potential at all times. Frequent grounding of shields
cannot be established on a practical basis for all cases, reduces the possibility of open sections on nonmetallic
but the following features should be considered as a covered cable, Multiple grounding of shields is
working basisfor the use of shielding. desirable in order to improve the reliability and safety
of the circuit. All grounding connections should be
G3.1.2 Where there is no metallic covering or shield made to the shield in such a way as to provide a per-
over the insulation, the electric field will be partly in the manentlow resistance bond. Shielding which does not =
insulation and partly inwhatever lies betweenthe insula- have adequate ground connection due to discontinuity
tion and ground. The external field, if sufficiently in- of the shield or to improper termination may be more
tense in air, will generate surface discharge and convert dangerous than nonshielded nonmetalliccable and haz-
atmospheric oxygen into ozone, whichmay be destruc- ardous to life.
tive to insulations and to protective jackets. If the sur-
face of the cable is separated from ground by a thin layer G5.1SHIELDMATERIALS
of air and the air gap is subjected to a voltagestress that
exceeds the dielectric strength of air, a discharge will G5.1.1 %o distinct typesof materials are employed in
occur, causing ozone formation. constructingcableshields.
G3.1.3 The ground may be either a metallicconduit, a G5.1.I.I Nonmetallic shields may consist of a con-
damp nonmetallicconduit, or a metallic binding tape or ducting tape or a layer of conducting compound. The
rings on an aerial cable, a loose metallic sheath, etc. tape may be conducting compound, fibrous tape faced
WC 7-1988
ICEA s-66-524 pages
JANUARY 1991
WC 8-1988
Page 94 ICEA s-66-524
Appendix H U
RECOMMENDED BENDING RADIIFOR CABLES
H1.l SCOPE H 3 . w TAPESHEWED CABLES
?his appendix contains the minimum values for themdii The minimum bending radius for tape shielded cables
to which insdated cables may bebentforpermanent given below appliesto helically applied flator cormgated
training during installation.These limits do not apply to tape ar longitudinally applied CORugated rape shielded
conduit bends, sheaves ar other curved surfacm mund cables.
which the cable maybe pulled under tension while being The minium bending radius for a single conductor
installed.*In all cases the minimum radii specified refers cable is twelve times the ovedl diameter.
totheinner~ofthecableandnottotheaxisofthe For multiple-conductorar multiplexed singleconductor
cable. cables having individually taped shiekled conductors,the
minimum bending radius is twelve tim the diameter of
H2.1POWER CABLES WITHOUTMETALLIC theindivi~conductorsorseventimesthe~eralldiame
SHEATH, SHIELDING OR ARMOR ter, whicheveris greater.
The minimum bending radii for both single-and multi- For multiple-canductor cables having an overall tape
ple-conductor cable without metallicsheath and without shield overthe assembly, the minimum h d i n g radius is
metallic shieldingor armor are shown in Table H-1. twelve times the overall diameter of the cable.
H3.1 POWER CABLES WITH METALUC H3.1.82 W E SHEWED CABm
SHIELDING SHEATHSOR ARMOR The minimum bending radius for a single conductor
H3.1.1 InterlockedArmored and Metallic cable is eight times the overalldiameter.
Sheathed Cables For multiplexonductor ar multiplexed single conductor
cables having wire shielded individual conductors, the
The minimum bending radius for interlocked ma
rd minimum bending radius is eight timesthe diameterof the
cables smooth or m g a t e d aluminum sheath or lead individual conductors ar five times the overall diameter,
sheath shall be in accurdance with M l e H-2. whichever is greater.
H3.1.2 Flat Tape Armored or Wire Armored For multipleconductorcables having awire shield over
Cables the assembly,the minimum bending radius is eight times
the overalldiameter of the cable.
The minimum bending radius for all flat tape armored
and all wire mored cables is twelve times the overall H4.1DRUMDIAMETERS OF REELS
diameterof cable. See NEMA Pub. No. WC26-1984,* Wie und Cubk
H3.1.3 Shielded cabe
l s,Without Armor Packaging, which is quoted in 'Mie H-3.
Table H-1
MINIMUM BENDING RADII FOR POWER CABLE
SINGLE & MULTIPLE CONDUCTOR CABLES
WITHOUT METALUCSHEATH, METALLIC SHIELDINGOR ARMOR
Table H-2 D
MINIMUM RADIIFOR POWER CABLE
SJNGLE & MULTIPLE CONDUCTOR CABLESWITH INTERLOCKED ARMOR,SMOOTH OR
CORRUGATED ALUMINUM SHEATH OR LEAD SHEATH
7 7 7
Multiple Conductor
WithIndividUally
Conductor
Shielded lm* lm* lm*
Multiple Conductor
12 with Overall Shield 12 12
Lead Sheath
12 12
+12x individual shielded ecndu*or diameter, or 7 x ovarll a b l e diameter, whichever is the grerter.
D Thle d d d 1-30-1991,
Appendix J
AMPACITIES AND VOLTAGE RATINGSOF PORTABLE CABLES
wY"c CorrectionFactors
'Qpe G -four and five conductor
10 1.26 'Qpe G-GC- three conductor
20 1.18 m e PG -two and three conductor
'Qpe PCG -two and three conductor
30 1.10 'Qpe SHC-GC- three conductor
40 1.00
5000 Volts
50 0.90
- m e G* -three conductor
When the cables are used with one or more layers
25000 Volts
wound on a reel, the ampacities shall be correctedas
'Qpe SH -single conductor
follows:
'Qpes SHD and SHD-GC
Number of Layers Multiplying CorrectionFactors
*Shielded cables provide
a higher level of safety
at ratings over 2000
1 0.85 volts.
2 0.65
3 0.45
4 0.35
WC 7-1988
Page 98 ICEA S-66-524
.. .. .. .. ..
.. .. .. .. ..
fijZ$$E Is:
m
3
i
c
Q I: . : . :. .:
3
WC 7-1988
ICEA S-66-524 Page 103
Appendix L
ADDITIONAL CONDUCTOR INFORMATION
Table L-1
Solid Aluminum and Copper Conductors
ApproximateWeight
Conductor Size,
Aluminum Copper
AWG or kcmil
per
Pounds loo0 Feet %m per
Pounds loo0 Feet dm
... ...
~ ~
22 2.88 1.94
20 ... ... 3.10 4.61
19 ... ... 3.90 5.81
18 ... ... 4.92 7.32
17 ... ... 6.21 9.24
16 ... ... 7.81 11.6
15 ... 14.7 ... 9.87
14 ... 18.5 ... 12.4
13 ... 23.4 ... 15.7
8.94 12 6.01
11 7.57 37.1 11.3 24.9
14.22 10 9.56
.9 12.04 58.9517.92 39.62
8 15.20 74.38 22.62 49.98
7 19.16 93.80 28.52 63.03
6 24.15 118.2 35.94 79.44
45.32 5 30.45 149.0 100.2
57.17 4 38.41 126.3 188.0
72.08 3 48.43 237.1 159.3
90.89 2 61.07 298.9 200.9
114.6 1 77.03 377.0 253.3
U0 97.15 475.5144.6 , 319.5
U0 122.5 182.3 402.8 599.5
310 154.4 755.8229.8 507.8
410 194.7 953.2289.8 640.5
250 230.1 342.4 ... ...
300 276.1 410.9 ... ...
350 322.1 479.4 ... ...
400 368.2 547.9 ... a..
Table L-2
Concentric Stranded ClassB Aluminum and Copper Conductors
Conductor Number of ApproximateDiameter of ApproximateOutside Approximate Weight
Size, AWG Strands Each Strand Diameter
or kcmil Copper AIuminum
mils mm inches mm Poundsper g/m Poundsper g/m
1O00 Feel Loo0 Feet
22
20
7
7
9.6
12.1
0.244
0.307
0.029
0.036
0.737
0.914
...
...
...
...
1.975
3.154
2.941
4.705
19 7 13.6 0.345 0.041 1.04 ... ... 3.974 5.922
18
17
7
7
15.2
17.2
0.386
0.437
0.046
0.052
1.17
1.32
...
... ...
...
5.015
6.324
7.462
9.429
16
15
7
7
19.2
21.6
0.488
0549
0.058
...
1.47
... ...
... ...6.. 7.974
9.959
11.86
14.98
14
13
7
7
24.2
27.2
0.615
0.691
...
... ...
... ...
...
...
... 12.68
16.01
18.88
23.82
12 7 30.5 0.775 e.. ... 6.13 9.12 20.16 30.00
11 7 34.3 0.871 ... 7.72 11.5 25.49 37.80
10
9
7
7
38.5
43.2
0.978
1.10
... ...
6..
...
...
...
15.5
195
23.1
29.1
51.0
64.2
75.9
95.7
6 7 61.2 1.56 ... ... 24.6 36.7 80.9 121
5
4
7
7
68.8
77.2
1.75
1.96
...
...
...
...
31.1
39.2
46.2
58.3
102
129
152
192
3
2
7
7
86.7
97.4
2.20
2.47
...
...
...
... 49.4
62.3
735
92.7
162 242
205 305
1 19 66.4 1.69 ... ... 78.6 117 259 385
110
2P
19
19
74.5
83.7
1.89
2.13
...
...
...
...
99.1
125
147
186
326
411
485
611
310 19 94.0 2.39 ..* ... 157 234 518 771
410 19 105.5 2.68 ... ... 199 296 653 972
250
300
37
37
82.2
90.0
2.09
2.29
...
...
...
... 235
282
349
419
772
925
1150
1380
350
400
37
37
97.3
104.0
2.47
2.64
...
... ...
...
329
376
489
559
1080
1236
1610
1840
450 37 110.3 2.80 ... ... 422 629 1390 2070
500 37 116.2 2.95 ... 469 699 1542 2300
...
a..
...
1173
1220
1313
1750
1820
1960
3859
4012
4320
5740
5970
6430
.
1500 91 128.4 3.26 ... ... 1408 2100 4632 6890
1600
1700
127
127
112.2
115.7
2.85
2.94
...
...
...
...
1501
1596
2240
2370
4936
5249
7350
1750
1800
127
127
117.4
119.1
2.98
3.02
...
...
...
...
1643
-~"
1691
2440
.... 5403
.... 2510 5562
1900
20009190
127
127
122.3
125.5
6176
3.11
3.19
...
...
2790
...
2650
... 1783
1877
5865
WC 7-1988
ICEA S-66-524 Page 105
0 Table L-3
Concentric Stranded ClassC and D Aluminum and Copper Conductors
Conductor Size, Class c D Class
AwG Or Number of Approximate
"
Diameter of Each
Strand
Number of Approximate
"
Diameter of Each Strand
Strands Strands
mils mils mm
22 ... ... ... ... ... ...
20
19
...
...
...
...
...
...
...
...
v.. ...
...
... ... ... ... ...
S..
18 ...
17 ... ... ... ... ... ...
16
15
...
...
...
...
... ...
...
S..
a..
...
14 19 14.7 0.%3 37 10.5 0.%7
13 19 16.5 0.419 37 11.8 0.300
12 19 18.5 0.470 37 13.3 0.338
Y
11 19 20.8 O528 37 14.9 0.378
10 19 23.4 O594 37 16.7 0.424
9 19 26.2 0.665 37 18.8 0.478
8 19 295 0.749 37 21.1 0.536
7 19 33.1 0.841 37 23.7 0.602
6 19 37.2 0.945 37 26.6 0.676
J 19 41.7 1.06 37 29.9 0.759
4 19 46.9 1.19 37 33.6 0.853
3 19 52.6 1.34 37 37.7 0.958
2 19 59.1 1.50 37 42.4 1.08
1 37 47.6 1.21 61
~~ 37.0 0.940
37
" 53.4 1.36 61 41.6 1.06
37 60.0 1.52 61 46.7 1.19
37 67.3 1.71 61 52.4 1.33
37 75.6 1.92 61 58.9 150
250 61 64.0 1.63 91 52.4 1.33
300 61 70.1 1.78 91 57.4 1.46
350 61 75.7 1.92 91 62.0 157
400 61 81.0 2.06 91 66.3 1.68
450 61 85.9 2.18 91 70.3 1.79
500
- .. 61
~~ 90.5 2.30 91 74.1 1.88
550 91 7.1
. ... 1.Gï 127 65.8 1.67
600 91 81.2 2.06 127 68.7 1.74
650 91 84.5 2.15 127 71.5 1.82
700 91 87.7 2.23 127 74.2 1.88
750 91 90.8 2.31 127 76.8 1.95
800 91 93.8 2.38 127 79.4 2.02
900 91 99.4 2.53 127 84.2 2.14
loo0 91 104.8 2.66 127 88.7 2.25
1100 127 93.1 2.36 169 80.7 2.05
127 1200 2.14 84.3
99.2 1250 127 2.18 169 86.0
127
2.23 1300 87.7 169 101.2 2.57
127 1400 105.0 2.67 2.31 169 91.0
1500 2.76 127 2.39 108.7 94.2 169
169 1600 2.18 85.9
100.3 1700 169 217 2.55 885 2.25
217 1750 2.59 169 101.8 89.8 2.28
217 1800 2.62 169 103.2 2.31
1900 169 217 106.0 2.69 93.6 2.38
6 108.8 2ooo 169 96.0 _e
2.44
NOTE?,-The weights of Class C and ClassD conductors are the same as for the equivalent ClassB conductor (see Table N-2).
Table L-4
Ro~e-LavAluminum andComer Conductors, Class G
Conduc- Number Suggested
Approximate
Diameter
Approximate
"
Outside
Approximate
Weight
~~
Table L-5
Rope-Lay Aluminum andCopper Conductors, Class H
Conduc-
Ap- Suggesfed
Approximate
Diameter of Approximate
Approximale Weigh(
Table L-6
Aluminum and Copper Conductors, ClassI Each Individual Strand24 AWG, 0.0201 Inch (0.511 mm)
Approximale
Approximate
Suggested
Conductor
Approximate
Weight
Outside " " I
Table L-7
Copper Conductors, ClassK Each Individual Strand30 AWG, 0.0100 Inch (0.254 mm)
Conductor Size, Suggested Approximate
Approximate
Outside Diameter Approximate
Weight
AWG or kcmil Construclion Number of
Strands
Inches mm Pounds perl000 dm
Feet
20 l x 10 10 0.038 0.97 3.2 4.59
18 l x 16 16 0.048 1.22 5.0 7.35
16 1x26 26 0.060 1.52 8.0 11.9
14 1x41 41 0.078 1.98 12.8 18.8
12 1x65 65 0.101 2.57 20.3 29.9
i 10 l x 104 104 0.126 3.20 32.5 47.8
9 7 x 19 133 0.150 3.81 42 62.3
8 7x24 168 0.157 3.99 53 78.7
v
7 7x30 210 0.179 4.55 66 98.4
6 7x38 266 0.210 5.33 84 125
5 7x48 336 0.235 5.97 106 157
4 7x60 420 0.272 6.91 132 197
3 19x28 532 0.304 7.72 169 252
2 19x35 665 0.338 8.59 211 315
1 19x44 836 0.397 10.1 266 395
110 19x 56 1064 0.451 11.5 338 503
U0 7x7~27 1323 0.470 11.9 425 632
310 7X7X34 1666 0.533 13.5 535 795
410 7X7X43 2107 0.627 15.9 676 1005
250 7x7~51 2499 0.682 17.3 802 1195
300 7X7X61 2989 0.768 19.5 960 1425
350 19X7X26 3458 0.809 20.5 1120 1665
400 19X7X30 3990 0.878 22.3 1290 1925
450 19x7~34 4522 0.933 23.7 1465 2180
500 19X7X38 5054 0.988 25.1 1635 2435
550 19X7X41 5453 1.056 26.8 1765 2630
600 19X7X45 5985 1.125 28.6 1940 2885
650 19x7~49 6517 1.166 29.6 2110 3140
700 19x7~52 6916 1.207 30.7 2240 3335
750 19x7~57 7581 1.276 32.4 2455 3655
9
800 19x7~60 7980 1.305 33.1 2585 3845
900 37X7X35 9065 1.323 33.6 2935 4370
lo00 37X7X39 10101 1.419 36.0 3270 4870
-
Authorized Engineering Information7-14-1982.
Table L-8
Copper Conductors, ClassM Each Individual Strand34 AWG, 0.0063 Inch (0.160 mm)
Conductor She, Suggested Approximate
Approximate Outside Diameter
Approximate Weight
AWG or kcmll Construction
Number of
inches mm Pounds per loo0 dm
Strands
Feet
20 1x26 26 0.038 0.97 3.2 4.74
18 1x41 41 0.048 1.22 5.0 7.48
16 1x65 65 0.060 1.52 8.0 11.9
14 l x 104 104 0.078 1.98 12.8 19.0
12 7x24 168 0.101 2.57 21.0 31.2
10 7x37 259 0.126 3.20 32.5 48.2
9 7x48 336 0.146 3.71 42 62.5
8 7x60 420 0.162 4.11 53 78.1
v
7 19x28 532 0.1% 4.98 67 100.0
6 19x35 665 0.215 5.46 84 125
5 19x44 836 0.240 6.10 105 157
4 19x56 1064 0.269 6.83 134 200
3 7X7X27 1323 0.305 7.75 169 251
2 7X7X34 1666 0.337 8.56 212 316
1 7X7X43 2107 0.376 9.55 268 399
110 7X7X54 2646 0.423 10.7 337 501
210 19X7X25 3325 0.508 12.9 427 636
310 19X7X32 4256 . 0.576 14.6 547 814
410 19X7X40 5320 0.645 16.4 684 1020
250 19x7~48 6384 0.713 18.1 821 1220
300 19x7~57 7581 0.768 19.5 975 1450
350 37X7X34 8806 0.825 21.0 1130 1685
400 37X7X39 10101 0.901 22.9 1300 1930
450 37X7X44 11396 0.940 23.9 1465 2180
500 37X7X49 12691 0.997 25.3 1630 2430
550 61x7~32 13664 1.035 26.3 1755 2615
600 61X7X35 14945 1.084 27.5 1920 2860
650 61X7X38 16226 1.133 28.8 2085 3105
700 61x7~41 17507 1.183 30.0 2250 3350
750 61x7~44 18788 1.207 30.7 2415 3595
800 61X7X47 20069 1.256 31.9 2580 3840 'i
900 61X7X53 22631 1.331 33.8 2910 4330
lo00 61x7~59 25193 1.404 35.7 32.40 4820
~~~ ~
E
Authorized Engineering Information 7-14-1982,
Purpose of Standards
National Electrical Manufacturers Association standardsare adopted in the public interest and
are designed to eliminate
misunderstandings between the manufacturer and the purchaser and to assist purchasers in selecting and obtaining the
proper product for their particular needs. Existence of a National Electrical Manufacturers Association standard does
not in any respect preclude any member or nonmember from manufacturing or selling products not conforming to the
standard. (Standardization Policies and Procedures, p . I )
Definition of a Standard
Dimensions
Where dimensions are given for interchangeability purposes, alternate dimensions satisfying the other provisions of
the Standards Publication may be capable of otherwise equivalent performance.
(Standardization Policies and Procedures, p . 8)
Categories of Standards
a 1. NEMA Standard, which relates to a product, process, or procedure commercially standardized and subject to
repetitive manufacture, which standard has been approved by at least 90 percent of the members of the Subdivi-
sion eligible to vote thereon;
2. Suggested Standard for Future Design, which may not have been regularly applied to a commercial product,
but which suggests a sound engineering approach to future development, which standard has been approved by
at least two-thirds of the members of the Subdivision eligible to vote thereon.
(Standardization Policies and Procedures, pp. 7 & 16)
Authorized Engineering Information consists of explanatory data andother engineering information of an informative
character not falling within the classification of NEMA Standard or Suggested Standard for Future Design, which stan-
dard has been approved by at least two-thirds of the members of the Subdivision eligible to vote on the standard.
(Standardization Policies and Procedures, pp. 7 & 16)
An Official Standards Proposal is an official draft of a proposed standard which is formally recommended to an
outside organization(s) for consideration, comment, and/or approval, and which has been approved by at least 90 per-
cent of the members of the Subdivision eligible to vote thereon.
(Standardization Policies and Procedures, pp. 7 & 14)
Identification of Status
Standards in NEMA Standards Publications are identified in the foreword or following each standard as “NEMA
Standard” or “Suggested Standard for Future Design.” These indicate the status of the standard. These words are
0 followed by a date which indicates when the standard was adopted in its present form by the Association.
The material identified as ‘‘Authorized Engineering Information” and ‘‘Official Standards Proposal’’ is designated
similarly.
September I I , 1989