Isolated Footing Design (IS 456-2000) : Footing No. Group ID Foundation Geometry - Length Width Thickness
Isolated Footing Design (IS 456-2000) : Footing No. Group ID Foundation Geometry - Length Width Thickness
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 2 of 167
Isolated Footing 73
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 3 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 4 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 5 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 6 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 11.508 kN
Governing Restoring Force : 29.072 kN
Minimum Sliding Ratio for the Critical Load Case : 2.526
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 8.855 kNm
Governing Resisting Moment : 52.620 kNm
Minimum Overturning Ratio for the Critical Load Case : 5.943
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 14.173 kN
Governing Restoring Force : 32.888 kN
Minimum Sliding Ratio for the Critical Load Case : 2.320
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -7.716 kNm
Governing Resisting Moment : 46.515 kNm
Minimum Overturning Ratio for the Critical Load Case : 6.028
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 7 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 8 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 9 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 10 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 11 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 12 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 13 of 167
Isolated Footing 74
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 14 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 15 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 16 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 17 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 19.086 kN
Governing Restoring Force : 48.700 kN
Minimum Sliding Ratio for the Critical Load Case : 2.552
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 12.844 kNm
Governing Resisting Moment : 55.186 kNm
Minimum Overturning Ratio for the Critical Load Case : 4.297
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 18.998 kN
Governing Restoring Force : 34.492 kN
Minimum Sliding Ratio for the Critical Load Case : 1.816
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -11.487 kNm
Governing Resisting Moment : 77.919 kNm
Minimum Overturning Ratio for the Critical Load Case : 6.783
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 18 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 19 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 20 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 21 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 22 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 23 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 24 of 167
Isolated Footing 75
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 25 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 26 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 27 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 28 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 19.310 kN
Governing Restoring Force : 57.964 kN
Minimum Sliding Ratio for the Critical Load Case : 3.002
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 12.708 kNm
Governing Resisting Moment : 56.877 kNm
Minimum Overturning Ratio for the Critical Load Case : 4.476
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 16.709 kN
Governing Restoring Force : 35.549 kN
Minimum Sliding Ratio for the Critical Load Case : 2.127
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -12.562 kNm
Governing Resisting Moment : 92.740 kNm
Minimum Overturning Ratio for the Critical Load Case : 7.382
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 29 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 30 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 31 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 32 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 33 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 34 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 35 of 167
Isolated Footing 76
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 36 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 37 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 38 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 39 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 18.425 kN
Governing Restoring Force : 44.220 kN
Minimum Sliding Ratio for the Critical Load Case : 2.400
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 11.528 kNm
Governing Resisting Moment : 48.967 kNm
Minimum Overturning Ratio for the Critical Load Case : 4.248
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 15.922 kN
Governing Restoring Force : 30.605 kN
Minimum Sliding Ratio for the Critical Load Case : 1.922
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -11.304 kNm
Governing Resisting Moment : 70.751 kNm
Minimum Overturning Ratio for the Critical Load Case : 6.259
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 40 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 41 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 42 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 43 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 44 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 45 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 46 of 167
Isolated Footing 77
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 47 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 48 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 49 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 50 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 11.978 kN
Governing Restoring Force : 68.437 kN
Minimum Sliding Ratio for the Critical Load Case : 5.713
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 9.766 kNm
Governing Resisting Moment : 51.325 kNm
Minimum Overturning Ratio for the Critical Load Case : 5.256
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 14.058 kN
Governing Restoring Force : 32.079 kN
Minimum Sliding Ratio for the Critical Load Case : 2.282
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -8.463 kNm
Governing Resisting Moment : 109.496 kNm
Minimum Overturning Ratio for the Critical Load Case : 12.939
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 51 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 52 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 53 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 54 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 55 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 56 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 57 of 167
Isolated Footing 78
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 58 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 59 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 60 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 61 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 13.585 kN
Governing Restoring Force : 85.609 kN
Minimum Sliding Ratio for the Critical Load Case : 6.302
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 14.551 kNm
Governing Resisting Moment : 115.424 kNm
Minimum Overturning Ratio for the Critical Load Case : 7.932
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 20.194 kN
Governing Restoring Force : 67.897 kN
Minimum Sliding Ratio for the Critical Load Case : 3.362
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -11.327 kNm
Governing Resisting Moment : 145.533 kNm
Minimum Overturning Ratio for the Critical Load Case : 12.849
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 62 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 63 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 64 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 65 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 66 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 67 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 68 of 167
Isolated Footing 79
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 69 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 70 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 71 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 72 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 12.967 kN
Governing Restoring Force : 73.305 kN
Minimum Sliding Ratio for the Critical Load Case : 5.653
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 10.461 kNm
Governing Resisting Moment : 101.792 kNm
Minimum Overturning Ratio for the Critical Load Case : 9.730
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 12.241 kN
Governing Restoring Force : 63.621 kN
Minimum Sliding Ratio for the Critical Load Case : 5.197
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -10.224 kNm
Governing Resisting Moment : 117.285 kNm
Minimum Overturning Ratio for the Critical Load Case : 11.472
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 73 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 74 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 75 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 76 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 77 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 78 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 79 of 167
Isolated Footing 80
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 80 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 81 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 82 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 83 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 19.561 kN
Governing Restoring Force : 65.363 kN
Minimum Sliding Ratio for the Critical Load Case : 3.342
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 12.247 kNm
Governing Resisting Moment : 132.910 kNm
Minimum Overturning Ratio for the Critical Load Case : 10.852
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 13.953 kN
Governing Restoring Force : 78.184 kN
Minimum Sliding Ratio for the Critical Load Case : 5.603
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -13.786 kNm
Governing Resisting Moment : 111.115 kNm
Minimum Overturning Ratio for the Critical Load Case : 8.060
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 84 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 85 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 86 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 87 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 88 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 89 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 90 of 167
Isolated Footing 81
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 91 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 92 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 93 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 94 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 18.823 kN
Governing Restoring Force : 142.338 kN
Minimum Sliding Ratio for the Critical Load Case : 7.562
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 11.167 kNm
Governing Resisting Moment : 322.845 kNm
Minimum Overturning Ratio for the Critical Load Case : 28.911
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 10.976 kN
Governing Restoring Force : 157.488 kN
Minimum Sliding Ratio for the Critical Load Case : 14.348
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -15.277 kNm
Governing Resisting Moment : 291.787 kNm
Minimum Overturning Ratio for the Critical Load Case : 19.099
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 95 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 96 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 97 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 98 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 99 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 100 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 101 of 167
Isolated Footing 82
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 102 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 103 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 104 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 105 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 19.031 kN
Governing Restoring Force : 40.585 kN
Minimum Sliding Ratio for the Critical Load Case : 2.133
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 13.225 kNm
Governing Resisting Moment : 322.722 kNm
Minimum Overturning Ratio for the Critical Load Case : 24.402
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 15.535 kN
Governing Restoring Force : 157.428 kN
Minimum Sliding Ratio for the Critical Load Case : 10.134
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -13.456 kNm
Governing Resisting Moment : 83.198 kNm
Minimum Overturning Ratio for the Critical Load Case : 6.183
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 106 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 107 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 108 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 109 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 110 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 111 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 112 of 167
Isolated Footing 83
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 113 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 114 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 115 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 116 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 12.794 kN
Governing Restoring Force : 24.954 kN
Minimum Sliding Ratio for the Critical Load Case : 1.950
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 9.733 kNm
Governing Resisting Moment : 102.751 kNm
Minimum Overturning Ratio for the Critical Load Case : 10.557
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 12.475 kN
Governing Restoring Force : 64.221 kN
Minimum Sliding Ratio for the Critical Load Case : 5.148
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -9.664 kNm
Governing Resisting Moment : 39.926 kNm
Minimum Overturning Ratio for the Critical Load Case : 4.131
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 117 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 118 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 119 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 120 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 121 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 122 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 123 of 167
Isolated Footing 84
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 124 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 125 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 126 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 127 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 13.337 kN
Governing Restoring Force : 26.494 kN
Minimum Sliding Ratio for the Critical Load Case : 1.987
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 13.088 kNm
Governing Resisting Moment : 86.311 kNm
Minimum Overturning Ratio for the Critical Load Case : 6.595
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 19.860 kN
Governing Restoring Force : 53.946 kN
Minimum Sliding Ratio for the Critical Load Case : 2.716
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -10.616 kNm
Governing Resisting Moment : 42.390 kNm
Minimum Overturning Ratio for the Critical Load Case : 3.993
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 128 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 129 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 130 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 131 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 132 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 133 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 134 of 167
Isolated Footing 85
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 135 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 136 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 137 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 138 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 20.758 kN
Governing Restoring Force : 77.314 kN
Minimum Sliding Ratio for the Critical Load Case : 3.724
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 16.287 kNm
Governing Resisting Moment : 106.026 kNm
Minimum Overturning Ratio for the Critical Load Case : 6.510
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 24.239 kN
Governing Restoring Force : 48.195 kN
Minimum Sliding Ratio for the Critical Load Case : 1.988
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -13.441 kNm
Governing Resisting Moment : 170.088 kNm
Minimum Overturning Ratio for the Critical Load Case : 12.654
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 139 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 140 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 141 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 142 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 143 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 144 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 145 of 167
Isolated Footing 86
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 146 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 147 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 148 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 149 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 20.757 kN
Governing Restoring Force : 124.125 kN
Minimum Sliding Ratio for the Critical Load Case : 5.980
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 16.373 kNm
Governing Resisting Moment : 103.251 kNm
Minimum Overturning Ratio for the Critical Load Case : 6.306
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 20.965 kN
Governing Restoring Force : 49.168 kN
Minimum Sliding Ratio for the Critical Load Case : 2.345
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -15.645 kNm
Governing Resisting Moment : 260.658 kNm
Minimum Overturning Ratio for the Critical Load Case : 16.660
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 150 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 151 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 152 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 153 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 154 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 155 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 156 of 167
Isolated Footing 87
Input Values
Footing Geomtery
Column Dimensions
Pedestal
Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 157 of 167
Design Parameters
Soil Properties
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 158 of 167
5 DEAD LOAD
6 LIVE LOAD
7 FLOOR LOAD
201 1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL+0.900 x DL
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 159 of 167
Length (L2) =
------------------------------------------------------
Area of
Pressure at Pressure at Pressure at Pressure at footing in
Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
------------------------------------------------------
Check For Stability Against Overturning And Sliding
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 160 of 167
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 1
Governing Disturbing Force : 20.564 kN
Governing Restoring Force : 77.601 kN
Minimum Sliding Ratio for the Critical Load Case : 3.774
Critical Load Case for Overturning about X-Direction : 2
Governing Overturning Moment : 16.961 kNm
Governing Resisting Moment : 152.605 kNm
Minimum Overturning Ratio for the Critical Load Case : 8.997
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 2
Governing Disturbing Force : 22.184 kN
Governing Restoring Force : 80.320 kN
Minimum Sliding Ratio for the Critical Load Case : 3.621
Critical Load Case for Overturning about Z-Direction : 1
Governing Overturning Moment : -15.468 kNm
Governing Resisting Moment : 147.439 kNm
Minimum Overturning Ratio for the Critical Load Case : 9.532
------------------------------------------------------
Moment Calculation
= 0.456026
Limiting Factor1 (Kumax) =
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 161 of 167
= 0.456026
Limiting Factor1 (Kumax) =
------------------------------------------------------
Shear Calculation
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 162 of 167
Ks = = 1.000
Ks x Tc = 1250.0000 kN/m2
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 163 of 167
Reinforcement Calculation
Along X Axis
Along Z Axis
Along Z Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 164 of 167
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 165 of 167
Along Z Axis
Along X Axis
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 166 of 167
------------------------------------------------------
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020
Isolated Footing Design Page 167 of 167
file:///C:/Staad.foundation%205.3/CalcXsl/footing.xml 16-11-2020