You are on page 1of 1

1 2 3 4 5 6 7 8

SCADA

SCADA
PBAX

PBAX
A0 OFPF AREA: 0 A3
A
TELECOMMUNICATION SCHEME OF CAM LAM SCADA
A
SOLAR POWER PLANT
ROUTER ROUTER
172.24.63.5/30 172.25.2.101/30
172.24.63.4/30
NOTE OSPF AREA: 1 172.25.2.100/30
OSPF AREA: 3

Devices provided by other supplier


E1/FE CONVERTER E1/FE CONVERTER

110kV Cam Ranh


110kV BÐ Cam Ranh

Telecommunication device VIETTEL/VNPT VIETTEL/VNPT


equiped by SERVICE NETWORK SERVICE NETWORK Telecommunication device
B VIETTEL/VNPT equiped by B
VIETTEL/VNPT

Teleprotection
Teleprotection

TELECOM
Distance protection relay PANEL
Distance protection relay

Telecommunication device Telecommunication device


equiped by equiped by
VIETTEL/VNPT VIETTEL/VNPT

C Teleprotection Teleprotection C

E1/FE CONVERTER E1/FE CONVERTER


Ge 0/0/0 172.24.63.6/30 Ge 0/0/0 172.25.2.102/30
Ge 0/0/1 Ge 0/0/1
IP: 172.29.9.34/27 IP: 172.29.9.33/27
Standby IP: 172.29.9.35/27 Standby IP: 172.29.9.35/27
Priority: 200 DM-RT-A0 DM-RT-A3 Priority: 100
ROUTER ROUTER

IP LAN: 172.29.9.32/27 Ge 0/0/2 Ge 0/0/2 IP LAN: 172.29.195.32/27


GE 0/0/2 GE 0/0/2
IP: 172.29.195.36/27 IP: 172.29.195.37/27
Standby IP: 172.29.195.38/27 Standby IP: 172.29.195.38/27
Priority: 100 Priority: 200
Ge 0/0/1 Ge 0/0/1
G4 G2
G3 G3

D G2
SWITCH SWITCH D
G1 VoIP phone A0 G1
-34 G4

FW1 FIREWALL FIREWALL FW2


NAT 1-1

NAT 1-1
VOIP PHONE
A0 VOIP PHONE
A0 MAIN A3
USER: 1032
PASS: XXXX USER: 8410
172.29.9.36/27 PASS: XXXX
GATEWAY: 172.29.9.35 172.29.195.35/27
SIP SERVER: 172.24.1.30 GATEWAY: 172.29.195.38
SIP SERVER: 172.25.129.30

E E
SUBSTATION GATEWAY
NAT A0: D400
A0 MAIN: 192.168.10.5/24 A3 MAIN: 192.168.12.5/24
192.168.10.5-172.29.9.38
NA A3:
192.168.12.5-172.29.195.35

IEC60870-5-104 IEC60870-5-104
KN PLANT VN PLANT
IEC61850
ETHERNET SWITCH
IEC61850
ETHERNET SWITCH
IEC61850

SUBSTATION
F F
Project Name Drawing title Drawing number
Bay =N
KN CAM LAM SOLAR POWER PLANT - TELECOMMUNICATION THT-SCA-CAM-001
Panel +COM
Contractors
TELECOM PANEL Job number
A FOR APPROVAL 2019-04-26 B.T.SON N.T.DUNG N.T.DUNG Thanh Dat Power Construction Designing Consulting Co., Ltd (TD) Page A04
THT-TEL-2018005
Rev. Revision Description Date Rev. Creator Checked Approved THT High Technology And Service Trading., JSC TELECOMMUNICATION SCHEME Next page A05
1 2 3 4 5 6 7 8